Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking systems (busways)

IEC 61439-6:2012 lays down the definitions and states the service conditions, construction requirements, technical characteristics and verification requirements for low voltage BTS (see 3.101) as follows:
- BTS for which the rated voltage does not exceed 1 000 V in case of a.c. or 1 500 V in case of d.c.;
- BTS intended for use in connection with the generation, transmission, distribution and conversion of electric energy, and for the control of electric energy consuming equipment;
- BTS designed for use under special service conditions, for example in ships, in rail vehicles, and for domestic applications (operated by unskilled persons), provided that the relevant specific requirements are complied with;
- BTS designed for electrical equipment of machines. Supplementary requirements for BTS forming part of a machine are covered by the IEC 60204 series. This first edition of IEC 61439-6 cancels and replaces the third edition of IEC 60439-2 (2000) and its Amendment 1 (2005), and constitutes a technical revision. This edition of IEC 61439-6 includes the following significant technical changes with respect to the latest edition of IEC 60439-2:
- alignment on the second edition of IEC 61439-1 (2011) regarding the structure and technical content, as applicable;
- introduction of new verifications, accordingly;
- correction of inconsistencies in resistance, reactance and impedance measurements and calculations;
- numerous editorial improvements.
This publication is to be read in conjunction with IEC 61439-1:2011.

Ensembles d'appareillage à basse tension - Partie 6: Systèmes de canalisation préfabriquée

La CEI 61439-6:2012 formule les définitions et indique les conditions d'emploi, les exigences de construction, les caractéristiques techniques et les exigences de vérification pour les SCP à basse tension (voir 3.101), comme suit:
- SCP dont la tension assignée ne dépasse pas 1 000 V en courant alternatif ou 1 500 V en courant continu;
- SCP destinés à être utilisés avec des équipements conçus pour la production, le transport, la distribution et la conversion de l'énergie électrique et la commande des matériels consommant de l'énergie électrique;
- SCP conçus pour être utilisés dans des conditions spéciales d'emploi, par exemple, à bord de navires et de véhicules ferroviaires, et pour des applications domestiques (utilisation par des personnes non qualifiées), sous réserve que les autres exigences spécifiques correspondantes soient respectées;
- SCP conçus pour l'équipement électrique des machines. Les exigences supplémentaires relatives aux SCP faisant partie intégrante d'une machine sont couvertes par la série CEI 60204. Cette première édition de la CEI 61439-6 annule et remplace la troisième édition de la CEI 60439-2 (2000) et son Amendement 1 (2005), dont elle constitue une révision technique. Cette édition de la CEI 61439-6 inclut les modifications techniques majeures suivantes par rapport à la dernière édition de la CEI 60439-2:
- alignement sur la deuxième édition de CEI 61439-1 (2011) concernant la structure et le contenu technique, selon le cas;
- introduction de nouvelles vérifications, en conséquence;
- correction des incohérences en termes de mesures et de calculs des valeurs de résistance, de réactance et d'impédance;
- nombreuses améliorations rédactionnelles.
Cette publication doit être lue conjointement avec la CEI 61439-1:2011.

General Information

Status
Published
Publication Date
22-May-2012
Current Stage
PPUB - Publication issued
Start Date
23-May-2012
Completion Date
15-Jun-2012
Ref Project

Relations

Standard
IEC 61439-6:2012 - Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking systems (busways)
English and French language
85 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 61439-6 ®
Edition 1.0 2012-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage switchgear and controlgear assemblies –
Part 6: Busbar trunking systems (busways)

Ensembles d'appareillage à basse tension –
Partie 6: Systèmes de canalisation préfabriquée

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les
microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.

Useful links:
IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org
The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and
by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and
committee,…). definitions in English and French, with equivalent terms in
It also gives information on projects, replaced and additional languages. Also known as the International
withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc
Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication
details all new publications released. Available on-line and or need further assistance, please contact the
also once a month by email. Customer Service Centre: csc@iec.ch.

A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.

Liens utiles:
Recherche de publications CEI - www.iec.ch/searchpub Electropedia - www.electropedia.org
La recherche avancée vous permet de trouver des Le premier dictionnaire en ligne au monde de termes
publications CEI en utilisant différents critères (numéro de électroniques et électriques. Il contient plus de 30 000
référence, texte, comité d’études,…). termes et définitions en anglais et en français, ainsi que
Elle donne aussi des informations sur les projets et les les termes équivalents dans les langues additionnelles.
publications remplacées ou retirées. Egalement appelé Vocabulaire Electrotechnique
International (VEI) en ligne.
Just Published CEI - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications de la CEI.
Just Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur
Disponible en ligne et aussi une fois par mois par email. cette publication ou si vous avez des questions
contactez-nous: csc@iec.ch.
IEC 61439-6 ®
Edition 1.0 2012-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage switchgear and controlgear assemblies –

Part 6: Busbar trunking systems (busways)

Ensembles d'appareillage à basse tension –

Partie 6: Systèmes de canalisation préfabriquée

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX X
ICS 29.130.20 ISBN 978-2-83220-084-1

– 2 – 61439-6 © IEC:2012
CONTENTS
FOREWORD . 3
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 6
4 Symbols and abbreviations . 8
5 Interface characteristics . 8
6 Information . 12
7 Service conditions . 12
8 Constructional requirements . 13
9 Performance requirements . 14
10 Design verifications . 15
11 Routine verifications . 27
Annexes . 28
Annex C (informative) Specification schedule . 29
Annex D (informative) Design verification . 33
Annex AA (informative) Voltage drop of the system. 34
Annex BB (informative) Phase conductor characteristics . 35
Annex CC (informative) Fault-loop zero-sequence impedances . 37
Annex DD (informative) Fault-loop resistances and reactances . 39
Annex EE (informative) Determination of the magnetic field in the vicinity of the BTS . 41
Bibliography . 42

Figure 101 – Mechanical load test of a straight unit . 16
Figure 102 – Mechanical load test of a joint . 16
Figure 103 – Test arrangement for verification of a fire-barrier BTU . 27
Figure BB.1 – Phase conductors characteristics determination . 35
Figure CC.1 – Fault loop zero-sequence impedances determination . 37
Figure DD.1 – Fault loop resistances and reactances determination . 39
Figure EE.1 – Magnetic field measurement arrangement . 41

Table 101 – Rated diversity factor for a tap-off unit . 10
Table 102 – Phase conductor characteristics . 11
Table 103 – Fault-loop characteristics . 11
Table 104 – Characteristics to be used for fault currents calculations . 12
Table 105 – Conditioning for the thermal cycling test . 18
Table C.1 – User specification schedule . 29
Table D.1 – Design verifications . 33

61439-6 © IEC:2012 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES –

Part 6: Busbar trunking systems (busways)

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61439-6 has been prepared by subcommittee 17D: Low-voltage
switchgear and controlgear assemblies, of IEC technical committee 17: Switchgear and
controlgear.
This first edition of IEC 61439-6 cancels and replaces the third edition of IEC 60439-2 (2000)
and its Amendment 1 (2005), and constitutes a technical revision.
This edition of IEC 61439-6 includes the following significant technical changes with respect
to the latest edition of IEC 60439-2:
• alignment on the second edition of IEC 61439-1 (2011) regarding the structure and
technical content, as applicable;
• introduction of new verifications, accordingly;
• correction of inconsistencies in resistance, reactance and impedance measurements and
calculations;
• numerous editorial improvements.

– 4 – 61439-6 © IEC:2012
The text of this standard is based on the following documents:
FDIS Report on voting
17D/452/FDIS 17D/454/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This standard is to be read in conjunction with the second edition of IEC 61439-1. The
provisions of the general rules dealt with in IEC 61439-1 (hereinafter referred to as Part 1) are
only applicable to this standard insofar as they are specifically cited. When this standard
states “addition”, “modification” or “replacement”, the relevant text in Part 1 is to be adapted
accordingly.
Subclauses that are numbered with a 101 (102, 103 etc.) suffix are additional to the same
subclause in Part 1.
Tables and figures in this Part 6 that are new are numbered starting with 101.
New annexes in this Part 6 are lettered AA, BB, etc.
The “in some countries” notes regarding differing national practices are contained in the
following subclauses:
5.4
A list of all parts of the IEC 61439 series, under the general title Low-voltage switchgear and
controlgear assemblies can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
61439-6 © IEC:2012 – 5 –
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ASSEMBLIES –

Part 6: Busbar trunking systems (busways)

1 Scope
NOTE 1 Throughout this part, the abbreviation BTS is used for a busbar trunking system. Where reference to
Part 1 is made, the term ASSEMBLY therefore reads as “BTS”.
This part of IEC 61439 lays down the definitions and states the service conditions,
construction requirements, technical characteristics and verification requirements for low
voltage BTS (see 3.101) as follows:
• BTS for which the rated voltage does not exceed 1 000 V in case of a.c. or 1 500 V in
case of d.c.;
• BTS intended for use in connection with the generation, transmission, distribution and
conversion of electric energy, and for the control of electric energy consuming equipment;
• BTS designed for use under special service conditions, for example in ships, in rail
vehicles, and for domestic applications (operated by unskilled persons), provided that the
relevant specific requirements are complied with;
NOTE 2 Supplementary requirements for BTS in ships are covered by IEC 60092-302.
• BTS designed for electrical equipment of machines. Supplementary requirements for BTS
forming part of a machine are covered by the IEC 60204 series.
This standard applies to all BTS whether they are designed, manufactured and verified on a
one-off basis or fully standardized and manufactured in quantity.
The manufacture and/or assembly may be carried out by a manufacturer other than the
original manufacturer (see 3.10.1 and 3.10.2 of Part 1).
This standard does not apply to individual devices and self-contained components, such as
motor starters, fuse switches, electronic equipment, etc. which will comply with the relevant
product standard.
This standard does not apply to the specific types of ASSEMBLIES covered by other parts of the
IEC 61439 series, to supply track systems in accordance with IEC 60570, to cable trunking
and ducting systems in accordance with the IEC 61084 series, nor to power track systems in
accordance with the IEC 61534 series.
2 Normative references
This clause of Part 1 is applicable except as follows.
Addition:
IEC 60332-3-10:2000, Tests on electric and optical fibre cables under fire conditions –
Part 3-10: Test for vertical flame spread of vertically-mounted bunched wires or cables –
Apparatus
IEC 60439-2:2000, Low-voltage switchgear and controlgear assemblies – Part 2: Particular
requirements for busbar trunking systems (busways)

– 6 – 61439-6 © IEC:2012
IEC 61439-1:2011, Low-voltage switchgear and controlgear assemblies – Part 1: General
rules
IEC 61786:1998, Measurement of low-frequency magnetic and electric fields with regard to
exposure of human beings – Special requirements for instruments and guidance for
measurements
ISO 834-1:1999, Fire-resistance tests – Elements of building construction – Part 1: General
requirements
3 Terms and definitions
This clause of Part 1 is applicable except as follows.
Additional definitions:
3.101
busbar trunking system
BTS
busway
enclosed ASSEMBLY used to distribute and control electrical energy for all types of loads,
intended for industrial, commercial and similar applications, in the form of a conductor system
comprising busbars which are spaced and supported by insulating material in a duct, trough
or similar enclosure
[SOURCE: IEC 60050-441:1984, 441-12-07 modified]
Note 1 to entry: See 3.1.1 of Part 1 for the definition of ASSEMBLY.
Note 2 to entry: The BTS may consist of a full range of mechanical and electrical components such as:
– busbar trunking units with or without tap-off facilities;
– phase transposition, expansion, flexible, feeder and adapter units;
– tap-off units;
– additional conductors for communication and/or control.
Note 3 to entry: The term "busbar'' does not presuppose the geometrical shape, size and dimensions of the
conductor.
3.102
busbar trunking unit
BTU
unit of a BTS complete with busbars, their supports and insulation, external enclosure and
any fixing and connecting means to other units, with or without tap-off facilities
Note 1 to entry: BTUs may have different geometrical shapes such as straight length, elbow, tee or cross.
3.103
busbar trunking run
BT run
number of BTUs connected together to form the BTS, excluding the tap-off units
3.104
busbar trunking unit with tap-off facilities
BTU with tap-off facilities
BTU designed to enable tap-off units to be installed at one or more points as predetermined
by the original manufacturer
61439-6 © IEC:2012 – 7 –
3.105
busbar trunking unit with trolley-type tap-off facilities
BTU with trolley-type tap-off facilities
BTU designed to permit the use of roller- or brush-type tap-off units
3.106
busbar trunking adapter unit
adapter BTU
BTU intended to connect two units of the same system but of different type or of different
rated current
3.107
busbar trunking thermal expansion unit
thermal expansion BTU
BTU intended to permit a certain movement in the axial direction of the BT run due to thermal
expansion of the system
Note 1 to entry: This term does not presuppose which elements permit movement, e.g. the conductors within the
enclosure or both conductors and enclosure
3.108
busbar trunking phase transposition unit
phase transposition BTU
BTU intended to change the relative positions of the phase conductors in order to balance the
inductive reactances or to transpose the phases (such as L1-L2-L3-N to N-L3-L2-L1)
3.109
flexible busbar trunking unit
flexible BTU
BTU having conductors and enclosures designed to allow a specified change of direction
during installation
3.110
busbar trunking feeder unit
feeder BTU
BTU serving as an incoming unit
Note 1 to entry: See 3.1.9 of Part 1 for the definition of incoming unit.
3.111
tap-off unit
outgoing unit, either fixed or removable, for tapping-off power from the BTU
Note 1 to entry: See 3.1.10, 3.2.1 and 3.2.2 of Part 1 for the definition of outgoing unit, fixed part and removable
part.
Note 2 to entry: A plug-in tap-off unit is a removable tap-off unit (see 8.5.2) which can be connected or
disconnected by manual operation
3.112
busbar trunking unit for building movements
BTU for building movements
BTU intended to allow for building movements due to thermal expansion, contraction and/or
flexing of the building
3.113
busbar trunking fire barrier unit
fire barrier BTU
BTU or a part of, intended to prevent the propagation of fire through building divisions for a
specified time under fire conditions

– 8 – 61439-6 © IEC:2012
4 Symbols and abbreviations
This clause of Part 1 is applicable except as follows.
Addition:
Symbol / Term Subclause
Abbreviation
k temperature factor of the BTS 5.3.1
1A
k
temperature factor of a circuit 5.3.2
1c
k mounting factor of a circuit 5.3.2
2c
R, X, Z phase conductor and fault-loop characteristics 5.101

5 Interface characteristics
This clause of Part 1 is applicable except as follows.
5.1 General
Replacement:
The characteristics of the BTS shall ensure compatibility with the ratings of the circuits to
which it is connected and the installation conditions and shall be declared by the BTS
manufacturer using the criteria identified in 5.2 to 5.6 and 5.101 to 5.102.
The specification schedule according to informative Annex C is intended to help the user and
the BTS manufacturer to meet this objective, whether the user:
• select catalogue products the characteristics of which meet their needs, and the
requirements of this standard,
• and/or make a specific agreement with the manufacturer.
NOTE Annex C also relates to the topics dealt with in Clauses 6 and 7.
In some cases information provided by the BTS manufacturer may take the place of an
agreement.
5.2.4 Rated impulse withstand voltage (U ) (of the ASSEMBLY)
imp
Replacement of the NOTE:
NOTE Unless otherwise specified, the rated impulse withstand voltage is selected according to overvoltage
category IV (origin of installation level) or III (distribution circuit level) as given in Table G.1 of Part 1.
5.3.1 Rated current of the ASSEMBLY (I )
nA
Addition:
NOTE 4 Where the BTS is not equipped with a single incoming unit at one end of the BT run, (e.g. incoming unit
not installed at one end of the BTS, or more than one incoming unit), the rated currents will be subject to
agreement between the user and the manufacturer.
The rated current shall apply for a specified mounting orientation (see 5.3.2). However the
influence of the mounting orientation may be ignored for short (e.g. less than 3 m long)
vertical sections in a horizontal BTS.

61439-6 © IEC:2012 – 9 –
The BTS manufacturer may state the rated currents of the BTS for different ambient
temperatures for example by means of the following formula:
I’ = k I
nA 1A nA
where k is a temperature factor, equal to 1 at an ambient air temperature of 35 °C.
1A
In case of significant harmonic currents, special agreement shall be made for a reduction
factor, if necessary.
5.3.2 Rated current of a circuit (I )
nc
Addition:
The rated current (I ) of each circuit (i.e. incoming unit, BTU, tap-off unit, outgoing circuit)
nc
shall be equal to or higher than its assumed loading. For tap-off units provided with more than
one main outgoing circuit, see also 5.4.
The rated current shall apply for specified mounting conditions. Mounting conditions may
include orientation and position, as follows:
a) orientation
Orientation may be horizontal or vertical.
Unless otherwise specified, the reference orientation is horizontal.
b) position
Position may be for example edgewise or flatwise for a BT run, and/or below or on top of
the BTU for a tap-off unit.
The BTS manufacturer may state different rated currents for different ambient temperatures
and/or mounting conditions, where applicable, for example by means of the following formula:
I’ = k k I
nc 1c 2c nc
where
k is a temperature factor, equal to 1 at an ambient air temperature of 35 °C;
1c
k is a mounting factor, equal to 1 in the reference mounting conditions.
2c
In case of significant harmonic currents, special agreement shall be made for a reduction
factor, if necessary.
5.4 Rated diversity factor (RDF)
Replacement:
For the whole BTS, unless otherwise specified, the RDF (see 3.8.11 of Part 1) shall be equal
to 1, i.e. all tap-off units can be continuously and simultaneously loaded with their full rated
current, within the limit of the rated current of the BT run(s) and feeder BTU(s)
NOTE 1 This is because thermal influence between tap-off units is considered negligible.
For tap-off units provided with more than one main outgoing circuit, these circuits shall be
able to be continuously and simultaneously loaded at their rated current multiplied by the
RDF, within the limit of the rated current of the tap-off unit. Unless otherwise specified, the
RDF of such tap-off units shall be equal to the values given in Table 101.

– 10 – 61439-6 © IEC:2012
Table 101 – Rated diversity factor for a tap-off unit
Number of main outgoing circuits Rated diversity factor
2 and 3 0,9
4 and 5 0,8
6 to 9 inclusive 0,7
10 (and above) 0,6
The RDF is applicable with the BTS operating at rated current (I )
nA
NOTE 2 The RDF recognizes that multiple functional units are in practice not fully loaded simultaneously or are
intermittently loaded.
NOTE 3 The assumed loading of the outgoing circuits can be a steady continuous current or the thermal
equivalent of a varying current.
NOTE 4 In Norway, the overload protection of conductors is not solely based on the use of diversity factors of the
downstream circuits.
5.6 Other characteristics
Modification of item e):
e) stationary BTS ;
Modification of item j):
j) enclosed BTS;
Addition:
aa) ability to withstand mechanical loads, either normal or heavy (see 8.1.101);
bb) resistance to flame propagation, if applicable (see 9.101);
cc) fire resistance in building penetration, if applicable (see 9.102).
Additional subclauses:
5.101 Phase conductor and fault-loop characteristics
NOTE 1 For BTS rated below 100 A, the reactances are deemed negligible.
R and X according to Table 102 are intended to be used to calculate voltage drops (see
informative Annex AA).
61439-6 © IEC:2012 – 11 –
Table 102 – Phase conductor characteristics
Mean phase conductor characteristics
at rated current I , and rated frequency f
nc n
Ω per-metre length
Resistance,
R
- at an ambient air temperature of 35 °C
R
- at a conductor temperature of 20 °C
Reactance (independent from temperature) X
Positive-sequence and negative-sequence impedances
- at an ambient air temperature of 35 °C Z = Z = Z
(1) (2)
- at a conductor temperature of 20 °C Z = Z = Z
20 (1)20 (2)20
All phase conductor characteristics may be determined according to Annex BB.

R and X according to Table 102, and fault-loop resistances and reactances according to
Table 103, i.e. the total resistances and reactances of the phase conductor(s) and return
path, are intended to be used to calculate fault currents according to the method of
impedances (see Table 104).
Z and Z according to Table 102, and fault-loop zero-sequence impedances according to
Table 103, i.e. the total zero-sequence impedances of the phase conductor(s) and return
path, are intended to be used to calculate fault currents according to the method of
symmetrical components (see Table 104).
NOTE 2 Fault currents reach their lowest value for the highest impedance values; this is deemed to happen when
the BTUs are operating at I at the maximum normal ambient air temperature i.e. 35 °C, resulting in a conductor
nc
temperature of (35 + ∆θ) °C, where ∆θ is the mean stabilized temperature rise measured according to 10.10.
Conversely fault currents reach their highest value for the lowest impedance values; this is deemed to happen
when the BTUs are not operating, resulting in a conductor temperature of 20 °C, and the circuit is closed while a
short-circuit is present.
Table 103 – Fault-loop characteristics
Mean fault-loop characteristics
Phase-to- Phase-to- Phase-to-
at rated frequency f Phase-to-PE
n
phase neutral PEN
Ω per-metre length
Zero-sequence impedances
- at an ambient air temperature of 35 °C Z Z Z
(0)bphN (0)bphPEN (0)bphPE
- at a conductor temperature of 20 °C Z Z Z
(0)b20phN (0)b20phPEN (0)b20phPE
Resistances
- at an ambient air temperature of 35 °C R R R R
bphph bphN bphPEN bphPE
- at a conductor temperature of 20 °C R R R R
b20phph b20phN b20phPEN b20phPE
Reactances (independent from temperature) X X X X
bphph bphN bphPEN bphPE
Fault-loop zero-sequence impedances may be determined according to Annex CC.
Fault-loop resistances and impedances may be determined according to Annex DD.

– 12 – 61439-6 © IEC:2012
Table 104 – Characteristics to be used for fault currents calculations
Method
Fault currents Method of impedances
of symmetrical components
Maximum short-circuit current
- 3-phase R , X Z
20 20
- phase-to-phase R , X Z
b20phph bphph 20
- phase-to-neutral R , X Z and Z
b20phN bphN 20 (0)20phN
Minimum short-circuit current
- phase-to-phase R , X Z
bphph bphph
R , X Z and Z
- phase-to-neutral
bphN bphN (0)phN
Earth fault current (phase-to-PE(N)) R , X Z and Z
bphPE(N) bphPE(N) (0)phPE(N)
NOTE 3 The method of symmetrical components is based on respectively summing the modulus of the fault-loop
positive-, negative- and zero-sequence impedances (see IEC 60909-0). Similarly the method of impedance is
based on respectively summing the modulus of the fault-loop resistances and reactances.
5.102 Electromagnetic field
The strength of the power frequency magnetic field in the vicinity of the BT run may be stated
by the BTS manufacturer.
NOTE The magnetic field is a fast-decreasing function of the distance.
A method for measurement and calculation of the modulus of the magnetic field around the
BTS is given in Annex EE.
6 Information
This clause of Part 1 is applicable except as follows.
6.1 ASSEMBLY designation marking
Addition after the first paragraph:
One nameplate shall be located near one end of each BTU and one on each tap-off unit.
Replacement:
d) IEC 61439-6.
7 Service conditions
This clause of Part 1 is applicable except as follows.
7.2 Special service conditions
Addition:
aa) exposure to special mechanical loads, such as lighting apparatus, additional cables,
ladder supports, etc.;
bb) applications with high repetitive overcurrent, for example resistance welding;
cc) installation near highly sensitive IT equipment, such as high-speed data networks,
radiology apparatus, workstation monitors, etc.;

61439-6 © IEC:2012 – 13 –
dd) applications requiring defined performance under fire conditions, e.g. circuit integrity for a
definite time.
8 Constructional requirements
This clause of Part 1 is applicable except as follows.
8.1.5 Mechanical strength
Addition after the last paragraph:
BTS with trolley-type tap-off facilities shall be able to carry out successfully 10 000 cycles of
to-and-fro movements along the conductors of the BT run, with the sliding contacts carrying
their rated current at rated voltage. In the case of a.c., the power factor of the load shall be
between 0,75 and 0,8.
Compliance to this requirement is checked by the test of 10.13.
Additional subclauses:
8.1.101 Ability to withstand mechanical loads
BTS intended for horizontal installation shall be able to withstand in use normal or heavy
mechanical loads as specified according to 5.6 aa).
Normal mechanical loads include the weight of the feeder unit, if not supported by its own
separate fixings, and tap-off units, in addition to the weight of the BTUs.
Heavy mechanical loads include additional loads such as the weight of a person.
NOTE This statement does not imply that a BTS is a walkway.
The necessary mechanical properties may be obtained by the choice of material, its
thickness, its shape, and/or by the number of and position of fixing points as indicated by the
original manufacturer.
Compliance to this requirement is checked by test according to 10.2.101.
8.1.102 Ability of plug-in tap-off units to withstand thermal variations
Plug-in tap-off units in which the contact force is developed by the deflection of a spring
member shall be able to withstand the mechanical constraints due to temperature variations
when subjected to intermittent duty.
NOTE For the purpose of this requirement, a disc spring is not considered to be a spring member.
Compliance is checked by test according to 10.2.102.
8.2.1 Protection against mechanical impact
Replacement:
Where a degree of protection against mechanical impact according to IEC 62262 IK code is
declared by the original manufacturer, the BTS shall be so designed that it is capable of
withstanding the test according to IEC 62262 IK code (see 10.2.6).

– 14 – 61439-6 © IEC:2012
8.3.2 Clearances
Addition after the first paragraph:
Clearances of supplementary insulation shall be not less than those specified for basic
insulation. Clearances of reinforced insulation shall be dimensioned to the rated impulse
voltage one step higher than those specified for basic insulation (see Table 1 of Part 1).
8.3.3 Creepage distances
Addition after the third paragraph:
Creepage distances of supplementary insulation shall be not less than those specified for
basic insulation. Creepage distances of reinforced insulation shall be twice those specified for
basic insulation (see Table 2 of Part 1).
8.4.3.2.3 Requirements for protective conductors providing protection against the
consequences of faults in external circuits supplied through the BTS
Addition after the last paragraph:
In BTS with trolley tap-off facilities, constructional precautions shall be taken to ensure good
and permanent conductivity between the exposed conductive parts of tap-off units and the
stationary exposed conductive parts, in particular when the enclosure of the fixed units is part
of the protective circuit of the installation.
8.5.2 Removable parts
Replacement of the third paragraph:
A removable part may be fitted with a device, which ensures that it can only be removed and
inserted after its main circuit has been switched off from the load.
Addition:
NOTE A tap-off unit is or is not a removable part as defined in this subclause and in 3.2.2 of Part 1, according to
the manufacturer’s designation.
8.5.5 Accessibility
This subclause of Part 1 is not applicable.
Additional subclause:
8.6.101 Correct connection between BTS units
BTUs shall be so designed as to ensure correct connection between the conductors of
adjacent units forming a BTS (power circuits, auxiliary and communication circuits, PE…).
This requirement may be achieved by proper identification of each connection.
BTUs and tap-off units shall be so designed as to ensure correct connection between their
conductors (power circuits, auxiliary and communication circuits, PE…). This requirement
shall be achieved by insertion interlocks (see 3.2.5 of Part 1).
9 Performance requirements
This clause of Part 1 is applicable except as follows.

61439-6 © IEC:2012 – 15 –
9.2 Temperature rise limits
d
Replacement of footnote in Table 6:
d
Unless otherwise specified, in the case of covers and enclosures, which are accessible but need not be
touched during normal operation, a 25 K increase on these temperature-rise limits for metal surfaces and a
15 K increase on these temperature-rise limits for insulating material surfaces are permissible.
Additional subclauses:
9.101 Resistance to flame propagation
A non-flame-propagating BTS either shall not ignite or, if ignited, shall not continue to burn
when the source of ignition is removed.
Compliance is checked by the flame-propagation tests according to 10.101.
9.102 Fire resistance in building penetration
A fire barrier BTU, if any, shall be designed to prevent the propagation of fire, for a specified
time, under fire conditions, where the BTS passes through horizontal or vertical building
divisions (for example, wall or floor).
Where applicable, the following times are preferred: 60 min, 90 min, 120 min, 180 min or
240 min.
This may be achieved by means of additional parts.
Compliance is checked by the fire-resistance test according to 10.102.
10 Design verifications
This clause of Part 1 is applicable except as follows.
10.1 General
Replacement of the second paragraph:
Where tests on the BTS have been conducted in accordance with IEC 60439-2, and the test
results fulfil the requirements of this Part 6 of IEC 61439, the verification of these
requirements need not be repeated.
Addition at the end of b) Performance:
10.101 Resistance to flame propagation;
10.102 Fire resistance in building penetration.
10.2.6 Mechanical impact
Replacement:
The BTS shall be tested according to IEC 62262.
After the test, the BTS shall continue to provide the IP code and dielectric strength; it shall be
possible to remove and reinstall removable covers and tap-off units and to open and close
doors, as applicable.
Additional subclauses:
– 16 – 61439-6 © IEC:2012
10.2.101 Ability to withstand mechanical loads
10.2.101.1 Test procedure for a straight busbar trunking unit
The first test shall be made on one straight BTU supported as in normal use at two positions
spaced at the maximum distance D specified by the original manufacturer. The location and
form of the supports shall be specified by the original manufacturer. See Figure 101.

M
D D
2 2
D
IEC  834/12
Figure 101 – Mechanical load test of a straight unit
A mass M shall be placed without dynamic loading on a square rigid piece with sides equal to
the width of the BTU, at the midpoint between the supports on top of the enclosure.
The mass M shall be equal to:
m + m for normal loads
• L
• m + m + 90 kg for heavy loads
L
where
• m is the mass of the BTU between the supports
• m is the mass of the feeder and tap-off units specified by the original manufacturer to be
L
connected to the length D.
The duration of the test shall be at least 5 min.
10.2.101.2 Test procedure for a joint
A second test shall be made on two BTUs joined together and supported as in normal use at
the minimum number of positions at the distances D and D . The distance D is that specified
in 10.2.101.1; the distance D is the maximum distance between supports adjacent to a joint
as specified by the original manufacturer. The joint shall be placed midway between the

supports. See Figure 102.
M
D D
1 1
2 2
D
D D
IEC  835/12
Figure 102 – Mechanical load test of a joint
A mass M shall be placed without dynamic loading on top of the enclosure at the joint on a
square rigid piece with sides equal to the width of the BTU.

61439-6 © IEC:2012 – 17 –
The mass M shall be equal to:
m + m for normal loads
• 1 L1
• m + m + 90 kg for heavy loads
1 L1
where
• m is the mass of those parts of the BTUs, including the joint, between the supports
located at distance D
is the maximum mass of the feeder and tap-off units specified by the original
• m
L1
manufacturer to be connected to the length D .
The duration of the test shall be at least 5 min.
10.2.101.3 Resistance of the enclosure to crushing
A straight BTU shall be subjected to a crushing force, successively at four or more points,
including one point between adjacent insulators, if any.
The BTU shall be supported horizontally on a flat surface and the force shall be applied
through a rigid plate equal to the width of the BTU and 120 mm long.
The crushing force shall at least be equal to 4 times the weight of 1 m length, for BTS stated
for normal mechanical loads; a mass of 90 kg shall be added for BTS stated for heavy
mechanical loads.
The duration of the test shall be at least 5 min per point.
10.2.101.4 Results to be obtained
During and after the tests according to 10.2.101.1 to 10.2.101.3, there shall be neither break,
nor permanent deformation of the enclosure which would compromise the degree of
protection, reduce the clearances and creepage distances to values lower than those
specified in 8.3, or impair the correct insertion of incoming and outgoing units.
The protective circuit shall remain functional and the test samples shall withstand the
dielectric test according to 10.9.2 of Part 1.
10.2.102 Thermal cycling test
10.2.102.1 General
Plug-in tap-off units shall be submitted to a thermal cycling test.
10.2.102.2 Test sample
If the same design of the plug assembly is used for a range of tap-off units of different rated
currents or of different protective devices, a test on one combination of a BTU and a tap-off
unit is considered to be representative of the range. The design of the plug assembly includes
the physical characteristics and the material and surface finish (e.g. plating), if applicable.
A tap-off unit incorporating fuses shall be fitted with the maximum size of fuses specified by
the original manufacturer. A tap-off unit incorporating a circuit-breaker shall be fitted with a
circuit-breaker of the maximum rating specified by the original manufacturer.
The tap-off unit shall be arranged and loaded as in 10.10.2.3.6.

– 18 – 61439-6 © IEC:2012
Prior to test, the sample is conditioned by a number of cycles of insertion and removal of the
tap-off unit in the intended manner, without load current, as given in Table 105.
Table 105 – Conditioning for the thermal cycling test
Rated current Number of cycles
A of insertion and removal
I ≤ 63 25
nc
63 < I ≤ 200 10
nc
200 < I
nc
10.2.102.3 Test procedure
The current is applied until the temperatures have stabilised. The temperatures as specified
for the temperature-rise test are recorded. Both currents are switched off and the sample is
allowed to return to room temperature.
The sample is then subjected to 84 cycles consisting of
a) 3 h ON at rated current and 3 h OFF, or
b) 2 h ON at rated current and 2 h OFF,
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...