Abstract

This part of IEC 60695 summarises the test methods that are used in the assessment of the corrosivity of fire effluent. It presents a brief summary of test methods in common use, either as international standards, national or industry standards. It includes special observations on their relevance, for electrotechnical products and their materials, to real fire scenarios and gives recommendations on their use.

Status
Published
Public Enquiry End Date
31-Mar-2026
Publication Date
04-Nov-2026
Technical Committee
I09 - Imaginarni 09
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
03-Nov-2026
Due Date
08-Jan-2027
Completion Date
05-Nov-2026

Buy Documents

Standard

SIST EN IEC 60695-5-2:2026

English language (27 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN IEC 60695-5-2:2026 is a Slovenian standard published by SIST from IEC 60695-5-2, in the field of fire hazard testing. It summarizes test methods used to assess the corrosivity of fire effluent and explains how relevant those methods are for electrotechnical products and their materials. The document is written for engineers, laboratories, product committees and buyers who need to choose a corrosion test and understand what its result means in practice.

What does SIST EN IEC 60695-5-2:2026 specify?

SIST EN IEC 60695-5-2:2026 specifies a summary of published methods for assessing the corrosivity of fire effluent. It also gives brief notes on how each method relates to real fire scenarios for electrotechnical products and materials, and it recommends how the methods should be used.

The document is organized into six clauses and two informative annexes.

AnnexWhat it covers
Annex ADifferences between acidity and conductivity test methods for aqueous solutions of combustion effluent
Annex BComparative tests and data on repeatability and reproducibility for solutions of combustion gases

Clause 1 gives the scope. Clause 2 lists the normative references. Clause 3 gives terms and definitions. Clause 4 classifies the methods. Clause 5 reviews the published test methods. Clause 6 gives an overview of the methods and the relevance of the data.

What are the key requirements of SIST EN IEC 60695-5-2:2026?

SIST EN IEC 60695-5-2:2026 is mainly a selection and interpretation document rather than a single test method. Its key requirement is that users choose a method that matches the specimen, the fire model and the way corrosivity will be measured.

Clause 4 - choose the method by specimen, fire model and measurement type

Clause 4 classifies the methods by three criteria: the kind of test specimen burned, the physical fire model used, and the nature of the corrosivity measurement. In practice, this means the same material can produce different results depending on how it is burnt and what is measured, so method choice matters before any comparison is made.

Clause 4.2 separates product testing from material or composite sample testing. That matters because a finished product, a cable, a board or a basic material do not always behave the same way in fire.

Clause 4.4 distinguishes three approaches:

  • product as target
  • simulated product as target
  • indirect assessment

This helps the reader decide whether the test is measuring damage on a real item, a surrogate target such as copper, or a gas property such as acidity.

Clause 5.2 - halogen acid in combustion gases

Clause 5.2 reviews IEC 60754-1, which measures halogen acid gas from cable materials. The method uses a small sample in a tube furnace, passes the gases through sodium hydroxide solution, and determines halogen acid by titration.

In practice, this is an analytical chemistry test, not a direct corrosion test. The document states that a high halogen acid result suggests a higher corrosive potential, but a low result does not prove low corrosive potential because other corrosive species are not detected.

Clause 5.3 - acidity and conductivity of combustion gases dissolved in water

Clause 5.3 reviews IEC 60754-2 and related national standards that bubble combustion effluent through water and then measure pH and, in some cases, conductivity. This method is used to estimate potential corrosivity from the aqueous solution created by the combustion gases.

The document notes that the method can rank materials within a similar family, but the result needs an established correlation before it is used as a corrosion indicator for a specific scenario. Annex A compares the main variations of these methods, and Annex B gives repeatability and reproducibility information from comparative tests.

Clause 5.4 - copper corrosion in ASTM D 2671

Clause 5.4 reviews ASTM D 2671 for heat-shrinkable insulating tubing. It describes three procedures: a copper mirror test, a heated copper conductor test, and a cyclical corrosion test with humidity and copper dust.

In practice, these procedures are qualitative and are intended to show whether a specimen can generate species that corrode copper under non-flaming oxidative decomposition. They do not provide a general fire-risk rating.

Clause 5.5 - cone corrosimeter method

Clause 5.5 reviews ISO 11907-4 and ASTM D 5485. The method measures corrosion damage on a metal target by tracking increase in electrical resistance, which is used to calculate metal loss.

This method is relevant when the user needs a direct measure of damage to a target. The document also notes that target thickness matters: results from different target thicknesses should be treated separately, not mixed in one report. For practice, that means the user must match the target to the expected corrosion range.

Clause 6 - use the results with other fire-hazard data

Clause 6 states that the methods should be used to evaluate the relative corrosive effect of fire effluents under controlled conditions. It also says that product committees choosing or adapting a method should make sure it is suitable for the intended use.

The document further explains that corrosivity data should be considered together with other fire-response characteristics such as ignitability, surface spread of flame and rate of heat release. In practice, corrosion ranking alone is not enough to describe actual fire risk.

What terms does SIST EN IEC 60695-5-2:2026 define?

  • corrosion damage - physical or chemical damage, or impaired function, caused by chemical action.
  • corrosion target - a sensor used to determine the degree of corrosion damage under specified test conditions.
  • fire effluent - all gases and aerosols, including suspended particles, created by combustion or pyrolysis and emitted to the environment.
  • fire scenario - a qualitative description of the course of a fire over time, identifying the key events that define it.
  • physical fire model - a laboratory process, including apparatus, environment and procedure, intended to represent a certain phase of a fire.
  • pyrolysis - chemical decomposition of a substance by the action of heat.
  • smoke - the visible part of fire effluent.

Who uses SIST EN IEC 60695-5-2:2026?

SIST EN IEC 60695-5-2:2026 is used by technical committees responsible for electrotechnical products when they choose a corrosion test and set a severity level. It is also useful for designers, materials specialists, test laboratories and quality teams working with products such as cables, printed circuit boards, switchboards, computers and heat-shrinkable tubing.

It matters most where corrosion after fire exposure can affect function, especially in high-value or safety-related products and installations. The document helps users decide which test is relevant, what it can show, and how far the result can be carried into a fire-hazard assessment.

Which standards are used with SIST EN IEC 60695-5-2:2026?

Clause 2 names three normative references:

  • IEC 60695-4 - provides fire-test terminology used throughout the document.
  • IEC 60695-5-1 - gives the general guidance for corrosion damage effects of fire effluent and is the companion part that this document is read with.
  • ISO 13943:2017 - supplies fire-safety vocabulary for terms such as fire effluent, fire scenario and smoke.

The foreword also points users to broader fire-hazard guidance in the IEC 60695-1 series, which supports interpretation of the test methods.

What does the SIST EN IEC 60695-5-2:2026 document contain?

The document contains a classification of test methods, summaries of published procedures, a comparison of how those methods relate to fire stages, and guidance on their relevance. Table 1 links fire stages to characteristics such as temperature, oxygen level and heat flux, using data from ISO 19706:2011.

Table 2 compares the methods by specimen type, measurement type and limitations on use. That table is useful when deciding whether a method is appropriate for indirect gas measurement, simulated-product testing or direct product damage measurement.

Figure 1 shows a typical corrosion target with active and reference elements. Annex A compares how different standards measure acidity and conductivity of aqueous solutions, while Annex B reports comparative pH and resistivity results and the associated repeatability and reproducibility data.

Relations

Effective Date
27-Oct-2026
Effective Date
27-Oct-2026
Effective Date
27-Oct-2026

Buy Documents

Standard

SIST EN IEC 60695-5-2:2026

English language (27 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

SIST EN IEC 60695-5-2:2026 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire hazard testing - Part 5-2: Corrosion damage effects of fire effluent - Summary and relevance of test methods (IEC 60695-5-2:2026)". This standard covers: This part of IEC 60695 summarises the test methods that are used in the assessment of the corrosivity of fire effluent. It presents a brief summary of test methods in common use, either as international standards, national or industry standards. It includes special observations on their relevance, for electrotechnical products and their materials, to real fire scenarios and gives recommendations on their use.

This part of IEC 60695 summarises the test methods that are used in the assessment of the corrosivity of fire effluent. It presents a brief summary of test methods in common use, either as international standards, national or industry standards. It includes special observations on their relevance, for electrotechnical products and their materials, to real fire scenarios and gives recommendations on their use.

SIST EN IEC 60695-5-2:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.99 - Other standards related to protection against fire; 19.020 - Test conditions and procedures in general; 29.020 - Electrical engineering in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN IEC 60695-5-2:2026 has the following relationships with other standards: It is inter standard links to SIST EN ISO 13943:2017, SIST EN IEC 60695-4:2021, SIST EN IEC 60695-5-1:2022. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN IEC 60695-5-2:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2026
Preskušanje požarne ogroženosti - 5-2. del: Poškodbe zaradi korozijskega učinka
izžarevanja ognja - Povzetek in relevantnost preskusnih metod (IEC 60695-5-
2:2026)
Fire hazard testing - Part 5-2: Corrosion damage effects of fire effluent - Summary and
relevance of test methods (IEC 60695-5-2:2026)
Prüfungen zur Beurteilung der Brandgefahr - Teil 5-2: Korrosionsschädigung durch
flüchtige Verbrennungsprodukte - Zusammenfassung und Anwendbarkeit der
Prüfverfahren (IEC 60695-5-2:2026)
Essais relatifs aux risques du feu - Partie 5-2: Effets des dommages de corrosion des
effluents du feu - Récapitulatif et pertinence des méthodes d'essai (IEC 60695-5-2:2026)
Ta slovenski standard je istoveten z: EN IEC 60695-5-2:2026
ICS:
13.220.99 Drugi standardi v zvezi z Other standards related to
varstvom pred požarom protection against fire
19.020 Preskuševalni pogoji in Test conditions and
postopki na splošno procedures in general
29.020 Elektrotehnika na splošno Electrical engineering in
general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 60695-5-2

NORME EUROPÉENNE
EUROPÄISCHE NORM October 2026
ICS 29.020; 19.020; 13.220.99
English Version
Fire hazard testing - Part 5-2: Corrosion damage effects of fire
effluent - Summary and relevance of test methods
(IEC 60695-5-2:2026)
Essais relatifs aux risques du feu - Partie 5-2: Effets des Prüfungen zur Beurteilung der Brandgefahr - Teil 5-2:
dommages de corrosion des effluents du feu - Récapitulatif Korrosionsschädigung durch flüchtige
et pertinence des méthodes d'essai Verbrennungsprodukte - Zusammenfassung und
(IEC 60695-5-2:2026) Anwendbarkeit der Prüfverfahren
(IEC 60695-5-2:2026)
This European Standard was approved by CENELEC on 2026-10-20. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2026 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 60695-5-2:2026 E

European foreword
The text of document 89/1672/FDIS, future edition 1 of IEC 60695-5-2, prepared by TC 89 "Fire
hazard testing" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2027-10-31
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2029-10-31
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document is read in conjunction with EN IEC 60695-5-1.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 60695-5-2:2026 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standard indicated:
IEC 60695-1-10 NOTE Approved as EN 60695-1-10
IEC 60695-1-11 NOTE Approved as EN 60695-1-11
IEC 60695-1-12 NOTE Approved as EN IEC 60695-1-12
IEC 60754-1 NOTE Approved as EN 60754-1
IEC 60754-2 NOTE Approved as EN 60754-2
IEC 60754-3 NOTE Approved as EN IEC 60754-3
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod),
the relevant EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cencenelec.eu.
Publication Year Title EN/HD Year
IEC 60695-4 - Fire hazard testing - Part 4: Terminology EN IEC 60695-4 -
concerning fire tests for electrotechnical
products
IEC 60695-5-1 - Fire hazard testing - Part 5-1: Corrosion EN IEC 60695-5-1 -
damage effects of fire effluent - General
guidance
ISO 13943 2017 Fire safety - Vocabulary EN ISO 13943 2017

This standard has been withdrawn and replaced with EN ISO 13943:2023.
IEC 60695-5-2 ®
Edition 1.0 2026-09
INTERNATIONAL
STANDARD
Fire hazard testing -
Part 5-2: Corrosion damage effects of fire effluent - Summary and relevance of
test methods
ICS 29.020; 19.020; 13.220.99 ISBN 978-2-8327-1506-2

IEC 60695-5-2:2026-09(en)
IEC 60695-5-2:2026 © IEC 2026
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Classification of test methods . 7
4.1 General . 7
4.2 Test specimen . 7
4.2.1 Product testing . 7
4.2.2 Material or composite sample testing . 8
4.3 The physical fire model . 8
4.4 The nature of the corrosivity measurement . 10
4.4.1 Product as target . 10
4.4.2 Simulated product as target . 10
4.4.3 Material as target. 10
4.4.4 Indirect assessment . 10
5 Published test methods . 10
5.1 General . 10
5.2 Tests for the determination of halogen acid in combustion gases . 10
5.2.1 Standards . 10
5.2.2 Purpose and principle . 10
5.2.3 Test specimen . 11
5.2.4 Test method . 11
5.2.5 Repeatability and reproducibility . 11
5.2.6 Relevance of test data to corrosion hazard assessment . 11
5.3 Tests for the determination of the acidity and conductivity of combustion
gases dissolved in an aqueous solution . 11
5.3.1 Standards . 11
5.3.2 Purpose and principle . 11
5.3.3 Test specimen . 12
5.3.4 Test method . 12
5.3.5 Repeatability and reproducibility . 12
5.3.6 Relevance of test data to corrosion hazard assessment . 12
5.4 Tests for the determination of corrosive gases by evaluation of copper
corrosion. 12
5.4.1 Purpose and principle . 12
5.4.2 Test specimen . 12
5.4.3 Test methods . 13
5.4.4 Special observations . 13
5.4.5 Repeatability and reproducibility . 13
5.4.6 Relevance of test data to corrosion hazard assessment . 13
5.5 Cone corrosimeter method . 13
5.5.1 Standards . 13
5.5.2 Purpose and principle . 13
5.5.3 Test specimen . 13
5.5.4 Corrosion target . 14
5.5.5 Test method . 14
IEC 60695-5-2:2026 © IEC 2026
5.5.6 Special observation . 15
5.5.7 Repeatability and reproducibility . 15
5.5.8 Relevance of test data to corrosion hazard assessment . 15
6 Overview of methods and relevance of data . 15
Annex A (informative) Acidity and conductivity of aqueous solutions – Test methods . 18
Annex B (informative) Determination of repeatability and reproducibility –
Comparative tests of solutions of combustion gases . 19
Bibliography . 23

Figure 1 – Schematic drawing of a typical corrosion target of defined metal thickness . 15

Table 1 – Characteristics of fire stages (from Table 1 in ISO 19706:2011 [12]) . 9
Table 2 – Overview of corrosivity test methods . 17
Table A.1 – Test methods for the measurement of acidity and conductivity of aqueous
solutions obtained after bubbling combustion effluent through water . 18
Table B.1 – Determination of repeatability and reproducibility – Comparative pH tests
on solutions of combustion gases . 20
Table B.2 – Determination of repeatability and reproducibility – Comparative resistivity
tests on solutions of combustion gases . 21
Table B.3 – Results obtained on brominated polycarbonate . 22

IEC 60695-5-2:2026 © IEC 2026
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
Fire hazard testing -
Part 5-2: Corrosion damage effects of fire effluent -
Summary and relevance of test methods

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
IEC 60695-5-2 has been prepared by IEC technical committee 89: Fire hazard testing. It is an
International Standard.
This first edition cancels and replaces the third edition of IEC TS 60695-5-2 published in 2021.
This edition constitutes a technical revision. This edition includes the following significant
technical changes with respect to IEC TS 60695-5-2:
a) 4.4, The nature of the corrosivity measurement, has been added to follow recent
technological developments;
b) 5.2, Tests for the determination of halogen acid in combustion gases, has been updated
following the recent development of IEC 60754.
IEC 60695-5-2:2026 © IEC 2026
The text of this International Standard is based on the following documents:
Draft Report on voting
89/1672/FDIS 89/1680/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
This International Standard is to be read in conjunction with IEC 60695-5-1.
A list of all parts in the IEC 60695 series, published under the general title Fire hazard testing,
can be found on the IEC website.
IEC 60695-5 consists of the following parts:
Part 5-1: Corrosion damage effects of fire effluent - General guidance
Part 5-2: Corrosion damage effects of fire effluent - Summary and relevance of test methods
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
– reconfirmed,
– withdrawn, or
– revised.
IEC 60695-5-2:2026 © IEC 2026
INTRODUCTION
In the design of an electrotechnical product the risk of fire and the potential hazards associated
with fire need to be considered. In this respect the objective of component, circuit and
equipment design, as well as the choice of materials, is to reduce the risk of fire to a tolerable
level even in the event of reasonably foreseeable (mis)use, malfunction or failure.
IEC 60695-1-10 [1] , IEC 60695-1-11 [2] and IEC 60695-1-12 [3] provide guidance on how this
is to be accomplished.
Fires involving electrotechnical products can also be initiated from external non-electrical
sources. Considerations of this nature are dealt with in an overall fire hazard assessment.
The aim of the IEC 60695 series is to save lives and property by reducing the number of fires
or reducing the consequences of the fire. This can be accomplished by:
– trying to prevent ignition caused by an electrically energised component part and, in the
event of ignition, to confine any resulting fire within the bounds of the enclosure of the
electrotechnical product.
– trying to minimise flame spread beyond the product's enclosure and to minimise the harmful
effects of fire effluents including heat, smoke, and toxic or corrosive combustion products.
All fire effluents are corrosive to some degree and the level of potential to corrode depends on
the nature of the fire, the combination of combustible materials involved in the fire, the nature
of the substrate under attack, and the temperature and relative humidity of the environment in
which the corrosion is taking place. There is no evidence that fire effluent from electrotechnical
products offers greater risk of corrosion damage than the fire effluent from other products such
as furnishings, building materials, etc.
The performance of electrical and electronic components can be adversely affected by
corrosion damage when subjected to fire effluent. A wide variety of combinations of small
quantities of effluent gases, smoke particles, moisture and temperature can provide conditions
for electrical component or system failures from breakage, overheating or shorting.
Evaluation of potential corrosion damage is particularly important for high value and safety-
related electrotechnical products and installations.
Technical committees responsible for the products will choose the test(s) and specify the level
of severity.
The study of corrosion damage requires an interdisciplinary approach involving chemistry,
electricity, physics, mechanical engineering, metallurgy and electrochemistry. In the
preparation of this document, all of the above have been considered.
IEC 60695-5-1 defines the scope of the guidance and indicates the field of application.
IEC 60695-5-2 provides a summary of test methods including relevance and usefulness.

___________
Numbers in square brackets refer to the bibliography.
IEC 60695-5-2:2026 © IEC 2026
1 Scope
This part of IEC 60695 summarises the test methods that are used in the assessment of the
corrosivity of fire effluent. It presents a brief summary of test methods in common use, either
as international standards, national or industry standards. It includes special observations on
their relevance, for electrotechnical products and their materials, to real fire scenarios and gives
recommendations on their use.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60695-4, Fire hazard testing - Part 4: Terminology concerning fire tests
IEC 60695-5-1, Fire hazard testing - Part 5-1: Corrosion damage effects of fire effluent -
General guidance
ISO 13943:2017, Fire safety - Vocabulary
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60695-4 and
ISO 13943:2017 (some of which are reproduced below) apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
– IEC Electropedia: available at https://www.electropedia.org/
– ISO Online browsing platform: available at https://www.iso.org/obp
3.1
corrosion damage
physical and/or chemical damage or impaired function caused by chemical action
[SOURCE: ISO 13943:2017, 3.69]
3.2
corrosion target
sensor used to determine the degree of corrosion damage (3.1), under specified test conditions
Note 1 to entry: This sensor can be a product or a component. It can also be a reference material or object used to
simulate the behaviour of a product or a component.
[SOURCE: ISO 13943:2017, 3.70]
3.3
fire effluent
all gases and aerosols, including suspended particles created by combustion or pyrolysis (3.6)
and emitted to the environment
[SOURCE: ISO 13943:2017, 3.123]
IEC 60695-5-2:2026 © IEC 2026
3.4
fire scenario
qualitative description of the course of a fire with respect to time, identifying key events that
characterize the studied fire and differentiate it from other possible fires
Note 1 to entry: See fire scenario cluster (ISO 13943:2017, 3.154) and representative fire scenario
(ISO 13943:2017, 3.153).
Note 2 to entry: It typically defines the ignition and fire growth processes, the fully developed fire stage, the fire
decay stage, and the environment and systems that will impact on the course of the fire.
Note 3 to entry: Unlike deterministic fire analysis, where fire scenarios are individually selected and used as design
fire scenarios, in fire risk assessment, fire scenarios are used as representative fire scenarios within fire scenario
clusters.
[SOURCE: ISO 13943:2017, 3.152]
3.5
physical fire model
laboratory process, including the apparatus, the environment and the fire test procedure
intended to represent a certain phase of a fire
[SOURCE: ISO 13943:2017, 3.298]
3.6
pyrolysis
chemical decomposition of a substance by the action of heat
Note 1 to entry: Pyrolysis is often used to refer to a stage of fire before flaming combustion has begun.
Note 2 to entry: In fire science, no assumption is made about the presence or absence of oxygen.
[SOURCE: ISO 13943:2017, 3.316]
3.7
smoke
visible part of a fire effluent (3.3)
[SOURCE: ISO 13943:2017, 3.347]
4 Classification of test methods
4.1 General
The test methods included in this document can generally be classified according to the
following three criteria:
a) the nature of the test specimen which is burnt;
b) the physical fire model used in the test;
c) the nature of the measurement of corrosivity.
4.2 Test specimen
4.2.1 Product testing
The test specimen for product testing shall be a finished manufactured product or a
representative portion taken from it. Examples include a printed circuit board, a switchboard, a
computer or a cable.
IEC 60695-5-2:2026 © IEC 2026
4.2.2 Material or composite sample testing
The test specimen for material or composite testing shall consists of a single material (solid or
liquid) or of a combination of different materials
4.3 The physical fire model
Test methods use a wide variety of heat sources and geometries. The amount, the rate of
production and the corrosive nature of fire effluent including smoke released from a given
material or product is not an inherent property of that material or product but is critically
dependent on the conditions under which that material or product is burnt. In a fire scenario or
a fire test, the chemical nature of the fuel, the decomposition temperature and the amount of
ventilation are the main variables which affect the composition of fire effluent.
It is critical to show that the test conditions defined in a standardized test method are relevant
to, and replicate, the desired stage of a real fire. ISO has published a general classification of
fire stages in ISO 19706 [12], shown in Table 1. The important factors affecting effluent
production are oxygen concentration, irradiance and temperature.

IEC 60695-5-2:2026 © IEC 2026
Table 1 –
...