SIST IEC 60145:1995
(Main)Var-hour (reactive energy) meters
- Abstract
Applicable to newly manufactured induction type var-hour meters for the measurement of reactive energy of frequency between 40 Hz and 60 Hz, of an accuracy class of 3.0 for ordinary usage, and to their type tests.
- Status
- Published
- Publication Date
- 31-Jul-1995
- Technical Committee
- MEE - Equipment for electrical energy measurement and load control
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 01-Aug-1995
- Due Date
- 01-Aug-1995
- Completion Date
- 01-Aug-1995
SIST IEC 60145:1995 is the SIST publication of the IEC standard for var-hour meters. It specifies requirements and type tests for newly manufactured induction type meters used to measure reactive energy on 40 Hz to 60 Hz systems, for ordinary usage accuracy class 3.0. The document is written for manufacturers, test laboratories, utilities, and buyers who need a common basis for design, marking, acceptance, and type testing.
What does SIST IEC 60145:1995 specify?
SIST IEC 60145:1995 covers induction type var-hour meters for reactive energy measurement and the tests used to qualify their type. It focuses on the meter as a complete product, including the case, terminals, register, markings, connection information, and accuracy behavior under specified test conditions.
The document is organized into clauses on scope, units, definitions, classification, mechanical requirements, electrical requirements, markings, accuracy, and connection diagrams. It ends with an appendix of graphical symbols for var-hour meters.
| Part | What it covers |
|---|---|
| Clause 1 | Scope and applicability |
| Clause 2 | Units used in the recommendations |
| Clause 3 | Definitions of meter terms and test terms |
| Clause 4 | Classification by accuracy and phase displacement |
| Clause 5 | Mechanical requirements |
| Clause 6 | Electrical requirements |
| Clause 7 | Markings and nameplates |
| Clause 8 | Accuracy and type-test conditions |
| Clause 9 | Connection diagrams and terminal markings |
| Appendix | Graphical symbols for var-hour meters |
What are the key requirements of SIST IEC 60145:1995?
Mechanical construction and enclosure
SIST IEC 60145:1995 requires the meter to use insulating materials that are not substantially hygroscopic and to protect parts exposed to normal service conditions against corrosion. In practice, this means the enclosure and internal materials must stay stable in ordinary indoor use and not deteriorate in a way that affects safety or accuracy.
The meter case must be reasonably dust-proof and sealable so that internal parts are accessible only after breaking seals. If the case is not transparent, it must have windows for reading the register and observing the rotor. Terminal design also matters: the terminals must be grouped on a strong terminal block, allow solid and stranded conductors, and support separate sealing of the terminal cover.
Meter indication and identification
SIST IEC 60145:1995 allows pointer or drum type registers, but the displayed quantity must be identified as kilovar-hour or megavar-hour. The rotor direction must be marked clearly, and the register markings must be indelible and easy to read. For the user, this avoids confusion during installation, reading, and billing.
Clause 7 sets the nameplate content. A meter must identify the manufacturer, type, circuit form, serial number, year of manufacture, reference voltage or voltages, basic current and rated maximum current, reference frequency, meter constant, and, where relevant, phase displacement class and special device information. If instrument transformers are part of the measurement arrangement, their transformation ratios must also be marked. This is what lets a technician verify that the meter matches the intended circuit before it is energised.
Electrical ratings and construction checks
SIST IEC 60145:1995 gives standard basic currents and standard reference voltages, and it limits the power taken by the voltage and current circuits. It also requires dielectric strength and temperature-rise performance to be demonstrated on the complete assembled meter. In practice, this means the meter must survive insulation and heating checks in the form in which it will be installed, not just as separate parts.
The document also specifies behavior under external influences. These include temperature coefficient, oblique suspension, voltage variation, frequency variation, external magnetic field, short-circuit withstand, running with no load, and starting at low current. Together, these checks show whether the meter remains usable when service conditions are less than ideal.
Accuracy and type testing
Clause 8 is the core performance section. SIST IEC 60145:1995 requires type tests to be made at the reference temperature, reference voltage, reference frequency, with sinusoidal voltage and current, steady thermal conditions, no significant stray magnetic field, and the correct phase sequence. The meter is tested under inductive and, where intended, capacitive loading.
The standard distinguishes between single-phase meters, polyphase meters with balanced loads, and polyphase meters with single-phase loads. It also covers temperature coefficient, effect of level, effect of voltage and frequency changes, external magnetic fields, and short-circuit recovery. For a buyer or test lab, this means the meter is not judged only at one ideal point - it must stay within its accuracy class across realistic service and test conditions.
Classification and connection information
Clause 4 classifies meters by accuracy class and by phase displacement. In this edition, the meters concerned are class 3.0, and the phase displacement classes used are 0, 90, and 60. Clause 9 requires a complete connection diagram showing the intended phase sequence and classification angle, which helps installers wire the meter correctly and helps test labs reproduce the intended configuration.
The appendix gives graphical symbols for common single-phase and three-phase connection arrangements. These symbols can simplify marking and make the same technical identification usable across languages.
What terms does SIST IEC 60145:1995 define?
- Var-hour meter - An integrating instrument that measures reactive energy in var-hours or suitable multiples.
- Induction meter - A meter in which fixed coils act on a conducting moving element, usually a disk.
- Multi-rate meter - A meter with several registers that operate at different times for different charge rates.
- Basic current - The current value used as the basis for the recommendations.
- Rated maximum current - The highest current for which the meter claims the highest accuracy level.
- Reference voltage - The voltage basis used for tests and marking, including the way a single value, a range, or two marked voltages are handled.
- Register - The counting mechanism that displays the measured energy.
Who uses SIST IEC 60145:1995?
Manufacturers of induction type reactive energy meters use SIST IEC 60145:1995 for design, construction, and marking. Test laboratories use it for type testing and verification of accuracy and endurance behavior. Utilities, metering engineers, and buyers use it when specifying or accepting meters for electricity supply systems and reactive energy measurement. It is also relevant to inspectors and quality managers who need to check that the meter, its nameplate, and its connection data match the intended application.
Which standards are used with SIST IEC 60145:1995?
The document ties its definitions to the International Electrotechnical Vocabulary (I.E.V.), especially for meter terms. It also aligns its standard reference voltages with IEC Publication 38, which gives the voltage values used as the basis for some markings and tests. Those references support consistent terminology and compatible voltage selection.
What does the SIST IEC 60145:1995 document contain?
SIST IEC 60145:1995 contains the technical framework for induction type var-hour meters: definitions, classification, mechanical and electrical requirements, markings, accuracy limits, and connection information. It includes tables for error limits and for test-related values, together with conditions for type testing across load, temperature, voltage, frequency, magnetic field, and short-circuit scenarios. The appendix adds graphical symbols and explanatory examples for common circuit connections. In practice, it serves as a specification for design review, conformity testing, and meter identification.
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

IMQ S.p.A. (Certification)
Italian electrical product certification.
Sponsored listings
Frequently Asked Questions
SIST IEC 60145:1995 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Var-hour (reactive energy) meters". This standard covers: Applicable to newly manufactured induction type var-hour meters for the measurement of reactive energy of frequency between 40 Hz and 60 Hz, of an accuracy class of 3.0 for ordinary usage, and to their type tests.
Applicable to newly manufactured induction type var-hour meters for the measurement of reactive energy of frequency between 40 Hz and 60 Hz, of an accuracy class of 3.0 for ordinary usage, and to their type tests.
SIST IEC 60145:1995 is classified under the following ICS (International Classification for Standards) categories: 17.220.20 - Measurement of electrical and magnetic quantities; 29.260.20 - Electrical apparatus for explosive atmospheres; 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST IEC 60145:1995 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1. SCOPE
- 2. UNITS
- 3.1 Var-hour meter
- 3.2 Induction meter
- 3.3 Multi-rate meter
- 3.4 Meter rotor
- 3.8 Meter base
- 3.9 Meter cover
- 3.10 Meter case
- 3.12 Terminal block
- 3.14 Current circuit
- 3.15 Voltage circuit
- 3.16 Auxiliary circuit(s)
- 3.19 Reference voltage
- 3.21 Reference speed
- 3.22 Reference torque
- 3.23 Constant of a var-hour meter
- 3.25 Type tests
- 3.26 Routine tests
- 3.27 Sampling tests
- 3.28 Errors
- 3.29 Distortion factor
- 3.30 Mean temperature coefficient
- 4. CLASSIFICATION
- 5.1 General
- 5.2 Case
- 5.3 Windows
- 5.4 Terminals — Terminal block
- 5.5 Terminal cover
- 5.6 Register (counting mechanism)
- 1 Mvarh/div ", and adjacent to the other dials shall be marked
- 5.8 Iron cores
- 6. ELECTRICAL REQUIREMENTS
- 6.1 Standard basic currents
- 6.3 a) Voltage circuit
- 6.4 Dielectric strength
- 6.5 Temperature rise
- 8. ACCURACY
- 8.2 Conditions under which type tests must be made and results to be obtained
- 9. CONNECTION DIAGRAMS AND TERMINAL MARKINGS
1. SCOPE
The present recommendations apply only to newly manufactured induction type var-hour meters for the measurement of reactive energy of frequency between 40 and 60 Hz (c/s), of an accuracy class of 3.0 for ordinary usage and to their type tests.
They do not apply to special types of var-hour meters except multi-rate meters. They do not apply to instrument transformers, even when used in conjunction with the meters covered by these recommendations.
2. UNITS
The units employed in these recommendations are those adopted by the International Electrotechnical Commission. DEFINITIONS 3.
Some of the following terms have been taken from those given in the International Electrotechnical 20 (Publication 50 (20) (1958). In such cases the appropriate I.E.V. reference is Vocabulary, Group given. Some other terms or their definitions have been added especially for these recommendations. (reactive energy meter)
3.1 Var-hour meter
An integrating instrument which measures reactive energy * in var-hours or in suitable multiples thereof.
3.2 Induction meter
A meter in which fixed coils carrying current act upon a conducting moving element, generally a disk, in which flow currents induced by the coils (I.E.V. 20-25-065). is not available in the I.E.V., and general definitions for reactive power and energy do not * The term reactive energy exist for cases where the alternating quantities are not sinusoidal. For these reasons the present recommendations are based on the following practical definitions, which are strictly correct only for sinusoidal voltages, but which are for practical purposes true where the voltages and currents are nearly sinusoidal.
Reactive energy in a single-phase circuit Quantity measured by a perfect watt-hour meter which carries the current of a single-phase circuit and a voltage equal in magnitude to the voltage across the single-phase circuit but in quadrature therewith. The reactive energy of an inductive circuit is positive.
Reactive energy in a polyphase circuit The algebraic sum of the reactive energies of the phases.
Because these practical definitions of reactive energy assume sinusoidal quantities, the inductive or capacitive state of a circuit in these recommendations is given by the factor " sin ". y
SIST IEC 60145:1995
3.3 Multi-rate meter
A meter provided with a number of registers each becoming operative at times corresponding to differing rates of charge (I.E.V. 20-25-110).
3.4 Meter rotor
The moving part of a meter upon which the fixed windings react. Driving element of an induction meter 3.5 One of the working parts of the meter which produces a torque by its action on the moving element. It generally comprises an electro-magnet with its control devices (I.E.V. 20-35-185). Meter braking element 3.6 That part of a meter which is intended to produce a braking torque by its action on the moving element. It comprises one or more magnets and their setting device (I.E.V. 20-35-190). Register of a meter (counting mechanism) 3.7 That part of a meter which registers the energy, or more generally the value of the quantity measured by the meter (I.E.V. 20-35-180).
3.8 Meter base
The back of the meter by which it is fixed and to which are attached the frame, the terminal block and the cover (I.E.V. 20-35-160).
3.9 Meter cover
The enclosure on the front of the meter, made sometimes of transparent material, but generally including transparent parts through which the movement of the disk can be seen, and the counting mechanism read (I.E.V. 20-35-170).
3.10 Meter case
This comprises the base and the cover (I.E.V. 20-35-175).
Meter frame 3,11 That part to which are affixed the driving element, the counting mechanism, usually the braking element, and sometimes the adjusting devices (I.E.V. 20-35-165).
3.12 Terminal block
A support made of insulating material on which all terminals of an instrument, or part of them, are grouped together (I.E.V. 20-35-135).
Terminal cover 3.13 Auxiliary cover which covers the meter terminals and the ends of the wires or the cables from the apparatus connected to these terminals (I.E.V. 20-35-195 modified).
3.14 Current circuit
That part of a meter through which flows the current in the circuit which it measures, or a proportional current supplied by a current transformer (I.E.V. 20-35-205 modified).
SIST IEC 60145:1995
3.15 Voltage circuit
That part of a meter supplied by the voltage of the circuit it is to measure or by a proportional voltage supplied by a transformer or voltage divider (I.E.V. 20-35-210 modified).
3.16 Auxiliary circuit(s)
Circuit(s) within the meter case and connected to an auxiliary device, for example, an hour meter, a clock, a trip coil, a relay.
Basic current 3.17 The value of the current which serves as a basis for these recommendations. Rated maximum current 3.18 The value of current up to which the meter purports to meet the highest accuracy requirements of these recommendations.
3.19 Reference voltage
The value of voltage which forms the basis of these recommendations, if the meter is marked for one voltage only.
If the meter is marked for a range of voltages of which the ratio between the upper and lower limits does not exceed 1.3 *, the reference voltage is the arithmetic mean of the extreme values of the range, for all tests except those prescribed in Sub-Clauses 8.2.1 and 8.2.5. If the meter is marked for two voltages of which the ratio between the higher one and lower one exceeds 1.3, these two voltages are to be considered as reference voltages and all the tests are to be made for both.
-hour meters for 3-phase circuits, the reference voltage will be the voltage applied to the In var voltage circuit(s), which may include external devices.
Reference frequency 3.20 The frequency which forms the basis of these recommendations.
3.21 Reference speed
The number of revolutions per minute of the rotor when the meter carries reference voltage, and basic current, sin y = 1.
3.22 Reference torque
The torque of the rotor when at rest, when the meter carries reference voltage and basic current, sin = 1.
*U upper 1.3 U lower
SIST IEC 60145:1995
3.23 Constant of a var-hour meter
Coefficient giving the relation between the reactive energy nominally measured by a meter and the corresponding angular movement of the rotor.
It is usually expressed as var-hours per revolution (varh/rev) or in revolutions per kilovar-hour (rev/kvarh).
Reference temperature 3.24 The ambient temperature for which the meter is intended.
3.25 Type tests
Qualifying tests which are made on a meter, or on a small number of meters of the same type.
3.26 Routine tests
Tests carried out on every meter in a consignment.
3.27 Sampling tests
Tests carried out on a sample of a consignment.
3.28 Errors
a) Absolute error The indicated value of reactive energy minus its true value . expressed algebraically (I.E.V. 20-40-085 modified).
b) Relative error The ratio of the absolute error to the true value of the reactive energy (I.E.V. 20-40-090 modified). c) Percentage error Relative error x 100.
3.29 Distortion factor
The ratio between the r.m.s. value of the harmonic content obtained by subtracting the fundamental wave from a non-sinusoidal periodic quantity and the r.m.s. value of the non-sinusoidal quantity. It is usually expressed as a percentage.
3.30 Mean temperature coefficient
The ratio between the relative variation of a quantity and the change of temperature which produces it.
4. CLASSIFICATION
4.1 Var-hour meters may be classified according to :
- Class of accuracy, each class being denoted by a number corresponding to the percentage accuracy limit at basic current and sin = 1 under the conditions of Sub-Clause 8.2.1. p In this edition of the recommendations the meters concerned are classified as 3.0.
SIST IEC 60145:1995
- Degree of phase displacement, each class of single driving element * of a var-hour meter which is characterized by the nominal phase displacement between the voltage and current magnetic fluxes in the principal air gaps when the voltage and current applied to this single driving element are in phase.
Var-hour meters which are the subject of these recommendations usually fall into one of three classes : 0, 90 and 60.
MECHANICAL REQUIREMENTS 5.
5.1 General
All insulating materials used in the construction of meters shall be substantially non-hygroscopic. All parts which are subject to corrosion under normal working conditions shall be effectively protected against corrosion due to atmospheric causes. Any protective coating shall not be liable to damage by ordinary handling nor injuriously affected by exposure to air, under ordinary conditions of service.
5.2 Case
The meter shall have a reasonably dust-proof case, which can be sealed such that the mechanism of the meter is only accessible after breaking the seals.
Metal cases of meters for use on a voltage exceeding 250 V to earth shall be provided with means for the effective connection of an adequate earthing conductor.
5.3 Windows
If the meter case is not transparent, one or more windows shall be provided for reading the register and the observation of the rotor. These windows shall be covered by plates of transparent material, which cannot be removed without breaking the seals.
5.4 Terminals — Terminal block
The terminals shall be grouped in a terminal block of adequate mechanical strength. They shall permit the connection of both solid and stranded conductors. It shall be possible easily to disconnect the voltage terminals from the current terminals.
The manner of fixing the conductors to the terminals shall ensure adequate and durable contact such that there is no risk of loosening or undue heating. The holes in the insulating material which form a prolongation of the terminal holes shall be of sufficient size to accommodate the insulation of the conductors.
5.5 Terminal cover
The terminals of a meter shall have a separate cover which can be sealed independently of the meter cover. The terminal cover shall enclose the actual terminals, their fixing screws, and if required a suitable length of the external conductors, and their insulation.
* Driving element here includes any necessary accessory resistors, inductors and shunts.
SIST IEC 60145:1995
When the meter is fixed, no access to the terminals shall be possible without breaking the seals of the terminal cover.
5.6 Register (counting mechanism)
The register may be of the pointer or of the drum type.
The principal terms in which the register records shall be the kilovar-hour (kvarh) or the megavarhour (Mvarh). In drum type registers, the terms in which the register records shall be marked adjacent to the assembly of drums.
In pointer type registers, the terms in which the register records shall be marked adjacent to the
1 Mvarh/div ", and adjacent to the other dials shall be marked
units dial in the form " 1 kvarh/div " or " the number of kilovarhours or megavarhours respectively corresponding to one division of each dial. For example, in a meter registering in terms of kilovarhours, the units dial shall be marked " kvarh/div " and adjacent to the other dials to the left of the units dial shall be marked 10 — 100 — 1 000 — etc. Decimal dials or drums shall be coloured, or encircled in colour, the fastest moving being graduated and numbered.
The register shall be able to record, starting from zero, for a minimum of 2 500 hours for meters 500 hours for those marked " 1 500 hours ", the reactive marked " 2 500 hours " and a minimum of 1 = 1.
energy corresponding to rated maximum current at reference voltage and sin y Register markings shall be indelible and easily readable.
Meter rotor, direction of rotation 5.7 The edge of the rotor near to an observer viewing a meter from the front shall move from left to right on inductive or capacitive load, according to the intended use of the meter. The direction of rotation shall be marked by a clearly visible, indelible arrow. a visible mark to facilitate revolution counting.
...