Abstract

This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2).
This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3).
The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.

Status
Published
Publication Date
30-Jun-2026
Technical Committee
CEN/TC 164 - Water supply
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
01-Jul-2026
Due Date
01-Jul-2026
Completion Date
01-Jul-2026

Buy Documents

Standard

EN 1717:2025+A1:2026 - BARVE

English language (67 pages)
Preview
Preview
e-Library read for
×1 day

EN 1717:2025+A1:2026 is a CEN European Standard for protecting water intended for human consumption in potable water installations against pollution by backflow. It sets out an analysis method, the fluid categories to use in that analysis, and the general requirements for backflow prevention devices and their installation. It is written for designers, installers, manufacturers, water-system operators, and anyone selecting protection for installations within premises and for water systems connected to a potable water distribution system up to the point of use.

What does EN 1717:2025+A1:2026 specify?

EN 1717:2025+A1:2026 specifies a method for assessing backflow pollution risk in potable water installations within and outside buildings but within premises, and it extends the same approach to water systems outside premises up to the point of use. The document also gives recommendations on design, risk analysis, device selection, and installation methods.

The standard is organized into:

  • Clause 1 on scope
  • Clause 2 on normative references
  • Clause 3 on terms and definitions
  • Clause 4 on general causes of pollution
  • Clause 5 on the analysis method and selection of protection
  • Clause 6 on point-of-use systems
  • Clause 7 on protection at the connection point to the public potable water system
  • Clause 8 on air break to drain
  • Annex A to Annex D
AnnexWhat it covers
Annex ANormative reference list of protection units and their general application, symbols, and installation conditions
Annex BInformative guide table for assigning fluid categories
Annex CInformative selection examples for domestic and non-domestic uses
Annex DInformative A-deviations

What are the key requirements of EN 1717:2025+A1:2026?

Risk analysis starts with the fluid and the installation

EN 1717:2025+A1:2026 requires a risk-based analysis of the installation before choosing a backflow protection unit. Clause 5 links the choice of protection to the fluid category, the pressure condition downstream of the protection point, the installation characteristics, and whether the connection already contains suitable protection.

In practice, this means the designer must identify what can reach the potable water, where the protection point is, and whether the downstream side is at atmospheric pressure or can be exposed to back pressure. The standard treats all connections as permanent, so temporary assumptions are not enough.

Fluids are classified into five categories

Clause 5.2 divides fluids into Categories 1 to 5, from potable water to fluids presenting microbiological, viral, or chemical hazards. If different fluids are mixed, the mixture is classified according to the highest category present.

This matters because the fluid category drives the acceptable protection unit. For example, category 4 and 5 fluids call for stronger separation than category 2 or 3 fluids, so the category has to be established before equipment is selected or installed.

Separation, walls, and air break to drain are part of the protection concept

Clause 5.4 distinguishes single-wall and double-wall separation. Category 2 or 3 fluids may be separated by a single wall with permanently fixed joints, while category 4 or 5 fluids require a double wall with a safety medium in between. If the downstream use is sanitary or food-related and the contaminant is category 4 or 5, the double wall is required.

Clause 5.5 states that if an apparatus is connected to a drainage system without an air break to drain meeting Clause 8, the fluid in that apparatus is treated as category 5. In practice, that means drainage design can change the risk category, so the drain interface must be checked as carefully as the water connection.

The protection unit must match the risk and the pressure condition

Clause 5.8 gives the matrix that matches protection units to fluid categories and to backsiphonage or backpressure conditions. The families and types include air gaps, backflow preventers with pressure zones, anti-vacuum valves, pipe interrupters, check valves, mechanical disconnectors, hose union devices, and pressurized air inlet valves.

The practical point is that not every device protects against every risk. Some devices cover backsiphonage only, while others also cover backpressure, so the installation pressure condition has to be known before selecting the device.

Domestic point-of-use systems have special permitted cases

Clause 6 requires each point of use to have suitable backflow protection, normally built into the equipment or installed at the supply connection. If analysis is not possible, only an air gap of family A, type A, B, or D may be used.

Clause 6.2 adds special provisions for domestic use and allows risk attenuation for specific equipment listed in Table 3. This is important for common household-type fixtures, because it identifies where a simplified selection is allowed and where the installation must still follow the general analysis method.

The connection to the public potable water system needs protection at the origin

Clause 7 requires backflow protection at the origin of the potable water installation network, at the appropriate place. Where inspection is possible and the guarantees are sufficient, the protection unit shall be a controllable check valve; where inspection is not possible or guarantees are insufficient, the unit must match the maximum assumed risk.

For systems with cross-connections to other water sources, the supply shall be protected for fluid category 5. In practice, this means the boundary between the public supply and the installation is not left unprotected just because individual downstream fittings also have local devices.

Air break to drain has defined geometric requirements

Clause 8 defines the air break to drain as a full vertical disconnection or an arrangement using air inlets, and it gives minimum dimensional rules and a calculation method for inlet or overflow areas. It also states that an air break to drain shall not be used as a potable water supply device.

This matters because the document treats the air break as a safety feature, not as a normal water-distribution component. The installation has to be sized so that discharge can be handled safely and contamination cannot bridge the separation.

What terms does EN 1717:2025+A1:2026 define?

  • Air break to drain - A vertical separation created by air inlets or full disconnection between the outlet and the spillover level of an atmospheric drain overflow.
  • Air gap - A permanent atmospheric separation between the upstream fluid supply and the downstream fluid.
  • Backflow protection device - A device intended to prevent pollution of potable water by backflow.
  • Point of use - The point where water is drawn by the user directly or by connecting an apparatus.
  • Potable water installation - The water installation located downstream of the delivery point specified by the water supply authorities or regulations.
  • Protection unit - A device combined with other hydraulic components that provides backflow protection.
  • Risk of flooding - A foreseeable situation where flooding can allow contact between non-potable water and atmospheric openings of anti-pollution devices.
  • Domestic use - Use common in a household environment, including similar use in flats, hotels, schools, offices, and collective residences.

Who uses EN 1717:2025+A1:2026?

EN 1717:2025+A1:2026 is used by people who specify, design, install, inspect, or maintain potable water installations and backflow protection. It is also used by manufacturers of backflow prevention devices because Annex A ties device families to product standards such as EN 12729, EN 13076, EN 13433, EN 13959, EN 14367, EN 14451, EN 14452, EN 14453, EN 14455, EN 14506, EN 14622, EN 14623, and EN 15096.

Typical users include:

  • plumbing and water-system designers
  • installers and commissioning teams
  • quality managers and technical purchasers
  • manufacturers developing new devices or systems
  • inspectors and operators checking installed protection
  • building operators managing domestic and non-domestic water uses

What changed in EN 1717:2025+A1:2026 from the previous edition?

EN 1717:2025+A1:2026 supersedes EN 1717:2025 and includes Amendment 1 approved by CEN on 25 March 2026. The foreword states that, compared with EN 1717:2000, the scope was made more precise, extended, and revised; the terms and definitions were amended; all figures were updated and redrawn; Table 2 was updated; the air break to drain clause was revised; Annex A and Annex B were completely revised; and Annex C was revised to provide application examples.

Which standards are used with EN 1717:2025+A1:2026?

EN 1717:2025+A1:2026 is used together with the EN 806 series and with the product standards named in Clause 2 and Annex A. Each reference supports a specific device family or the wider installation rules.

Referenced standardWhat it contributes
EN 806 (all parts)Rules for installations inside buildings conveying water for human consumption, including maintenance context
EN 12729Product standard for BA backflow preventers with controllable reduced pressure zones
EN 13076Product standard for AA unrestricted air gaps
EN 13077Product standard for AB air gaps with non-circular overflow
EN 13078Product standard for AC air gaps with submerged feed and air inlet plus overflow
EN 13079Product standard for AD air gaps with injector
EN 13433Product standard for GA mechanical disconnectors, direct actuated
EN 13959Product standard for EA, EB, EC, and ED antipollution check valves
EN 14367Product standard for CA backflow preventers with different non-controllable pressure zones
EN 14451Product standard for DA in-line anti-vacuum valves
EN 14452Product standard for DB pipe interrupters with atmospheric vent and moving element
EN 14453Product standard for DC pipe interrupters with permanent atmospheric vent
EN 14622Product standard for AF air gaps with circular overflow
EN 14623Product standard for AG air gaps with minimum circular overflow

What does the EN 1717:2025+A1:2026 document contain?

EN 1717:2025+A1:2026 contains the risk analysis method, the fluid-category system, the installation matrix, the protection-unit matrix, and the special rules for point-of-use and supply-connection protection. It also contains a detailed normative annex with the reference list of protection units and their symbols, installation positions, and operating conditions.

The informative annexes add a practical fluid-category guide, worked examples for domestic and non-domestic cases such as rainwater use, heating-system filling, detergent dosing, animal drinking troughs, and vehicle tank filling, and national A-deviations. Clause 8 and Annex A also include dimensional conditions and calculation methods for air breaks to drain and air inlets or overflow openings, which are used for design and verification.

Relations

Effective Date
01-Apr-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
29-Jul-2026
Effective Date
01-Apr-2026
Effective Date
01-Apr-2026

Buy Documents

Standard

EN 1717:2025+A1:2026 - BARVE

English language (67 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

EN 1717:2025+A1:2026 is a standard published by the European Committee for Standardization (CEN). Its full title is "Protection against pollution of water intended for human consumption in potable water installations and general requirements for devices to prevent pollution by backflow". This standard covers: This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2). This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.

This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2). This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.

EN 1717:2025+A1:2026 is classified under the following ICS (International Classification for Standards) categories: 13.060.20 - Drinking water; 23.060.01 - Valves in general; 91.140.60 - Water supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 1717:2025+A1:2026 has the following relationships with other standards: It is inter standard links to EN 1717:2025, EN 13076:2003, EN 14367:2005, EN 806-5:2012, EN 14622:2005, EN 13433:2021, EN 13433:2006, EN 806-3:2006, EN 13078:2003, EN 806-1:2000/A1:2001, EN 806-4:2010, EN 14452:2005, EN 14453:2005, EN 14623:2005, EN 13079:2025. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 1717:2025+A1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 air break to drain
  • 3.2 air gap
  • 3.3 air inlet
  • 3.4 appliance
  • 3.5 backflow
  • 3.6 backflow protection device
  • 3.7 different liquid levels
  • 3.7.1 critical level
  • 3.7.2 maximum level
  • 3.7.3 spillover level
  • 3.8 disconnection
  • 3.8.1 controllable disconnection
  • 3.8.2 non-controllable disconnection
  • 3.9 domestic use
  • 3.10 downstream
  • 3.11 family of protection
  • 3.12 fluid
  • 3.14 non-domestic use
  • 3.15 overflow
  • 3.16 point of use
  • 3.17 pollution of potable water
  • 3.18 potable water
  • 3.19 potable water installation
  • 3.20 protection point
  • 3.21 protection unit
  • 3.22 risk of flooding
  • 3.23 type of protection
  • 3.24 upstream
  • 4 Pollution of potable water: general observations
  • 4.1 General
  • 4.2 Backflow of non-potable water
  • 4.3 Cross-connection
  • 4.4 External influences
  • 4.5 Materials
  • 4.6 Stagnation
  • 4.7 Inadequate or improper maintenance
  • 5 Analysis method of the pollution risks and choice of protection
  • 5.1 General remarks
  • 5.2 Determination of fluid categories
  • 5.3 Determination of the installation characteristics
  • 5.4 Separation by single or double walls
  • 5.5 Air break to drain
  • 5.6 Installation matrix
  • 5.7 Protection units
  • 5.8 Matrix of the protection units appropriate to fluid categories
  • 5.9 Summary of analysis method
  • 6 Protection of equipment installed at the draw-off point (Point-of-Use systems)
  • 6.1 General
  • 6.2 Special provisions for domestic Point-of-Use systems
  • 7 Protection at the connection point to the public potable water system
  • 8 Air break to drain
  • 8.1 General
  • 8.2 Minimum requirements
  • 8.3 Calculation of air inlets or overflow openings
  • Annex A
  • 1 Optional test port
  • Annex B
  • 1 Water intended for human consumption Category
  • 2 Category
  • 3 Water from other uses Category
  • Annex C
  • Annex D
  • Bibliography
  • 16 December 2020 on the quality of water intended for human consumption (recast)

Introduction

In respect of potential adverse effects on the quality of water intended for human consumption, caused by the products covered by this document, it provides no information as to whether the products may be used without restriction in any of the Member state of the EU or EFTA; NOTE While awaiting the adoption of verifiable European criteria, attention is also drawn to national regulations that can apply.

The UK Matrix of the protection units appropriate to fluid categories (Table 2) and the determination of fluid categories (5.2) differs to that detailed within the body of this document. The British Standard version of EN 1717 therefore contains an A deviation to cover the limited technical deviations to ensure compliance with the Water Supply (fittings) Regulations 1999.

Annex A of this document is normative.

Annex B and Annex C of this document are informative.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

1 Scope

This document specifies an analysing methodology for protecting potable water in potable water installations within and outside buildings but within premises from the risk of pollution by backflow of non-potable water and gives recommendations on the design, risk analysis, backflow prevention devices and their installation methods (see Figure 1 and Figure 2).

This methodology is also intended to be used outside premises for all water systems connected to a potable water distribution system up to and including the point of use (see Figure 3). The product standards for the specific backflow prevention devices or arrangements are intended to be used in conjunction with this document. For the development of new devices or systems, this document is intended to be used as a reference to establish the necessary level of backflow protection.

Figure 1 — Operator of a building on own property (land), delivery point (DP) in the building, EN 1717 Scope of application inside and outside buildings

Figure 2 — Operator of a building with its own property (land), delivery point (DP) at the property boundary, EN 1717 Scope of application inside and outside buildings.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

Figure 3 — Withdrawal of drinking water from a public drinking water service pipeline at the delivery point (DP) for the operation and/or filling of mobile units with containers (vehicles on road, water, air, rail), EN 1717 with scope at the transfer point in the outdoor area, supply network

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 806 (all parts), Specifications for installations inside buildings conveying water for human consumption EN 12729, Devices to prevent pollution by backflow of potable water - Controllable backflow preventer with reduced pressure zone - Family B - Type A EN 13076, Devices to prevent pollution by backflow of potable water - Unrestricted air gap-Family A - Type A EN 13077, Devices to prevent pollution by backflow of potable water - Air gap with non-circular overflow (unrestricted) - Family A - Type B EN 13078, Devices to prevent pollution by backflow of potable water - Air gap with submerged feed incorporating air inlet plus overflow - Family A, type C EN 13079, Devices to prevent pollution by backflow of potable water - Air gap with injector - Family A - Type D

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) EN 13433, Devices to prevent pollution by backflow of potable water - Mechanical disconnector, direct actuated - Family G, type A EN 13959, Anti-pollution check valves - DN 6 to DN 250 inclusive family E, type A, B, C and D EN 14367, Non controllable backflow preventer with different pressure zones - Family C, type A EN 14451, Devices to prevent pollution by backflow of potable water - In-line anti-vacuum valves DN 10 to DN 50 inclusive - Family D, type A EN 14452, Devices to prevent pollution by backflow of potable water - Pipe interrupter with atmospheric vent and moving element DN 10 to DN 20 - Family D, type B EN 14453, Devices to prevent pollution by backflow of potable water - Pipe interrupter with permanent atmospheric vent DN 10 to DN 20 - Family D, type C EN 14622, Devices to prevent pollution by backflow of potable water - Air gap with circular overflow (restricted) - Family A, type F EN 14623, Devices to prevent pollution by backflow of potable water - Air gaps with minimum circular overflow (verified by test or measurement) - Family A, type G

3 Terms and definitions

For the purposes of this document, the terms and definitions given in the EN 806 series and the following apply.

ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/

3.1 air break to drain

vertical distance realised by air inlets or full disconnection between the lowest point of the outlet and the spillover level of the atmospheric drain overflow

3.2 air gap

permanent atmospheric separation between the upstream fluid supply and the downstream fluid

3.3 air inlet

orifice designed to admit air from the atmosphere into a hydraulic system

3.4 appliance

equipment device in which the potable water is used and/or is modified Note 1 to entry: e.g. water heater, coffee-machine, WC-pan, etc.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

3.5 backflow

movement of the fluid from downstream to upstream within an installation

3.6 backflow protection device

device which is intended to prevent pollution of potable water by backflow

3.7 different liquid levels

3.7.1 critical level

physical or piezometric level of the fluid reached in any part of the appliance after closing the water inlet, starting from maximum level

3.7.2 maximum level

highest fluid level reached above the spillover level under positive pressure fault conditions with all outlets closed but with the overflow open

3.7.3 spillover level

level at which water will start to overflow the receiving vessel with all outlets closed

3.8 disconnection

break in a hydraulic system creating an atmospheric separation between two elements, one carrying or containing potable water (upstream) and another carrying or containing another fluid (downstream)

3.8.1 controllable disconnection

device having the ability through the provision of test ports to verify the performance parameters of a pressure controlled zone – such as the differential pressure

3.8.2 non-controllable disconnection

device which has no provision of test ports or other means to verify performance parameters of pressure controlled zones

3.9 domestic use

intended use of applications and appliances that are common for a potable water installation in a household environment Note 1 to entry: The same use of these appliances and applications in e.g. flats, hotels, schools, offices and collective residences (student and nurse accommodations or similar) is considered to be domestic use (see also 6.2)

3.10 downstream

side to which fluid flows under normal conditions

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

3.11 family of protection

general identification of a backflow protection device principle

3.12 fluid

liquid that can assume the shape of any container or vessel, and they are relatively incompressible Note 1 to entry: Fluids are divided into liquids and gases.

3.13 LD

calculated value, based on OECD 423 test method, of the quantities of substances or mixture which, given on one intake through oral and parental path, bring about within 15 days (the required time to consider potential delayed effects) the death of 50 out of 100 treated animals Note 1 to entry: It should be realized that the results of the LD50-test methods are used only as a tool to differentiate between category 3 and category 4 for selecting appropriate family and types of protection units. The LD50-method is not sufficient for conducting a full toxicological evaluation.

3.14 non-domestic use

application different from the domestic use (3.9)

3.15 overflow

means for discharging naturally excess fluid from an appliance when it has reached a specified level

3.16 point of use

point where water is drawn by the user either directly or by connecting an apparatus

3.17 pollution of potable water

reduction in organoleptic (turbidity, odour), taste, chemical or biological quality of potable water Note 1 to entry: Attention is drawn to DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption

3.18 potable water

water intended for human consumption Note 1 to entry: Attention is drawn to DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption

3.19 potable water installation

water installation located downstream of the delivery point specified by the water supply authorities or regulations Note 1 to entry: In DIRECTIVE (EU) 2020/2184 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 2020 on the quality of water intended for human consumption the potable water system is denominated as “domestic distribution system”.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

3.20 protection point

location in a hydraulic system where a protection unit is installed

3.21 protection unit

device in combination with other hydraulic components which constitutes the protection against backflow

3.22 risk of flooding

foreseeable situation where contact between non-potable water and potable water by penetration into the atmospheric openings of the anti-pollution devices is possible due to flooding of a room or area in a building in which anti-pollution device is installed

3.23 type of protection

identified operating principle applied to a protection device belonging to a given family

3.24 upstream

side from which fluid flows under normal conditions

4 Pollution of potable water: general observations

4.1 General

The criteria in this clause shall be considered in any risk-based determination of the necessary protection device to prevent the pollution of potable water installations. The following conditions can give raise to risk of pollution of the potable water.

4.2 Backflow of non-potable water

The quality of the potable water distributed can be impaired when non-potable water flows back into the potable water installation.

4.3 Cross-connection

The quality of the potable water distributed can be impaired by a cross-connection with non-potable water, this can be an actual or potential physical connection between a potable water supply and any other non-potable water system.

4.4 External influences

Potable water cisterns, pipes and protection units shall be protected from external pollution (see the EN 806 series).

No other fluid shall be conveyed in a potable water installation (gas, compressed air, ventilation conduct, vapour, chemicals, water used in heating equipment, recycled water, drainage or run-off water, waste water, etc.) other than potable water. If it is considered possible that under the prescribed operation any contaminant could enter through the protection device (e.g. air gap, air inlet) into the potable water installation, additional corresponding protection measures are to be provided.

4.5 Materials

The quality of the potable water distributed can be impaired by the use of inappropriate materials.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) All materials coming into contact with water intended for human consumption shall present no health risk nor cause any change to the water in terms of quality, appearances, smell or taste. They shall be compatible with each other, with the water supplied, and with the fluids or substances that can come into contact with them.

4.6 Stagnation

Stagnation (e.g. as a result of interruptions to operation and disconnection, see the EN 806 series) of potable water in the systems can result in impairment of the water quality due to a significant concentration substances released from materials or due to microbial proliferation. The level of impairment depends on the materials used, the water quality, the ambient temperature (e.g. pipes for potable water in boiler rooms) and the duration of stagnation.

4.7 Inadequate or improper maintenance

Any insufficient or improper maintenance of the potable water installation including backflow protection devices can result in an impaired water quality. For proper maintenance see EN 806-5.

5 Analysis method of the pollution risks and choice of protection

5.1 General remarks

Pollution in a potable water supply system can occur by:

a) backsiphonage: by partial vacuum (drop in pressure) in the potable water supply system (due e.g. to the operation of a valve, the bursting of a pipe, the operation of a booster pump, excessive water demands in a part of the system, water taken for emergency use from a fire hydrant); b) back pressure: originated in a non-potable water system in which the pressure exceeds the pressure in the potable water system; c) back growth: back contamination pollution in the potable water installation as a result of proliferation of microorganisms, from the downstream system; d) stagnation, see 4.6.

5.2 Determination of fluid categories

5.2.1 General

Fluids which could be in contact with potable water are classified in five categories as defined below. 5.2.2 Category 1 Water intended for human consumption coming directly from a potable water distribution system. 5.2.3 Category 2 Fluid recognized as being fit for human consumption, including water taken from a potable water distribution system, which has undergone a change in taste, odour, colour or an active change in temperature (heating or cooling).

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E) 5.2.4 Category 3 Fluid representing a slight human health hazard due to the presence of one or more harmful substances

of low acute toxicity to be determined by the LD -method > 200 mg/kg, see 3.14 .

5.2.5 Category 4 Fluid presenting a significant human health hazard due to the presence of one or more toxic or very toxic substances of high acute toxicity to be determined by the LD -method ≤ 200 mg/kg, see 3.14. or one or

more carcinogenic mutagenic and reprotoxic (CMR) substances.

5.2.6 Category 5 Fluid presenting a human health hazard due to the presence of microbiological or viral elements.

5.2.7 Mixture of fluids

If fluids are mixed than the mixture will be classified according to the highest fluid category in the mixture (independent of the ratio).

5.3 Determination of the installation characteristics

5.3.1 General

The analysis of an existing or projected installation provides information about its characteristics and the fluid categories.

That information shall then be used to determine an appropriate protection unit to prevent pollution of the potable water supply or installation.

The analysis is done as described in the following clauses.

The result of this analysis is fixed by a cross in the appropriate field of the installation matrix (see Table 1).

5.3.2 Pressure

Locate the point(s) within the potable water installation that need to be protected against pollution. Determine whether downstream of the protection point is subjected to atmospheric pressure (P = atm) or to a pressure exceeding atmospheric pressure (P > atm):

- the situation will be P = atm if the protection point is subject to backsiphonage only (see Figure 4); - the situation will be P > atm if the protection point is subject to backsiphonage or back pressure (see Figure 5).

The border between fluid category 3 and 4 is in principle LD = 200 mg/kg body weight, in accordance with

OECD 423, December 17, 2001.

When the outcome of the calculation method indicates that a dose equal or less than 200 mg/kg body weight of a fluid is deadly for at least 50 % of the animals, then the fluid is classified into category 4. When the calculation indicates that a dose of more than 200 mg/kg is required the fluid is regarded as less harmful and the fluid is classified into category 3.

Remark: In 2002 the original LD50-test, OECD 401 (8), has been deleted from the OECD guidelines. The LD50-test method in this document is just used as a means for selecting appropriate protection unit. It is not intended as a replacement for undertaking a full toxicological evaluation of the health risk.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

Figure 4 — Pressure equal atmosphere

Figure 5 — Pressure bigger atmosphere

5.3.3 Connections

All connections are considered permanent.

5.3.4 Risk attenuation

The principle of risk attenuation is accepted only for certain facilities for domestic use listed in Clause 6.2 and in conformity with Table 3.

5.4 Separation by single or double walls

5.4.1 General

A single wall separator consists of a single fixed and sealed partition or casing that can be in contact with the potable water on one side, and with another fluid on the other. A double wall separator consists of at least two fixed and sealed partitions or casings creating a neutral intermediate zone between the potable water on one side and another fluid on the other. The intermediate zone may be designed in two ways:

  • containing a pressurized gaseous fluid or an inert porous material (open cells);
  • containing a fluid of category 2 or 3.
5.4.2 Rules
5.4.2.1 With respect to pollution prevention

Category 2 or 3 fluids shall be separated from the potable water by a single wall including permanently fixed joints.

When the fluid from which potable water shall be protected against pollution is of category 4 or 5, a single wall is not sufficient. A double wall with a safety medium in between (see 5.4.1) is appropriate to separate the potable water from the second fluid.

SIST EN 1717:2025+A1:2026 EN 1717:2025+A1:2026 (E)

5.4.2.2 With respect to direct consumer protection

When the fluid from which potable water shall be protected against is of category 4 or 5 and downstream of the appliance the water is intended for sanitary or food related use, a double wall shall be required.

5.4.3 Leakage test on double-wall-separation

Separation by a double-wall with a safety medium in between shall be constructed such that any leakage from one of the walls shall be routed to the outside of the appliance to give a visual leakage detection or that the leakage initiates a visible and/or acoustic signal.

The leakage test, conducted on a test sample is as follows:

a) drill a (2 ± 0,1) mm hole through the partition wall in contact with the fluid the potable water needs to be protected against. For the position the most critical location in the double-wall is selected. (normally the furthest point from the connections); b) subject the hole in this side of the separation wall with a pressure of (50 ± 5) kPa and maintain that pressure; c) verify if a leakage detection is established within (300 ± 5) s after applying the pressure, e.g. by:

1) observing that fluid emerges to the outside of the double wall construction in the atmosphere; 2) a visual alarm is initiated; 3) an acoustic alarm signal is initiated.

5.5 Air break to drain

If apparatus is connected to a drainage system, which does not have an air break to drain that satisfies the requirements given in Clause 8, the fluid in the apparatus shall be considered as fluid category 5.

...