SIST EN 1717:2025+A1:2026
(Main + Amendment)Protection against pollution of water intended for human consumption in potable water installations and general requirements for devices to prevent pollution by backflow
- Abstract
This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2).
This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3).
The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.
- Status
- Published
- Publication Date
- 12-Jul-2026
- Technical Committee
- IOVO - Water supply and waste water engineering
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 09-Jul-2026
- Due Date
- 13-Sep-2026
- Completion Date
- 13-Jul-2026
SIST EN 1717:2025+A1:2026 is the Slovenian adoption of EN 1717:2025+A1:2026 from CEN. It specifies how to assess the risk of pollution of potable water by backflow and how to choose and install backflow protection for potable water installations and point-of-use systems.
It is written for people who design, select, install, inspect, or maintain water systems. In practice, it helps you classify the connected fluid, decide the needed protection level, and match that level to a suitable device family and installation arrangement.
What does SIST EN 1717:2025+A1:2026 specify?
SIST EN 1717:2025+A1:2026 specifies an analysing methodology for protecting potable water from pollution by backflow of non-potable water. It covers potable water installations within and outside buildings but within premises, and it also applies outside premises to water systems connected to a potable water distribution system up to and including the point of use.
The standard combines risk analysis, device selection, and installation guidance. It also states that product standards for the specific backflow prevention devices or arrangements are to be used together with it, and that it serves as a reference for new devices or systems to establish the needed level of protection.
| Annex | What it covers |
|---|---|
| Annex A | Normative reference list of the protection units, with device families, types, symbols, operating principles, and installation conditions |
| Annex B | Informative guide table for determining the fluid category from which protection is required |
| Annex C | Informative application examples for domestic and non-domestic selection of protection devices |
| Annex D | Informative A-deviations |
The document is organized into clauses on scope, normative references, terms and definitions, general observations on pollution, the analysis method, protection of point-of-use equipment, protection at the connection point to the public potable water system, and air break to drain.
What are the key requirements of SIST EN 1717:2025+A1:2026?
SIST EN 1717:2025+A1:2026 is built around a risk-based selection method. Clause 5 classifies the hazard, Clause 6 and Clause 7 place the protection at the right point in the system, and Clause 8 defines the air break to drain where that concept is used.
1. Classify the fluid and the pressure situation
Clause 5 divides fluids into five categories, from category 1 potable water to category 5 fluids with microbiological or viral hazard. The same clause also distinguishes downstream conditions of P = atm and P > atm, because the backflow risk changes between backsiphonage only and backsiphonage plus back pressure.
In practice, this means the first task is not device selection but hazard classification. You identify what can contact the potable water and whether the protection point can see atmospheric pressure or higher downstream pressure.
2. Use the installation matrix and protection matrix
Clause 5 uses an installation matrix to combine the fluid category with the downstream pressure condition. Clause 5.8 then matches that risk to protection unit families and types.
In practice, this is the document’s core decision tool. If you have the right fluid category and the right pressure condition, the matrix shows which device families are suitable and which are not.
3. Consider the main pollution paths
Clause 4 identifies the main causes of potable water pollution as backflow, cross-connection, external influences, unsuitable materials, stagnation, and poor maintenance. Clause 5 adds backsiphonage, back pressure, back growth, and stagnation as the main backflow-related mechanisms.
This matters because the standard does not treat every risk the same way. It asks the reader to look at the system, not only the device, and to account for water quality impacts from materials and maintenance as well as flow reversal.
4. Choose the right separation method
Clause 5.4 distinguishes single-wall and double-wall separation. Category 2 and 3 fluids may be separated by a single wall with permanently fixed joints, while category 4 and 5 fluids require a double wall with a safety medium between the walls.
In practice, this tells you when a physical barrier alone is acceptable and when the design must include a more secure separation and leakage detection. For direct consumer protection with category 4 or 5 fluids and sanitary or food-related downstream use, a double wall is required.
5. Use an air break to drain where required
Clause 5.5 treats an apparatus connected to drainage without a compliant air break to drain as category 5. Clause 8 then sets the minimum requirements and sizing method for the air break to drain.
In practice, this is a strong design trigger. If the drain connection is not properly separated from potable water, the fluid has to be treated as the highest hazard category, which drives stricter protection selection.
6. Install and maintain protection units correctly
Clause 5.7 says protection units must safely prevent pollution and remain accessible for inspection, test, replacement, or repair. It also sets general operating expectations, including operation up to 1 000 kPa and temperature limits, with special cases only where product standards allow them.
In practice, this means selection is not enough. You also have to check access, orientation, same-room placement where required, in-situ maintenance for larger diameters, and compatibility with the applicable product standard.
7. Apply the point-of-use and connection-point rules
Clause 6 requires a suitable backflow prevention device at each point of use. It allows one device to protect several non-potable circuits only when its capability matches the highest risk downstream, and it limits risk attenuation to the domestic cases listed in Table 3.
Clause 7 requires protection at the origin of the potable water installation network. Where inspection is possible and guarantees are sufficient, a controllable check valve is used; where they are not, the device is chosen for the maximum assumed or perceived risk.
What terms does SIST EN 1717:2025+A1:2026 define?
- Air break to drain - A vertical or equivalent atmospheric separation between an outlet and the spillover level of the drain overflow.
- Air gap - A permanent atmospheric separation between the upstream supply and the downstream fluid.
- Backflow - Flow that moves from downstream to upstream inside an installation.
- Backflow protection device - A device intended to prevent pollution of potable water by backflow.
- Fluid category - The hazard class used by the document to group fluids from category 1 to category 5.
- Potable water installation - The water installation located downstream of the delivery point defined by the water supply authorities or regulations.
- Protection unit - A device, together with the hydraulic components needed for proper protection and functioning, that provides backflow protection.
- LD - The calculated value used in the document to distinguish category 3 from category 4 fluids for device selection.
Who uses SIST EN 1717:2025+A1:2026?
SIST EN 1717:2025+A1:2026 is used by designers of potable water installations, plumbing engineers, manufacturers of backflow protection devices, installers, inspectors, maintenance teams, and water suppliers. It is also relevant to quality managers and buyers who need to check whether a device or arrangement fits a given water-use risk.
Typical tasks include choosing the right family and type of protection, checking whether a point of use needs a device built into the appliance or installed upstream, and documenting the risk analysis for domestic and non-domestic systems. Annex C shows the kind of cases it is meant to support, such as rain water use, heating system filling, and vehicle tank filling.
What changed in SIST EN 1717:2025+A1:2026 from the previous edition?
SIST EN 1717:2025+A1:2026 supersedes EN 1717:2025 and includes Amendment 1 approved by CEN on 25 March 2026. The European foreword states that, compared with EN 1717:2000, the scope was made more precise, extended and revised; the terms and definitions were amended; all figures were updated and redrawn; Table 2 was updated; the air break to drain clause was revised; Annex A and Annex B were completely revised; and Annex C was revised to provide application examples.
Which standards are used with SIST EN 1717:2025+A1:2026?
| Standard | What it contributes |
|---|---|
| EN 806 (all parts) | Specifications for installations inside buildings conveying water for human consumption, including maintenance-related guidance used by this document |
| EN 12729 | Device standard for a controllable backflow preventer with reduced pressure zone, family B type A |
| EN 13076 | Unrestricted air gap, family A type A |
| EN 13077 | Air gap with non-circular overflow, family A type B |
| EN 13078 | Air gap with submerged feed incorporating air inlet plus overflow, family A type C |
| EN 13079 | Air gap with injector, family A type D |
| EN 13433 | Mechanical disconnector, direct actuated, family G type A |
| EN 13959 | Anti-pollution check valves, family E types A to D |
| EN 14367 | Non-controllable backflow preventer with different pressure zones, family C type A |
| EN 14451 | In-line anti-vacuum valves, family D type A |
| EN 14452 | Pipe interrupter with atmospheric vent and moving element, family D type B |
| EN 14453 | Pipe interrupter with permanent atmospheric vent, family D type C |
| EN 14622 | Air gap with circular overflow, family A type F |
| EN 14623 | Air gaps with minimum circular overflow, family A type G |
| EN 14454 | Hose union backflow preventer, family H type A |
| EN 15096 | Hose union anti-vacuum valve and related combined version, family H types B and D |
| EN 14506 | Automatic diverter used in bath/shower tapware |
| EN 14455 | Pressurized air inlet valve, family L types A and B |
| EN 806-5 | Maintenance of water installations, cited for maintenance of protection units |
What does the SIST EN 1717:2025+A1:2026 document contain?
SIST EN 1717:2025+A1:2026 contains the risk-analysis method, the installation matrix, the fluid-category guide, the protection-unit matrix, and the rules for point-of-use and public-network connection protection. It also contains the air break to drain requirements and calculation method.
Annex A is especially important because it gives the device families and types, their graphic symbols, and their main installation conditions. Annex C then turns the rules into worked application examples for domestic and non-domestic situations, which is useful when you need to decide how the standard applies to a real installation.
Relations
- Effective Date
- 01-Apr-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 29-Jul-2026
- Effective Date
- 15-Apr-2026
- Effective Date
- 01-Apr-2026
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
SIST EN 1717:2025+A1:2026 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Protection against pollution of water intended for human consumption in potable water installations and general requirements for devices to prevent pollution by backflow". This standard covers: This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2). This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.
This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2). This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.
SIST EN 1717:2025+A1:2026 is classified under the following ICS (International Classification for Standards) categories: 13.060.20 - Drinking water; 23.060.01 - Valves in general; 91.140.60 - Water supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN 1717:2025+A1:2026 has the following relationships with other standards: It is inter standard links to SIST EN 1717:2025, SIST EN 13078:2004, SIST EN 14367:2005, SIST EN 13433:2006, SIST EN 806-4:2011, SIST EN 14453:2005, SIST EN 14622:2005, SIST EN 13076:2003, SIST EN 806-3:2006, SIST EN 13433:2022, SIST EN 14452:2005, SIST EN 806-5:2012, SIST EN 806-1:2001/A1:2001, SIST EN 1287:2026, SIST EN 997:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
SIST EN 1717:2025+A1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 air break to drain
- 3.2 air gap
- 3.3 air inlet
- 3.4 appliance
- 3.5 backflow
- 3.6 backflow protection device
- 3.7 different liquid levels
- 3.7.1 critical level
- 3.7.2 maximum level
- 3.7.3 spillover level
- 3.8 disconnection
- 3.8.1 controllable disconnection
- 3.8.2 non-controllable disconnection
- 3.9 domestic use
- 3.10 downstream
- 3.11 family of protection
- 3.12 fluid
- 3.14 non-domestic use
- 3.15 overflow
- 3.16 point of use
- 3.17 pollution of potable water
- 3.18 potable water
- 3.19 potable water installation
- 3.20 protection point
- 3.21 protection unit
- 3.22 risk of flooding
- 3.23 type of protection
- 3.24 upstream
- 4 Pollution of potable water: general observations
- 4.1 General
- 4.2 Backflow of non-potable water
- 4.3 Cross-connection
- 4.4 External influences
- 4.5 Materials
- 4.6 Stagnation
- 4.7 Inadequate or improper maintenance
- 5 Analysis method of the pollution risks and choice of protection
- 5.1 General remarks
- 5.2 Determination of fluid categories
- 5.3 Determination of the installation characteristics
- 5.4 Separation by single or double walls
- 5.5 Air break to drain
- 5.6 Installation matrix
- 5.7 Protection units
- 5.8 Matrix of the protection units appropriate to fluid categories
- 5.9 Summary of analysis method
- 6 Protection of equipment installed at the draw-off point (Point-of-Use systems)
- 6.1 General
- 6.2 Special provisions for domestic Point-of-Use systems
- 7 Protection at the connection point to the public potable water system
- 8 Air break to drain
- 8.1 General
- 8.2 Minimum requirements
- 8.3 Calculation of air inlets or overflow openings
- Annex A
- 1 Optional test port
- Annex B
- 1 Water intended for human consumption Category
- 2 Category
- 3 Water from other uses Category
- Annex C
- Annex D
- Bibliography
- 16 December 2020 on the quality of water intended for human consumption (recast)
Introduction
In respect of potential adverse effects on the quality of water intended for human consumption, caused by the products covered by this document, it provides no information as to whether the products may be used without restriction in any of the Member state of the EU or EFTA; NOTE While awaiting the adoption of verifiable European criteria, attention is also drawn to national regulations that can apply.
The UK Matrix of the protection units appropriate to fluid categories (Table 2) and the determination of fluid categories (5.2) differs to that detailed within the body of this document. The British Standard version of EN 1717 therefore contains an A deviation to cover the limited technical deviations to ensure compliance with the Water Supply (fittings) Regulations 1999.
Annex A of this document is normative.
Annex B and Annex C of this document are informative.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
1 Scope
This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2).
This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.
Figure 1 — Operator of a building on own property (land), delivery point (DP) in the building, EN 1717 Scope of application inside and outside buildings
Figure 2 — Operator of a building with its own property (land), delivery point (DP) at the property boundary, EN 1717 Scope of application inside and outside buildings.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
Figure 3 — Withdrawal of drinking water from a public drinking water service pipeline at the delivery point (DP) for the operation and/or filling of mobile units with containers (vehicles on road, water, air, rail), EN 1717 with scope at the transfer point in the outdoor area, supply network
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 806 (all parts), Specifications for installations inside buildings conveying water for human consumption EN 12729, Devices to prevent pollution by backflow of potable water - Controllable backflow preventer with reduced pressure zone - Family B - Type A EN 13076, Devices to prevent pollution by backflow of potable water - Unrestricted air gap-Family A - Type A EN 13077, Devices to prevent pollution by backflow of potable water - Air gap with non-circular overflow (unrestricted) - Family A - Type B EN 13078, Devices to prevent pollution by backflow of potable water - Air gap with submerged feed incorporating air inlet plus overflow - Family A, type C EN 13079, Devices to prevent pollution by backflow of potable water - Air gap with injector - Family A - Type D
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) EN 13433, Devices to prevent pollution by backflow of potable water - Mechanical disconnector, direct actuated - Family G, type A EN 13959, Anti-pollution check valves - DN 6 to DN 250 inclusive family E, type A, B, C and D EN 14367, Non controllable backflow preventer with different pressure zones - Family C, type A EN 14451, Devices to prevent pollution by backflow of potable water - In-line anti-vacuum valves DN 10 to DN 50 inclusive - Family D, type A EN 14452, Devices to prevent pollution by backflow of potable water - Pipe interrupter with atmospheric vent and moving element DN 10 to DN 20 - Family D, type B EN 14453, Devices to prevent pollution by backflow of potable water - Pipe interrupter with permanent atmospheric vent DN 10 to DN 20 - Family D, type C EN 14622, Devices to prevent pollution by backflow of potable water - Air gap with circular overflow (restricted) - Family A, type F EN 14623, Devices to prevent pollution by backflow of potable water - Air gaps with minimum circular overflow (verified by test or measurement) - Family A, type G
3 Terms and definitions
For the purposes of this document, the terms and definitions given in the EN 806 series and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
- ISO Online browsing platform: available at https://www.iso.org/obp/
- IEC Electropedia: available at https://www.electropedia.org/
3.1 air break to drain
vertical distance realised by air inlets or full disconnection between the lowest point of the outlet and the spillover level of the atmospheric drain overflow
3.2 air gap
permanent atmospheric separation between the upstream fluid supply and the downstream fluid
3.3 air inlet
orifice designed to admit air from the atmosphere into a hydraulic system
3.4 appliance
equipment device in which the potable water is used and/or is modified Note 1 to entry: e.g. water heater, coffee-machine, WC-pan, etc.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
3.5 backflow
movement of the fluid from downstream to upstream within an installation
3.6 backflow protection device
device which is intended to prevent pollution of potable water by backflow
3.7 different liquid levels
3.7.1 critical level
physical or piezometric level of the fluid reached in any part of the appliance after closing the water inlet, starting from maximum level
3.7.2 maximum level
highest fluid level reached above the spillover level under positive pressure fault conditions with all outlets closed but with the overflow open
3.7.3 spillover level
level at which water will start to overflow the receiving vessel with all outlets closed
3.8 disconnection
break in a hydraulic system creating an atmospheric separation between two elements, one carrying or containing potable water (upstream) and another carrying or containing another fluid (downstream)
3.8.1 controllable disconnection
device having the ability through the provision of test ports to verify the performance parameters of a pressure controlled zone – such as the differential pressure
3.8.2 non-controllable disconnection
device which has no provision of test ports or other means to verify performance parameters of pressure controlled zones
3.9 domestic use
intended use of applications and appliances that are common for a potable water installation in a household environment Note 1 to entry: The same use of these appliances and applications in e.g. flats, hotels, schools, offices and collective residences (student and nurse accommodations or similar) is considered to be domestic use (see also 6.2)
3.10 downstream
side to which fluid flows under normal conditions
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
3.11 family of protection
general identification of a backflow protection device principle
3.12 fluid
liquid that can assume the shape of any container or vessel, and they are relatively incompressible Note 1 to entry: Fluids are divided into liquids and gases.
3.13 LD
calculated value, based on OECD 423 test method, of the quantities of substances or mixture which, given on one intake through oral and parental path, bring about within 15 days (the required time to consider potential delayed effects) the death of 50 out of 100 treated animals Note 1 to entry: It should be realized that the results of the LD50-test methods are used only as a tool to differentiate between category 3 and category 4 for selecting appropriate family and types of protection units. The LD50-method is not sufficient for conducting a full toxicological evaluation.
3.14 non-domestic use
application different from the domestic use (3.9)
3.15 overflow
means for discharging naturally excess fluid from an appliance when it has reached a specified level
3.16 point of use
point where water is drawn by the user either directly or by connecting an apparatus
3.17 pollution of potable water
reduction in organoleptic (turbidity, odour), taste, chemical or biological quality of potable water Note 1 to entry: Attention is drawn to DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption
3.18 potable water
water intended for human consumption Note 1 to entry: Attention is drawn to DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption
3.19 potable water installation
water installation located downstream of the delivery point specified by the water supply authorities or regulations Note 1 to entry: In DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption the potable water system is denominated as “domestic distribution system”.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
3.20 protection point
location in a hydraulic system where a protection unit is installed
3.21 protection unit
device in combination with other hydraulic components which constitutes the protection against backflow
3.22 risk of flooding
foreseeable situation where contact between non-potable water and potable water by penetration into the atmospheric openings of the anti-pollution devices is possible due to flooding of a room or area in a building in which anti-pollution device is installed
3.23 type of protection
identified operating principle applied to a protection device belonging to a given family
3.24 upstream
side from which fluid flows under normal conditions
4 Pollution of potable water: general observations
4.1 General
The criteria in this clause shall be considered in any risk-based determination of the necessary protection device to prevent the pollution of potable water installations. The following conditions can give raise to risk of pollution of the potable water.
4.2 Backflow of non-potable water
The quality of the potable water distributed can be impaired when non-potable water flows back into the potable water installation.
4.3 Cross-connection
The quality of the potable water distributed can be impaired by a cross-connection with non-potable water, this can be an actual or potential physical connection between a potable water supply and any other non-potable water system.
4.4 External influences
Potable water cisterns, pipes and protection units shall be protected from external pollution (see the EN 806 series).
No other fluid shall be conveyed in a potable water installation (gas, compressed air, ventilation conduct, vapour, chemicals, water used in heating equipment, recycled water, drainage or run-off water, waste water, etc.) other than potable water. If it is considered possible that under the prescribed operation any contaminant could enter through the protection device (e.g. air gap, air inlet) into the potable water installation, additional corresponding protection measures are to be provided.
4.5 Materials
The quality of the potable water distributed can be impaired by the use of inappropriate materials.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) All materials coming into contact with water intended for human consumption shall present no health risk nor cause any change to the water in terms of quality, appearances, smell or taste. They shall be compatible with each other, with the water supplied, and with the fluids or substances that can come into contact with them.
4.6 Stagnation
Stagnation (e.g. as a result of interruptions to operation and disconnection, see the EN 806 series) of potable water in the systems can result in impairment of the water quality due to a significant concentration substances released from materials or due to microbial proliferation. The level of impairment depends on the materials used, the water quality, the ambient temperature (e.g. pipes for potable water in boiler rooms) and the duration of stagnation.
4.7 Inadequate or improper maintenance
Any insufficient or improper maintenance of the potable water installation including backflow protection devices can result in an impaired water quality. For proper maintenance see EN 806-5.
5 Analysis method of the pollution risks and choice of protection
5.1 General remarks
Pollution in a potable water supply system can occur by:
a) backsiphonage: by partial vacuum (drop in pressure) in the potable water supply system (due e.g. to the operation of a valve, the bursting of a pipe, the operation of a booster pump, excessive water demands in a part of the system, water taken for emergency use from a fire hydrant); b) back pressure: originated in a non-potable water system in which the pressure exceeds the pressure in the potable water system; c) back growth: back contamination pollution in the potable water installation as a result of proliferation of microorganisms, from the downstream system; d) stagnation, see 4.6.
5.2 Determination of fluid categories
5.2.1 General
Fluids which could be in contact with potable water are classified in five categories as defined below. 5.2.2 Category 1 Water intended for human consumption coming directly from a potable water distribution system. 5.2.3 Category 2 Fluid recognized as being fit for human consumption, including water taken from a potable water distribution system, which has undergone a change in taste, odour, colour or an active change in temperature (heating or cooling).
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) 5.2.4 Category 3 Fluid representing a slight human health hazard due to the presence of one or more harmful substances
of low acute toxicity to be determined by the LD -method > 200 mg/kg, see 3.14 .
5.2.5 Category 4 Fluid presenting a significant human health hazard due to the presence of one or more toxic or very toxic substances of high acute toxicity to be determined by the LD -method ≤ 200 mg/kg, see 3.14. or one or
more carcinogenic mutagenic and reprotoxic (CMR) substances.
5.2.6 Category 5 Fluid presenting a human health hazard due to the presence of microbiological or viral elements.
5.2.7 Mixture of fluids
If fluids are mixed than the mixture will be classified according to the highest fluid category in the mixture (independent of the ratio).
5.3 Determination of the installation characteristics
5.3.1 General
The analysis of an existing or projected installation provides information about its characteristics and the fluid categories.
That information shall then be used to determine an appropriate protection unit to prevent pollution of the potable water supply or installation.
The analysis is done as described in the following clauses.
The result of this analysis is fixed by a cross in the appropriate field of the installation matrix (see Table 1).
5.3.2 Pressure
Locate the point(s) within the potable water installation that need to be protected against pollution. Determine whether downstream of the protection point is subjected to atmospheric pressure (P = atm) or to a pressure exceeding atmospheric pressure (P > atm):
- the situation will be P = atm if the protection point is subject to backsiphonage only (see Figure 4); - the situation will be P > atm if the protection point is subject to backsiphonage or back pressure (see Figure 5).
The border between fluid category 3 and 4 is in principle LD = 200 mg/kg body weight, in accordance with
OECD 423, December 17, 2001.
When the outcome of the calculation method indicates that a dose equal or less than 200 mg/kg body weight of a fluid is deadly for at least 50 % of the animals, then the fluid is classified into category 4. When the calculation indicates that a dose of more than 200 mg/kg is required the fluid is regarded as less harmful and the fluid is classified into category 3.
Remark: In 2002 the original LD50-test, OECD 401 (8), has been deleted from the OECD guidelines. The LD50-test method in this document is just used as a means for selecting appropriate protection unit. It is not intended as a replacement for undertaking a full toxicological evaluation of the health risk.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
Figure 4 — Pressure equal atmosphere
Figure 5 — Pressure bigger atmosphere
5.3.3 Connections
All connections are considered permanent.
5.3.4 Risk attenuation
The principle of risk attenuation is accepted only for certain facilities for domestic use listed in Clause 6.2 and in conformity with Table 3.
5.4 Separation by single or double walls
5.4.1 General
A single wall separator consists of a single fixed and sealed partition or casing that can be in contact with the potable water on one side, and with another fluid on the other. A double wall separator consists of at least two fixed and sealed partitions or casings creating a neutral intermediate zone between the potable water on one side and another fluid on the other. The intermediate zone may be designed in two ways:
- containing a pressurized gaseous fluid or an inert porous material (open cells);
- containing a fluid of category 2 or 3.
5.4.2 Rules
5.4.2.1 With respect to pollution prevention
Category 2 or 3 fluids shall be separated from the potable water by a single wall including permanently fixed joints.
When the fluid from which potable water shall be protected against pollution is of category 4 or 5, a single wall is not sufficient. A double wall with a safety medium in between (see 5.4.1) is appropriate to separate the potable water from the second fluid.
SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)
5.4.2.2 With respect to direct consumer protection
When the fluid from which potable water shall be protected against is of category 4 or 5 and downstream of the appliance the water is intended for sanitary or food related use, a double wall shall be required.
5.4.3 Leakage test on double-wall-separation
Separation by a double-wall with a safety medium in between shall be constructed such that any leakage from one of the walls shall be routed to the outside of the appliance to give a visual leakage detection or that the leakage initiates a visible and/or acoustic signal.
The leakage test, conducted on a test sample is as follows:
a) drill a (2 ± 0,1) mm hole through the partition wall in contact with the fluid the potable water needs to be protected against. For the position the most critical location in the double-wall is selected. (normally the furthest point from the connections); b) subject the hole in this side of the separation wall with a pressure of (50 ± 5) kPa and maintain that pressure; c) verify if a leakage detection is established within (300 ± 5) s after applying the pressure, e.g. by:
1) observing that fluid emerges to the outside of the double wall construction in the atmosphere; 2) a visual alarm is initiated; 3) an acoustic alarm signal is initiated.
5.5 Air break to drain
If apparatus is connected to a drainage system, which does not have an air break to drain that satisfies the requirements given in Clause 8, the fluid in the apparatus shall be considered as fluid category 5.
...