M/117 - CPD: Resistance to fire
Horizontal complement to the mandates to CEN/CENELEC concerning the execution of standardization work for the valuation of construction products and elements in respect of their resistance to fire
General Information
This document is applicable to all coverings, including but not limited to renderings, boards with and without air gaps and installed with various support systems. This document specifies a method for determining the ability of a covering to protect underlying materials against damage during a specified fire exposure.
The document is not used for the evaluation of fire resistance classifications (e.g. EI, EW, E) or reaction to fire classifications (specified in EN 13501-1).
The fire protection ability is influenced by the presence of combustible materials in the cavity behind the covering. The applicability of the results is limited according to the quantity and position of such combustible materials within that cavity.
NOTE The amount of combustible materials permissible in the cavity is generally laid down in national regulations.
- Standard32 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to hinged and pivoted doors, doorsets and door assemblies with glass based leaves. Throughout this document the term “doorset” will be used to cover doors, doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1 and/or EN 1634-3 and/or EN 1191.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
— integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
— ambient temperature smoke control (Sa) and medium temperature smoke control (S200) classifications;
— ability to close and durability of self-closing (C0 – C5);
— glazed elements;
— side, transom or over panels;
— items of building hardware;
— decorative and protective finishes;
— intumescent seals and non-intumescent (e.g. smoke, draught or acoustic) seals;
— alternative supporting construction(s).
This document does not apply to horizontal doorsets and windows.
- Standard120 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to hinged and pivoted doors, doorsets and door assemblies with glass based leaves. Throughout this document the term “doorset” will be used to cover doors, doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1 and/or EN 1634-3 and/or EN 1191.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
— integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
— ambient temperature smoke control (Sa) and medium temperature smoke control (S200) classifications;
— ability to close and durability of self-closing (C0 – C5);
— glazed elements;
— side, transom or over panels;
— items of building hardware;
— decorative and protective finishes;
— intumescent seals and non-intumescent (e.g. smoke, draught or acoustic) seals;
— alternative supporting construction(s).
This document does not apply to horizontal doorsets and windows.
- Standard120 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to all coverings, including but not limited to renderings, boards with and without air gaps and installed with various support systems. This document specifies a method for determining the ability of a covering to protect underlying materials against damage during a specified fire exposure.
The document is not used for the evaluation of fire resistance classifications (e.g. EI, EW, E) or reaction to fire classifications (specified in EN 13501-1).
The fire protection ability is influenced by the presence of combustible materials in the cavity behind the covering. The applicability of the results is limited according to the quantity and position of such combustible materials within that cavity.
NOTE The amount of combustible materials permissible in the cavity is generally laid down in national regulations.
- Standard32 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the procedure for classification of the resistance to fire performance of construction products and building elements used as components of building service installations, using data from fire resistance tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
Construction products or building elements for use in ventilation systems include (excluding smoke control system):
— fire resisting ventilation ducts;
— fire dampers.
Construction products or building elements for use in or as cables systems:
— unprotected electric cables with intrinsic fire resistance;
— fire protective systems for cable systems and associated components.
Relevant test methods which have been prepared for these construction products/building elements are listed in Clause 2.
NOTE Cables associated with fire dampers are not generally covered by this document unless there is a local regulation that requires it.
- Standard29 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the procedure for classification of the resistance to fire performance of construction products and building elements used as components of building service installations, using data from fire resistance tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
Construction products or building elements for use in ventilation systems include (excluding smoke control system):
— fire resisting ventilation ducts;
— fire dampers.
Construction products or building elements for use in or as cables systems:
— unprotected electric cables with intrinsic fire resistance;
— fire protective systems for cable systems and associated components.
Relevant test methods which have been prepared for these construction products/building elements are listed in Clause 2.
NOTE Cables associated with fire dampers are not generally covered by this document unless there is a local regulation that requires it.
- Standard29 pagesEnglish languagesale 10% offe-Library read for1 day
This test method specifies methods for determining the fire resistance of open-state cavity barriers and is to be used in conjunction with EN 1363-1.
This document is applicable to non-loadbearing vertically or horizontally oriented open-state cavity barriers, which are designed to close and provide fire separation in the event of fire.
Open-state cavity barriers in facades, where the fire exposure comes as a result of a breaking window and allowing a developed fire to come into contact with the façade, can be tested to the optional "flame" criteria.
This document is not applicable to cavity barriers containing penetration seals, which are covered by EN 1366-3.
This document is not applicable to closed cavity barriers, which are covered by EN 1366-4.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This test method specifies methods for determining the fire resistance of open-state cavity barriers and is to be used in conjunction with EN 1363-1.
This document is applicable to non-loadbearing vertically or horizontally oriented open-state cavity barriers, which are designed to close and provide fire separation in the event of fire.
Open-state cavity barriers in facades, where the fire exposure comes as a result of a breaking window and allowing a developed fire to come into contact with the façade, can be tested to the optional "flame" criteria.
This document is not applicable to cavity barriers containing penetration seals, which are covered by EN 1366-3.
This document is not applicable to closed cavity barriers, which are covered by EN 1366-4.
- Standard18 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.
- Standard194 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a service or services. Penetration seals used to seal gaps around chimneys, air ventilation systems, fire rated ventilation ducts, fire rated service ducts, shafts and smoke extraction ducts as well as combined penetration seals are excluded from this part of the EN 1366 series.
NOTE EN 15882-5 [6] deals with penetration seals including ducts and dampers.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. These simulate the interaction between the test specimen and the separating element into which the sealing system is to be installed in practice.
This part of the EN 1366 series is intended to be used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the penetration seal, of the penetrating service or services and of the separating element in the surrounding area of the penetration seal.
No information can be implied by the test concerning the influence of the inclusion of such penetrations and penetration seals on the loadbearing capacity of the separating element.
It is assumed that in each case the lintel above a penetration seal in the wall is designed in hot and cold state in a way that it does not apply any additional vertical load on the penetration seal.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the penetration seal to withstand stress caused by movements or displacements of the penetrating services.
The risk of spread of fire downwards caused by burning material, which drips e.g. through a pipe downwards to floors below, is at present excluded from this document.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of pipes in case of fire.
Tests in accordance with this part of the EN 1366 series of pipe penetration seals for pipes of pneumatic dispatch systems, pressurized air systems, etc. simulate a situation where the systems are shut off in case of fire.
Explanatory notes to this test method are given in Annex H.
All values given without tolerances in this document are nominal ones unless otherwise specified.
All pipe diameters are outside diameters unless otherwise specified.
- Standard194 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers single and double leaf, hinged and pivoted, steel based doorsets except steel doorsets with metal framed door leaves covered by EN 15269-5. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
- integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
- door leaf;
- side panels, transom panels, flush overpanels;
- air transfer grilles (e.g. ventilation grilles/louvres);
- components (e.g. frame/suspension system) fixed to the supporting construction (e.g. wall/ceiling);
- glazing within the doorset (e.g. for door leaf, side, transom and flush overpanels);
- items of building hardware;
- decorative and protective finishes;
- intumescent seals, strips and non-intumescent (smoke, draught or acoustic) seals;
- alternative supporting construction(s).
This document does not cover horizontally installed doorsets (e.g. traps).
The effect on the classification ‘C’ for the doorsets following an extended application process is not addressed in this document.
- Standard141 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers single and double leaf, hinged and pivoted, steel based doorsets except steel doorsets with metal framed door leaves covered by EN 15269-5. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests, the extended application may cover all or some of the following examples:
- integrity (E), integrity and radiation (EW) or integrity and insulation (EI1 or EI2) classification;
- door leaf;
- side panels, transom panels, flush overpanels;
- air transfer grilles (e.g. ventilation grilles/louvres);
- components (e.g. frame/suspension system) fixed to the supporting construction (e.g. wall/ceiling);
- glazing within the doorset (e.g. for door leaf, side, transom and flush overpanels);
- items of building hardware;
- decorative and protective finishes;
- intumescent seals, strips and non-intumescent (smoke, draught or acoustic) seals;
- alternative supporting construction(s).
This document does not cover horizontally installed doorsets (e.g. traps).
The effect on the classification ‘C’ for the doorsets following an extended application process is not addressed in this document.
- Standard141 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a test method for determining the fire resistance of smoke extraction ducts. It is applicable only to smoke extraction ducts that pass through another fire compartment apart from the compartment from where smoke needs to be extracted in case of fire. It represents fire exposure of a fully developed fire.
This method of test is only applicable to fire resistant ventilation ducts (same construction) with the following classification according to EN 13501-3:
- fire from inside and outside i ↔ o;
- applicable to a pressure difference up to 500 Pa in fire conditions;
NOTE 1 It is assumed that the duct A test(s) in accordance with EN 1366-1 has been performed with an under-pressure of minimum 500 Pa.
- with integrity (E) and insulation (I) criteria equal to or higher than the intended classification for the smoke extraction duct.
For the purposes of the test described in this document, the duct is referred to as duct C.
This test method has been designed to cover both vertical and horizontal smoke extraction ducts. A vertical system need not be evaluated to this method provided that:
- both horizontal (ho) and vertical (ve) classification according to EN 13501-3 has been obtained for the ventilation duct;
- it has been tested in a horizontal orientation to this method.
If the ventilation duct in practise is only used for vertical applications in smoke extraction systems, only vertical (ve) classification is obtained in accordance with EN 13501-3 and tested only in a vertical orientation to this test method.
This test method is suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
NOTE 2 Reaction with components of the duct can affect the oxygen concentration inside the duct leading to inaccurate calculation of the leakage rate. If it is determined this has happened refer to Annex D.
This document applies to four sided rectangular and circular ducts only (with fire exposure on all sides). Ducts that utilize elements of construction for one, two or three sides are not covered. An alternative test method for one, two and three sided ducts will be developed separately.
- Standard58 pagesEnglish languagesale 10% offe-Library read for1 day
This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.
- Standard49 pagesEnglish languagesale 10% offe-Library read for1 day
This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.
- Standard49 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a test method for determining the fire resistance of smoke extraction ducts. It is applicable only to smoke extraction ducts that pass through another fire compartment apart from the compartment from where smoke needs to be extracted in case of fire. It represents fire exposure of a fully developed fire.
This method of test is only applicable to fire resistant ventilation ducts (same construction) with the following classification according to EN 13501-3:
- fire from inside and outside i ↔ o;
- applicable to a pressure difference up to 500 Pa in fire conditions;
NOTE 1 It is assumed that the duct A test(s) in accordance with EN 1366-1 has been performed with an under-pressure of minimum 500 Pa.
- with integrity (E) and insulation (I) criteria equal to or higher than the intended classification for the smoke extraction duct.
For the purposes of the test described in this document, the duct is referred to as duct C.
This test method has been designed to cover both vertical and horizontal smoke extraction ducts. A vertical system need not be evaluated to this method provided that:
- both horizontal (ho) and vertical (ve) classification according to EN 13501-3 has been obtained for the ventilation duct;
- it has been tested in a horizontal orientation to this method.
If the ventilation duct in practise is only used for vertical applications in smoke extraction systems, only vertical (ve) classification is obtained in accordance with EN 13501-3 and tested only in a vertical orientation to this test method.
This test method is suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
NOTE 2 Reaction with components of the duct can affect the oxygen concentration inside the duct leading to inaccurate calculation of the leakage rate. If it is determined this has happened refer to Annex D.
This document applies to four sided rectangular and circular ducts only (with fire exposure on all sides). Ducts that utilize elements of construction for one, two or three sides are not covered. An alternative test method for one, two and three sided ducts will be developed separately.
- Standard58 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests.
NOTE Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.
- Standard99 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests.
NOTE Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.
- Standard99 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the procedure for classification of construction products and building elements using data from fire resistance and/or smoke leakage/control tests and/or mechanical tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
This document deals with:
a) loadbearing elements without a fire separating function:
- walls;
- floors;
- roofs;
- beams;
- columns;
- balconies;
- walkways;
- stairs.
b) loadbearing elements with a fire separating function, with or without glazing, services and fixtures:
- walls;
- floors;
- roofs;
- raised floors.
c) products and systems for protecting elements or parts of the works:
- ceilings with no independent fire resistance;
- fire protective coatings, claddings and screens;
d) non-loadbearing elements or parts of works, with or without glazing, services and fixtures:
- partitions;
- facades (curtain walls) and external walls;
- ceilings with independent fire resistance;
- raised floors;
- fire resisting doorsets, shutter assemblies and openable windows and their closing devices;
- smoke control doorsets and shutter assemblies and their closing devices;
- conveyor systems and their closures;
- penetration seals;
- linear joint seals;
- combined penetration seals;
- service ducts and shafts;
- air transfer grilles.
- chimneys.
e) wall and ceiling coverings with fire protection ability.
f) lift landing doors which are tested according to EN 81-58 are excluded from this document. Lift landing doors which are tested in accordance with EN 1634-1 are classified in accordance with 7.5.5.
Relevant test methods which have been prepared for these construction products are listed in Clauses 2 and 7.
- Standard86 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies the procedure for classification of construction products and building elements using data from fire resistance and/or smoke leakage/control tests and/or mechanical tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
This document deals with:
a) loadbearing elements without a fire separating function:
- walls;
- floors;
- roofs;
- beams;
- columns;
- balconies;
- walkways;
- stairs.
b) loadbearing elements with a fire separating function, with or without glazing, services and fixtures:
- walls;
- floors;
- roofs;
- raised floors.
c) products and systems for protecting elements or parts of the works:
- ceilings with no independent fire resistance;
- fire protective coatings, claddings and screens;
d) non-loadbearing elements or parts of works, with or without glazing, services and fixtures:
- partitions;
- facades (curtain walls) and external walls;
- ceilings with independent fire resistance;
- raised floors;
- fire resisting doorsets, shutter assemblies and openable windows and their closing devices;
- smoke control doorsets and shutter assemblies and their closing devices;
- conveyor systems and their closures;
- penetration seals;
- linear joint seals;
- combined penetration seals;
- service ducts and shafts;
- air transfer grilles.
- chimneys.
e) wall and ceiling coverings with fire protection ability.
f) lift landing doors which are tested according to EN 81-58 are excluded from this document. Lift landing doors which are tested in accordance with EN 1634-1 are classified in accordance with 7.5.5.
Relevant test methods which have been prepared for these construction products are listed in Clauses 2 and 7.
- Standard86 pagesEnglish languagesale 10% offe-Library read for1 day
This document gives the procedures for preparing standards and reports following the extended application (EXAP) process using the results of reaction to fire tests, fire resistance tests (including other performance characteristics e.g. smoke leakage/control and/or durability of self-closing), and external fire exposure to roof tests undertaken for fire classification of products and product families in accordance with the various parts of EN 13501. EXAP rules limit the number of tests required by implementing methods to determine the fire classification of a range of products (e.g. range of product, larger dimensions etc.) and EXAP rules form a standardized technical agreement on the parameter changes.
The fundamental concept of EXAP is the development of safe methods that provide extensions to the scope of the tested product while maintaining the required classification for the product. Test reports constitute the basis of an EXAP report.
This document makes reference to ‘extended application standards’ throughout; wherever this term is used it refers to either a standard prepared by CEN/TC 127 ‘Fire safety in buildings’ or the relevant product standard which includes information on extended application.
The European system currently permits extended application rules to be included in technical specifications. CEN Technical Committees and EOTA Working groups producing these rules are asked to seek the guidance of CEN/TC 127 to ensure that their rules comply with standards prepared by CEN/TC 127. In cases where extended application rules in harmonized EN product standards and ETAs do not comply with standards prepared by CEN/TC 127 the CEN BT are informed.
This document does not cover the incorporation of the product into the construction works that is justified by national rules.
Expert judgements (i.e. an opinion that is not considered/covered by an EXAP standard and only based on the experience of one individual) do not form part of this process.
- Standard26 pagesEnglish languagesale 10% offe-Library read for1 day
This document gives the procedures for preparing standards and reports following the extended application (EXAP) process using the results of reaction to fire tests, fire resistance tests (including other performance characteristics e.g. smoke leakage/control and/or durability of self-closing), and external fire exposure to roof tests undertaken for fire classification of products and product families in accordance with the various parts of EN 13501. EXAP rules limit the number of tests required by implementing methods to determine the fire classification of a range of products (e.g. range of product, larger dimensions etc.) and EXAP rules form a standardized technical agreement on the parameter changes.
The fundamental concept of EXAP is the development of safe methods that provide extensions to the scope of the tested product while maintaining the required classification for the product. Test reports constitute the basis of an EXAP report.
This document makes reference to ‘extended application standards’ throughout; wherever this term is used it refers to either a standard prepared by CEN/TC 127 ‘Fire safety in buildings’ or the relevant product standard which includes information on extended application.
The European system currently permits extended application rules to be included in technical specifications. CEN Technical Committees and EOTA Working groups producing these rules are asked to seek the guidance of CEN/TC 127 to ensure that their rules comply with standards prepared by CEN/TC 127. In cases where extended application rules in harmonized EN product standards and ETAs do not comply with standards prepared by CEN/TC 127 the CEN BT are informed.
This document does not cover the incorporation of the product into the construction works that is justified by national rules.
Expert judgements (i.e. an opinion that is not considered/covered by an EXAP standard and only based on the experience of one individual) do not form part of this process.
- Standard26 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers steel rolling shutters as covered by EN 15269 10 or EN 15269 20.
This document prescribes the methodology for extending the application of test results obtained from durability self-closing test(s) conducted in accordance with EN 16034.
Subject to the completion of the appropriate self-closing test or tests, the extended application could cover all or some of the following non-exhaustive list:
— shutter curtain;
— wall/ceiling fixed elements (frame/suspension system);
— decorative finishes;
— intumescent, smoke, draught or acoustic seals;
— alternative supporting construction(s).
- Standard73 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to the following types of steel based doorsets: horizontally sliding single and double leaf doorsets, horizontally sliding single and double leaf telescopic doorsets, vertically sliding single leaf doorsets and vertically sliding single leaf telescopic doorsets as covered by EN 15269-7 or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 12605:2000 and/or EN 1191.
Subject to the completion of the appropriate durability of self-closing test or tests, the extended application can cover all or some of the following non-exhaustive list:
- door leaf (of the sliding doorset and its pass door);
- integrated pass doors;
- wall or ceiling fixed parts or items of the doorset, e.g. frame or suspension systems;
- ventilation grilles and/or louvres;
- glazing for door leaf;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard60 pagesEnglish languagesale 10% offe-Library read for1 day
This document provides the reaction to fire classification procedure for electric cables.
NOTE For the purpose of this document, the term "electric cables" covers all power, control and communication cables, including optical fibre cables.
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a method of test for determining the reaction to fire performance of construction products excluding floorings, and excluding products which are indicated in Delegated Regulation (EU) 2016/364, when exposed to thermal attack by a single burning item (SBI). The calculation procedures are given in Annex A. Information on the precision of the test method is given in Annex B. The calibration procedures are given in Annexes C and D, of which Annex C is a normative annex.
NOTE This document has been developed to determine the reaction to fire performance of essentially flat products. The treatment of some families of products, e.g. linear products (pipes, ducts, cables etc.), can need special rules.
- Standard101 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers hinged or pivoted doorsets and door assemblies with wood-based door leaves and/or timber framed glazed door leaves and openable timber framed windows. Throughout this document, the term “doorset” will be used to cover doorsets, door assemblies and openable windows. It prescribes the rules for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
This document covers only doorsets with wood-based or metal frames. The door leaves are comprised of wood-based perimeter framing and wood-based structural facings.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classifications;
- glazing within the doorset, e.g. side and over panels, vision panels and framed glazed doorsets;
- air transfer grilles (e.g. ventilation grilles/louvres);
- side, transom or over panels;
- items of building hardware;
- decorative and protective finishes;
- intumescent strips and non-intumescent seals (e.g. smoke, draught or acoustic seals);
- alternative supporting construction(s).
This document covers only the effect on the fire resistance classifications E, EW, EI1 and EI2.
This document does not cover horizontal doorsets.
- Standard198 pagesEnglish languagesale 10% offe-Library read for1 day
This document provides the reaction to fire classification procedure for electric cables.
NOTE For the purpose of this document, the term "electric cables" covers all power, control and communication cables, including optical fibre cables.
- Standard31 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers steel rolling shutters as covered by EN 15269 10 or EN 15269 20.
This document prescribes the methodology for extending the application of test results obtained from durability self-closing test(s) conducted in accordance with EN 16034.
Subject to the completion of the appropriate self-closing test or tests, the extended application could cover all or some of the following non-exhaustive list:
— shutter curtain;
— wall/ceiling fixed elements (frame/suspension system);
— decorative finishes;
— intumescent, smoke, draught or acoustic seals;
— alternative supporting construction(s).
- Standard73 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers single and double leaf, hinged and pivoted, steel based doorsets as covered by EN 15269-2 and/or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 1191 and or EN 12605:2000, as appropriate.
Subject to the completion of the appropriate durability of self-closing test(s), the extended application can cover all or some of the following non-exhaustive list:
- door leaf;
- side, transom and/or overpanels;
- ventilation grilles and/or louvres;
- wall or ceiling fixed parts or items of the doorset, e.g. frame or suspensions systems;
- glazing for door leaf, side, transom and flush over panels;
- items of building hardware;
- decorative finishes;
- intumescent strips, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard88 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to the following types of steel based doorsets: horizontally sliding single and double leaf doorsets, horizontally sliding single and double leaf telescopic doorsets, vertically sliding single leaf doorsets and vertically sliding single leaf telescopic doorsets as covered by EN 15269-7 or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 12605:2000 and/or EN 1191.
Subject to the completion of the appropriate durability of self-closing test or tests, the extended application can cover all or some of the following non-exhaustive list:
- door leaf (of the sliding doorset and its pass door);
- integrated pass doors;
- wall or ceiling fixed parts or items of the doorset, e.g. frame or suspension systems;
- ventilation grilles and/or louvres;
- glazing for door leaf;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard60 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers hinged or pivoted doorsets and door assemblies with wood-based door leaves and/or timber framed glazed door leaves and openable timber framed windows. Throughout this document, the term “doorset” will be used to cover doorsets, door assemblies and openable windows. It prescribes the rules for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
This document covers only doorsets with wood-based or metal frames. The door leaves are comprised of wood-based perimeter framing and wood-based structural facings.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classifications;
- glazing within the doorset, e.g. side and over panels, vision panels and framed glazed doorsets;
- air transfer grilles (e.g. ventilation grilles/louvres);
- side, transom or over panels;
- items of building hardware;
- decorative and protective finishes;
- intumescent strips and non-intumescent seals (e.g. smoke, draught or acoustic seals);
- alternative supporting construction(s).
This document covers only the effect on the fire resistance classifications E, EW, EI1 and EI2.
This document does not cover horizontal doorsets.
- Standard198 pagesEnglish languagesale 10% offe-Library read for1 day
This document covers single and double leaf, hinged and pivoted, steel based doorsets as covered by EN 15269-2 and/or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 1191 and or EN 12605:2000, as appropriate.
Subject to the completion of the appropriate durability of self-closing test(s), the extended application can cover all or some of the following non-exhaustive list:
- door leaf;
- side, transom and/or overpanels;
- ventilation grilles and/or louvres;
- wall or ceiling fixed parts or items of the doorset, e.g. frame or suspensions systems;
- glazing for door leaf, side, transom and flush over panels;
- items of building hardware;
- decorative finishes;
- intumescent strips, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard88 pagesEnglish languagesale 10% offe-Library read for1 day
This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types:
- hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1);
- horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2);
- metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3).
The following construction products are not covered by this standard:
- unframed glass doors and openable windows;
- sectional doors (including stacking doors);
- vertically and horizontally folding doors;
- horizontally and vertically moving timber sliding doors;
- horizontally and vertically moving framed sliding doors (metal or timber).
In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications;
- leaf/leaves;
- wall/ceiling fixed elements;
- glazed elements, louvres and/or vents;
- side, transom or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This document provides guidance and rules to notified bodies (for fire dampers) allowing them to produce/validate an extended field of application report for fire dampers based on testing undertaken in accordance with EN 1366 2. This document identifies the parameters that affect the fire resistance of fire dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control or non-mechanical fire barriers.
It is the intention that the application of this document makes it possible to identify which specifications to test to maximize the field of application. Some information on test programmes is given for guidance purposes.
- Standard45 pagesEnglish languagesale 10% offe-Library read for1 day
This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types:
- hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1);
- horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2);
- metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3).
The following construction products are not covered by this standard:
- unframed glass doors and openable windows;
- sectional doors (including stacking doors);
- vertically and horizontally folding doors;
- horizontally and vertically moving timber sliding doors;
- horizontally and vertically moving framed sliding doors (metal or timber).
In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications;
- leaf/leaves;
- wall/ceiling fixed elements;
- glazed elements, louvres and/or vents;
- side, transom or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Corrigendum2 pagesEnglish languagesale 10% offe-Library read for1 day
This document provides guidance and rules to notified bodies (for fire dampers) allowing them to produce/validate an extended field of application report for fire dampers based on testing undertaken in accordance with EN 1366 2. This document identifies the parameters that affect the fire resistance of fire dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control or non-mechanical fire barriers.
It is the intention that the application of this document makes it possible to identify which specifications to test to maximize the field of application. Some information on test programmes is given for guidance purposes.
- Standard45 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a method of test for determining the reaction to fire performance of construction products excluding floorings, and excluding products which are indicated in Delegated Regulation (EU) 2016/364, when exposed to thermal attack by a single burning item (SBI). The calculation procedures are given in Annex A. Information on the precision of the test method is given in Annex B. The calibration procedures are given in Annexes C and D, of which Annex C is a normative annex.
NOTE This document has been developed to determine the reaction to fire performance of essentially flat products. The treatment of some families of products, e.g. linear products (pipes, ducts, cables etc.), can need special rules.
- Standard101 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard describes the method to evaluate the performance of protective systems for electrical cable and busbar systems in order to maintain the circuit integrity under fire conditions to classify the protective system according to EN 13501 3 for the P classification. The test examines the behaviour of cable protection systems exposed to fire from outside. The tests specified in this standard are not aimed for assessing the performance of the fire protective system and the penetration seal for maintaining the requirements of the penetrated wall or ceiling (classification E / I).
This method is very different to EN 50200 for the PH classification and also to IEC 60331-11, IEC 60331-21, IEC 60331-23, and IEC 60331-25, which are not designed for fire protective systems for electrical cable systems.
This standard should be used in conjunction with EN 1363-1.
The test results apply to fire protective systems for electrical cable systems rated for voltages up to 1 kV.
The test procedure should also be used to determine the performance of protective systems for use with data and optical cables, however, verification procedures for such cables are still under development. Proposals are given in Annex C.
The protective system may include ventilation devices, inspection hatches, fixed or removable lids etc.
The tests specified in this standard are not aimed for assessing the performance of sprayed or painted coatings (e.g. intumescent or ablative coating, plastic film, epoxy resin) and similar protective layers (e.g. wrap, bandage) applied directly on the cables or bus bars as fire protective system. Also, cables and bus bars with intrinsic resistance to fire, and without fire protective systems around, are excluded (see CENELEC standard EN 50577).
This test method is not applicable for cabinets for electrical accessory containing bus systems, relays or similar.
The cables identified in this document are for testing only. It is not intended that they shall be used in protective systems installed in buildings.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
The purpose of this document is to provide the principles and guidance for the preparation of extended application documents for combined penetration seals where the systems were tested in accordance with (EN 1366-3 and EN 1366-1) or (EN 1366-3 and EN 1366-2). The field of the extended application document is additional to the direct field of application given within EN 1366-1, EN 1366-2 and EN 1366-3 and can be applied on a number of tests from each standard, which provide the relevant information for the formulation of an extended application.
This EXAP is intended to allow the penetration sealing of more than one service (e.g. cables, pipes, conduits) and four-sided fire resisting ducts (ventilation ducts) or fire dampers in the same penetration.
This EXAP is not used for extended applications in accordance with EN 1366-8, EN 1366-10 and/or EN 1366-12 (this will be dealt with in the next revision of the standard).
- Standard37 pagesEnglish languagesale 10% offe-Library read for1 day
This European Standard describes the method to evaluate the performance of protective systems for electrical cable and busbar systems in order to maintain the circuit integrity under fire conditions to classify the protective system according to EN 13501 3 for the P classification. The test examines the behaviour of cable protection systems exposed to fire from outside. The tests specified in this standard are not aimed for assessing the performance of the fire protective system and the penetration seal for maintaining the requirements of the penetrated wall or ceiling (classification E / I).
This method is very different to EN 50200 for the PH classification and also to IEC 60331-11, IEC 60331-21, IEC 60331-23, and IEC 60331-25, which are not designed for fire protective systems for electrical cable systems.
This standard should be used in conjunction with EN 1363-1.
The test results apply to fire protective systems for electrical cable systems rated for voltages up to 1 kV.
The test procedure should also be used to determine the performance of protective systems for use with data and optical cables, however, verification procedures for such cables are still under development. Proposals are given in Annex C.
The protective system may include ventilation devices, inspection hatches, fixed or removable lids etc.
The tests specified in this standard are not aimed for assessing the performance of sprayed or painted coatings (e.g. intumescent or ablative coating, plastic film, epoxy resin) and similar protective layers (e.g. wrap, bandage) applied directly on the cables or bus bars as fire protective system. Also, cables and bus bars with intrinsic resistance to fire, and without fire protective systems around, are excluded (see CENELEC standard EN 50577).
This test method is not applicable for cabinets for electrical accessory containing bus systems, relays or similar.
The cables identified in this document are for testing only. It is not intended that they shall be used in protective systems installed in buildings.
- Standard34 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to single and double leaf, hinged and pivoted metal framed, glazed doorsets or openable windows as covered by EN 15269 5 or EN 15269 20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 1191.
Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or some of the following non-exhaustive list:
- doorsets and openable windows;
- door or window leaves;
- wall or ceiling fixed elements (frame or suspension system);
- glazing and non-glazed panels in doorset and openable window, side, transom and/or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard55 pagesEnglish languagesale 10% offe-Library read for1 day
The purpose of this document is to provide the principles and guidance for the preparation of extended application documents for combined penetration seals where the systems were tested in accordance with (EN 1366-3 and EN 1366-1) or (EN 1366-3 and EN 1366-2). The field of the extended application document is additional to the direct field of application given within EN 1366-1, EN 1366-2 and EN 1366-3 and can be applied on a number of tests from each standard, which provide the relevant information for the formulation of an extended application.
This EXAP is intended to allow the penetration sealing of more than one service (e.g. cables, pipes, conduits) and four-sided fire resisting ducts (ventilation ducts) or fire dampers in the same penetration.
This EXAP is not used for extended applications in accordance with EN 1366-8, EN 1366-10 and/or EN 1366-12 (this will be dealt with in the next revision of the standard).
- Standard37 pagesEnglish languagesale 10% offe-Library read for1 day
This part of the EN 1366 series specifies a method for determining the fire resistance of linear joint seals based on their intended end use. Perimeter seals of curtain walling are excluded from this part of the EN 1366 series.
This document is intended to be used in conjunction with EN 1363-1.
The following tests are included in this document:
- no mechanically induced movement;
- mechanically induced movement.
Tests in accordance with this part of the EN 1366 series are not intended to provide quantitative information on the rate of leakage of smoke and/or hot gases, or on the transmission or generation of fumes. Such phenomena are only noted in the test report in describing the general behaviour of test specimens during the test.
The load-bearing capacity of a linear joint seal is not addressed in this part of the EN 1366 series. No information can be implied by the test concerning the influence of the inclusion of linear joint seals on the loadbearing capacity of the separating element.
- Standard56 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies a method for determining the fire resistance of horizontal service ducts and vertical service shafts, which pass through walls or floors and enclose pipes and cables, to classify them according to EN 13501-2. The test scenario examines the behaviour of ducts and shafts exposed to fire either from outside or from inside the system. This document is intended to be read in conjunction with EN 1363-1.
This document does not examine the risk of fire spread as a result of thermal conduction along the piping or cabling installed in service ducts or shafts or thermal conduction through the media these pipes carry. It does not cover the risk of damage produced by thermal elongation or shortening of tubes and cables as a result of fire or damaged pipe suspensions. This document does not give guidance on how to test one, two or three sided service ducts or shafts.
NOTE Guidance on testing service ducts and shafts of less than four sides will be covered in the extended field of application rules being developed by CEN/TC 127.
This test can be used for systems with boards and also for such systems with continuous covering with intumescent materials on the boards. It cannot be used for systems where intumescent material is only applied in the range of the penetration.
This test is unsuitable for evaluating service ducts or shafts with internal barriers at walls and floors.
This test is unsuitable for evaluating fire protective systems for cable systems and associated components with maintenance of integrity in case of fire. This is covered by EN 1366-11: Fire protective systems for cable systems and associated components - Part 11: Fire protective systems for cable systems and associated components.
Whilst the walls of service ducts or shafts tested to this method may provide specified levels of integrity or insulation, testing according this document does not replace the testing of the functional endurance of small electrical cables which is covered in EN 50200.
Fire resistance testing of ducts for air distribution systems is covered in EN 1366-1.
- Standard27 pagesEnglish languagesale 10% offe-Library read for1 day
This document is applicable to single and double leaf, hinged and pivoted metal framed, glazed doorsets or openable windows as covered by EN 15269 5 or EN 15269 20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 1191.
Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or some of the following non-exhaustive list:
- doorsets and openable windows;
- door or window leaves;
- wall or ceiling fixed elements (frame or suspension system);
- glazing and non-glazed panels in doorset and openable window, side, transom and/or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard55 pagesEnglish languagesale 10% offe-Library read for1 day
This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types:
- hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1);
- horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2);
- metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3).
The following construction products are not covered by this standard:
- unframed glass doors and openable windows;
- sectional doors (including stacking doors);
- vertically and horizontally folding doors;
- horizontally and vertically moving timber sliding doors;
- horizontally and vertically moving framed sliding doors (metal or timber).
In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications;
- leaf/leaves;
- wall/ceiling fixed elements;
- glazed elements, louvres and/or vents;
- side, transom or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Standard193 pagesEnglish languagesale 10% offe-Library read for1 day
This document specifies test methods for determining the contribution of fire protection kits to the fire resistance of structural timber members.
Such fire protection kits include claddings, sprayed fire protection and reactive coatings.
The method is applicable to all fire protection kits used for the protection of timber members. These can be fixed directly, totally or in part, to the timber member and can include an air gap between the fire protectionkit and the timber member, as an integral part of its design.
Evaluation of timber constructions protected by horizontal or vertical protective membranes are the subject of EN 13381-1 or EN 13381-2 respectively.
The test method is applicable to the determination of the contribution of fire protection kits to the fire resistance of loadbearing timber structural members including floors, roofs, walls, beams and columns.
This document contains the fire test which specifies the test to be carried out to determine the ability of the fire protection kit at a specified thickness to delay the temperature rise throughout the timber member, to determine the ability of the fire protection kit at a specified thickness to remain coherent and fixed to the timber member and to provide data for determining the charring rate of the protected test member, when exposed to the standard temperature/time curve according to the procedures defined herein. This document is not appropriated to classify the tested assembly according to EN 13501-2.
The test to subject reactive protection material to a smouldering temperature time fire curve and the special circumstances for this are detailed in Annex G.
The fire test methodology makes provision for the collection and presentation of data which can be used as direct input to the calculation of fire resistance of timber members in accordance with the procedures given in EN 1995-1-2.
A description of the relationship of this test method and the assessment of the results obtained therefrom to EN 1995-1-2 and guidelines for the use of this test method in accordance with that standard are given in Annex B.
This document also contains the assessment which indicates how the analysis of the test data should be made and gives guidance to the procedures by which interpolation should be undertaken.
The limits of applicability of the results of the assessment arising from the fire test are defined, together with the direct application of the results to different timber constructions with the specified thickness and fixation of the applied fire protection kit tested.
- Standard90 pagesEnglish languagesale 10% offe-Library read for1 day