SC 77A - EMC - Low frequency phenomena
Standardization in the field of electromagnetic compatibility with regard to low frequency phenomena (ca Note: This limit frequency can be adapted to a higher frequency according to the phenomena or equipment
CEM - Phénomènes basse fréquence
Normalisation dans le domaine de la compatibilité électromagnétique concernant les phénomènes à basses fréquences (environ Note: Cette fréquence limite peut être fixée à une valeur plus élevée selon le phénomène ou équipement considéré
General Information
IEC 61000-2-4:2024 is related to conducted disturbances in the frequency range from 0 kHz to 150 kHz. It gives compatibility levels in differential mode (L-L and L-N) for industrial locations, with a nominal voltage up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.
NOTE 1 Industrial locations are defined in 3.1.8.
Power distribution systems on ships, aircraft, offshore platforms and railways are not included.
NOTE 2 See also Annex E. The compatibility levels specified in this document apply at the in-plant point of coupling (IPC). The level of the low-frequency disturbances at the terminals of equipment receiving its supply from the IPC is generally assumed to be similar to the disturbance level at the IPC itself. However, in some situations this is not the case, particularly when a long feeder is dedicated to the supply of a particular load, or when a disturbance is generated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for the types of low-frequency electromagnetic disturbances expected at any in-plant point of coupling (IPC) within industrial locations, for guidance in the definition of:
a) limits for disturbance emissions in industrial power distribution systems (including the planning levels defined in 3.1.5);
NOTE 3 A very wide range of conditions is possible in the electromagnetic environments of industrial networks. These are approximated in this document by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above-mentioned limits.
b) immunity levels for the equipment within these systems.
The disturbance phenomena considered are:
- voltage deviations;
- voltage dips and short interruptions;
- voltage imbalance;
- power-frequency variations;
- harmonics up to order 40;
- interharmonics up to the 40th harmonic;
- voltage components above the 40th harmonic up to 150 kHz;
- DC component;
- transient overvoltages.
The compatibility levels are given for different classes of environment determined by the characteristics of the supply network and loads.
NOTE 4 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. IEC TR 61000‑3‑6 and IEC TR 61000‑3‑7 describe the approach of power distribution system operators to the limitation of emissions from installations and large loads.
This third edition cancels and replaces the second edition published in 2002. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) introduction of new classes 2a, 2b and 2L (former class 2);
b) modification of existing compatibility levels for class 3;
c) addition of compatibility levels in the frequency range 2 kHz to 150 kHz;
d) addition of compatibility levels using a new quantity: partial weighted harmonic distortion (PWHD).
- Standard150 pagesEnglish languagesale 15% off
- Standard96 pagesEnglish and French languagesale 15% off
IEC TR 61000-1-9:2024 which is a Technical Report, provides examples for the evaluation of measurement uncertainty of harmonic emission tests performed using IEC 61000-3-2 and IEC 61000-3-12, and their application to the relevant conformity decisions. It also contains practical formulae to enable calculations in accordance with ISO/IEC Guide 98-3 (GUM).
- Technical report23 pagesEnglish languagesale 15% off
- Standard38 pagesEnglish and French languagesale 15% off
IEC 61000-3-2:2018 deals with the limitation of harmonic currents injected into the public supply system. It specifies limits of harmonic components of the input current which can be produced by equipment tested under specified conditions. It is applicable to electrical and electronic equipment having a rated input current up to and including 16 A per phase, and intended to be connected to public low-voltage distribution systems. Arc welding equipment which is not professional equipment, with a rated input current up to and including 16 A per phase, is included in this document. Arc welding equipment intended for professional use, as specified in IEC 60974-1, is excluded from this document and can be subject to installation restrictions as indicated in IEC 61000-3-12. The tests according to this document are type tests. For systems with nominal voltages less than but not equal to 220 V (line-to-neutral), the limits have not yet been considered.
This fifth edition cancels and replaces the fourth edition published in 2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) an update of the emission limits for lighting equipment with a rated power = 25 W to take into account new types of lighting equipment;
b) the addition of a threshold of 5 W under which no emission limits apply to all lighting equipment;
c) the modification of the requirements applying to the dimmers when operating non-incandescent lamps;
d) the addition of test conditions for digital load side transmission control devices;
e) the removal of the use of reference lamps and reference ballasts for the tests of lighting equipment;
f) the simplification and clarification of the terminology used for lighting equipment;
g) the classification of professional luminaires for stage lighting and studios under Class A;
h) a clarification about the classification of emergency lighting equipment;
i) a clarification for lighting equipment including one control module with an active input power = 2 W;
j) an update of the test conditions for television receivers;
k) an update of the test conditions for induction hobs, taking also into account the other types of cooking appliances;
l) for consistency with IEC 61000-3-12, a change of the scope of IEC 61000-3-2 from equipment with an input current = 16 A to equipment with a rated input current = 16 A.
- Standard114 pagesEnglish languagesale 15% off
- Standard80 pagesEnglish languagesale 15% off
- Standard73 pagesEnglish and French languagesale 15% off
- Standard168 pagesEnglish and French languagesale 15% off
- Standard210 pagesEnglish and French languagesale 15% off
IEC TR 61000-3-18:2024 which is a technical report, reports on the development of a methodology for adapting IEC equipment emission limits from IEC 61000-3-2 and IEC 61000-3-12 for use in regions not covered by these documents. It identifies gaps in the existing equipment emission limit standards concerning their international applicability and identifies public power system characteristics important for the evaluation of harmonic voltage performance. The purpose of adapting the above-mentioned IEC equipment harmonic emission standards in a particular region is to maintain similar electromagnetic compatibility (EMC) of equipment up to 75 A per phase in the public power systems in those regions.
NOTE The boundaries between the various voltage levels differ amongst different countries (see IEC 60050‑601:1985, 601-01-28). This document uses the following terms when referring to 50 Hz and 60 Hz system voltages:
- low voltage (LV) refers to Un ≤ 1 kV;
- medium voltage (MV) refers to 1 kV - high voltage (HV) refers to 35 kV EMC requirements can have economic and societal impacts; these have not been considered in the development of this document. The consideration of these factors generally occurs in the technical committees working on development and maintenance of emission limit standards.
- Technical report58 pagesEnglish languagesale 15% off
IEC TS 61300-3-16:2023 which is a technical specification, deals with the limits for harmonic (including grouped interharmonic) currents produced by the inverter of inverter-type electrical energy-supplying equipment (ESE) as defined in 3.2, but which does not include energy storage. The limits given in this document are applicable to inverters with a reference current as defined in 3.3 (see also 5.2.3) less than or equal to 75 A per phase, intended to be connected to public low-voltage AC distribution systems of the following types:
- single-phase, two or three wires; nominal voltage up to 240 V
- three-phase, three or four wires; nominal voltage up to 690 V
- nominal frequency of 50 Hz or 60 Hz.
This document specifies:
a) requirements and emission limits for equipment;
b) methods for type tests and simulations.
Tests in accordance with this document are type tests of complete pieces of equipment.
Equipment which mainly absorbs energy but which is capable of supplying energy to the public supply as a secondary function is out of the scope of this document.
EXAMPLE An elevator motor drive returning energy during braking.
This document provides limits and testing procedures for equipment in the range up to harmonic order 40 (h40), i.e. 2 000 Hz or 2 400 Hz depending on line frequency.
NOTE 1 It is possible that limits for frequencies in the range from 2 kHz to 9 kHz will be added in a future edition of this document.
NOTE 2 It is possible that limits and procedures for storage systems will be added in a future edition of this document.
- Technical specification20 pagesEnglish languagesale 15% off
IEC TR 61000-2-15: 2023 which is a Technical Report, addresses in particular the following main phenomena, which affect the power quality in modern distribution systems with high penetration of power electronics converters. As some aspects of the subject have already been addressed in the past, considering the evolution of the LV and MV networks, this document focuses on the following aspects:
resonances in the network, modelling and on-site validation;
supraharmonics and measurements issues;
impact of increased number of power electronic converters;
stability and instability issues for the equipment to be connected
The target phenomena and conditions of this document are the following:
frequency: ≤ 2 kHz, 2 kHz to 9 kHz, ≥ 9 kHz;
voltage levels: LV, MV;
harmonic sources: all types of converters (EV battery chargers, appliances, etc.…).
Some of these frequency ranges have already been standardized in some countries (Japan, Germany, Switzerland, etc.), but the resulting phenomena developed will benefit being described in more details, with a focus on the interaction between the converters and the electrical networks. The case of the presence of a large number of converters is also at stake. Some complex phenomena can also arise when the full system is not stable anymore. NOTE Whereas it is expected that the models and derived calculations form this document can be applied to the Americas electrical systems its formal validation studies are still pending.
- Technical report105 pagesEnglish languagesale 15% off
I
- Standard2 pagesEnglish and French languagesale 15% off
IEC TR 61000-1-4:2022 which is a technical report, reviews the sources and effects of power frequency conducted harmonic current emissions in the frequency range up to 2 kHz on the public electricity supply, and gives an account of the reasoning and calculations leading to the existing emission limits for equipment in the editions of IEC 61000-3-2, up to and including the fifth edition (2018) with Amendment 1 (2020), and in the second edition of IEC 61000-3-12. The history is traced from the first supra-national standard on low-frequency conducted emissions into the public electricity supply, EN 50006:1975 and its evolution through IEC (60)555-2 to IEC 61000-3-2, IEC TR 61000-3-4 and IEC 61000-3-12. To give a full picture of the history, that of the standard for the measuring instrument IEC 61000-4-7 is mentioned as well. NOTE All IEC standards were renumbered starting from 60000 from 1998-01-01. To indicate the references of standards withdrawn before, or not reprinted after, that date, the “60x” prefix is here enclosed in parentheses. Hence “IEC (60)555-2”. Some concepts in this document apply to all low voltage AC systems, but the numerical values apply specifically to the European 230 V;400 V 50 Hz system. This second edition cancels and replaces the first edition published in 2005. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- relation between compatibility levels, emission limits and immunity requirements clarified;
- sharing of emission levels between LV, MV and HV clarified;
- new historical information added.
- Technical report38 pagesEnglish languagesale 15% off
- Technical report94 pagesEnglish languagesale 15% off
- Standard2 pagesEnglish and French languagesale 15% off
- Standard13 pagesEnglish and French languagesale 15% off
IEC 61000-3-12:2011 deals with the limitation of harmonic currents injected into the public supply system. The limits given in this International Standard are applicable to electrical and electronic equipment with a rated input current exceeding 16 A and up to and including 75 A per phase, intended to be connected to public low-voltage a.c. distribution systems of the following types:
- nominal voltage up to 240 V, single-phase, two or three wires;
- nominal voltage up to 690 V, three-phase, three or four wires;
- nominal frequency 50 Hz or 60 Hz. Other distribution systems are excluded. The limits given in this edition apply to equipment when connected to 230/400 V, 50 Hz systems. This standard applies to equipment intended to be connected to low-voltage systems interfacing with the public supply at the low-voltage level. It does not apply to equipment intended to be connected only to private low-voltage systems interfacing with the public supply only at the medium- or high-voltage level. This standard defines:
a) requirements and emission limits for equipment;
b) methods for type tests and simulations. Tests according to this International Standard are type tests of complete pieces of equipment. Conformity with this standard can also be determined by validated simulations. This second edition cancels and replaces the first edition published in 2004 and constitutes a technical revision. The significant technical changes with respect to the previous edition are:
- the replacement of the reference fundamental current I1 by the reference current Iref for the calculation of emission limits;
- a new added table of current emission limits (Table 5);
- a new added annex (Annex A) to define test conditions for some types of equipment;
- Deletion of the former Annexes B (Approximate interpolation formulas) and D (Information on the PWHD factor).
- Standard51 pagesEnglish and French languagesale 15% off
- Standard54 pagesEnglish and French languagesale 15% off
IEC 61000-3-3:2013 is concerned with the limitation of voltage fluctuations and flicker impressed on the public low-voltage system. It specifies limits of voltage changes which may be produced by an equipment tested under specified conditions and gives guidance on methods of assessment. It is applicable to electrical and electronic equipment having an input current equal to or less than 16 A per phase, intended to be connected to public low-voltage distribution systems of between 220 V and 250 V line to neutral at 50 Hz, and not subject to conditional connection. IEC 61000-3-3 has the status of a product family standard within the IEC 61000 series. This third edition cancels and replaces the second edition published in 2008. This edition constitutes a technical revision which takes account of the changes made in IEC 61000-4-15:2010.
- Standard108 pagesEnglish languagesale 15% off
- Standard72 pagesEnglish languagesale 15% off
- Standard69 pagesEnglish and French languagesale 15% off
- Standard138 pagesEnglish and French languagesale 15% off
- Standard148 pagesEnglish and French languagesale 15% off
The contents of the corrigendum of January 2022 have been included in this copy.
- Standard7 pagesEnglish languagesale 15% off
- Standard13 pagesEnglish and French languagesale 15% off
- Standard8 pagesEnglish and French languagesale 15% off
IEC 61000-4-30:201 5 defines the methods for measurement and interpretation of results for power quality parameters in a.c. power supply systems with a declared fundamental frequency of 50 Hz or 60 Hz. Measurement methods are described for each relevant parameter in terms that give reliable and repeatable results, regardless of the method;s implementation. This standard addresses measurement methods for in-situ measurements. Measurement of parameters covered by this standard is limited to conducted phenomena in power systems. The power quality parameters considered in this standard are power frequency, magnitude of the supply voltage, flicker, supply voltage dips and swells, voltage interruptions, transient voltages, supply voltage unbalance, voltage harmonics and interharmonics, mains signalling on the supply voltage, rapid voltage changes, and current measurements. Emissions in the 2 kHz to 150 kHz range are considered in Annex C (informative), and over- and underdeviations are considered in Annex D (informative). Depending on the purpose of the measurement, all or a subset of the phenomena on this list may be measured. This third edition cancels and replaces the second edition published in 2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- the measurement method for current, previously informative, is now normative with some changes;
- the measurement method for RVC (rapid voltage change) has been added;
- the measurement method for conducted emissions in the 2 kHz to 150 kHz range has been added in informative Annex C;
- underdeviation and overdeviation parameters are moved to informative Annex D;
- Class A and Class S measurement methods are defined and clarified, while Class B is moved to informative Annex E and considered for future removal;
- measurement methods continue in this standard, but responsibility for influence quantities, performance, and test procedures are transferred to IEC 62586-2.
The contents of the corrigendum of December 2016 have been included in this copy.
- Standard232 pagesEnglish languagesale 15% off
- Standard146 pagesEnglish and French languagesale 15% off
- Standard292 pagesEnglish and French languagesale 15% off
The contents of the Interpretation sheet of August 2021, applying to the English version only, have been included in this copy.
- Standard17 pagesEnglish languagesale 15% off
- Standard34 pagesEnglish and French languagesale 15% off
- Standard3 pagesEnglish and French languagesale 15% off
IEC TR 61000-4-40:2020 which is a Technical Report, deals with the assessment of electrical power quantities (RMS voltage, RMS current and active power). It explains and compares two digital algorithms suitable for power quantity measurements in fluctuating or non-periodic loads. The examples are from 50 Hz or 60 Hz power systems. This document does not attempt to cover all possible digital implementations of the algorithms used for power quantity assessment in fluctuating loads, for example in the context of the EMC assessment described in several IEC documents. Rather, it compares averaging with one of the filtering algorithms. This document aims to highlight some examples of applications that illustrate how the presented algorithms work. Further, guidance is given for quantifying the accuracy of each approach.
- Technical report34 pagesEnglish languagesale 15% off
IEC 61000-4-11:2020 defines the immunity test methods and range of preferred test levels for electrical and electronic equipment connected to low-voltage power supply networks for voltage dips, short interruptions, and voltage variations. This document applies to electrical and electronic equipment having a rated input current not exceeding 16 A per phase, for connection to 50 Hz or 60 Hz AC networks. It does not apply to electrical and electronic equipment for connection to 400 Hz AC networks. Tests for these networks will be covered by future IEC documents. The object of this document is to establish a common reference for evaluating the immunity of electrical and electronic equipment when subjected to voltage dips, short interruptions and voltage variations.
NOTE 1 Voltage fluctuation immunity tests are covered by IEC 61000-4-14. The test method documented in this document describes a consistent method to assess the immunity of equipment or a system against a defined phenomenon.
NOTE 2 As described in IEC Guide 107, this is a basic EMC publication for use by product committees of the IEC. As also stated in Guide 107, the IEC product committees are responsible for determining whether this immunity test standard should be applied or not, and, if applied, they are responsible for defining the appropriate test levels. Technical committee 77 and its sub-committees are prepared to co-operate with product committees in the evaluation of the value of particular immunity tests for their products. This third edition cancels and replaces the second edition published in 2004 and Amendment 1:2017. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- rise time and fall time of transients are now defined terms in Clause 3;
- the origin of voltage dips and short interruptions is now stated in Clause 4.
The contents of the corrigendum of May 2020 and October 2022 have been included in this copy.
- Standard194 pagesEnglish languagesale 15% off
- Standard62 pagesEnglish and French languagesale 15% off
IEC TR 61000-1-8:2019, which is a technical report, provides information about the current conditions, and project future developments, of prevailing phase angles, predominantly for the 3rd and 5th harmonic currents, on public supply networks. This objective is accomplished by monitoring a number of networks, and efforts to forecast the effects of changes in technologies. This document presents information to guide the discussion about the effectiveness of potential mitigation techniques and the generalisation of effects of the prevailing angle positions of selected current harmonics. This document mainly deals with the phase angles of the 3rd and 5th harmonic currents, but also contains information about other harmonics.
Keywords: 3rd and 5th harmonic currents, phase angles
- Technical report67 pagesEnglish languagesale 15% off
- Standard12 pagesEnglish and French languagesale 15% off
This amendment 1 is valid for the following parts of the IEC 60317: Part 2 (1990), Part 3 (1990), Part 4 (1990), Part 10 (1972), Part 12 (1990), Part 14 (1990), Part 15 (1990), Part 16 (1990), Part 17 (1990), Part 18 (1990), Part 19 (1990), Part 20 (1990), Part 21 (1990), Part 22 (1990), Part 23 (1990), Part 24 (1990), Part 26 (1990), Part 28 (1990), Part 29 (1990), Part 30 (1990), Part 35 (1992), Part 36 (1992), Part 37 (1992) and Part 38 (1992).
- Standard5 pagesEnglish and French languagesale 15% off
IEC 61000-3-11:2017 is concerned with the emission of voltage changes, voltage fluctuations and flicker produced by equipment and impressed on the public low-voltage supply system. It specifies the limits of voltage changes produced by equipment tested under specified conditions.
This edition includes the following significant technical changes with respect to the previous edition:
a) addition of a new Annex A which explains the limitations and effectiveness of IEC 61000-3-11 regarding the connection of multiple items of similar equipment at the same location in the supply network.
- Standard60 pagesEnglish languagesale 15% off
- Standard38 pagesEnglish and French languagesale 15% off
- Standard3 pagesEnglish and French languagesale 15% off
IEC TR 61000-1-7:2016(E) provides definitions of various electrical power quantities and the relationship between them under non-sinusoidal conditions, in order to give clear information on both components in the power factor:
- the fundamental power factor, which is due to the phase difference between the voltage and current at the fundamental frequency, and
- the non-fundamental power factor, which is related to the distortion of the voltage and/or current. This Technical Report is applicable only to single-phase systems.
- Technical report34 pagesEnglish languagesale 15% off
- Standard9 pagesEnglish and French languagesale 15% off
IEC 61000-4-16:2015 relates to the immunity requirements and test methods for electrical and electronic equipment to conducted, common mode disturbances in the range d.c. to 150 kHz. The object of this standard is to establish a common and reproducible basis for testing electrical and electronic equipment with the application of common mode disturbances to power supply, control, signal and communication ports. It has the status of a basic EMC publication in accordance with IEC Guide 107. This second edition cancels and replaces the first edition published in 1998, Amendment 1:2001 and Amendment 2:2009. This edition constitutes a technical revision.
- Standard82 pagesEnglish languagesale 15% off
- Standard53 pagesEnglish and French languagesale 15% off
IEC TR 61000-4-38:2015(E) defines a test protocol for flicker test systems designed to perform compliance tests in accordance with IEC 61000-3-3 and IEC 61000-3-11. It is intended to provide test system manufacturers and testing laboratories with systematic methods to determine if the flicker test system meets the IEC design specifications for a wide range of voltage fluctuations and fluctuation frequencies, as specified in IEC 61000-4-15:2010, Table 5, that have been observed in product testing. It has the status of a basic EMC publication in accordance with IEC Guide 107.
- Technical report25 pagesEnglish languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC 61000-3-2:2014 deals with the limitation of harmonic currents injected into the public supply system. It specifies limits of harmonic components of the input current which may be produced by equipment tested under specified conditions. It is applicable to electrical and electronic equipment having an input current up to and including 16 A per phase, and intended to be connected to public low voltage distribution systems. Arc welding equipment which is not professional equipment, with input current up to and including 16 A per phase, is included in this standard. Arc welding equipment intended for professional use, as specified in IEC 60974-1, is excluded from this standard and may be subject to installation restrictions as indicated in IEC/TR 61000-3-4 or IEC 61000-3-12. The tests according to this standard are type tests. Test conditions for particular equipment are given in Annex C. For systems with nominal voltages less than 220 V (line-to-neutral), the limits have not yet been considered. This fourth edition cancels and replaces the third edition published in 2005, Amendment 1:2008, Amendment 2:2009 and Corrigendum of August 2009. This edition includes the following significant technical changes with respect to the previous edition:
- a clarification of the repeatability and reproducibility of measurements;
- a more accurate specification of the general test conditions for information technology equipment;
- the addition of optional test conditions for information technology equipment with external power supplies or battery chargers;
- the addition of a simplified test method for equipment that undergoes minor changes or updates;
- an update of the test conditions for washing machines;
- a clarification of the requirements for Class C equipment with active input power ≤ 25 W;
- an update of the test conditions for audio amplifiers;
- a clarification of the test conditions for lamps;
- an update of the test conditions for vacuum cleaners;
- the addition of test conditions for high pressure cleaners;
- an update of the test conditions for arc welding equipment;
- the reclassification of refrigerators and freezers with variable-speed drives into Class D;
- and the addition of test conditions for refrigerators and freezers.
- Standard69 pagesEnglish and French languagesale 15% off
IEC 61000-4-19:2014 relates to the immunity requirements and test methods for electrical and electronic equipment to conducted, differential mode disturbances and signalling in the range 2 kHz up to 150 kHz at a.c. power ports. The object of this standard is to establish a common and reproducible basis for testing electrical and electronic equipment with the application of differential mode disturbances and signalling to a.c. power ports. This standard defines:
- test waveforms;
- range of test levels;
- test equipment;
- test setup;
- test procedures;
- and verification procedures. These tests are intended to demonstrate the immunity of electrical and electronic equipment operating at a mains supply voltage up to 280 V (from phase to neutral or phase to earth, if no neutral is used) and a frequency of 50 Hz or 60 Hz when subjected to conducted, differential mode disturbances such as those originating from power electronics and power line communication systems. The immunity to harmonics and interharmonics, including mains signalling, on a.c. power ports up to 2 kHz in differential mode is covered by IEC 61000-4-13. Emissions in the frequency range 2 kHz to 150 kHz often have both differential mode and common mode components. This standard provides immunity tests only for differential mode disturbances and signalling. It is recommended to perform common mode tests as well, which are covered by IEC 61000-4-16. Key words: electromagnetic compatibility, EMC
- Standard68 pagesEnglish and French languagesale 15% off
- Standard2 pagesEnglish and French languagesale 15% off
IEC/TR 60725:2012, which is a technical report, records the information that was available and the factors that were taken into account in arriving at the reference impedances that were incorporated in IEC 60555 and which are now incorporated in some parts of IEC 61000-3. In addition, information is given on the impedances of public supply networks associated with service current capacities ≤100 A per phase. The third edition includes brings two mainly significant technical changes with respect to the previous edition:
- a new survey and other data from countries with public supply networks operating at 60 Hz have been included; and
- recommendations that were applicable to 50 Hz systems are now mirrored by new recommendations that are relevant to 60 Hz systems.
- Technical report58 pagesEnglish and French languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC TR 61000-3-14:2011 is a Technical Report which provides guidance on principles that can be used as the basis for determining the requirements for the connection of disturbing installations to low voltage (LV) public power systems. For the purposes of this part of IEC 61000, a disturbing installation means an installation (which may be a load or a generator) that produces disturbances: harmonics and/or interharmonics, voltage flicker and/or rapid voltage changes, and/or voltage unbalance. The primary objective is to provide guidance to system operators or owners for engineering practices, which will facilitate the provision of adequate service quality for all connected customer installations. In addressing installations, this report is not intended to replace equipment standards for emission limits. This report addresses the allocation of the capacity of the system to absorb disturbances. It does not address how to mitigate disturbances, nor does it address how the capacity of the system can be increased.
- Technical report102 pagesEnglish languagesale 15% off
- Technical report213 pagesEnglish and French languagesale 15% off
IEC/TR 61000-3-15:2011(E) is concerned with the critical assessment of existing and emerging national and international standards for single and multi-phase dispersed generation systems up to 75 A per phase, particularly converters connected to the public supply low voltage network. This Technical Report intends to serve as a starting point and to ultimately pave the way for the definition of appropriate EMC requirements and test conditions. This Technical Report is limited to EMC issues (immunity and emission) up to 9 kHz and does not include other aspects of connection of generators to the grid. This Technical Report focuses on emission caused by distributed generation (mainly harmonics and inter-harmonics, DC emissions flicker, rapid voltage changes and fluctuations), as well as immunity aspects to normally occurring events in the public supply network (voltage dips and short interruptions, frequency variations, harmonics and interharmonics). Every effort has been made to utilize already existing emission and immunity standards, including the test set-up and existing test equipment in use.
- Technical report48 pagesEnglish languagesale 15% off
Establishes a common and reproducible basis for testing electrical and electronic equipment with the application of common mode disturbances to power supply, control, signal and communication ports. This standard defines test voltage and current waveform, range of test levels, test equipment, test set-up and test procedures. The test is intended to demonstrate the immunity of electrical and electronic equipment when subjected to conducted, common mode disturbances such as those originating from power line currents and return leakage currents in the earthing/grounding system.
- Standard49 pagesEnglish and French languagesale 15% off
- Standard50 pagesEnglish and French languagesale 15% off
- Standard49 pagesEnglish and French languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC 61000-4-15:2010 gives a functional and design specification for flicker measuring apparatus intended to indicate the correct flicker perception level for all practical voltage fluctuation waveforms. Information is presented to enable such an instrument to be constructed. A method is given for the evaluation of flicker severity on the basis of the output of flickermeters complying with this standard. The flickermeter specifications in this part of IEC 61000 relate only to measurements of 120 V and 230 V, 50 Hz and 60 Hz inputs. Characteristics of some incandescent lamps for other voltages are sufficiently similar to the values in Table 1 and Table 2, that the use of a correction factor can be applied for those other voltages. Some of these correction factors are provided in the Annex B. Detailed specifications for voltages and frequencies other than those given above, remain under consideration. The object of this part of IEC 61000 is to provide basic information for the design and the instrumentation of an analogue or digital flicker measuring apparatus. It does not give tolerance limit values of flicker severity. This second edition cancels and replaces the first edition published in 1997 and its Amendment 1 (2003) and constitutes a technical revision. This new edition, in particular, adds or clarifies the definition of several directly measured parameters, so that diverging interpretations are avoided. It has the status of a basic EMC publication in accordance with IEC Guide 107.
The contents of the corrigendum of March 2012 have been included in this copy.
- Standard83 pagesEnglish and French languagesale 15% off
- Standard190 pagesEnglish and French languagesale 15% off
Enumerates a series of environmental tests and appropriate severities, and prescribes various atmospheric conditions for measurements for the ability of specimens to perform under normal conditions of transportation, storage and operational use. It has the status of a horizontal standard in accordance with IEC Guide 108.
- Technical specification10 pagesEnglish and French languagesale 15% off
Subscribe to IEC 60061 Database to access the full and updated content of the series.
- Technical report10 pagesEnglish languagesale 15% off
IEC 61000-4-34:2005+A1:2009 defines the immunity test methods and range of preferred test levels for electrical and electronic equipment connected to low-voltage power supply networks for voltage dips, short interruptions, and voltage variations. This standard applies to electrical and electronic equipment having a rated input current exceeding 16 A per phase. It covers equipment installed in residential areas as well as industrial machinery, specifically voltage dips and short interruptions for equipment connected to either 50 Hz or 60 Hz a.c. networks, including 1-phase and 3-phase mains. The object of this standard is to establish a common reference for evaluating the immunity of electrical and electronic equipment when subjected to voltage dips, short interruptions and voltage variations. The test method documented in this part of IEC 61000 describes a consistent method to assess the immunity of equipment or a system against a defined phenomenon. It has the status of a Basic EMC Publication in accordance with IEC Guide 107. This consolidated version consists of the first edition (2005) and its amendment 1 (2009). Therefore, no need to order amendment in addition to this publication.
- Standard66 pagesEnglish and French languagesale 15% off
- Standard10 pagesEnglish and French languagesale 15% off
IEC 61000-4-7:2002+A1:2008 applies to instrumentation intended for measuring spectral components in the frequency range up to 9 kHz which are superimposed on the fundamental of the power supply systems at 50 Hz and 60 Hz. For practical considerations, this standard distinguishes between harmonics, interharmonics and other components above the harmonic frequency range, up to 9 kHz. Defines the measurement instrumentation intended for testing individual items of equipment in accordance with emission limits given in certain standards (for example, harmonic current limits as given in IEC 61000-3-2) as well as for the measurement of harmonic currents and voltages in actual supply systems. The contents of the corrigendum of July 2004 have been included in this copy. This consolidated version consists of the second edition (2002) and its amendment 1 (2008). Therefore, no need to order amendment in addition to this publication.
- Standard82 pagesEnglish and French languagesale 15% off
- Technical specification10 pagesEnglish and French languagesale 15% off