Instrument transformers - Part 14: Additional requirements for current transformers for DC applications

IEC 61869-14:2018 provides all requirements specific to current transformers to be used in DC applications (DCCTs), whatever the technology used. The output signal can be analogue or digital. It is applicable to newly manufactured current transformers used for measuring, protection and/or control applications in DC power systems with a rated voltage above 1,5 kV. The general configuration of a single-pole low-power instrument transformer is described in Figure 601 of IEC 61869-6:2016. The DCCTs intended for current measurement in the transistor branch of the VSC valve (referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this document, and will be considered in a future revision. IEC 61869-14:2018 applies to current transformers intended to be used in DC applications with at least one of the following functions: • measure DC current (with significant harmonics); • withstand DC voltage. Depending on the position on the DC system, different kinds of application exist, which are briefly described below, together with the approximate voltage or current wave shape.

Messwandler - Teil 14: Zusätzliche Anforderungen an Stromwandler für Gleichstromanwendungen

Transformateurs de mesure - Partie 14: Exigences supplémentaires concernant les transformateurs de courant pour application en courant continu

IEC 61869-14:2018 couvre toutes les exigences particulières concernant les transformateurs de courant utilisés dans les applications en courant continu (DCCTs), quelle que soit la technologie utilisée. Le signal de sortie peut être analogique ou numérique. Elle s'applique aux transformateurs de courant fabriqués récemment et utilisés pour des applications de mesure, de protection et/ou de commande sur des systèmes d'alimentation électrique en courant continu dont la tension assignée est supérieure à 1,5 kV. La configuration générale d'un transformateur de mesure de faible puissance unipolaire est décrite à la Figure 601 de l'IEC 61869-6:2016. Les transformateurs de courant continu destinés aux mesures de courant dans la branche du transistor de la valve VSC (dénommés CT4a et CT4b à la Figure 1403 et au Tableau 1402) ne sont pas couverts par le présent document et seront traités lors d'une prochaine révision. IEC 61869-14:2018 s'applique aux transformateurs de courant destinés à être utilisés dans les applications en courant continu avec l'une des fonctions suivantes au moins:
• mesurage du courant continu (avec des harmoniques élevées); • tension continue de tenue. Selon la position du système à courant continu, différents types d'applications existent. Ils sont décrits brièvement ci-dessous, ainsi que la tension approximative ou la forme d'onde du courant.

Instrumentni transformatorji - 14. del: Dodatne zahteve za tokovne transformatorje za enosmerno napajanje (IEC 61869-14:2018)

Ta del standarda IEC 61869 podaja vse zahteve, specifične za tokovne transformatorje, ki se uporabljajo pri enosmernem toku (DCCT-je), ne glede na uporabljeno tehnologijo. Izhodni signal je lahko analogni ali digitalni.
Uporablja se za nove tokovne transformatorje, ki se uporabljajo za merjenje, zaščito in/ali nadzor v omrežjih enosmernega toka z nazivno napetostjo nad 1,5 kV.
Splošna konfiguracija enopolnega nizkonapetostnega merilnega transformatorja je opisana na sliki 601 standarda IEC 61869-6:2016.
DCCT-ji, ki so namenjeni merjenju toka v tranzistorski veji ventila VSC (imenovani tudi CT4a in CT4b na sliki 1403 in v preglednici 1402), v tem dokumentu niso zajeti in bodo upoštevani v prihodnji reviziji.

General Information

Status
Published
Publication Date
04-Jul-2019
Withdrawal Date
04-Jul-2022
Drafting Committee
Current Stage
6060 - Document made available - Publishing
Start Date
05-Jul-2019
Completion Date
05-Jul-2019

Overview

EN IEC 61869-14:2019 (CLC adoption of IEC 61869-14:2018) defines additional requirements for current transformers for DC applications (DCCTs). It applies to newly manufactured instrument current transformers used for measuring, protection and control in DC power systems with a rated voltage above 1.5 kV. The standard covers DCCTs regardless of technology and supports devices with analogue or digital outputs. Note: DCCTs intended for the transistor branch of the VSC valve (CT4a/CT4b) are excluded and will be addressed in a future revision.

Key Topics

  • Scope & Ratings: Intended functions (measure DC, withstand DC voltage) and applicable system locations (LCC, VSC converter schemes), with guidance on rated currents and insulation requirements.
  • Design & Construction: Requirements for mechanical, electrical and insulation layout suited to DC stress and converter environments.
  • Performance & Accuracy: Definitions of accuracy classes, ratio error limits and step response behavior (including polarity reversal and transient performance).
  • Tests & Type Tests: Mandatory and recommended tests such as thermal testing (including harmonic heating considerations), partial discharge, static withstand, polarity reversal, step-response timing and arc-fault performance.
  • Annexes: Informative Annex 14A on equivalent thermal current and harmonic loss effects; Annex 14B proposing rated insulation levels for DCCTs.
  • Marking & Documentation: Rating plate and terminal marking requirements for traceability and installation.

Applications

EN IEC 61869-14 is directly applicable to:

  • HVDC transmission systems (line-commutated converters - LCC) and voltage-source converter (VSC) DC links where DC current measurement and insulation across DC potentials are required.
  • Protection and control systems in converter stations, DC substations and HVDC cable systems.
  • Metering and telemetry for DC networks where accurate DC current sensing with harmonic content is necessary.
  • Manufacture and type-approval of DCCT devices with analogue or digital instrument interfaces.

Who Uses This Standard

  • Transformer and sensor manufacturers designing DC current transformers and low‑power converter modules.
  • Utilities and HVDC project engineers specifying equipment for DC transmission and converter stations.
  • Testing and certification laboratories performing type and routine tests (thermal, partial discharge, withstand, dynamic response).
  • Protection, metering and control engineers integrating DCCTs in protection relays, control loops and merging units.

Related Standards

  • IEC 61869 series: 61869-1 (general requirements), 61869-6 (low-power instrument transformers), 61869-9 (digital interface for instrument transformers).
  • Normative references include technical specifications for DC insulators and pollution testing (see Annex ZA for cross-references).

Keywords: EN IEC 61869-14:2019, DCCT, current transformers, instrument transformers, DC applications, HVDC, LCC, VSC, thermal testing, partial discharge, DC power systems.

Standard
EN IEC 61869-14:2019 - BARVE na PDF-str 13,14,15,16,46
English language
45 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard
EN IEC 61869-14:2019 - BARVE
English language
45 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-oktober-2019
Merilni transformatorji - 14. del: Dodatne zahteve za tokovne transformatorje za
enosmerno napajanje (IEC 61869-14:2018)
Instrument transformers - Part 14: Additional requirements for current transformers for
DC applications (IEC 61869-14:2018)
Messwandler - Teil 14: Besondere Anforderungen für Gleichstromwandler (IEC 61869-
14:2018)
Transformateurs de mesure - Partie 14: Exigences supplémentaires concernant les
transformateurs de courant pour application en courant continu (IEC 61869-14:2018)
Ta slovenski standard je istoveten z: EN IEC 61869-14:2019
ICS:
17.220.20 Merjenje električnih in Measurement of electrical
magnetnih veličin and magnetic quantities
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61869-14

NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2019
ICS 17.200.20
English Version
Instrument transformers - Part 14: Additional requirements for
current transformers for DC applications
(IEC 61869-14:2018)
Transformateurs de mesure - Partie 14: Exigences Messwandler - Teil 14: Besondere Anforderungen für
supplémentaires concernant les transformateurs de courant Gleichstromwandler
pour application en courant continu (IEC 61869-14:2018)
(IEC 61869-14:2018)
This European Standard was approved by CENELEC on 2018-08-21. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61869-14:2019 E

European foreword
The text of document 38/560/FDIS, future edition 1 of IEC 61869-14, prepared by IEC/TC 38
"Instrument transformers" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN IEC 61869-14:2019.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2020-01-05
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2022-07-05
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Directive(s).
For the relationship with EU Directive(s) see informative Annex ZZ, which is an integral part of this
document.
Endorsement notice
The text of the International Standard IEC 61869-14:2018 was approved by CENELEC as a European
Standard without any modification.

Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Clause 2 of IEC 61869-6:2016 is applicable, with the following additions and modifications:
Publication Year Title EN/HD Year
IEC/TS 60815-4 2019 Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 4: Insulators for d.c.
systems
IEC/TS 61245:2015 2015 Artificial pollution tests on high-voltage - -
ceramic and glass insulators to be used on
d.c. systems
IEC 61869-6 2016 Instrument transformers - Part 6: Additional EN 61869-6 2016
general requirements for low-power
instrument transformers
IEC 61869-9 2016 Instrument transformers - Part 9: Digital EN IEC 61869-9 2019
interface for instrument transformers

IEC 61869-14 ®
Edition 1.0 2018-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Instrument transformers –
Part 14: Additional requirements for current transformers for DC applications

Transformateurs de mesure –
Partie 14: Exigences supplémentaires concernant les transformateurs de

courant pour application en courant continu

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 17.220.20 ISBN 978-2-8322-5803-3

– 2 – IEC 61869-14:2018 © IEC 2018
CONTENTS
FOREWORD . 4
INTRODUCTION . 7
1 Scope . 11
2 Normative references . 11
3 Terms and definitions . 11
5 Ratings . 16
6 Design and construction . 20
7 Tests . 25
Annex 14A (informative) Equivalent thermal current in CTs for DC application . 37
14A.1 General . 37
14A.2 Current harmonic content . 37
14A.3 Losses in primary conductor due to harmonic content . 38
14A.4 Thermal test with AC current . 40
Annex 14B (informative) Proposed rated insulation level applicable to current
transformers for DC application. 41
Bibliography . 42

Figure 1401 – Example of LCC scheme . 7
Figure 1402 – Typical scheme for VSC – symmetrical monopole . 8
Figure 1403 – Typical scheme for VSC – asymmetrical monopole or bipole . 9
Figure 1404 – Typical step responses of a system . 14
Figure 1405 – Accuracy limits of a DCCT . 19
Figure 1406 – Polarity reversal test profile . 30
Figure 1407 – Measurement of the step response time . 32
Figure 14A.1 – Typical waveform of current flowing in the primary conductor for LCC
applications . 37
Figure 14A.2 – The two terms that make up the total losses in the primary conductor . 39
Figure 14A.3 – Additional losses in conductors due to typical current harmonics . 40
Figure 14A.4 – Power-frequency losses in conductors compared to DC losses . 40

Table 1401 – Current and voltage in current transformers for LCC application . 8
Table 1402 – Current and voltage in current transformers for VSC application . 10
Table 3 – Partial discharge test voltages and permissible levels . 17
Table 1403 – Limits of ratio error for DCCT (classes from 0,1 to 1) . 19
Table 7 – Static withstand test loads . 21
Table 8 – Arc fault duration and performance criteria . 22
Table 1404 – Markings of terminals . 23
Table 1405 – Rating plate marking for common rating plate . 24
Table 1406 – Rating plate marking for each secondary converter . 24
Table 1407 – Rating plate marking for auxiliary power supply . 25

IEC 61869-14:2018 © IEC 2018 – 3 –
Table 10 – List of tests. 26
Table 14A.1 – Typical harmonic current values (800 kV LCC) . 38
Table 14B.1 – Proposed rated primary terminal insulation levels for current
transformers for DC application. 41

– 4 – IEC 61869-14:2018 © IEC 2018
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
INSTRUMENT TRANSFORMERS –
Part 14: Additional requirements for current
transformers for DC applications

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61869-14 has been prepared by IEC technical committee 38:
Instrument transformers.
The text of this standard is based on the following documents:
FDIS Report on voting
38/560/FDIS 38/565/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.

IEC 61869-14:2018 © IEC 2018 – 5 –
A list of all parts in the IEC 61869 series, published under the general title Instrument
transformers, can be found on the IEC website.
This Part 14 is to be used in conjunction with, and is based on, IEC 61869-1:2007, General
requirements, and IEC 61869-6:2016, Additional general requirements for low-power
instrument transformers – however the reader is encouraged to use the most recent editions.
This Part 14 follows the structure of IEC 61869-1:2007 and IEC 61869-6:2016 and
supplements or modifies their corresponding clauses.
When a subclause of Part 1 or Part 6 is not mentioned in this Part 14, that subclause applies.
When this standard states “addition”, “modification” or “replacement”, the relevant text in
Part 1 or Part 6 is to be adapted accordingly.
For additional clauses, subclauses, figures, tables, annexes or notes, the following numbering
system is used:
• clauses, subclauses, tables, figures and notes that are numbered starting from 1401 are
additional to those in Part 1 and Part 6;
• additional annexes are lettered 14A, 14B, etc.
An overview of the planned set of standards at the date of publication of this document is
given below. The updated list of standards issued by IEC TC 38 is available at the website:
www.iec.ch
PRODUCT FAMILY STANDARDS PRODUCT PRODUCTS OLD
STANDARD STANDARD
61869-1 61869-2 ADDITIONAL REQUIREMENTS FOR 60044-1
CURRENT TRANSFORMERS 60044-6
GENERAL
REQUIREMENTS
61869-3 ADDITIONAL REQUIREMENTS FOR 60044-2
INDUCTIVE VOLTAGE TRANSFORMERS
61869-4 ADDITIONAL REQUIREMENTS FOR 60044-3
COMBINED TRANSFORMERS
61869-5 ADDITIONAL REQUIREMENTS FOR 60044-5
CAPACITIVE VOLTAGE TRANSFORMERS
ADDITIONAL REQUIREMENTS FOR
61869-6 61869-7 60044-7
ELECTRONIC VOLTAGE TRANSFORMERS
ADDITIONAL
GENERAL 61869-8 ADDITIONAL REQUIREMENTS FOR 60044-8
REQUIREMENTS
ELECTRONIC CURRENT
FOR LOW-POWER
TRANSFORMERS
INSTRUMENT
DIGITAL INTERFACE FOR INSTRUMENT
61869-9
TRANSFORMERS
TRANSFORMERS
61869-10 ADDITIONAL REQUIREMENTS FOR LOW-
POWER PASSIVE CURRENT
TRANSFORMERS
61869-11 ADDITIONAL REQUIREMENTS FOR LOW- 60044-7
POWER PASSIVE VOLTAGE
TRANSFORMERS
61869-12 ADDITIONAL REQUIREMENTS FOR
COMBINED ELECTRONIC INSTRUMENT
TRANSFORMER OR COMBINED LOW-
POWER PASSIVE TRANSFORMERS
61869-13 STAND ALONE MERGING UNIT
ADDITIONAL REQUIREMENTS FOR
61869-14
CURRENT TRANSFORMERS FOR DC
APPLICATIONS
61869-15 ADDITIONAL REQUIREMENTS FOR
VOLTAGE TRANSFORMERS FOR DC
APPLICATIONS
– 6 – IEC 61869-14:2018 © IEC 2018
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
IEC 61869-14:2018 © IEC 2018 – 7 –
INTRODUCTION
General
This document applies to current transformers intended to be used in DC applications with at
least one of the following functions:
• measure DC current (with significant harmonics);
• withstand DC voltage.
Depending on the position of the current transformer on the DC system, different kinds of
application exist, which are briefly described below, together with the approximate voltage or
current wave shape.
Line-commutated converters (LCC)
Line-commutated converters (LCC) are based on thyristor converters (see Figure 1401). They
are characterized by a single direction of current flow, and a voltage polarity reversal
possibility. Significant voltage and current harmonics exist up to frequencies of about 3 kHz to
4 kHz.
Figure 1401 – Example of LCC scheme
We distinguish three different current-measurement functions:
• CT1: measurement of the current at the AC side of the converter;
• CT2: measurement of the current at the DC side of the converter;
• CT3: measurement of the current in the DC filter.
Table 1401 gives an overview of the current and voltage waveshapes as well as the main
characteristics of the different applications of the CT.

– 8 – IEC 61869-14:2018 © IEC 2018
Table 1401 – Current and voltage in current transformers for LCC application
Current Voltage Characteristics
CT1 AC current
AC + DC voltage
Large amount of current harmonics
Mainly for protection purposes

CT2 Pure DC application
High-accuracy measurement
Harmonics measurement
Metering, control and protection
purposes
CT3 DC voltage stress with harmonics
DC current = 0
Harmonics measurement
Mainly for protection purposes

Voltage-source converters (VSC)
Voltage-source converters (VSC) are based on transistor converters. They are characterized
by a bi-directional current flow and a single voltage polarity. Voltage and current harmonics
exist up to frequencies of about 20 kHz.
Two variants of VSC schemes exist: symmetrical monopoles (using one single converter) and
asymmetrical monopole or bipole (with one converter for each polarity).
Both schemes are shown in Figure 1402 and Figure 1403.

Figure 1402 – Typical scheme for VSC – symmetrical monopole

IEC 61869-14:2018 © IEC 2018 – 9 –

Figure 1403 – Typical scheme for VSC – asymmetrical monopole or bipole
We distinguish three different current-measurement functions:
• CT4: measurement of the current in the transistor branches of the converter.
The CT can be placed before (CT4a) or after the transistor branch (CT4b);
• CT2: measurement of the current at the DC side of the converter;
• CT3: measurement of the current in the DC filter (not always present in this scheme).
Table 1402 gives an overview of the current and voltage waveshapes as well as the main
characteristics of the different applications of the CT.

– 10 – IEC 61869-14:2018 © IEC 2018
Table 1402 – Current and voltage in current transformers for VSC application
Current Voltage Characteristics
CT2 Pure DC application
High accuracy
measurement
Harmonics measurement
Metering, control and
protection purposes
Short step response time
CT3 DC voltage stress
DC current = 0
Harmonics measurement
Mainly for protection
purposes
CT4a Symmetrical monopole: Pure AC voltage or DC +
AC voltage
DC + AC current
High-accuracy
measurement
Short step response time
Asymmetrical monopoles /
bipoles:
CT4b DC voltage stress
DC + AC current
High-accuracy
measurement
Short step response time
IEC 61869-14:2018 © IEC 2018 – 11 –
INSTRUMENT TRANSFORMERS –
Part 14: Additional requirements for current
transformers for DC applications

1 Scope
This part of IEC 61869 provides all requirements specific to current transformers to be used in
DC applications (DCCTs), whatever the technology used. The output signal can be analogue
or digital.
It is applicable to newly manufactured current transformers used for measuring, protection
and/or control applications in DC power systems with a rated voltage above 1,5 kV.
The general configuration of a single-pole low-power instrument transformer is described in
Figure 601 of IEC 61869-6:2016.
The DCCTs intended for current measurement in the transistor branch of the VSC valve
(referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this
document, and will be considered in a future revision.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
Clause 2 of IEC 61869-6:2016 is applicable, with the following additions and modifications:
IEC TS 60815-4:2016, Selection and dimensioning of high-voltage insulators intended for use
in polluted conditions – Part 4: Insulators for DC systems
IEC TS 61245:2015, Artificial pollution tests on high-voltage ceramic and glass insulators to
be used on DC systems
IEC 61869-6:2016, Instrument transformers – Part 6: Additional general requirements for low-
power instrument transformers
IEC 61869-9:2016, Instrument transformers – Part 9: Digital interface for instrument
transformers
3 Terms and definitions
Clause 3 of IEC 61869-1:2007, of IEC 61869-6:2016 and of IEC 61869-9:2016 are applicable
with the following additions and modifications.

– 12 – IEC 61869-14:2018 © IEC 2018
3.1 General definitions
3.1.1401
instrument transformer for DC application
instrument transformer intended to be used in DC applications with at least one of the
following functions:
• measure DC current or DC voltage (with significant harmonics);
• withstand DC voltage.
3.1.1402
current transformer for DC application
DCCT
instrument transformer for DC application in which the secondary signal, under normal
conditions of use, is substantially proportional to the primary current
Note 1 to entry: The different applications are described in the introduction.
3.2 Definitions related to dielectric ratings
3.2.2
highest voltage for equipment
U
m
Definition 3.2.2 of IEC 61869-1:2007 is replaced by the following one:
highest value of DC voltage for which the equipment is designed to operate continuously, in
respect of its insulation as well as other characteristics that relate to this voltage
3.3 Definitions related to current ratings
3.3.1401
DC overload current
overcurrent occurring in an electric circuit, which is not caused by a short-circuit or an earth
fault
Note 1 to entry: The DC overload current is specified by the customer in terms of value and duration.
[SOURCE: IEC 60050-826:2004, 826-11-15, modified – “DC” added in the term and Note 1 to
entry added.]
3.3.1402
short-time overload current
I
sov
DC overload current occurring for a duration shorter than one minute
3.3.1403
long-time overload current
I
lov
DC overload current occurring for a duration of minutes or hours
Note 1 to entry: Different values of long-time overload can be specified for different durations.
3.3.1404
maximum peak fault current
I
sc
maximum peak value of current occurring during a fault condition of the DC power system

IEC 61869-14:2018 © IEC 2018 – 13 –
3.4 Definitions related to accuracy
3.4.1401
Absolute error
ε
A
error (expressed in A) that a current transformer introduces into the measurement and which
arises from the fact that the actual transformation ratio is not equal to the rated transformation
ratio
Note 1 to entry: The absolute error is defined by the following formula:

ε = K ⋅ U – I
A r s p
where
K is the rated transformation ratio;
r
I is the DC value of the actual primary current in steady state;
p
U is the DC value of the output voltage.
s
3.5 Definitions related to other ratings
3.5.1401
step response
duration between the instant when the measurand (or quantity supplied) is subjected to a
specified abrupt change and the instant when the indication (or quantity supplied) reaches,
and remains within specified limits of, its final steady-state value
Note 1 to entry: See graphical explanation in Figure 1404.

– 14 – IEC 61869-14:2018 © IEC 2018

a
For periodic behaviour
b
For aperiodic behaviour
u Input variable
U Initial value of the input variable
U Step height of the input variable
s
v Output variable
V , V Steady-state values before and after application of the step
0 ∞
v Overshoot
m
Specified tolerance limit
2 ∆v
s
T Step response time
sr
T Settling time
s
T Dead time
t
Figure 1404 – Typical step responses of a system
Note 2 to entry: The dead time includes the delay time.
[SOURCE: IEC 60050-311:2001, 311-06-04 and IEC 60050-351:2013, 351-45-27 modified –
Note 1 to entry has been added; the notes of the sources have been deleted.]

IEC 61869-14:2018 © IEC 2018 – 15 –
3.5.1402
step response time
T
sr
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the output variable reaches for the first time a specified
percentage of the difference between the final and the initial steady-state values
Note 1 to entry: The step response time includes the delay time of the current transformer.
[SOURCE: IEC 60050-351:2013, 351-45-36, modified – Note 1 to entry has been modified
and the figure has been deleted.]
3.5.1403
settling time
T
s
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the difference between the step response and their
steady-state value remains smaller than the transient value tolerance
Note 1 to entry: The settling time includes the delay time of the current transformer.
[SOURCE: IEC 60050-351:2013, 351-45-37, modified – Note 1 to entry has been modified
and the figure has been deleted.]
3.5.1404
overshoot
v
m
for a step response of a transfer element, the maximum transient deviation from the final
steady-state value of the output variable, usually expressed in percent of the difference
between the final and the initial steady-state values and for reference-variable step response
or disturbance-variable step response of a control system the maximum transient deviation
from the desired value
[SOURCE: IEC 60050-351:2013, 351-45-38, modified – Note 1 to entry and the figure have
been deleted.]
– 16 – IEC 61869-14:2018 © IEC 2018
3.7 Index of abbreviations and symbols
The table in 3.7 of IEC 61869-6:2016 is replaced by the following one:
DCCT current transformer for DC application
F mechanical load
I maximum supply current
amax
I rated supply current
ar
I rated continuous thermal current
cth
I rated primary current
pr
I long-time overload current
lov
I short-time overload current
sov
I maximum peak fault current
sc
IT instrument transformer
K accuracy limit factor
ALF
K extended primary current factor
pcr
K rated transformation ratio
r
R rated burden
br
t delay time
d
t rated delay time
dr
T settling time
s
T step response time
sr
T dead time
t
U auxiliary power supply voltage
ar
U highest voltage for equipment
m
U rated secondary voltage
sr
v overshoot
m
ε ratio error
absolute error
ε
A
5 Ratings
5.1 General
Subclause 5.1 of IEC 61869-1:2007 is replaced by the following one:
If applicable, the ratings of DC current transformers, including their auxiliary equipment, shall
be selected from the following ones:
• highest voltage for equipment (U );
m
• rated primary current (I );
pr
• rated delay time (t );
dr
• rated continuous thermal current (I );
cth
• long-time overload current (I );
lov
• short time overload current (I );
sov
• maximum peak fault current (I );
sc
• rated secondary voltage (U );
sr
IEC 61869-14:2018 © IEC 2018 – 17 –
• insulation level;
• rated burden (R );
br
• rated accuracy class;
• accuracy limit factor (K );
ALF
);
• rated extended primary current factor (K
pcr
• rated step response time (T ).
sr
The rating applies at the standardized reference atmosphere (temperature 20 °C,
pressure 101,3 kPa, and humidity 11 g/m ) as specified in IEC 60071-1.
NOTE The ratings are specified by the purchaser depending on the characteristics of the whole DC system
application.
5.2 Highest voltage for equipment
Subclause 5.2 of IEC 61869-1:2007 is replaced by the following one:
There are no standard values for highest voltage for equipment.
However, a tentative list of standard values is given in Annex 14B.
5.3 Rated insulation levels
5.3.1 General
Subclause 5.3.1 of IEC 61869-1:2007 is replaced by the following one:
The standard values of insulation level of IEC 60071-1 are not applicable to DC systems.
Methods of calculation for applied dielectric test voltages are given in the relevant clauses of
this document.
Additionally, indications for impulse withstand voltage values are given in Annex 14B.
5.3.3 Other requirements for primary terminals insulation
5.3.3.1 Partial discharges
Subclause 5.3.3.1 of IEC 61869-1:2007 is replaced by the following one:
The partial discharge level measured during the power-frequency voltage withstand test, shall
not exceed the limits specified in Table 3.
Table 3 – Partial discharge test voltages and permissible levels
Maximum permissible PD level
PD test voltage
pC
(r.m.s.)
Type of insulation
kV
immersed in liquid or gas solid
1,5 U /√2 10 50
m
1,2 U /√2 5 20
m
– 18 – IEC 61869-14:2018 © IEC 2018
5.4 Rated frequency
Subclause 5.4 of IEC 61869-1:2007 is replaced by the following one:
The rated frequency is equal to 0 (which means DC).
5.5 Rated output
5.5.602 Standard values for the rated delay time (t )
dr
Subclause 5.5.602 of IEC 61869-6:2016 is replaced by the following one:
The standard values for rated delay time are:
5 µs – 25 µs – 100 µs
5.5.1401 Standard values of rated secondary voltage
The standard values of rated secondary DC voltage are:
150 mV – 1,66 V – 3 V – 5 V
NOTE Generally, DC current transformers are multipurpose CTs.
5.6 Rated accuracy class
5.6.1401 Accuracy class designation
The accuracy class is designated by the highest permissible percentage of the ratio error at
rated primary current and with the rated burden.
5.6.1402 Standard accuracy classes
The standard accuracy classes are:
0,1 – 0,2 – 0,5 – 1
5.6.1403 Standard accuracy limit factors (K )
ALF
The standard values for K are:
ALF
3 – 6 – 10 – 20
5.6.1404 Limits of ratio error
5.6.1404.1 Ratio error for DC current measurement
This is applicable for DCCT intended to measure DC current at the DC side of the converter.
NOTE They are referred as CT2 in the introduction.
The ratio error for the DC component, measured at the secondary terminals at rated or higher
burden, shall not exceed the values given in Table 1403, expressed as a percentage of the
measured current. A graphical representation of error limits is shown in Figure 1405.
The accuracy shall be guaranteed for the whole range of temperature, both for the outdoor
and the indoor part of the current transformer and for both polarities.

IEC 61869-14:2018 © IEC 2018 – 19 –
Table 1403 – Limits of ratio error for
DCCT (classes from 0,1 to 1)
Ratio error
± %
Accuracy class
at % of rated current
5 20 100 K K
pcr ALF
0,1 1 0,25 0,1 0,1 1
0,2 2 0,5 0,2 0,2 2
0,5 3,5 1 0,5 0,5 5
1 5 2 1 1 10
For current lower than 5 % of the rated current, the absolute error ε shall not increase above
A
the value at 5 % of the rated current.
NOTE The purpose of this requirement is to consider a minimum value of error due to offset voltage and noise.

Figure 1405 – Accuracy limits of a DCCT
5.6.1404.2 Accuracy requirements for AC current measurement
These CT’s are exposed to DC voltage, but are intended to measure AC current
NOTE They are referred as CT3 in the introduction.
The error shall be specified in accordance with 5.6.201.3 or 5.6.202.2 of IEC 61869-2:2012,
or both. The reference rated frequency shall be defined.
NOTE Typically, the rated frequency refers to the AC network frequency.
5.6.1405 Accuracy requirements for harmonic measurement
This subclause is applicable for the measurement of the ripple of the DC current.

– 20 – IEC 61869-14:2018 © IEC 2018
Subclause 6A.4.3 of IEC 61869-6:2016 is applicable.
5.1401 Rated step response time
This subclause is not applicable to DCCT intended for AC current measurement.
The standard values for the rated step response time are:
25 µs – 250 µs – 500 µs
6 Design and construction
6.6 Requirements for the external insulation
6.6.1 Pollution
Subclause 6.6.1 of IEC 61869-1:2007 is replaced by the following.
This subclause is applicable to current transformers having U equal to or above 20 kV.
m
The purchaser shall specify the minimum creepage distance or the minimum USCD
(see IEC TS 60815-4:2016) or, alternatively, the DC site pollution severity.
The necessary creepage distance may be determined from the USCD by:
USCD × U
m
where USCD is the minimum nominal unified specific creepage distance (mm/kV), see
IEC 60050-471:2007, 471-01-16.
For indoor current transformers, the minimum USCD value shall be 14 mm/kV.
For outdoor current transformers, if artificial pollution tests are required, they shall be
performed in accordance with 7.4.1401.
NOTE Values for USCD for outdoor current transformers are considered in IEC TS 60815-4:2016. These values
are strongly dependent on the insulator material. Additional factors relating to the insulator profile and insulator
material are also specified.
6.7 Mechanical requirements
Subclause 6.7 of IEC 61869-1:2007 is replaced by the following one:
These requirements apply only to free-standing current transformers.
The required static load that current transformers shall be able to withstand is given
in Table 7. The figures include loads due to wind and ice.
The specified test loads are intended to be applied in any direction at the level of the primary
terminals.
IEC 61869-14:2018 © IEC 2018 – 21 –
Table 7 – Static withstand test loads
Static withstand test load, F
Highest voltage for
equipment, U
N
m
kV
Current transformers with terminals
Up to 100 2 500
> 100 up to 300 3 000
> 300 up to 500 4 000
> 500 5 000
NOTE 1 The sum of the loads acting in routine operating conditions should not exceed 50 % of the specified
withstand test load.
NOTE 2 Current transformers should withstand rarely occurring extreme dynamic loads (e.g. short circuits) not
exceeding 1,4 times the static withstand test load.
NOTE 3 For some applications, it may be necessary to establish the resistance to rotation of the primary
terminals. The moment to be applied during test is agreed between the manufacturer and the purchaser.

6.8 Multiple chopped impulse on primary terminals
Subclause 6.8 of IEC 61869-1:2007 is replaced by the following one:
If additionally specified, the primary terminals of oil-immersed current transformers having U
m
equal to or above 100 kV shall withstand multiple chopped impulses in accordance with 7.4.2
of IEC 61869-1:2007.
NOTE Requirements and tests relate to the behaviour of the internal shields and connections carrying high-
frequency transient currents. The test can also be applied to ratings below this level.
6.9 Internal arc fault protection requirements
Subclause 6.9 of IEC 61869-1:2007 is replaced by the following one:
These requirements apply to oil-immersed and gas-insulated free-standing current
transformers having U equal to or above 100 kV, for which an internal arc fault protection
m
class is additionally specified.
If additionally specified, the instrument transformer shall be able to withstand an internal arc
of the specified current and duration.
The applied current is a symmetrical sinusoidal current. The r.m.s. current value is
I /√2
SC
The arc fault duration shall be defined in accordance with Table 8.
It shall be considered that compliance with these requirements is achieved if the instrument
transformer passes the test described in 7.4.6 of IEC 61869-1:2007.

– 22 – IEC 61869-14:2018 © IEC 2018
Table 8 – Arc fault duration and performance criteria
Protection Arc fault Internal arc fault protection Internal arc fault protection
stage duration class I class II
s
1 0,2 Fracture of the housing and fire permitted, No external effect other than the operation
but all projected parts to be confined of suitable pressure relief device
within the containment area
2 0,5 No fragmentation (burn-through or fire
acceptable)
6.11 Electromagnetic compatibility (EMC)
6.11.2 Requirement for radio interference voltage (RIV)
Subclause 6.11.2 of IEC 61869-1:2007 is replaced by the following one:
The RIV requirement applies to current transformers having U equal to or above 100 kV to
m
be installed in air-insulated substations.
During test with power-frequency voltage, the radio interference voltage shall not exceed
2 500 µV at 1,1 × U / √2.
m
NOTE This requirement is included to meet certain electromagnetic compatibility regulations.
6.13 Markings
6.13.1401 Terminal markings
The markings shall identify
a) The primary and the secondary terminals;
b) The relative polarity of terminals.
6.13.1402 Method of marking
The primary terminals shall be marked clearly and indelibly, either on their surface or in their
immediate vicinity. If possible, the secondary terminals shall be identified clearly and
indelibly, either on the surface of the DCCT or in the immediate vicinity of the terminals.
6.13.1403 Terminal markings
The markings of DCCT terminals shall be as indicated in Table 1404:

IEC 61869-14:2018 © IEC 2018 – 23 –
Table 1404 – Markings of terminals

Primary terminals
Secondary terminals
DCCT with one secondary output

Primary terminals
Secondary terminals
DCCT with two secondary outputs

6.13.1404 Rating plate markings
Subclause 6.13 of IEC 61869-1:2007 and IEC 61869-6:2016 is replaced by the following one:
All current transformers shall carry at least the following markings:
a) manufacturer’s name or other mark by which the manufacturer can be readily identified;
b) year of manufacture and a serial number or a type designation, preferably both;
c) highest voltage for equipment (U );
m
d) insulation level;
e) rated primary current (I );
pr
f) rated continuous thermal current (I );
cth
g) long-time overload current (I ) (if specified);
lov
h) short time overload current (I ) (if specified);
sov
i) accuracy limit factor (K ) (if specified);
ALF
j) extended primary current factor (K );
pcr
k) accuracy class.
When the instrument transformer is intended for both DC and AC measurements, the
accuracy for both applications shall be marked separately.
l) temperature category;
m) mass in kg (when ≥ 25 kg);
n) thermal class of insulation if different from Class A;
If several classes of insulating material are used, the one which limits the temperature rise
shall be indicated.
In addition, the following information shall be marked (if applicable):
o) maximum static mechanical load;
p) type of insulating fluid;
q) rated filling pressure;
– 24 – IEC 61869-14:2018 © IEC 2018
r) minimum functional pressure;
s) insulating fluid volume (or mass) contained in the current transformer;
t) on transformers with secondary converters, the use of each one and its corresponding
terminals.
For analogue secondary output, the following information shall be marked:
u) rated secondary output voltage;
v) rated burden (R );
br
);
w) rated delay time (t
dr
x) on current transformers with two or more secondary terminals, the ratings of each one
(e.g. transformation ratio, accuracy class).
...


SLOVENSKI STANDARD
01-oktober-2019
Instrumentni transformatorji - 14. del: Dodatne zahteve za tokovne transformatorje
za enosmerno napajanje (IEC 61869-14:2018)
Instrument transformers - Part 14: Additional requirements for current transformers for
DC applications (IEC 61869-14:2018)
Messwandler - Teil 14: Besondere Anforderungen für Gleichstromwandler (IEC 61869-
14:2018)
Transformateurs de mesure - Partie 14: Exigences supplémentaires concernant les
transformateurs de courant pour application en courant continu (IEC 61869-14:2018)
Ta slovenski standard je istoveten z: EN IEC 61869-14:2019
ICS:
17.220.20 Merjenje električnih in Measurement of electrical
magnetnih veličin and magnetic quantities
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61869-14

NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2019
ICS 17.200.20
English Version
Instrument transformers - Part 14: Additional requirements for
current transformers for DC applications
(IEC 61869-14:2018)
Transformateurs de mesure - Partie 14: Exigences Messwandler - Teil 14: Besondere Anforderungen für
supplémentaires concernant les transformateurs de courant Gleichstromwandler
pour application en courant continu (IEC 61869-14:2018)
(IEC 61869-14:2018)
This European Standard was approved by CENELEC on 2018-08-21. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61869-14:2019 E

European foreword
The text of document 38/560/FDIS, future edition 1 of IEC 61869-14, prepared by IEC/TC 38
"Instrument transformers" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN IEC 61869-14:2019.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2020-01-05
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2022-07-05
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Directive(s).
For the relationship with EU Directive(s) see informative Annex ZZ, which is an integral part of this
document.
Endorsement notice
The text of the International Standard IEC 61869-14:2018 was approved by CENELEC as a European
Standard without any modification.

Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Clause 2 of IEC 61869-6:2016 is applicable, with the following additions and modifications:
Publication Year Title EN/HD Year
IEC/TS 60815-4 2019 Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 4: Insulators for d.c.
systems
IEC/TS 61245:2015 2015 Artificial pollution tests on high-voltage - -
ceramic and glass insulators to be used on
d.c. systems
IEC 61869-6 2016 Instrument transformers - Part 6: Additional EN 61869-6 2016
general requirements for low-power
instrument transformers
IEC 61869-9 2016 Instrument transformers - Part 9: Digital EN IEC 61869-9 2019
interface for instrument transformers

IEC 61869-14 ®
Edition 1.0 2018-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Instrument transformers –
Part 14: Additional requirements for current transformers for DC applications

Transformateurs de mesure –
Partie 14: Exigences supplémentaires concernant les transformateurs de

courant pour application en courant continu

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 17.220.20 ISBN 978-2-8322-5803-3

– 2 – IEC 61869-14:2018 © IEC 2018
CONTENTS
FOREWORD . 4
INTRODUCTION . 7
1 Scope . 11
2 Normative references . 11
3 Terms and definitions . 11
5 Ratings . 16
6 Design and construction . 20
7 Tests . 25
Annex 14A (informative) Equivalent thermal current in CTs for DC application . 37
14A.1 General . 37
14A.2 Current harmonic content . 37
14A.3 Losses in primary conductor due to harmonic content . 38
14A.4 Thermal test with AC current . 40
Annex 14B (informative) Proposed rated insulation level applicable to current
transformers for DC application. 41
Bibliography . 42

Figure 1401 – Example of LCC scheme . 7
Figure 1402 – Typical scheme for VSC – symmetrical monopole . 8
Figure 1403 – Typical scheme for VSC – asymmetrical monopole or bipole . 9
Figure 1404 – Typical step responses of a system . 14
Figure 1405 – Accuracy limits of a DCCT . 19
Figure 1406 – Polarity reversal test profile . 30
Figure 1407 – Measurement of the step response time . 32
Figure 14A.1 – Typical waveform of current flowing in the primary conductor for LCC
applications . 37
Figure 14A.2 – The two terms that make up the total losses in the primary conductor . 39
Figure 14A.3 – Additional losses in conductors due to typical current harmonics . 40
Figure 14A.4 – Power-frequency losses in conductors compared to DC losses . 40

Table 1401 – Current and voltage in current transformers for LCC application . 8
Table 1402 – Current and voltage in current transformers for VSC application . 10
Table 3 – Partial discharge test voltages and permissible levels . 17
Table 1403 – Limits of ratio error for DCCT (classes from 0,1 to 1) . 19
Table 7 – Static withstand test loads . 21
Table 8 – Arc fault duration and performance criteria . 22
Table 1404 – Markings of terminals . 23
Table 1405 – Rating plate marking for common rating plate . 24
Table 1406 – Rating plate marking for each secondary converter . 24
Table 1407 – Rating plate marking for auxiliary power supply . 25

IEC 61869-14:2018 © IEC 2018 – 3 –
Table 10 – List of tests. 26
Table 14A.1 – Typical harmonic current values (800 kV LCC) . 38
Table 14B.1 – Proposed rated primary terminal insulation levels for current
transformers for DC application. 41

– 4 – IEC 61869-14:2018 © IEC 2018
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
INSTRUMENT TRANSFORMERS –
Part 14: Additional requirements for current
transformers for DC applications

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61869-14 has been prepared by IEC technical committee 38:
Instrument transformers.
The text of this standard is based on the following documents:
FDIS Report on voting
38/560/FDIS 38/565/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.

IEC 61869-14:2018 © IEC 2018 – 5 –
A list of all parts in the IEC 61869 series, published under the general title Instrument
transformers, can be found on the IEC website.
This Part 14 is to be used in conjunction with, and is based on, IEC 61869-1:2007, General
requirements, and IEC 61869-6:2016, Additional general requirements for low-power
instrument transformers – however the reader is encouraged to use the most recent editions.
This Part 14 follows the structure of IEC 61869-1:2007 and IEC 61869-6:2016 and
supplements or modifies their corresponding clauses.
When a subclause of Part 1 or Part 6 is not mentioned in this Part 14, that subclause applies.
When this standard states “addition”, “modification” or “replacement”, the relevant text in
Part 1 or Part 6 is to be adapted accordingly.
For additional clauses, subclauses, figures, tables, annexes or notes, the following numbering
system is used:
• clauses, subclauses, tables, figures and notes that are numbered starting from 1401 are
additional to those in Part 1 and Part 6;
• additional annexes are lettered 14A, 14B, etc.
An overview of the planned set of standards at the date of publication of this document is
given below. The updated list of standards issued by IEC TC 38 is available at the website:
www.iec.ch
PRODUCT FAMILY STANDARDS PRODUCT PRODUCTS OLD
STANDARD STANDARD
61869-1 61869-2 ADDITIONAL REQUIREMENTS FOR 60044-1
CURRENT TRANSFORMERS 60044-6
GENERAL
REQUIREMENTS
61869-3 ADDITIONAL REQUIREMENTS FOR 60044-2
INDUCTIVE VOLTAGE TRANSFORMERS
61869-4 ADDITIONAL REQUIREMENTS FOR 60044-3
COMBINED TRANSFORMERS
61869-5 ADDITIONAL REQUIREMENTS FOR 60044-5
CAPACITIVE VOLTAGE TRANSFORMERS
ADDITIONAL REQUIREMENTS FOR
61869-6 61869-7 60044-7
ELECTRONIC VOLTAGE TRANSFORMERS
ADDITIONAL
GENERAL 61869-8 ADDITIONAL REQUIREMENTS FOR 60044-8
REQUIREMENTS
ELECTRONIC CURRENT
FOR LOW-POWER
TRANSFORMERS
INSTRUMENT
DIGITAL INTERFACE FOR INSTRUMENT
61869-9
TRANSFORMERS
TRANSFORMERS
61869-10 ADDITIONAL REQUIREMENTS FOR LOW-
POWER PASSIVE CURRENT
TRANSFORMERS
61869-11 ADDITIONAL REQUIREMENTS FOR LOW- 60044-7
POWER PASSIVE VOLTAGE
TRANSFORMERS
61869-12 ADDITIONAL REQUIREMENTS FOR
COMBINED ELECTRONIC INSTRUMENT
TRANSFORMER OR COMBINED LOW-
POWER PASSIVE TRANSFORMERS
61869-13 STAND ALONE MERGING UNIT
ADDITIONAL REQUIREMENTS FOR
61869-14
CURRENT TRANSFORMERS FOR DC
APPLICATIONS
61869-15 ADDITIONAL REQUIREMENTS FOR
VOLTAGE TRANSFORMERS FOR DC
APPLICATIONS
– 6 – IEC 61869-14:2018 © IEC 2018
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
IEC 61869-14:2018 © IEC 2018 – 7 –
INTRODUCTION
General
This document applies to current transformers intended to be used in DC applications with at
least one of the following functions:
• measure DC current (with significant harmonics);
• withstand DC voltage.
Depending on the position of the current transformer on the DC system, different kinds of
application exist, which are briefly described below, together with the approximate voltage or
current wave shape.
Line-commutated converters (LCC)
Line-commutated converters (LCC) are based on thyristor converters (see Figure 1401). They
are characterized by a single direction of current flow, and a voltage polarity reversal
possibility. Significant voltage and current harmonics exist up to frequencies of about 3 kHz to
4 kHz.
Figure 1401 – Example of LCC scheme
We distinguish three different current-measurement functions:
• CT1: measurement of the current at the AC side of the converter;
• CT2: measurement of the current at the DC side of the converter;
• CT3: measurement of the current in the DC filter.
Table 1401 gives an overview of the current and voltage waveshapes as well as the main
characteristics of the different applications of the CT.

– 8 – IEC 61869-14:2018 © IEC 2018
Table 1401 – Current and voltage in current transformers for LCC application
Current Voltage Characteristics
CT1 AC current
AC + DC voltage
Large amount of current harmonics
Mainly for protection purposes

CT2 Pure DC application
High-accuracy measurement
Harmonics measurement
Metering, control and protection
purposes
CT3 DC voltage stress with harmonics
DC current = 0
Harmonics measurement
Mainly for protection purposes

Voltage-source converters (VSC)
Voltage-source converters (VSC) are based on transistor converters. They are characterized
by a bi-directional current flow and a single voltage polarity. Voltage and current harmonics
exist up to frequencies of about 20 kHz.
Two variants of VSC schemes exist: symmetrical monopoles (using one single converter) and
asymmetrical monopole or bipole (with one converter for each polarity).
Both schemes are shown in Figure 1402 and Figure 1403.

Figure 1402 – Typical scheme for VSC – symmetrical monopole

IEC 61869-14:2018 © IEC 2018 – 9 –

Figure 1403 – Typical scheme for VSC – asymmetrical monopole or bipole
We distinguish three different current-measurement functions:
• CT4: measurement of the current in the transistor branches of the converter.
The CT can be placed before (CT4a) or after the transistor branch (CT4b);
• CT2: measurement of the current at the DC side of the converter;
• CT3: measurement of the current in the DC filter (not always present in this scheme).
Table 1402 gives an overview of the current and voltage waveshapes as well as the main
characteristics of the different applications of the CT.

– 10 – IEC 61869-14:2018 © IEC 2018
Table 1402 – Current and voltage in current transformers for VSC application
Current Voltage Characteristics
CT2 Pure DC application
High accuracy
measurement
Harmonics measurement
Metering, control and
protection purposes
Short step response time
CT3 DC voltage stress
DC current = 0
Harmonics measurement
Mainly for protection
purposes
CT4a Symmetrical monopole: Pure AC voltage or DC +
AC voltage
DC + AC current
High-accuracy
measurement
Short step response time
Asymmetrical monopoles /
bipoles:
CT4b DC voltage stress
DC + AC current
High-accuracy
measurement
Short step response time
IEC 61869-14:2018 © IEC 2018 – 11 –
INSTRUMENT TRANSFORMERS –
Part 14: Additional requirements for current
transformers for DC applications

1 Scope
This part of IEC 61869 provides all requirements specific to current transformers to be used in
DC applications (DCCTs), whatever the technology used. The output signal can be analogue
or digital.
It is applicable to newly manufactured current transformers used for measuring, protection
and/or control applications in DC power systems with a rated voltage above 1,5 kV.
The general configuration of a single-pole low-power instrument transformer is described in
Figure 601 of IEC 61869-6:2016.
The DCCTs intended for current measurement in the transistor branch of the VSC valve
(referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this
document, and will be considered in a future revision.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
Clause 2 of IEC 61869-6:2016 is applicable, with the following additions and modifications:
IEC TS 60815-4:2016, Selection and dimensioning of high-voltage insulators intended for use
in polluted conditions – Part 4: Insulators for DC systems
IEC TS 61245:2015, Artificial pollution tests on high-voltage ceramic and glass insulators to
be used on DC systems
IEC 61869-6:2016, Instrument transformers – Part 6: Additional general requirements for low-
power instrument transformers
IEC 61869-9:2016, Instrument transformers – Part 9: Digital interface for instrument
transformers
3 Terms and definitions
Clause 3 of IEC 61869-1:2007, of IEC 61869-6:2016 and of IEC 61869-9:2016 are applicable
with the following additions and modifications.

– 12 – IEC 61869-14:2018 © IEC 2018
3.1 General definitions
3.1.1401
instrument transformer for DC application
instrument transformer intended to be used in DC applications with at least one of the
following functions:
• measure DC current or DC voltage (with significant harmonics);
• withstand DC voltage.
3.1.1402
current transformer for DC application
DCCT
instrument transformer for DC application in which the secondary signal, under normal
conditions of use, is substantially proportional to the primary current
Note 1 to entry: The different applications are described in the introduction.
3.2 Definitions related to dielectric ratings
3.2.2
highest voltage for equipment
U
m
Definition 3.2.2 of IEC 61869-1:2007 is replaced by the following one:
highest value of DC voltage for which the equipment is designed to operate continuously, in
respect of its insulation as well as other characteristics that relate to this voltage
3.3 Definitions related to current ratings
3.3.1401
DC overload current
overcurrent occurring in an electric circuit, which is not caused by a short-circuit or an earth
fault
Note 1 to entry: The DC overload current is specified by the customer in terms of value and duration.
[SOURCE: IEC 60050-826:2004, 826-11-15, modified – “DC” added in the term and Note 1 to
entry added.]
3.3.1402
short-time overload current
I
sov
DC overload current occurring for a duration shorter than one minute
3.3.1403
long-time overload current
I
lov
DC overload current occurring for a duration of minutes or hours
Note 1 to entry: Different values of long-time overload can be specified for different durations.
3.3.1404
maximum peak fault current
I
sc
maximum peak value of current occurring during a fault condition of the DC power system

IEC 61869-14:2018 © IEC 2018 – 13 –
3.4 Definitions related to accuracy
3.4.1401
Absolute error
ε
A
error (expressed in A) that a current transformer introduces into the measurement and which
arises from the fact that the actual transformation ratio is not equal to the rated transformation
ratio
Note 1 to entry: The absolute error is defined by the following formula:

ε = K ⋅ U – I
A r s p
where
K is the rated transformation ratio;
r
I is the DC value of the actual primary current in steady state;
p
U is the DC value of the output voltage.
s
3.5 Definitions related to other ratings
3.5.1401
step response
duration between the instant when the measurand (or quantity supplied) is subjected to a
specified abrupt change and the instant when the indication (or quantity supplied) reaches,
and remains within specified limits of, its final steady-state value
Note 1 to entry: See graphical explanation in Figure 1404.

– 14 – IEC 61869-14:2018 © IEC 2018

a
For periodic behaviour
b
For aperiodic behaviour
u Input variable
U Initial value of the input variable
U Step height of the input variable
s
v Output variable
V , V Steady-state values before and after application of the step
0 ∞
v Overshoot
m
Specified tolerance limit
2 ∆v
s
T Step response time
sr
T Settling time
s
T Dead time
t
Figure 1404 – Typical step responses of a system
Note 2 to entry: The dead time includes the delay time.
[SOURCE: IEC 60050-311:2001, 311-06-04 and IEC 60050-351:2013, 351-45-27 modified –
Note 1 to entry has been added; the notes of the sources have been deleted.]

IEC 61869-14:2018 © IEC 2018 – 15 –
3.5.1402
step response time
T
sr
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the output variable reaches for the first time a specified
percentage of the difference between the final and the initial steady-state values
Note 1 to entry: The step response time includes the delay time of the current transformer.
[SOURCE: IEC 60050-351:2013, 351-45-36, modified – Note 1 to entry has been modified
and the figure has been deleted.]
3.5.1403
settling time
T
s
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the difference between the step response and their
steady-state value remains smaller than the transient value tolerance
Note 1 to entry: The settling time includes the delay time of the current transformer.
[SOURCE: IEC 60050-351:2013, 351-45-37, modified – Note 1 to entry has been modified
and the figure has been deleted.]
3.5.1404
overshoot
v
m
for a step response of a transfer element, the maximum transient deviation from the final
steady-state value of the output variable, usually expressed in percent of the difference
between the final and the initial steady-state values and for reference-variable step response
or disturbance-variable step response of a control system the maximum transient deviation
from the desired value
[SOURCE: IEC 60050-351:2013, 351-45-38, modified – Note 1 to entry and the figure have
been deleted.]
– 16 – IEC 61869-14:2018 © IEC 2018
3.7 Index of abbreviations and symbols
The table in 3.7 of IEC 61869-6:2016 is replaced by the following one:
DCCT current transformer for DC application
F mechanical load
I maximum supply current
amax
I rated supply current
ar
I rated continuous thermal current
cth
I rated primary current
pr
I long-time overload current
lov
I short-time overload current
sov
I maximum peak fault current
sc
IT instrument transformer
K accuracy limit factor
ALF
K extended primary current factor
pcr
K rated transformation ratio
r
R rated burden
br
t delay time
d
t rated delay time
dr
T settling time
s
T step response time
sr
T dead time
t
U auxiliary power supply voltage
ar
U highest voltage for equipment
m
U rated secondary voltage
sr
v overshoot
m
ε ratio error
absolute error
ε
A
5 Ratings
5.1 General
Subclause 5.1 of IEC 61869-1:2007 is replaced by the following one:
If applicable, the ratings of DC current transformers, including their auxiliary equipment, shall
be selected from the following ones:
• highest voltage for equipment (U );
m
• rated primary current (I );
pr
• rated delay time (t );
dr
• rated continuous thermal current (I );
cth
• long-time overload current (I );
lov
• short time overload current (I );
sov
• maximum peak fault current (I );
sc
• rated secondary voltage (U );
sr
IEC 61869-14:2018 © IEC 2018 – 17 –
• insulation level;
• rated burden (R );
br
• rated accuracy class;
• accuracy limit factor (K );
ALF
);
• rated extended primary current factor (K
pcr
• rated step response time (T ).
sr
The rating applies at the standardized reference atmosphere (temperature 20 °C,
pressure 101,3 kPa, and humidity 11 g/m ) as specified in IEC 60071-1.
NOTE The ratings are specified by the purchaser depending on the characteristics of the whole DC system
application.
5.2 Highest voltage for equipment
Subclause 5.2 of IEC 61869-1:2007 is replaced by the following one:
There are no standard values for highest voltage for equipment.
However, a tentative list of standard values is given in Annex 14B.
5.3 Rated insulation levels
5.3.1 General
Subclause 5.3.1 of IEC 61869-1:2007 is replaced by the following one:
The standard values of insulation level of IEC 60071-1 are not applicable to DC systems.
Methods of calculation for applied dielectric test voltages are given in the relevant clauses of
this document.
Additionally, indications for impulse withstand voltage values are given in Annex 14B.
5.3.3 Other requirements for primary terminals insulation
5.3.3.1 Partial discharges
Subclause 5.3.3.1 of IEC 61869-1:2007 is replaced by the following one:
The partial discharge level measured during the power-frequency voltage withstand test, shall
not exceed the limits specified in Table 3.
Table 3 – Partial discharge test voltages and permissible levels
Maximum permissible PD level
PD test voltage
pC
(r.m.s.)
Type of insulation
kV
immersed in liquid or gas solid
1,5 U /√2 10 50
m
1,2 U /√2 5 20
m
– 18 – IEC 61869-14:2018 © IEC 2018
5.4 Rated frequency
Subclause 5.4 of IEC 61869-1:2007 is replaced by the following one:
The rated frequency is equal to 0 (which means DC).
5.5 Rated output
5.5.602 Standard values for the rated delay time (t )
dr
Subclause 5.5.602 of IEC 61869-6:2016 is replaced by the following one:
The standard values for rated delay time are:
5 µs – 25 µs – 100 µs
5.5.1401 Standard values of rated secondary voltage
The standard values of rated secondary DC voltage are:
150 mV – 1,66 V – 3 V – 5 V
NOTE Generally, DC current transformers are multipurpose CTs.
5.6 Rated accuracy class
5.6.1401 Accuracy class designation
The accuracy class is designated by the highest permissible percentage of the ratio error at
rated primary current and with the rated burden.
5.6.1402 Standard accuracy classes
The standard accuracy classes are:
0,1 – 0,2 – 0,5 – 1
5.6.1403 Standard accuracy limit factors (K )
ALF
The standard values for K are:
ALF
3 – 6 – 10 – 20
5.6.1404 Limits of ratio error
5.6.1404.1 Ratio error for DC current measurement
This is applicable for DCCT intended to measure DC current at the DC side of the converter.
NOTE They are referred as CT2 in the introduction.
The ratio error for the DC component, measured at the secondary terminals at rated or higher
burden, shall not exceed the values given in Table 1403, expressed as a percentage of the
measured current. A graphical representation of error limits is shown in Figure 1405.
The accuracy shall be guaranteed for the whole range of temperature, both for the outdoor
and the indoor part of the current transformer and for both polarities.

IEC 61869-14:2018 © IEC 2018 – 19 –
Table 1403 – Limits of ratio error for
DCCT (classes from 0,1 to 1)
Ratio error
± %
Accuracy class
at % of rated current
5 20 100 K K
pcr ALF
0,1 1 0,25 0,1 0,1 1
0,2 2 0,5 0,2 0,2 2
0,5 3,5 1 0,5 0,5 5
1 5 2 1 1 10
For current lower than 5 % of the rated current, the absolute error ε shall not increase above
A
the value at 5 % of the rated current.
NOTE The purpose of this requirement is to consider a minimum value of error due to offset voltage and noise.

Figure 1405 – Accuracy limits of a DCCT
5.6.1404.2 Accuracy requirements for AC current measurement
These CT’s are exposed to DC voltage, but are intended to measure AC current
NOTE They are referred as CT3 in the introduction.
The error shall be specified in accordance with 5.6.201.3 or 5.6.202.2 of IEC 61869-2:2012,
or both. The reference rated frequency shall be defined.
NOTE Typically, the rated frequency refers to the AC network frequency.
5.6.1405 Accuracy requirements for harmonic measurement
This subclause is applicable for the measurement of the ripple of the DC current.

– 20 – IEC 61869-14:2018 © IEC 2018
Subclause 6A.4.3 of IEC 61869-6:2016 is applicable.
5.1401 Rated step response time
This subclause is not applicable to DCCT intended for AC current measurement.
The standard values for the rated step response time are:
25 µs – 250 µs – 500 µs
6 Design and construction
6.6 Requirements for the external insulation
6.6.1 Pollution
Subclause 6.6.1 of IEC 61869-1:2007 is replaced by the following.
This subclause is applicable to current transformers having U equal to or above 20 kV.
m
The purchaser shall specify the minimum creepage distance or the minimum USCD
(see IEC TS 60815-4:2016) or, alternatively, the DC site pollution severity.
The necessary creepage distance may be determined from the USCD by:
USCD × U
m
where USCD is the minimum nominal unified specific creepage distance (mm/kV), see
IEC 60050-471:2007, 471-01-16.
For indoor current transformers, the minimum USCD value shall be 14 mm/kV.
For outdoor current transformers, if artificial pollution tests are required, they shall be
performed in accordance with 7.4.1401.
NOTE Values for USCD for outdoor current transformers are considered in IEC TS 60815-4:2016. These values
are strongly dependent on the insulator material. Additional factors relating to the insulator profile and insulator
material are also specified.
6.7 Mechanical requirements
Subclause 6.7 of IEC 61869-1:2007 is replaced by the following one:
These requirements apply only to free-standing current transformers.
The required static load that current transformers shall be able to withstand is given
in Table 7. The figures include loads due to wind and ice.
The specified test loads are intended to be applied in any direction at the level of the primary
terminals.
IEC 61869-14:2018 © IEC 2018 – 21 –
Table 7 – Static withstand test loads
Static withstand test load, F
Highest voltage for
equipment, U
N
m
kV
Current transformers with terminals
Up to 100 2 500
> 100 up to 300 3 000
> 300 up to 500 4 000
> 500 5 000
NOTE 1 The sum of the loads acting in routine operating conditions should not exceed 50 % of the specified
withstand test load.
NOTE 2 Current transformers should withstand rarely occurring extreme dynamic loads (e.g. short circuits) not
exceeding 1,4 times the static withstand test load.
NOTE 3 For some applications, it may be necessary to establish the resistance to rotation of the primary
terminals. The moment to be applied during test is agreed between the manufacturer and the purchaser.

6.8 Multiple chopped impulse on primary terminals
Subclause 6.8 of IEC 61869-1:2007 is replaced by the following one:
If additionally specified, the primary terminals of oil-immersed current transformers having U
m
equal to or above 100 kV shall withstand multiple chopped impulses in accordance with 7.4.2
of IEC 61869-1:2007.
NOTE Requirements and tests relate to the behaviour of the internal shields and connections carrying high-
frequency transient currents. The test can also be applied to ratings below this level.
6.9 Internal arc fault protection requirements
Subclause 6.9 of IEC 61869-1:2007 is replaced by the following one:
These requirements apply to oil-immersed and gas-insulated free-standing current
transformers having U equal to or above 100 kV, for which an internal arc fault protection
m
class is additionally specified.
If additionally specified, the instrument transformer shall be able to withstand an internal arc
of the specified current and duration.
The applied current is a symmetrical sinusoidal current. The r.m.s. current value is
I /√2
SC
The arc fault duration shall be defined in accordance with Table 8.
It shall be considered that compliance with these requirements is achieved if the instrument
transformer passes the test described in 7.4.6 of IEC 61869-1:2007.

– 22 – IEC 61869-14:2018 © IEC 2018
Table 8 – Arc fault duration and performance criteria
Protection Arc fault Internal arc fault protection Internal arc fault protection
stage duration class I class II
s
1 0,2 Fracture of the housing and fire permitted, No external effect other than the operation
but all projected parts to be confined of suitable pressure relief device
within the containment area
2 0,5 No fragmentation (burn-through or fire
acceptable)
6.11 Electromagnetic compatibility (EMC)
6.11.2 Requirement for radio interference voltage (RIV)
Subclause 6.11.2 of IEC 61869-1:2007 is replaced by the following one:
The RIV requirement applies to current transformers having U equal to or above 100 kV to
m
be installed in air-insulated substations.
During test with power-frequency voltage, the radio interference voltage shall not exceed
2 500 µV at 1,1 × U / √2.
m
NOTE This requirement is included to meet certain electromagnetic compatibility regulations.
6.13 Markings
6.13.1401 Terminal markings
The markings shall identify
a) The primary and the secondary terminals;
b) The relative polarity of terminals.
6.13.1402 Method of marking
The primary terminals shall be marked clearly and indelibly, either on their surface or in their
immediate vicinity. If possible, the secondary terminals shall be identified clearly and
indelibly, either on the surface of the DCCT or in the immediate vicinity of the terminals.
6.13.1403 Terminal markings
The markings of DCCT terminals shall be as indicated in Table 1404:

IEC 61869-14:2018 © IEC 2018 – 23 –
Table 1404 – Markings of terminals

Primary terminals
Secondary terminals
DCCT with one secondary output

Primary terminals
Secondary terminals
DCCT with two secondary outputs

6.13.1404 Rating plate markings
Subclause 6.13 of IEC 61869-1:2007 and IEC 61869-6:2016 is replaced by the following one:
All current transformers shall carry at least the following markings:
a) manufacturer’s name or other mark by which the manufacturer can be readily identified;
b) year of manufacture and a serial number or a type designation, preferably both;
c) highest voltage for equipment (U );
m
d) insulation level;
e) rated primary current (I );
pr
f) rated continuous thermal current (I );
cth
g) long-time overload current (I ) (if specified);
lov
h) short time overload current (I ) (if specified);
sov
i) accuracy limit factor (K ) (if specified);
ALF
j) extended primary current factor (K );
pcr
k) accuracy class.
When the instrument transformer is intended for both DC and AC measurements, the
accuracy for both applications shall be marked separately.
l) temperature category;
m) mass in kg (when ≥ 25 kg);
n) thermal class of insulation if different from Class A;
If several classes of insulating material are used, the one which limits the temperature rise
shall be indicated.
In addition, the following information shall be marked (if applicable):
o) maximum static mechanical load;
p) type of insulating fluid;
q) rated filling pressure;
– 24 – IEC 61869-14:2018 © IEC 2018
r) minimum functional pressure;
s) insulating fluid volume (or mass) contained in the current transformer;
t) on transformers with secondary converters, the use of each one and its corresponding
terminals.
For analogue secondary output, the following information shall be marked:
u) rated secondary output voltage;
v) rated burden (R );
br
);
w) rated delay time (t
dr
x) on current transformers with two or more secondary terminals, the ratings of each one
(e.g. transformation ratio, accuracy class).
The rating plate of all DCCTs, where practicable, s
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

EN IEC 61869-14:2019 is a standard published by CLC. Its full title is "Instrument transformers - Part 14: Additional requirements for current transformers for DC applications". This standard covers: IEC 61869-14:2018 provides all requirements specific to current transformers to be used in DC applications (DCCTs), whatever the technology used. The output signal can be analogue or digital. It is applicable to newly manufactured current transformers used for measuring, protection and/or control applications in DC power systems with a rated voltage above 1,5 kV. The general configuration of a single-pole low-power instrument transformer is described in Figure 601 of IEC 61869-6:2016. The DCCTs intended for current measurement in the transistor branch of the VSC valve (referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this document, and will be considered in a future revision. IEC 61869-14:2018 applies to current transformers intended to be used in DC applications with at least one of the following functions: • measure DC current (with significant harmonics); • withstand DC voltage. Depending on the position on the DC system, different kinds of application exist, which are briefly described below, together with the approximate voltage or current wave shape.

IEC 61869-14:2018 provides all requirements specific to current transformers to be used in DC applications (DCCTs), whatever the technology used. The output signal can be analogue or digital. It is applicable to newly manufactured current transformers used for measuring, protection and/or control applications in DC power systems with a rated voltage above 1,5 kV. The general configuration of a single-pole low-power instrument transformer is described in Figure 601 of IEC 61869-6:2016. The DCCTs intended for current measurement in the transistor branch of the VSC valve (referred to as CT4a and CT4b in Figure 1403 and Table 1402) are not covered by this document, and will be considered in a future revision. IEC 61869-14:2018 applies to current transformers intended to be used in DC applications with at least one of the following functions: • measure DC current (with significant harmonics); • withstand DC voltage. Depending on the position on the DC system, different kinds of application exist, which are briefly described below, together with the approximate voltage or current wave shape.

EN IEC 61869-14:2019 is classified under the following ICS (International Classification for Standards) categories: 17.200.20 - Temperature-measuring instruments. The ICS classification helps identify the subject area and facilitates finding related standards.

EN IEC 61869-14:2019 is associated with the following European legislation: EU Directives/Regulations: 2004/108/EC, 2004/108/EU. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase EN IEC 61869-14:2019 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.