This document specifies ranges, construction, performances, output characteristics and testing of rotary displacement gas meters (hereinafter referred to as RD meters or simply meters) for gas volume measurement.
This document applies to rotary displacement gas meters used to measure the volume of fuel gases of at least the 1st, 2nd and 3rd gas families, the composition of which is specified in EN 437:2021, at a maximum working pressure up to and including 20 bar over an ambient and gas temperature range of at least −10 °C to +40 °C.
This document applies to meters that are installed in locations with vibration and shocks of low significance (class M1) and in
-   closed locations (indoor or outdoor with protection) with condensing or with non-condensing humidity
or,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity,
and in locations with electromagnetic disturbances (class E1 and E2). The standard applies to mechanical meters with mechanical index, electronic devices are not covered by this standard.
Unless otherwise specified in this standard:
-   all pressures used are gauge;
-   all influence quantities, except the one under test, are kept relatively constant at their reference value.
This document applies to meters with a maximum allowable pressure PS and the volume V of less than 6 000 bar · L or with a product of PS and DN of less than 3 000 bar.
This document is to be used for both pattern approval and individual meter testing. Cross-reference tables are given in:
-   Annex A for the tests that need to be undertaken for pattern approval;
-   Annex B for individual meter testing.
Some parts of this standard cover meters with mechanical index only.
The risk philosophy adopted in this standard is based on the analysis of hazards including pressure. The standard applies principles to eliminate or reduce hazards. Where these hazards cannot be eliminated appropriate protection measures are specified.

  • Standard
    73 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies ranges, construction, performances, output characteristics and testing of rotary displacement gas meters (hereinafter referred to as RD meters or simply meters) for gas volume measurement.
This document applies to rotary displacement gas meters used to measure the volume of fuel gases of at least the 1st, 2nd and 3rd gas families, the composition of which is specified in EN 437:2021, at a maximum working pressure up to and including 20 bar over an ambient and gas temperature range of at least −10 °C to +40 °C.
This document applies to meters that are installed in locations with vibration and shocks of low significance (class M1) and in
-   closed locations (indoor or outdoor with protection) with condensing or with non-condensing humidity
or,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity,
and in locations with electromagnetic disturbances (class E1 and E2). The standard applies to mechanical meters with mechanical index, electronic devices are not covered by this standard.
Unless otherwise specified in this standard:
-   all pressures used are gauge;
-   all influence quantities, except the one under test, are kept relatively constant at their reference value.
This document applies to meters with a maximum allowable pressure PS and the volume V of less than 6 000 bar · L or with a product of PS and DN of less than 3 000 bar.
This document is to be used for both pattern approval and individual meter testing. Cross-reference tables are given in:
-   Annex A for the tests that need to be undertaken for pattern approval;
-   Annex B for individual meter testing.
Some parts of this standard cover meters with mechanical index only.
The risk philosophy adopted in this standard is based on the analysis of hazards including pressure. The standard applies principles to eliminate or reduce hazards. Where these hazards cannot be eliminated appropriate protection measures are specified.

  • Standard
    73 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the characteristics of fusion fittings made from polyethylene (PE) as well as of mechanical fittings for piping systems in the field of the supply of gaseous fuels.
NOTE 1   Additional information related to the installation of PE 100-RC systems is given in EN 1555-1:2025, Annex A.
NOTE 2   Additional information about the suitability of PE pipe systems for hydrogen and its admixtures is given in EN 1555-1:2025, Annex B.
It also specifies the test parameters for the test methods referred to in this document.
In conjunction with EN 1555-1, EN 1555-2, EN 1555-4 and EN 1555-5, this document is applicable to PE pipes, fittings and valves, their joints, and joints with components of PE and other materials intended to be used under the following conditions:
a)   a maximum operating pressure, MOP, up to and including 10 bar , at a design reference temperature of 20 °C;
b)   an operating temperature between −20 °C and 40 °C.
For operating temperatures between 20 °C and 40 °C, derating coefficients are specified in EN 1555-5.
The EN 1555 series covers a range of MOPs and gives requirements concerning colours.
This document is applicable for fittings of the following types:
a)   electrofusion socket fittings;
b)   electrofusion saddle fittings;
c)   spigot end fittings (for butt fusion using heated tools and electrofusion);
d)   mechanical fittings.
It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national guidance or regulations and installation practices or codes.
NOTE 3   The fittings can be, for example, in the form of couplers, saddles, equal and reduced tees, reducers, elbows, bends or end caps.

  • Standard
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the characteristics of valves made from polyethylene (PE) for piping systems in the field of the supply of gaseous fuels.
It is applicable to isolating unidirectional and bi-directional valves with spigot ends or electrofusion sockets intended to be fused with PE pipes or fittings conforming to EN 1555 2 and EN 1555 3 respectively.
Valves made from materials other than PE, designed for the supply of gaseous fuels conforming to the relevant standards can be used in PE piping systems according to EN 1555 (all parts), provided that they have PE connections for butt fusion or electrofusion ends, including integrated material transition joints, conforming to EN 1555 3.
It also specifies the test parameters for the test methods referred to in this document.
In conjunction with EN 1555-1, EN 1555-2, EN 1555-3 and EN 1555-5, this document is applicable to PE pipes, fittings and valves, their joints and, joints with components of PE and other materials intended to be used under the following conditions:
a)   a maximum operating pressure, MOP, up to and including 10 bar  at a design reference temperature of 20 °C;
NOTE 1   For the purpose of this document and the references to ISO 8233, MOP is considered to be nominal pressure.
b)   an operating temperature between −20 °C to 40 °C.
For operating temperatures between 20 °C and 40 °C, derating coefficients are specified in EN 1555 5.
The EN 1555 series covers a range of MOPs and gives requirements concerning colours.
It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national regulations and installation practices or codes.
This document covers valve bodies designed for connection with pipes with a nominal outside diameter dn ≤ 400 mm.
NOTE 2   Additional information related to the installation of PE 100-RC systems is given in EN 1555-1:2025, Annex A.
NOTE 3   Additional information about the suitability of PE pipe systems for hydrogen and its admixtures is given in EN 1555-1:2025, Annex B.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the characteristics of pipes made from polyethylene (PE) for piping systems in the field of the supply of gaseous fuels.
NOTE 1   Additional information related to the installation of PE 100-RC systems is given in EN 1555-1:2025, Annex A.
NOTE 2   Additional information about the suitability of PE pipe systems for hydrogen and its admixtures is given in EN 1555-1:2025, Annex B.
It also specifies the test parameters for the test methods referred to in this document.
In conjunction with EN 1555-1, EN 1555-3, EN 1555-4 and EN 1555-5, this document is applicable to PE pipes, fittings and valves, their joints, and joints with components of PE and other materials intended to be used under the following conditions:
a)   a maximum operating pressure, MOP, up to and including 10 bar  at a design reference temperature of 20 °C;
b)   an operating temperature between −20 °C and 40 °C.
For operating temperatures between 20 °C and 40 °C derating coefficients are specified in EN 1555-5.
The EN 1555 series covers a range of MOPs and gives requirements concerning colours.
This document is applicable to three types of pipe:
-   PE pipes (outside diameter, dn) including any identification stripes;
-   PE pipes with co-extruded layers on either or both the outside and/or inside of the pipe (total outside diameter, dn) as specified in Annex A, where all PE layers have the same MRS rating;
-   PE pipes (outside diameter, dn) with a peelable and contiguous thermoplastics additional layer on the outside of the pipe (”coated pipe”) as specified in Annex B.
It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national guidance or regulations and installation practices or codes.

  • Standard
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies materials and the general aspects of polyethylene (PE) piping systems in the field of the supply of gaseous fuels.
NOTE   For the purpose of this document the term gaseous fuels include for example natural gas, methane, butane, propane, hydrogen, manufactured gas, biogas, and mixtures of these gases.
It also specifies the test parameters for the test methods referred to in this document.
In conjunction with EN 1555-2, EN 1555-3, EN 1555-4 and EN 1555-5, this document is applicable to PE pipes, fittings and valves, their joints and, joints with components of PE and other materials intended to be used under the following conditions:
a)   a maximum operating pressure, MOP, up to and including 10 bar  at a design reference temperature of 20 °C;
b)   an operating temperature between −20 °C and 40 °C.
For operating temperatures between 20 °C and 40 °C, derating coefficients are specified in EN 1555-5.
The EN 1555 series covers a range of MOPs and gives requirements concerning colours.
It is the responsibility of the purchaser or specifier to make the appropriate selections from these aspects, taking into account their particular requirements and any relevant national guidance or regulations and installation practices or codes.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies requirements and tests for the construction, performance, safety and production of battery powered class 1,5 Capillary Thermal-Mass Flow sensor gas meters (hereinafter referred to as meter(s)). This applies to meters having co-axial single pipe, or two pipe connections, which are used to measure volumes of fuel gases of the 2nd and/or 3rd family, as given in EN 437:2018.
In general, the term “thermal mass flow meters” applies to a flow-measuring device using heat transfer to measure and indicate gas flowrate, as defined in ISO 14511.
NOTE 1   Although the word “mass” is present in the definition of the measurement principle, gas meters covered by this document provide measurement of gas at base conditions of temperature and pressure.
These meters have a maximum working pressure not exceeding 0,5 bar and a maximum flowrate not exceeding 160 m3/h over a minimum ambient temperature range of −10 °C to +40 °C and a gas temperature range as specified by the manufacturer with a minimum range of 40 °C.
This document applies to meters indicating volume at base conditions, which are installed in locations with vibration and shocks of low significance. It applies to meters in:
—   closed locations (indoor or outdoor with protection, as specified by the manufacturer) with condensing humidity or with non-condensing humidity;
or, if specified by the manufacturer:
—   open locations (outdoor without any covering) both with condensing humidity or with non-condensing humidity;
and in locations with electromagnetic disturbances likely to be found in residential, commercial and light industrial use.
For meters which indicate unconverted volume, reference can be made to Annex C.
Unless otherwise stated, all pressures given in this document are gauge pressures.
Requirements for electronic indexes, valves and additional requirements for batteries incorporated in the meter and any other additional functionalities are given in EN 16314:2013.
Unless otherwise stated in a particular test, the tests are carried out on meters that include additional functionality devices intended by the manufacturer.
Clauses 1 to 13 are for design and type testing only.

  • Standard
    83 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies requirements and tests for the construction, performance, safety and production of battery powered class 1,5 Capillary Thermal-Mass Flow sensor gas meters (hereinafter referred to as meter(s)). This applies to meters having co-axial single pipe, or two pipe connections, which are used to measure volumes of fuel gases of the 2nd and/or 3rd family, as given in EN 437:2018.
In general, the term “thermal mass flow meters” applies to a flow-measuring device using heat transfer to measure and indicate gas flowrate, as defined in ISO 14511.
NOTE 1   Although the word “mass” is present in the definition of the measurement principle, gas meters covered by this document provide measurement of gas at base conditions of temperature and pressure.
These meters have a maximum working pressure not exceeding 0,5 bar and a maximum flowrate not exceeding 160 m3/h over a minimum ambient temperature range of −10 °C to +40 °C and a gas temperature range as specified by the manufacturer with a minimum range of 40 °C.
This document applies to meters indicating volume at base conditions, which are installed in locations with vibration and shocks of low significance. It applies to meters in:
—   closed locations (indoor or outdoor with protection, as specified by the manufacturer) with condensing humidity or with non-condensing humidity;
or, if specified by the manufacturer:
—   open locations (outdoor without any covering) both with condensing humidity or with non-condensing humidity;
and in locations with electromagnetic disturbances likely to be found in residential, commercial and light industrial use.
For meters which indicate unconverted volume, reference can be made to Annex C.
Unless otherwise stated, all pressures given in this document are gauge pressures.
Requirements for electronic indexes, valves and additional requirements for batteries incorporated in the meter and any other additional functionalities are given in EN 16314:2013.
Unless otherwise stated in a particular test, the tests are carried out on meters that include additional functionality devices intended by the manufacturer.
Clauses 1 to 13 are for design and type testing only.

  • Standard
    83 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements for material, design, manufacture, testing, marking and documentation of stainless steel pliable corrugated gas tubing kits for gas installation pipework with a maximum allowable pressure (PS):
-   less than or equal to 0,5 bar within a nominal size range from DN 10 to DN 50 (class 1); and
-   less than or equal to 2 bar within a nominal size range from DN 10 to DN 25 (class 2).
This document applies to stainless steel pliable corrugated gas tubing kits used for 1st, 2nd and 3rd family gases (see EN 437) in residential, commercial and industrial gas installations to be installed outdoors or indoors at a temperature range from –20 °C to +60 °C.
This document does not apply to:
-   pliable tubing without cover;
-   corrugated safety metal hose assemblies for connection to moveable appliances.
NOTE   This document does not cover the installation aspects of stainless steel pliable corrugated gas tubing kits.

  • Standard
    47 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document describes the specific functional requirements for the transportation of gases (gaseous energy carriers) through service lines in addition to the general functional requirements of EN 12007 1 for:
a)   a maximum operating pressure (MOP) up to and including 16 bar;
b)   an operating temperature between −20 °C and +40 °C;
c)   gases and blends of gases which are in the gaseous state when conveyed in the gas pipeline infrastructure such as hydrogen, hydrogen rich, and methane rich gases, dimethyl ether (DME) and propane and butanes used for combustion and/or as feedstock, excluding steam and compressed air, where technical evaluation has ensured that operating conditions, constituents and properties of the gas do not affect the safe operation and maintenance of the service line.
It applies to their design, construction, commissioning, decommissioning, operation, maintenance, extension and other associated works including safety and environmental aspects. The service line is the physical asset comprising of pipework from the gas main branch saddle or top tee to the outlet of the distribution system operator’s nominated point(s) of delivery (for example: isolation valve, regulator, meter connection or combination of regulator and isolation valve).
This document does not apply retrospectively to installations before the publication date unless specifically stated.
Specific functional requirements for:
—   polyethylene pipelines are given in EN 12007 2;
—   steel pipelines are given in EN 12007 3;
—   polyamide (PA-U) pipelines are given in CEN/TS 12007 6;
—   pipework for buildings are given in EN 1775;
—   pressure regulating installations are given in EN 12279 or EN 12186;
—   pressure testing, commissioning and decommissioning are given in EN 12327;
—   safety management system (SMS) and pipeline integrity management system (PIMS) are given in EN 17649.
This document specifies common basic principles for gas infrastructure. Users of this document are expected to be aware that there can exist more detailed national standards and/or codes of practice in the CEN member countries. This document is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
In the event of terms of additional requirements in legislation/regulation than in this document, CEN/TR 13737 (all parts) illustrates these terms.
CEN/TR 13737 gives:
—   description of legislations/regulations applicable in a member state;
—   if appropriate, more restrictive national requirements;
—   a national contact point for the latest information.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies safety, constructional, performance, testing and documentation requirements of gas safety shut-off devices (SSDs). This document is applicable to SSDs with operating pressures greater than 500 kPa (5 bar) up to 10 MPa (100 bar) of nominal connection sizes up to and including DN 400 for use with fuel gases such as natural gas, manufactured gas, biomethane or liquefied petroleum gas (LPG) in commercial industrial installations, including fuel gas infrastructures. This document is applicable to SSDs for an operating temperature range from −20 °C to +60 °C; This document is applicable to: — test methods which are intended for product type tests, routine tests and batch surveillance tests; — SSDs which use the pipeline gas as a source of control energy unassisted by any external power source; — SSDs integrating on the same body a second SSD, conforming to the requirements in this document; — SSDs integrating a gas pressure regulator conforming to ISO 23555-2; — SSDs incorporating a creep (venting) relief device and/or a vent limiter conforming to the requirements in this document; This document does not apply to: — SSDs upstream from/on/in domestic gas-consuming appliances which are installed downstream of domestic gas meters; — SSDs designed to be incorporated into pressure control systems used in service lines (pipework from the main pipework in a gas infrastructure to the point of delivery of the gas) with declared volumetric flow rate ≤ 200 m3/h (n); — industrial process control valves on/off type (see IEC 60534 for information on the design, classification and tests for this type of valve); NOTE Such valves cannot be declared conformant to this document. — SSDs used in sour gas environments (gas environments containing water and H2S are considered sour) or corrosive conditions; — SSDs in service conditions with waste gases (e.g. biogas etc.), if additional information is not provided (e.g. contaminant, liquid etc.).

  • Standard
    50 pages
    English language
    sale 15% off

This document describes the functional requirements for pipelines for maximum operating pressure over 16 bar. This document also describes the mechanical requirements for pipework in stations with a maximum operating pressure greater than 16 bar.
NOTE 1   Welding requirements are described in EN 12732. Functional requirements for stations are given in EN 1776, EN 1918-5, EN 12186, and EN 12583.
This document is applicable for transporting gas via onshore high-pressure steel pipeline infrastructures, where the following applies:
-   onshore:
-   from the point where the pipeline first crosses what is normally accepted as battery limit between onshore and offshore, and that is not located within commercial or industrial premises as an integral part of the industrial process on these premises except for any pipelines and facilities supplying such premises;
-   pipeline system with a starting point onshore, also when parts of the pipeline system on the mainland subsequently cross fjords, lakes, etc.
-   high pressure: gas with a maximum operating pressure over 16 bar and a design temperature between −40 °C and 120 °C.
-   steel pipeline infrastructure: infrastructure consisting of pipeline components, such as pipes, valves, couplings and other equipment, restricted to components made of unalloyed or low alloyed carbon steel and joined by welds, flanges or mechanical couplings.
-   gas: non-corrosive natural gas, biomethane gas, hydrogen gas and mixtures of these gases where technical evaluation has ensured that operating conditions or constituents or properties of the gas do not affect the safe operation of the pipeline.
Gas infrastructures covered by this document begin after the gas producer's metering station.
NOTE 2   The functional demarcation of the pipeline system is usually directly after an isolating valve of the installation, but can differ in particular situations. The functional demarcation of the pipeline system is usually located on an isolating valve of the installation, but can differ in particular situations.
A schematic representation of pipelines for gas infrastructure is given in Figure 1.
This document can also be applied to the repurposing of existing pipelines.
[Figure 1 - Schematic representation of pipelines for gas supply over 16 bar]
This document specifies common basic principles for gas infrastructure. Users of this standard are expected to be aware that more detailed national standards and/or code of practice can exist in the CEN member countries.
This document is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation with the requirements of this standard, the national legislation/regulation takes precedence as illustrated in CEN/TR 13737.
CEN/TR 13737 gives:
-   clarification of all legislations/regulations applicable in a member state;
-   if appropriate, more restrictive national requirements;
-   a national contact point for the latest information.

  • Standard
    69 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the measuring conditions, requirements and tests for the construction, performance and safety of class 1,0 axial and radial turbine gas meters with mechanical indicating devices, hereinafter referred to as a meter(s), having in-line pipe connections for gas flow measurement.
This document applies to turbine gas meters used to measure the volume of fuel gases of the 1st and 2nd gas families, the composition of which is specified in EN 437:2021, at maximum working pressures up to 420 bar, actual flow rates up to 25 000 m3/h over a gas temperature range of at least 40 K and for a climatic environmental temperature range of at least 50 K.
This document applies to meters that are installed in locations with vibration and shocks of low significance and in:
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) with condensing or with non-condensing humidity;
or, if specified by the manufacturer,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity;
and in locations with electromagnetic disturbances.
Unless otherwise specified in this document:
-   all pressures used are gauge;
-   all influence quantities, except the one under test, are kept relatively constant at their reference value.
Clauses 1 to 7 and Annex B are for design and type testing only, with the exception of 6.2.4.3, 6.2.5.3, 6.7.1.2.2 and 6.7.2.2.2. Annex C can be used to provide guidance on periodic tests during use. Clause 8 and Annexes D and E are for each meter prior to dispatch. Annex A is intended to be used for both type and individual testing. Annex F is intended to be used for individual testing. Annex G is intended to be used for design.

  • Standard
    75 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies requirements and associated test methods for rubber materials used in gas installations, gas equipment and gas appliances in contact with 1st, 2nd and 3rd family combustible gases as classified in EN 437:2018, additionally LPG, bio methane and bio LPG, in the same quality, are covered. It also establishes a classification based on temperature range and hardness. This document is applicable to materials from which homogeneous seals and homogeneous or reinforced diaphragms are manufactured.
Since the dimensions and shape of the components differ from those of standard test pieces taken from sheet material as used for type testing of the rubber materials according to this document, tolerances have been made in the requirements specified by Annex A for the components with respect to those specified for standard test pieces.
The range of operating temperatures covered by this document is –40 °C to +150 °C.
For applications with potential condensation, this document is not applicable for silicon rubber, e.g. above 200 hPa (200 mbar) nominal pressure or at temperatures below 0 °C with 3rd family gases.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the measuring conditions, requirements and tests for the construction, performance and safety of class 1,0 axial and radial turbine gas meters with mechanical indicating devices, hereinafter referred to as a meter(s), having in-line pipe connections for gas flow measurement.
This document applies to turbine gas meters used to measure the volume of fuel gases of the 1st and 2nd gas families, the composition of which is specified in EN 437:2021, at maximum working pressures up to 420 bar, actual flow rates up to 25 000 m3/h over a gas temperature range of at least 40 K and for a climatic environmental temperature range of at least 50 K.
This document applies to meters that are installed in locations with vibration and shocks of low significance and in:
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) with condensing or with non-condensing humidity;
or, if specified by the manufacturer,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity;
and in locations with electromagnetic disturbances.
Unless otherwise specified in this document:
-   all pressures used are gauge;
-   all influence quantities, except the one under test, are kept relatively constant at their reference value.
Clauses 1 to 7 and Annex B are for design and type testing only, with the exception of 6.2.4.3, 6.2.5.3, 6.7.1.2.2 and 6.7.2.2.2. Annex C can be used to provide guidance on periodic tests during use. Clause 8 and Annexes D and E are for each meter prior to dispatch. Annex A is intended to be used for both type and individual testing. Annex F is intended to be used for individual testing. Annex G is intended to be used for design.

  • Standard
    75 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report gives explanation on the pressure definitions and pressure units used by the gas network operators with regard to the standards of CEN/TC 234 “Gas infrastructure” listed in Clause 2.
The European Standards of CEN/TC 234 comprise the functional requirements in the field of gas infrastructure from the input of gas into the on-shore transmission network up to the inlet connection of gas appliances, including transmission, distribution, storage, compression, pressure regulation and metering, installation, injection of (renewable) gases such as biomethane, hydrogen, gas quality issues and others.

  • Technical report
    16 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report gives explanation on the pressure definitions and pressure units used by the gas network operators with regard to the standards of CEN/TC 234 “Gas infrastructure” listed in Clause 2.
The European Standards of CEN/TC 234 comprise the functional requirements in the field of gas infrastructure from the input of gas into the on-shore transmission network up to the inlet connection of gas appliances, including transmission, distribution, storage, compression, pressure regulation and metering, installation, injection of (renewable) gases such as biomethane, hydrogen, gas quality issues and others.

  • Technical report
    16 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies detailed functional requirements for the design, selection of materials, construction, inspection and testing of:
-   industrial gas installation pipework and assemblies with an operating pressure greater than 0,5 bar; and
-   non-industrial gas installation pipework (residential and commercial) with an operating pressure greater than 5 bar in buildings;
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas appliance; normally the inlet isolation valve. This standard also covers the pipework to the inlet connection of a gas appliance that is not included within the scope of the appliance standard.
NOTE 1   The use of the term installation and pipework is interchangeable.
Apart from the exceptions stated below, this standard applies to gas installations operating at ambient temperatures between −20 °C and 40 °C and operating pressures up to and including 60 bar. For operating conditions outside these limitations, reference should additionally be made to EN 13480 (all parts) for metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and commercial) gas installations up to and including 5 bar in buildings, EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this standard applies.
In this European Standard, the term “gas“ refers to combustible gases, which are gaseous at 15 °C and 1 013 mbar absolute atmospheric pressure (normal conditions). These gases are commonly referred to as manufactured gas, natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family gases as classified in EN 437:2003+A1:2009, Table 1. The given values are considered as normal conditions for all volumes given in this standard.
This European Standard is applicable to installation pipework for the carriage of:
-   processed, non-toxic and non-corrosive natural gas according to EN 437:2003+A1:2009 and EN 16726 "Gas infrastructure - Quality of gas - Group H";
-   vaporized LPG;
-   biomethane, complying with EN 16723 1;
-   vaporized LNG.
NOTE 2   The specification of vaporized LNG is equal to that of natural gas as classified in EN 437:2003+A1:2009.
This European Standard does not cover pipework for hydrogen rich gases that fall outside the definitions within EN 437:2003+A1:2009.
LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations operating at vapour pressure in the liquid state (e.g. between the storage vessel and any pressure regulator).
In this standard, all pressures are gauge pressures unless otherwise stated.
This standard has been harmonized to address the essential safety requirements of the Pressure Equipment Directive (PED, 2014/68/EU [formerly 97/23/EC]) relevant for the joining of gas installation pipework (assemblies) falling within the scope of the PED. These are listed in Annex ZA. However, "this Directive does not cover the assembly of pressure equipment on the site and under the responsibility of the user, as in the case of industrial installations" (PED, Preamble, 7th recital, last paragraph).
Although in this respect, the standard takes into account the essential safety requirements of the PED, no inference can be drawn from this as to whether or not the installation or parts of the installation falls within the scope of the PED. Reference should therefore be made to the PED and relevant national legislation.
This European Standard specifies common basic principles for gas supply systems. Users of this European Standard should be aware (...)

  • Standard
    131 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies detailed functional requirements for the commissioning, operation and maintenance of
-   industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of
-   non-industrial gas installations (residential and commercial) with an operating pressure greater than 5 bar,
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas appliance; normally the inlet isolation valve. This European Standard also covers the pipework to the inlet connection of a gas appliance that is not included within the scope of the appliance standard.
NOTE   The use of the term installation and pipework is interchangeable.
Apart from the exceptions stated below, this standard applies to gas installations operating at ambient temperatures between -20 °C and 40 °C and operating pressures up to and including 60 bar. For operating conditions outside these limitations, reference should additionally be made to EN 13480 for metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and commercial) gas installations up to and including 5 bar EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this European Standard applies.
In this European Standard, the term "gas" refers to combustible gases, which are gaseous at 15 °C and 1 013 mbar absolute atmospheric pressure. These gases are commonly referred to as manufactured gas, natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family gases as classified in Table 1 of EN 437:2003+A1:2009. The given values are considered as normal conditions for all volumes given in this standard.
This European Standard is applicable to installation pipework for the carriage of:
-   processed, non-toxic and non-corrosive natural gas according to EN 437:2003+A1:2009 and EN 16726 -Gas infrastructure - Quality of gas - Group H”,
-   vaporized LNG,
-   biomethane, complying with EN 16723-1,
-   vaporized LNG.
NOTE   The specification of vaporized LNG is equal to that of natural gas as classified in EN 437:2003+A1:2009.
This European Standard does not cover pipework for hydrogen rich gases that fall outside the definitions within EN 437:2003+A1:2009. LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations operating at vapour pressure (e.g. between the storage vessel and its pressure regulator).
In this European Standard, all pressures are gauge pressures unless otherwise stated.
This European Standard specifies common basic principles for gas supply systems. Users of this European Standard should be aware that more detailed national standards and/or code of practice may exist in the CEN member countries.
This European Standard is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
For gas installations within the scope of this standard, national legislation and regulations have to be taken into account.
Functional requirements for design, selection of materials, construction, inspection and testing of industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of gas installations greater than 5 bar in buildings and areas intended for residential, commercial, public and mixed uses are described in EN 15001-1.
Generally, additional safety precautions may be necessary where non odorized gas is used. For non-industrial purposes, the gas should be odorized.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies detailed functional requirements for the design, selection of materials, construction, inspection and testing of:
-   industrial gas installation pipework and assemblies with an operating pressure greater than 0,5 bar; and
-   non-industrial gas installation pipework (residential and commercial) with an operating pressure greater than 5 bar in buildings;
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas appliance; normally the inlet isolation valve. This standard also covers the pipework to the inlet connection of a gas appliance that is not included within the scope of the appliance standard.
NOTE 1   The use of the term installation and pipework is interchangeable.
Apart from the exceptions stated below, this standard applies to gas installations operating at ambient temperatures between −20 °C and 40 °C and operating pressures up to and including 60 bar. For operating conditions outside these limitations, reference should additionally be made to EN 13480 (all parts) for metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and commercial) gas installations up to and including 5 bar in buildings, EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this standard applies.
In this European Standard, the term “gas“ refers to combustible gases, which are gaseous at 15 °C and 1 013 mbar absolute atmospheric pressure (normal conditions). These gases are commonly referred to as manufactured gas, natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family gases as classified in EN 437:2003+A1:2009, Table 1. The given values are considered as normal conditions for all volumes given in this standard.
This European Standard is applicable to installation pipework for the carriage of:
-   processed, non-toxic and non-corrosive natural gas according to EN 437:2003+A1:2009 and EN 16726 "Gas infrastructure - Quality of gas - Group H";
-   vaporized LPG;
-   biomethane, complying with EN 16723 1;
-   vaporized LNG.
NOTE 2   The specification of vaporized LNG is equal to that of natural gas as classified in EN 437:2003+A1:2009.
This European Standard does not cover pipework for hydrogen rich gases that fall outside the definitions within EN 437:2003+A1:2009.
LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations operating at vapour pressure in the liquid state (e.g. between the storage vessel and any pressure regulator).
In this standard, all pressures are gauge pressures unless otherwise stated.
This standard has been harmonized to address the essential safety requirements of the Pressure Equipment Directive (PED, 2014/68/EU [formerly 97/23/EC]) relevant for the joining of gas installation pipework (assemblies) falling within the scope of the PED. These are listed in Annex ZA. However, "this Directive does not cover the assembly of pressure equipment on the site and under the responsibility of the user, as in the case of industrial installations" (PED, Preamble, 7th recital, last paragraph).
Although in this respect, the standard takes into account the essential safety requirements of the PED, no inference can be drawn from this as to whether or not the installation or parts of the installation falls within the scope of the PED. Reference should therefore be made to the PED and relevant national legislation.
This European Standard specifies common basic principles for gas supply systems. Users of this European Standard should be aware (...)

  • Standard
    131 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies detailed functional requirements for the commissioning, operation and maintenance of
-   industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of
-   non-industrial gas installations (residential and commercial) with an operating pressure greater than 5 bar,
starting from the outlet of the network operator’s point of delivery up to the inlet connection to the gas appliance; normally the inlet isolation valve. This European Standard also covers the pipework to the inlet connection of a gas appliance that is not included within the scope of the appliance standard.
NOTE   The use of the term installation and pipework is interchangeable.
Apart from the exceptions stated below, this standard applies to gas installations operating at ambient temperatures between -20 °C and 40 °C and operating pressures up to and including 60 bar. For operating conditions outside these limitations, reference should additionally be made to EN 13480 for metallic pipework.
For industrial gas installations up to and including 0,5 bar and for non-industrial (residential and commercial) gas installations up to and including 5 bar EN 1775 applies.
For gas installations that do not fall within the scope of EN 1775 or other European Standards, this European Standard applies.
In this European Standard, the term "gas" refers to combustible gases, which are gaseous at 15 °C and 1 013 mbar absolute atmospheric pressure. These gases are commonly referred to as manufactured gas, natural gas or Liquefied Petroleum Gas (LPG). They are also referred to as first, second or third family gases as classified in Table 1 of EN 437:2003+A1:2009. The given values are considered as normal conditions for all volumes given in this standard.
This European Standard is applicable to installation pipework for the carriage of:
-   processed, non-toxic and non-corrosive natural gas according to EN 437:2003+A1:2009 and EN 16726 -Gas infrastructure - Quality of gas - Group H”,
-   vaporized LNG,
-   biomethane, complying with EN 16723-1,
-   vaporized LNG.
NOTE   The specification of vaporized LNG is equal to that of natural gas as classified in EN 437:2003+A1:2009.
This European Standard does not cover pipework for hydrogen rich gases that fall outside the definitions within EN 437:2003+A1:2009. LPG storage vessels (including all ancillaries fitted directly to storage vessels) are excluded. Also excluded are LPG installations and sections of LPG installations operating at vapour pressure (e.g. between the storage vessel and its pressure regulator).
In this European Standard, all pressures are gauge pressures unless otherwise stated.
This European Standard specifies common basic principles for gas supply systems. Users of this European Standard should be aware that more detailed national standards and/or code of practice may exist in the CEN member countries.
This European Standard is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
For gas installations within the scope of this standard, national legislation and regulations have to be taken into account.
Functional requirements for design, selection of materials, construction, inspection and testing of industrial gas installations and assemblies with an operating pressure greater than 0,5 bar and of gas installations greater than 5 bar in buildings and areas intended for residential, commercial, public and mixed uses are described in EN 15001-1.
Generally, additional safety precautions may be necessary where non odorized gas is used. For non-industrial purposes, the gas should be odorized.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the safety, design, construction, performance requirements and testing of Temperature Control Functions (TCF) and Combustion Product Discharge Safety Devices (TTB) for gas and liquid fuel burners and appliances burning one or more gaseous or liquid fuels, hereafter referred to as ‘TCF’ or ‘TTB’.
It also describes the test procedures for checking compliance with these requirements.
This document is applicable to AC and DC supplied TCF and TTB (for TCF and TTB supplied by stand-alone battery system, battery systems for mobile applications or systems which are intended to be connected to DC supply networks, see Annex I).
This document is applicable to electronically based TTB and TCF only.
For both TTB and TCF, the requirements in this document are applicable to the combination of sensing element and control.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies requirements on the development and implementation of a Safety Management System (SMS) and a Pipeline Integrity Management System (PIMS). The SMS is applicable for system operators of a gas infrastructure. The PIMS is applicable for system operators of gas infrastructure with a maximum operating pressure (MOP) over 16 bar.
This document refers to all activities and processes related to safety aspects and performed by system operators of a gas infrastructure, including those activities entrusted to contractors. It includes safety-related provisions on operation of the gas infrastructure.
This document is applicable to infrastructure for the conveyance of processed, non-toxic and non-corrosive natural gas according to EN ISO 13686 and gases such as biomethane and hydrogen and to mixtures of these gases with natural gas.
This document covers also gases classified as group H, that are to be transmitted, injected into and from storages, distributed and utilized, as specified in EN 16726. For the requirements and test methods for biomethane at the point of entry into a natural gas network, reference is made to EN 16723-1.
This document can be applied for gas infrastructure conveying gases of the 3rd gas family as classified in EN 437 or for other gases such as carbon dioxide.
Specific requirements for occupational health and safety are excluded from this document. For these, other European and/or international standards, e.g. ISO 45001, apply.
This document specifies common basic principles for gas infrastructure. It is important that users of this document are expected to be aware that more detailed national standards and/or codes of practice exist in the CEN member countries. This document is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation with the requirements of this document, the national legislation/regulation takes precedence as illustrated in CEN/TR 13737 (all parts).
NOTE CEN/TR 13737 (all parts) contains:
- clarification of relevant legislation/regulations applicable in a country;
- if appropriate, more restrictive national requirements;
- national contact points for the latest information.

  • Standard
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the safety, design, construction, performance requirements and testing of Temperature Control Functions (TCF) and Combustion Product Discharge Safety Devices (TTB) for gas and liquid fuel burners and appliances burning one or more gaseous or liquid fuels, hereafter referred to as ‘TCF’ or ‘TTB’.
It also describes the test procedures for checking compliance with these requirements.
This document is applicable to AC and DC supplied TCF and TTB (for TCF and TTB supplied by stand-alone battery system, battery systems for mobile applications or systems which are intended to be connected to DC supply networks, see Annex I).
This document is applicable to electronically based TTB and TCF only.
For both TTB and TCF, the requirements in this document are applicable to the combination of sensing element and control.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day

EN 13611:2019, Clause 1 is replaced by the following:
This document specifies methods for the classification and assessment of function blocks for burners and appliances burning one or more gaseous or liquid fuels with particular regards to their fault behaviour and preventative measures.
This document is applicable to new control function blocks, not covered by dedicated control standards.

  • Standard
    41 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements and tests for the construction, performance, safety and conformity of gas-volume electronic conversion devices associated to gas meters, used to measure volumes of fuel gases of the 1st and 2nd families according to EN 437.
This document is intended for type testing, the detailed relevant provisions of which are given in Annex A.
Only three kinds of conversion are treated in this document:
-   conversion as a function of temperature only (called T conversion);
-   conversion as a function of the pressure and of the temperature with constant compression factor (called PT conversion);
-   conversion as a function of the pressure, the temperature and taking into account the compression factor (called PTZ conversion).
This document is not relevant to temperature conversion integrated into gas meters which only indicate the converted volume.
Gas-volume conversion devices consist of a calculator and a temperature transducer or a calculator, a temperature transducer and a pressure transducer locally installed.
For application of this document, a conversion device may be, as a choice of the manufacturer, considered as a complete instrument (Type 1) or made of separate elements (Type 2), according to the definitions given in 3.1.20.1 and 3.1.20.2.
In this last case, the provisions concerning pressure transducers, temperature sensors and temperature transducers are given in Annexes B, C and D respectively.
Any conversion device can provide an error curve correction for a gas meter.
NOTE   When rendering an account to an end user the readings from the conversion device can be used in conjunction with the readings from a gas meter conforming to EN 1359, EN 12480, or EN 12261, as appropriate, or to any other appropriate and relevant international or national standard for gas meters, without prejudice of national regulations.

  • Standard
    122 pages
    English language
    sale 10% off
    e-Library read for
    1 day

EN 13611:2019, Clause 1 is replaced by the following:
This document specifies methods for the classification and assessment of function blocks for burners and appliances burning one or more gaseous or liquid fuels with particular regards to their fault behaviour and preventative measures.
This document is applicable to new control function blocks, not covered by dedicated control standards.

  • Standard
    41 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies generic safety, constructional, performance, testing and documentation requirements for high pressure controls for use in gas transmission, distribution and installations (hereafter referred to as controls). This document is applicable to controls with operating pressures greater than 500 kPa (5 bar) and up to and including 10 MPa (100 bar) and nominal size up to DN 400 for use with fuel gases as natural gas, manufactured gas, biomethane or liquefied petroleum gas (LPG) in commercial, industrial installations, including fuel gas infrastructures. The test methods given in this document are intended for product type test, routine tests and batch surveillance tests. This document is not applicable to: — controls upstream from/on/in domestic gas-consuming appliances which are installed downstream of domestic gas meters; — controls designed with declared maximum capacity ≤200 m3/h (normal conditions) and declared maximum inlet pressure ≤500 kPa (5 bar), to be incorporated into pressure control systems used in service lines (pipework from the main pipework in a gas infrastructure to the point of delivery of the gas); — industrial process control valves, such as IEC 60534; — controls used in aggressive/sour gas environments (gas environments containing water and H2S are considered sour) or severely corrosive conditions; — controls in service conditions with renewables (e.g. H2NG with hydrogen more than 10 %) and/or waste gases (e.g. biogas, etc.), if additional information is not provided (e.g. contaminant, liquid, etc.).

  • Standard
    70 pages
    English language
    sale 15% off

This document specifies safety, constructional, performance, testing and documentation requirements for gas pressure regulators for use in gas transmission and distribution installations (hereafter referred to as regulators). This document is applicable to regulators with operating pressures greater than 500 kPa and up to and including 10 MPa (100 bar) and nominal diameters up to DN 400 for use with fuel gases as natural gas, manufactured gas, biomethane or liquefied petroleum gas (LPG). This document is applicable to: — test methods which are intended for product type test, routine tests and product surveillance tests; — regulators which use the pipeline gas as a source of control energy unassisted by any external power source; — regulators integrating on the same body a second regulator, used as monitor, complying with the requirements in this document; — regulators integrating a safety shut off device (SSD) according to ISO 23555-3; — regulators incorporating a creep (venting) relief device and/or a vent limiter complying with the requirements in this document. This document does not apply to: — regulators upstream from/on/in domestic gas‑consuming appliances which are installed downstream of domestic gas meters; — regulators designed to be incorporated into pressure control systems used in service lines (pipework from the main pipework in a gas infrastructure to the point of delivery of the gas) with declared volumetric flow rate ≤ 200 m3/h at normal conditions and declared inlet pressure ≤ 500 kPa (5 bar); — industrial process control valves, such as IEC 60534 (all parts); — regulators used in aggressive/sour gas environments (gas environments containing water and H2S are considered sour) or severely corrosive conditions; — regulators in service conditions with renewables (e.g. H2NG with hydrogen more than 10 %) and/or waste gases (e.g. biogas etc.), if additional information is not provided (e. g. contaminant, liquid, etc.).

  • Standard
    58 pages
    English language
    sale 15% off

This document specifies the requirements and tests for the construction, performance, safety and conformity of gas-volume electronic conversion devices associated to gas meters, used to measure volumes of fuel gases of the 1st and 2nd families according to EN 437.
This document is intended for type testing, the detailed relevant provisions of which are given in Annex A.
Only three kinds of conversion are treated in this document:
-   conversion as a function of temperature only (called T conversion);
-   conversion as a function of the pressure and of the temperature with constant compression factor (called PT conversion);
-   conversion as a function of the pressure, the temperature and taking into account the compression factor (called PTZ conversion).
This document is not relevant to temperature conversion integrated into gas meters which only indicate the converted volume.
Gas-volume conversion devices consist of a calculator and a temperature transducer or a calculator, a temperature transducer and a pressure transducer locally installed.
For application of this document, a conversion device may be, as a choice of the manufacturer, considered as a complete instrument (Type 1) or made of separate elements (Type 2), according to the definitions given in 3.1.20.1 and 3.1.20.2.
In this last case, the provisions concerning pressure transducers, temperature sensors and temperature transducers are given in Annexes B, C and D respectively.
Any conversion device can provide an error curve correction for a gas meter.
NOTE   When rendering an account to an end user the readings from the conversion device can be used in conjunction with the readings from a gas meter conforming to EN 1359, EN 12480, or EN 12261, as appropriate, or to any other appropriate and relevant international or national standard for gas meters, without prejudice of national regulations.

  • Standard
    122 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document contains requirements for the production and testing of weld joints for the installation and modification, including in-service welding, of onshore steel pipelines and pipework used in gas infrastructure. This includes all pressure ranges and processed, non-toxic and non-corrosive natural gas according to EN ISO 13686 and non-conventional gases such as (injected) biomethane and hydrogen, where:
-   the pipeline elements are made of unalloyed or low-alloyed carbon steel;
-   the pipeline is not located within commercial or industrial premises as integral part of the industrial process on those premises except for any pipelines and facilities delivering gas to such premises;
-   the pipework is not located within households or industrial installations according to EN 1775 or EN 15001;
-   the design temperature of the system is between −40 °C up to and including 120 °C.
For injected biomethane or hydrogen a detailed technical evaluation of the functional requirements is required, ensuring there are no other constituents or properties of the gases that can affect the integrity of the pipeline.
This document is not applicable to welds produced prior to the publication of this document.
This document specifies common basic principles for gas infrastructure. Users of this document are expected to be aware that there can exist more detailed national standards and/or codes of practice in the CEN member countries.
This document is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation with the requirements of this document, the national legislation/regulation takes precedence as illustrated in CEN/TR 13737 (all parts).
NOTE   CEN/TR 13737 (all parts) contains:
-   clarification of relevant legislation/regulations applicable in a country;
-   if appropriate, more restrictive national requirements;
-   national contact point for the latest information.

  • Standard
    81 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives guidance for the assessment of conformity of compounds, products, joints and assemblies in accordance with the applicable part(s) of EN 1555 intended to be included in the manufacturer’s quality plan as part of the quality management system and for the establishment of certification procedures.
This document gives recommendations that the quality management system conforms to or is no less stringent than the relevant requirements to EN ISO 9001.
NOTE 1 If certification is involved, the certification and inspection body is preferably compliant with EN ISO/IEC 17065, EN IS0/IEC 17021 or EN ISO/IEC 17020, as applicable.
In conjunction with Parts 1 to 5 of EN 1555 (see Foreword), this document is applicable to polyethylene (PE) plastics piping systems for the supply of gaseous fuels. It is applicable to PE pipes, fittings, and valves, their joints and to joints with components of other materials intended to be used under the following conditions:
a) a maximum operating pressure, MOP, up to and including 10 bar;
b) an operating temperature of 20 °C as reference temperature.
NOTE 2 For other operating temperatures, derating coefficients can be used; see EN 1555-5.

  • Technical specification
    43 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives guidance for the assessment of conformity of compounds, products, joints and assemblies in accordance with the applicable part(s) of EN 1555 intended to be included in the manufacturer’s quality plan as part of the quality management system and for the establishment of certification procedures.
This document gives recommendations that the quality management system conforms to or is no less stringent than the relevant requirements to EN ISO 9001.
NOTE 1 If certification is involved, the certification and inspection body is preferably compliant with EN ISO/IEC 17065, EN IS0/IEC 17021 or EN ISO/IEC 17020, as applicable.
In conjunction with Parts 1 to 5 of EN 1555 (see Foreword), this document is applicable to polyethylene (PE) plastics piping systems for the supply of gaseous fuels. It is applicable to PE pipes, fittings, and valves, their joints and to joints with components of other materials intended to be used under the following conditions:
a) a maximum operating pressure, MOP, up to and including 10 bar;
b) an operating temperature of 20 °C as reference temperature.
NOTE 2 For other operating temperatures, derating coefficients can be used; see EN 1555-5.

  • Technical specification
    43 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the test gases, test pressures and categories of appliances relative to the use of gaseous fuels of the first, second and third families. It serves as a reference document in the specific standards for appliances.
The document makes recommendations for the use of the gases and pressures to be applied for the tests of appliances burning gaseous fuels.
NOTE   Procedures for tests are given in the corresponding appliance standards. The test gases and the test pressures specified in this standard are in principle intended to be used with all types of appliances.
However, the use of some test gases and test pressures may not be appropriate in the following cases:
-   appliances with nominal heat input greater than 300 kW;
-   appliances constructed on site;
-   appliances in which the final design is influenced by the user;
-   appliances constructed for use with high supply pressures (notably direct use of the saturated vapour pressure).
In these cases, the specific appliance standards may specify other test conditions in order to establish compliance with their requirements.

  • Standard
    57 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements of fitness for purpose of the polyethylene (PE) piping system in the field of the supply of gaseous fuels.
It specifies the requirements for electrofusion, butt fusion and mechanical joints.
It specifies the method of preparation of test piece joints, and the tests to be carried out on these joints for assessing the fitness for purpose of the system under normal and extreme conditions.
It specifies the test parameters for the test methods referred to in this document.
NOTE 1 This document is intended only to be used by the product manufacturer to assess the performance of components according to EN 1555-2, EN 1555-3:2021, and EN 1555-4:2021 when joined together under normal and extreme conditions in accordance with this document. It is not intended for on-site testing of pipe systems.
In conjunction with Parts 1 to 4 of EN 1555, it is applicable to PE pipes, fittings, valves, their joints and to joints with components of other materials intended to be used under the following conditions:
a) a maximum operating pressure, MOP, up to and including 10 bar1 at a reference temperature of 20 °C for design purposes;
b) an operating temperature between − 20 °C and 40 °C.
NOTE 2 For other operating temperatures between 20 °C and 40 °C, derating coefficients are defined in Annex A.
EN 1555 (all parts) covers a range of maximum operating pressures and gives requirements concerning colours.

  • Standard
    16 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the test gases, test pressures and categories of appliances relative to the use of gaseous fuels of the first, second and third families. It serves as a reference document in the specific standards for appliances.
The document makes recommendations for the use of the gases and pressures to be applied for the tests of appliances burning gaseous fuels.
NOTE   Procedures for tests are given in the corresponding appliance standards. The test gases and the test pressures specified in this standard are in principle intended to be used with all types of appliances.
However, the use of some test gases and test pressures may not be appropriate in the following cases:
-   appliances with nominal heat input greater than 300 kW;
-   appliances constructed on site;
-   appliances in which the final design is influenced by the user;
-   appliances constructed for use with high supply pressures (notably direct use of the saturated vapour pressure).
In these cases, the specific appliance standards may specify other test conditions in order to establish compliance with their requirements.

  • Standard
    57 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document presents guidelines for the implementation of Essential Requirements of Gas Appliances Regulation (EU) 2016/426 into hEN candidates for citation in the OJEU.
This document gives guidance that is additional to the CEN/CENELEC Internal Regulations, Part 3:2019, when this is necessary owing to the special requirements of gas appliances and fittings.
This document is intended for the drafting of gas appliances and fittings standards.

  • Guide
    21 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document describes the specific functional requirements for polyamide (PA) pipelines in addition to the general functional requirements of EN 12007-1 for:
a) a maximum operating pressure (MOP) up to and including 16 bar;
b) an operating temperature between −20 °C and +40 °C.
This document covers one type of pipe:
- PA pipes single layer solid wall.
This document specifies common basic principles for gas infrastructure.
NOTE 1 Users of this document are aware that more detailed national standards and/or code of practice can exist in the CEN member countries.
This document is intended to be applied in association with these national standards and/or codes of practice setting out the above-mentioned basic principles.
NOTE 2 In the event of conflicts in terms of more restrictive requirements in national legislation/regulation with the requirements of this document, the national legislation/regulation takes precedence as illustrated in CEN/TR 13737 (all parts).
CEN/TR 13737 (all parts) give:
- clarification of all legislations/regulations applicable in a member state;
- if appropriate, more restrictive national requirements;
- a national contact point for the latest information.

  • Technical specification
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives details for the classification of gas appliances according to the method of supplying combustion air and of evacuating the combustion products (types). This classification refers to gas appliances that are intended to be installed within buildings and/or outside of the building .
The document classifies appliances as type A, B or C according to the basic principle for the evacuation of the combustion products and air inlet.
This document is the reference for the harmonization of product standards, for the preparation of installation standards and for the common understanding of the types of gas appliances.
This document is neither an installation standard nor a product standard.
In references to a gas appliance or gas appliances connected via "its" or "their" duct or ducts, it is intended that the air inlet duct and/or the discharge duct for carrying any combustion products are part of the gas appliance. This means that such ducts are certified together with the gas appliance. Informative Annex C identifies appliance types that are designed for connection to separate chimney products, which may be part of the construction of the building.
In terms of this document, a "single duct" is a flue duct designed and capable of discharging the combustion products and/or air inlet duct for the air supply for only one appliance.
In terms of this document, a "common duct" is a flue duct designed and capable of discharging the combustion products and/or air inlet duct for the air supply for more than one appliance.

  • Standard
    48 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives details for the classification of gas appliances according to the method of supplying combustion air and of evacuating the combustion products (types). This classification refers to gas appliances that are intended to be installed within buildings and/or outside of the building .
The document classifies appliances as type A, B or C according to the basic principle for the evacuation of the combustion products and air inlet.
This document is the reference for the harmonization of product standards, for the preparation of installation standards and for the common understanding of the types of gas appliances.
This document is neither an installation standard nor a product standard.
In references to a gas appliance or gas appliances connected via "its" or "their" duct or ducts, it is intended that the air inlet duct and/or the discharge duct for carrying any combustion products are part of the gas appliance. This means that such ducts are certified together with the gas appliance. Informative Annex C identifies appliance types that are designed for connection to separate chimney products, which may be part of the construction of the building.
In terms of this document, a "single duct" is a flue duct designed and capable of discharging the combustion products and/or air inlet duct for the air supply for only one appliance.
In terms of this document, a "common duct" is a flue duct designed and capable of discharging the combustion products and/or air inlet duct for the air supply for more than one appliance.

  • Standard
    48 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies requirements and tests for the construction, performance and safety of class 1,0 and class 1,5 battery powered ultrasonic gas meters (hereinafter referred to as meters), having co-axial single pipe, or two pipe connections, used to measure volumes of distributed fuel gases of the second and/or third family, as given in EN 437, at maximum working pressures not exceeding 0,5 bar ) and maximum actual flow rates of up to 10 m3/h over a minimum ambient temperature range of -10 °C to +40 °C, and minimum gas temperature span of 40 K, for domestic applications. This European Standard applies to meters where the measuring element and the register(s) are enclosed in the same case.
This European Standard applies to meters with and without built-in temperature conversion, that are installed in locations with vibration and shocks of low significance and in
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) with condensing or with non-condensing humidity
or, if specified by the manufacturer,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity
and in locations with electromagnetic disturbances.
Unless otherwise stated, all pressures given in this European Standard are gauge pressures.
When more than one meter type is submitted for testing, then each meter type is required to be tested against this European Standard.
Clauses 1 to 15 and Annex C are for design and type testing only.
NOTE   See Annex A for production requirements.

  • Standard
    79 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document, read in conjunction with ISO 11299-1, specifies requirements and test methods for pipes and fittings which are part of plastics piping systems installed as continuous pipes in the renovation of underground gas supply networks. It is applicable to polyethylene (PE) pipes of three different types:
—          PE solid wall single layered pipes (nominal outside diameter, dn), including any identification stripes;
—          PE pipes with co-extruded layers on either or both the outside and inside of the pipe (total outside diameter, dn), as specified in Annex A, where all layers have the same MRS rating;
—          Coated PE pipes (outside diameter, dn) having a peelable, contiguous, thermoplastics additional layer on the outside of the pipe ("coated pipe"), as described in Annex A.
In addition it covers:
—          jointing of pipe lengths by means of butt fusion;
—          fabricated and injection-moulded fittings made of PE;
It is applicable to PE pipes, fittings and assemblies intended to be used at an operating temperature of 20 °C as the reference temperature.
NOTE       For other operating temperatures, guidance is given in ISO 4437-5:2014.

  • Standard
    18 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements and test methods for plastics piping systems intended to be used for the renovation of underground gas supply networks. It is applicable to pipes and fittings, as manufactured, as well as to the installed lining system. It is not applicable to the existing pipeline or any sprayed coatings or annular filler.
This document gives the general requirements common to all relevant renovation techniques.

  • Standard
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document, in conjunction with ISO 11299‑1, specifies requirements and test methods for close-fit lining systems intended to be used for the renovation of gas supply networks.
It applies to pipes and fittings, as manufactured, as well as to the installed lining system. It is applicable to polyethylene (PE) pipe of either solid wall single layer or co-extruded layer construction, which is reduced in the factory or on site to provide a close-fitting independent or interactive pressure pipe liner, as well as associated fittings and joints for the construction of the lining system. This document is not applicable for coated PE pipes having a peelable, contiguous, thermoplastics additional layer on the outside of the pipes.
It is applicable to PE pipes, fittings and assemblies intended to be used at an operating temperature of 20 °C as the reference temperature.
NOTE       For other operating temperatures, guidance is given in ISO 4437‑5:2014.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies requirements and tests for the construction, performance and safety of class 1,0 and class 1,5 battery powered ultrasonic gas meters (hereinafter referred to as meters), having co-axial single pipe, or two pipe connections, used to measure volumes of distributed fuel gases of the second and/or third family, as given in EN 437, at maximum working pressures not exceeding 0,5 bar ) and maximum actual flow rates of up to 10 m3/h over a minimum ambient temperature range of -10 °C to +40 °C, and minimum gas temperature span of 40 K, for domestic applications. This European Standard applies to meters where the measuring element and the register(s) are enclosed in the same case.
This European Standard applies to meters with and without built-in temperature conversion, that are installed in locations with vibration and shocks of low significance and in
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) with condensing or with non-condensing humidity
or, if specified by the manufacturer,
-   open locations (outdoor without any covering) with condensing humidity or with non-condensing humidity
and in locations with electromagnetic disturbances.
Unless otherwise stated, all pressures given in this European Standard are gauge pressures.
When more than one meter type is submitted for testing, then each meter type is required to be tested against this European Standard.
Clauses 1 to 15 and Annex C are for design and type testing only.
NOTE   See Annex A for production requirements.

  • Standard
    79 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and tests for the construction, performance, safety and production of class 1,5 diaphragm gas meters (referred to as meters). This applies to meters with co-axial single pipe, or two pipe connections, that are used to measure volumes of fuel gases, which are within the limits of test gases of the 1st, 2nd and 3rd families described in EN 437. The meters have maximum working pressures not exceeding 0,5 bar and maximum actual flow rates not exceeding 160 m3.h−1 over a minimum ambient temperature range of −10 °C to 40 °C and a gas temperature range as specified by the manufacturer with a minimum range of 40 K.
This standard applies to meters with and without built-in temperature conversion that are installed in locations with vibration and shocks of low significance (see MID Annex 1 Chapter 1.3.2 (a), class M1). It also applies to meters in:
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) both with condensing humidity or with non-condensing humidity;
or, if specified by the manufacturer:
-   open locations (outdoor without any covering) both with condensing humidity and with non-condensing humidity;
-   in locations with electromagnetic disturbances corresponding to those likely to be found in residential, commercial and light industrial buildings (see MID Annex 1 Chapter 1.3.3 (a), class E1).
Unless otherwise stated, all pressures given in this document are gauge pressure.
Requirements for electronic indexes, batteries, valves incorporated in the meter and other additional functionalities are given in EN 16314.
Unless otherwise stated in a particular test, the tests are carried out on meters that include additional functionality devices intended by the manufacturer.
Clauses 1 to 9 and Annexes B and C are for design and type testing only.
NOTE   The content of OIML Publication 'International Recommendation R 137' has been taken into account in the drafting of this standard.
If no specific requirements are given for test equipment, the instruments used should be traceable to a national or international reference standard and the uncertainty (2σ) should be better than 1/5 of the maximum value of the parameter to be tested. For differential results the repeatability (2σ)/resolution should be better than 1/5 of the maximum value of the parameter to be tested.

  • Standard
    71 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and tests for the construction, performance, safety and production of class 1,5 diaphragm gas meters (referred to as meters). This applies to meters with co-axial single pipe, or two pipe connections, that are used to measure volumes of fuel gases, which are within the limits of test gases of the 1st, 2nd and 3rd families described in EN 437. The meters have maximum working pressures not exceeding 0,5 bar and maximum actual flow rates not exceeding 160 m3.h−1 over a minimum ambient temperature range of −10 °C to 40 °C and a gas temperature range as specified by the manufacturer with a minimum range of 40 K.
This standard applies to meters with and without built-in temperature conversion that are installed in locations with vibration and shocks of low significance (see MID Annex 1 Chapter 1.3.2 (a), class M1). It also applies to meters in:
-   closed locations (indoor or outdoor with protection as specified by the manufacturer) both with condensing humidity or with non-condensing humidity;
or, if specified by the manufacturer:
-   open locations (outdoor without any covering) both with condensing humidity and with non-condensing humidity;
-   in locations with electromagnetic disturbances corresponding to those likely to be found in residential, commercial and light industrial buildings (see MID Annex 1 Chapter 1.3.3 (a), class E1).
Unless otherwise stated, all pressures given in this document are gauge pressure.
Requirements for electronic indexes, batteries, valves incorporated in the meter and other additional functionalities are given in EN 16314.
Unless otherwise stated in a particular test, the tests are carried out on meters that include additional functionality devices intended by the manufacturer.
Clauses 1 to 9 and Annexes B and C are for design and type testing only.
NOTE   The content of OIML Publication 'International Recommendation R 137' has been taken into account in the drafting of this standard.
If no specific requirements are given for test equipment, the instruments used should be traceable to a national or international reference standard and the uncertainty (2σ) should be better than 1/5 of the maximum value of the parameter to be tested. For differential results the repeatability (2σ)/resolution should be better than 1/5 of the maximum value of the parameter to be tested.

  • Standard
    71 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report gives recommendations to ensure the quality and safety of domestic gas installations. This Technical Report covers pipe work, appliances installation, their combustion air supply and flue products exhaust commissioning, inspection and maintenance activities carried out by operatives.
This document addresses the following three main factors, which have an influence on gas safety in general:
a)   quality and safety of components of gas installations and gas appliances,
b)   quality of the work when gas installations are constructed and commissioned,
c)   inspection and maintenance of installations and gas appliances.
Potential ways in which individual competence of operatives and/or businesses can be ensured and mutually recognized between Member States are considered.
The means of assuring responsible behaviour of consumers is not covered in this document.
It does not address metering or non-domestic (industrial and commercial) installations.

  • Technical report
    19 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report gives recommendations to ensure the quality and safety of domestic gas installations. This Technical Report covers pipe work, appliances installation, their combustion air supply and flue products exhaust commissioning, inspection and maintenance activities carried out by operatives.
This document addresses the following three main factors, which have an influence on gas safety in general:
a)   quality and safety of components of gas installations and gas appliances,
b)   quality of the work when gas installations are constructed and commissioned,
c)   inspection and maintenance of installations and gas appliances.
Potential ways in which individual competence of operatives and/or businesses can be ensured and mutually recognized between Member States are considered.
The means of assuring responsible behaviour of consumers is not covered in this document.
It does not address metering or non-domestic (industrial and commercial) installations.

  • Technical report
    19 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies functional requirements for the design, construction, testing, commissioning/decommissioning, operation, maintenance and where appropriate calibration, together with suitable documented provisions for all new gas measuring systems and any major changes of existing systems.
This European Standard also specifies accuracy classes of measuring systems and thresholds applicable to these classes. Demonstration of compliance is achieved through the selection, installation and operation of appropriate measurement instruments, together with suitable documented provisions for calculations. Examples of demonstration of compliance are provided for each accuracy class; however, they are not prescriptive solutions.
This European Standard is applicable for gases of the 2nd family as classified in EN 437. It is also applicable for treated non-conventional combustible gases complying with EN 437 and for which a detailed technical evaluation of the functional requirements (such as injected biomethane) is performed ensuring there are no other constituents or properties of the gases that can affect the metrological and physical integrity of the measuring systems.
This European Standard can also be used as a guideline for 1st and 3rd family gases as classified in EN 437; however additional considerations should be taken with regard to the different constituents and physical characteristics of the gas family.
This European Standard is not applicable for raw or sour gases.
This European Standard is not applicable for gas measurement in CNG filling station.
This European Standard gives guidelines when designing, installing and operating gas meters with additional functionalities (smart meters).
Unless otherwise specified all pressures used in this European Standard are gauge pressures.
For associated pressure regulating systems the requirements of EN 12186 and/or EN 12279 apply.
For requirements on design, housing, lay-out, materials for components, construction, ventilation, venting and overall safety of gas measuring systems within the scope of this European Standard, EN 15001, EN 12186, EN 12279 and/or EN 1775 apply additionally, where relevant.
This European Standard specifies common basic principles for gas infrastructure. Users of this European Standard should be aware that more detailed national standards and/or codes of practice may exist in the CEN member countries.
This European Standard is intended to be applied in association with these national standards and/or codes of practice setting out the above mentioned basic principles.
In the event of conflicts in terms of more restrictive requirements in national legislation/regulation with the requirements of this European Standard, national legislation/regulation takes precedence as illustrated in CEN/TR 13737 parts 1 and 2.
CEN/TR 13737 (all parts) gives:
   clarification of all legislation/regulations applicable in a member state;
   if appropriate, more restrictive national requirements;
   a national contact point for the latest information.

  • Standard
    86 pages
    English language
    sale 10% off
    e-Library read for
    1 day