Shell Boilers - Part 6: Requirements for equipment for the boiler

This document specifies the minimum requirements for safety related equipment for shell boilers (generator and/or assemblies) as specified in EN 12953-1:2012, to ensure the boiler operates within the allowable limits (pressure, temperature, etc.) and if the limits are exceeded the energy supply is automatically interrupted and locked out, irrespective of the degree of intervention.
NOTE 1    For this document, the term “boiler” is applicable for generator and/or assemblies.
NOTE 2   The maximum time of operation without manual (human) intervention can be specified for each boiler system.
NOTE 3   Annex C gives recommendations of operation and testing of the boiler system with a maximum time of operation without manual (human) intervention of 24 h and 72 h.

Großwasserraumkessel - Teil 6: Anforderungen an die Ausrüstung für den Kessel

Dieses Dokument legt die Mindestanforderungen an die sicherheitstechnische Ausrüstung (Dampf-/Heißwassererzeuger und/oder Baugruppen) der in EN 12953 1:2012 definierten Großwasserraumkessel fest, um sicherzustellen, dass der Kessel innerhalb der zulässigen Grenzen (Druck, Temperatur usw.) arbeitet und, sofern die Grenzen überschritten werden, die Energiezufuhr automatisch am Kessel unterbrochen und verriegelt wird, unabhängig vom Grad des Eingriffs.
ANMERKUNG 1   In diesem Dokument ist der Begriff „Kessel“ für Dampf-/Heißwassererzeuger und/oder Baugruppen anwendbar.
ANMERKUNG 2   Die maximale Betriebsdauer ohne manuelles (menschliches) Eingreifen kann für jedes Kesselsystem festgelegt werden.
ANMERKUNG 3   Anhang C enthält Empfehlungen zum Betrieb und zur Prüfung des Kesselsystems mit einer maximalen Betriebsdauer ohne manuelles (menschliches) Eingreifen von 24 h und 72 h.

Chaudières à tubes de fumée - Partie 6: Exigences pour l'équipement de la chaudière

Le présent document spécifie les exigences minimales pour l'équipement relatif à la sécurité des chaudières à tubes de fumée (générateurs et/ou ensembles) spécifiées dans l'EN 12953 1:2012, afin de garantir que la chaudière fonctionne dans les limites admissibles (pression, température, etc.) et, dans le cas où les limites seraient dépassées, que l'alimentation en énergie est interrompue et verrouillée automatiquement, indépendamment du degré d'intervention.
NOTE 1   Dans le cadre du présent document, le terme « chaudière » s'applique aux générateurs et/ou ensembles.
NOTE 2   La durée maximale de fonctionnement sans intervention manuelle (humaine) peut être spécifiée pour chaque système de chaudière.
NOTE 3   L'Annexe C donne des recommandations de fonctionnement et d'essai du système de chaudière avec une durée maximale de fonctionnement sans intervention manuelle (humaine) de 24 h et 72 h.

Mnogovodni kotli - 6. del: Zahteve za opremo kotla

Ta dokument določa minimalne zahteve za varnostno opremo mnogovodnih kotlov (generator in/ali sklope), kot je določeno v standardu EN 12953-1:2012, da se zagotovi obratovanje kotla v dovoljenih mejah (tlak, temperatura itd.); če so te meje presežene, mora ta oprema prekiniti in varnostno zaustaviti oskrbo z energijo, ne glede na stopnjo človeške intervencije.
OPOMBA 1: V tem dokumentu se izraz »kotel« uporablja za generator in/ali sklope.
OPOMBA 2: Za vsak kotlovski sistem je mogoče določiti najdaljši čas obratovanja brez ročne (človekove) intervencije.
OPOMBA 3: V dodatku C so podana priporočila glede obratovanja in preskušanja kotlovskega sistema z najdaljšim časom obratovanja brez ročne (človekove) intervencije 24 in 72 ur.

General Information

Status
Published
Publication Date
17-Dec-2024
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
18-Dec-2024
Due Date
26-Feb-2024
Completion Date
18-Dec-2024

Relations

Standard
EN 12953-6:2025
English language
72 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2025
Nadomešča:
SIST EN 12953-6:2011
Mnogovodni kotli - 6. del: Zahteve za opremo kotla
Shell Boilers - Part 6: Requirements for equipment for the boiler
Großwasserraumkessel - Teil 6: Anforderungen an die Ausrüstung für den Kessel
Chaudières à tube de fumée - Partie 6: Exigences pour l'équipement de la chaudière
Ta slovenski standard je istoveten z: EN 12953-6:2024
ICS:
27.060.30 Grelniki vode in prenosniki Boilers and heat exchangers
toplote
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 12953-6
EUROPEAN STANDARD
NORME EUROPÉENNE
December 2024
EUROPÄISCHE NORM
ICS 27.060.30 Supersedes EN 12953-6:2011
English Version
Shell Boilers - Part 6: Requirements for equipment for the
boiler
Chaudières à tubes de fumée - Partie 6: Exigences pour Großwasserraumkessel - Teil 6: Anforderungen an die
l'équipement de la chaudière Ausrüstung für den Kessel
This European Standard was approved by CEN on 20 October 2024.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12953-6:2024 E
worldwide for CEN national Members.

Contents
European foreword . 5
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
4 General requirements for steam boilers and hot water boilers . 12
4.1 Safeguards (safety valves) against excessive pressure . 12
4.2 Materials for valves, fittings, flanges and bolting . 12
4.3 Protective systems . 12
4.4 Energy supply . 13
4.4.1 General . 13
4.4.2 Start up . 13
4.4.3 Normal shutdown . 14
4.5 Flue-gas heated economizers. 14
4.6 Drain and blowdown devices . 14
4.7 Water quality . 15
4.8 Water quality protection . 15
4.8.1 Conductivity in steam boiler water . 15
4.8.2 Condensate in steam boiler plants . 15
4.8.3 Water circulating system in hot water boiler plants . 16
4.8.4 Make-up water or feed water . 16
4.9 Furnace temperature monitoring system . 16
5 Special requirements for steam boilers . 18
5.1 Water level indication . 18
5.2 Steam pressure and temperature indication . 21
5.3 Valves for connections . 21
5.3.1 Steam outlets . 21
5.3.2 Feed pipe connections . 21
5.4 Feed water supply . 22
5.5 Feed water control . 22
5.6 Limiting and monitoring devices. 22
5.6.1 Low and high water level protection . 22
5.6.2 Pressure limitation . 23
5.6.3 Temperature limitation . 23
5.6.4 Flow monitoring device . 23
5.7 Electrically heated steam boilers . 23
6 Special requirements for hot water boilers . 24
6.1 Hot water generating systems . 24
6.2 Expansion and feed lines for open vented systems . 25
6.3 Water supply . 27
6.4 Water level indication . 27
6.5 Limiting and monitoring devices. 27
6.5.1 Low water protection . 27
6.5.2 Pressure and temperature limitation . 27
6.5.3 Flow monitoring device . 28
6.5.4 High water level protection . 28
6.6 Vent valves . 28
6.7 Pressure and temperature indication . 28
6.8 Electrically heated hot water boilers . 29
6.9 Parallel mode of operation of hot water boilers . 29
7 Operating instructions and operational aspects including maintenance and testing . 29
8 Alarms and monitoring from the boiler plant . 30
Annex A (informative) Typical examples of steam and hot water boiler systems . 31
A.1 General . 31
A.2 Key to figures. 31
A.3 Plant with open vented system . 33
A.4 Plant with closed system . 34
A.4.1 Hot water system with external pressure generating and expansion system . 34
A.4.2 Hot water system with internal pressure generating and expansion system - Steam
cushion in the boiler . 35
A.4.3 Steam boiler . 36
A.5 Superheater and economizer . 37
A.5.1 Superheater . 37
A.5.2 Economizer . 38
Annex B (informative) Dimensioning of expansion space . 39
B.1 General . 39
B.2 Required data . 39
B.3 Formulas for dimensioning . 40
Annex C (informative) Aspects of boiler operation . 42
C.1 General . 42
C.2 Maintenance . 42
C.3 Boiler operation and testing . 42
Annex D (informative) Drain and blowdown devices. 47
D.1 General . 47
D.2 Design of the drain and blowdown devices . 47
Annex E (informative) Alarms and monitoring from the boiler plant. 49
E.1 General . 49
E.2 Conditions for alarms and monitoring . 49
Annex F (normative) Requirements for monitoring devices . 52
F.1 General requirements for monitoring devices . 52
F.1.1 General . 52
F.1.2 Components . 52
F.1.3 Materials and design . 52
F.1.4 Electrical equipment . 53
F.1.5 Test procedure . 54
F.1.6 Marking . 55
F.1.7 Operating instructions . 55
F.2 Additional requirements for water monitoring devices. 55
F.2.1 Functional requirements. 55
F.2.2 Special requirements for water hardness monitoring devices . 55
F.2.3 Special requirements for devices for detecting and monitoring water for ingress of
harmful foreign matter . 56
F.2.4 Special requirements for water conductivity monitoring devices. 56
F.3 Additional requirements for flow monitoring devices . 57
F.3.1 Design . 57
F.3.2 Examination of functional capability . 58
G.1 General . 60
G.2 Key to figures . 60
G.3 Recommendations for expansion system. 61
G.4 Expansion and pressure holding for hot water boiler system . 62
G.4.1 Pressure pump-controlled system with pressureless membrane type expansion
vessel . 63
G.4.2 Pressure pump-controlled system with open expansion vessel . 64
G.4.3 Membrane type expansion vessel with pre-pressurized gas cushion. 65
G.4.4 Membrane type expansion vessel with controlled gas cushion . 66
G.4.5 Closed expansion vessel with pre-pressurized gas cushion . 67
G.4.6 Closed expansion vessel with gas or steam cushion. 68
Annex H (informative) Significant technical changes between this document and the
previous edition . 69
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of EU Directive 2014/68/EU aimed to be covered. 70
Bibliography . 72

European foreword
This document (EN 12953-6:2024) has been prepared by Technical Committee CEN/TC 269 “Shell and
water-tube boilers”, the secretariat of which is held by DIN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by June 2025, and conflicting national standards shall be
withdrawn at the latest by June 2025.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 12953-6:2011.
This document has been prepared under a standardization request addressed to CEN by the European
Commission. The Standing Committee of the EFTA States subsequently approves these requests for its
Member States.
For the relationship with EU Legislation, see informative Annex ZA, which is an integral part of this
document.
Annex H provides details of significant technical changes between this document and the previous
edition.
The series concerning shell boilers consists of the following parts:
— Part 1: General
— Part 2: Materials for pressure parts of boilers and accessories
— Part 3: Design and calculation for pressure parts
— Part 4: Workmanship and construction of pressure parts of the boiler
— Part 5: Inspection during construction, documentation and marking of pressure parts of the boiler
— Part 6: Requirements for equipment for the boiler
— Part 7: Requirements for firing systems for liquid and gaseous fuels for the boiler
— Part 8: Requirements for safeguards against excessive pressure
— Part 9: Requirements for limiting devices of the boiler and accessories
— Part 10: Requirements for boiler feed water and boiler water quality
— Part 11: Acceptance tests
— Part 12: Requirements for firing systems for solid fuels for the boiler
— Part 13: Operating instructions
Although these parts can be obtained separately, it should be recognized that the parts are inter-
dependent. As such, the design and manufacture of shell boilers requires the application of more than
one part in order for the requirements of the standard to be satisfactorily fulfilled.
NOTE A “Boiler Helpdesk” has been established in CEN/TC 269 which can be contacted for any questions
regarding the application of the European Standards series EN 12952 and EN 12953 see the following website:
http://www.boiler-helpdesk.din.de.
Any feedback and questions on this document should be directed to the users’national standards body. A
complete listing of these bodies can be found on the CENwebsite.
According to the CEN-CENELEC Internal Regulations, the national standardsorganisations of the
following countries are bound to implement this EuropeanStandard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark,Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia,Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic ofNorth
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,Türkiye and the United
Kingdom.
1 Scope
This document specifies the minimum requirements for safety related equipment for shell boilers
(generator and/or assemblies) as specified in EN 12953-1:2012, to ensure the boiler operates within the
allowable limits (pressure, temperature, etc.) and if the limits are exceeded the energy supply is
automatically interrupted and locked out, irrespective of the degree of intervention.
NOTE 1 For this document, the term “boiler” is applicable for generator and/or assemblies.
NOTE 2 The maximum time of operation without manual (human) intervention can be specified for each boiler
system.
NOTE 3 Annex C gives recommendations of operation and testing of the boiler system with a maximum time of
operation without manual (human) intervention of 24 h and 72 h.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN ISO 5167-1:2022, Measurement of fluid flow by means of pressure differential devices inserted in
circular cross-section conduits running full - Part 1: General principles and requirements (ISO 5167-1:2022)
EN 12953-1:2012, Shell boilers - Part 1: General
EN 12953-2:2012, Shell boilers - Part 2: Materials for pressure parts of boilers and accessories
EN 12953-3:2016, Shell boilers - Part 3: Design and calculation for pressure parts
EN 12953-7:2002, Shell boilers - Part 7 : Requirements for firing systems for liquid and gaseous fuels for the
boilers
EN 12953-8:2001, Shell boilers - Part 8: Requirements for safeguards against excessive pressure
EN 12953-9:2024, Shell boilers - Part 9: Requirements for limiting devices of the boiler and accessories
EN 12953-10:2003, Shell boilers - Part 10 : Requirements for feedwater and boiler water quality
EN 12953-12:2003, Shell boilers - Part 12: Requirements for grate firing systems for solid fuels for the boiler
EN 12953-13:2012, Shell boilers - Part 13: Operating instructions
EN 14597:2012, Temperature control devices and temperature limiters for heat generating systems
EN 50156-1:2015, Electrical equipment for furnaces and ancillary equipment - Part 1: Requirements for
application design and installation
EN 60529:1991, Degrees of protection provided by enclosures (IP Code) (IEC 60529:1989)
EN 60730-1:2016, Automatic electrical controls - Part 1: General requirements (IEC 60730-1:2013)

Document impacted by A1:2000, A2:2013 and AC:2016.
EN 61140:2016, Protection against electric shock - Common aspects for installation and equipment
(IEC 61140:2016)
EN 61558-2-6:2009, Safety of transformers, reactors, power supply units and similar products for supply
voltages up to 1 100 V - Part 2-6: Particular requirements and tests for safety isolating transformers and
power supply units incorporating safety isolating transformers (IEC 61558-2-6:2009)
EN 61558-2-16:2009, Safety of transformers, reactors, power supply units and similar products for supply
voltages up to 1 100 V - Part 2-16: Particular requirements and tests for switch mode power supply units
and transformers for switch mode power supply units (IEC 61558-2-16:2009)
ISO 2186:2007, Fluid flow in closed conduits — Connections for pressure signal transmissions between
primary and secondary elements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12953-1:2012 and the following
apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at http://www.electropedia.org/
3.1
control
device used for maintaining the variable to be controlled (pressure, temperature, etc.) at a specific value
(set point)
3.2
monitoring system
monitoring device
system which checks given parameters and draws attention to those which are outside normal operating
limits but which are below the limiting values determined by the hazard and risk analysis and specified
e.g. in the operation manual
Note 1 to entry: Normal operating conditions of the process can be restored either directly by the system or by a
boiler attendant depending on the individual requirements.
3.3
safety accessory
device designed to protect pressure equipment against the allowable limits being exceeded, including
devices for direct pressure limitation, such as safety valves, bursting disc safety devices, buckling rods,
controlled safety pressure relief systems (CSPRS), and limiting devices, which either activate the means
for correction or provide for shutdown or shutdown and lockout, such as pressure switches or
temperature switches or fluid level switches and safety related measurement control and regulation
(SRMCR) devices
[SOURCE: PED 2014/68/EU]
3.4
pressure accessory
device with an operational function and having pressure-bearing housings
[SOURCE: PED 2014/68/EU]
3.5
limiter
limiting device
safety accessory which, on reaching a limiting value (water level, pressure, temperature, flow, water
quality), is used to interrupt and lock out the energy supply
Note 1 to entry: A limiter is an element of a safety device and a safety accessory for shell boilers as specified in
the Pressure Equipment Directive 2014/68/EU, Article 2, Clause 4. A limiter contains a sensor, possibly a sensor
control unit and ends at the output contact. The following safety logic and actuating element are not components of
this part of the standard, see EN 12953-9:2024, Figure A.1.
Note 2 to entry: A limiting device comprises
— a measuring function and
— optional with a display and
— an activation function for correction, or shut-down, or safety shut-down and fault shut-down, and which
is used to carry out safety related functions as specified in the PED 2014/68/EU. These functions may be on their
own or as part of a safety (protective) system (e.g. sensors, limiters). If this is achieved by multichannel systems,
then all items or limiters for safety purposes are included within the safety (protective) system.
3.6
lock-out
safety shut-down condition of the protective device, such that a restart can only be accomplished by a
manual reset of the limiter or by a manual reset of the safety logic on site and by no other means
3.7
functional check
testing of the safety device to ensure it performs its intended function
3.8
electrically heated boiler
boiler in which water is heated by an electric current flowing between electrodes or by immersion
heaters
3.9
expansion vessel
vessel to compensate for temperature dependent changes in water volume of a hot water boiler, where
— a closed expansion vessel is pressurised and
— an open expansion vessel is vented to atmospheric pressure and is not pressurised
3.10
allowable heat output
maximum heat output (water mass flow times the difference between outlet and inlet enthalpy) that can
be generated during continuous operation and at which hot water boilers can be operated
3.11
maximum allowable temperature
TS
maximum temperature for which the pressure equipment is designed, as specified by the manufacturer
Note 1 to entry For hot water boiler, TS means the maximum allowable flow temperature measured at the outlet
branch.
Note 2 to entry For steam generator, TS means the maximum allowable saturated steam temperature at PS.
Note 3 to entry For superheater, TS means the maximum allowable temperature of the hot steam measured at
the outlet branch.
Note 4 to entry For economizer, TS means the maximum allowable flow temperature measured at the outlet
branch.
Note 5 to entry TS corresponds to Pressure Equipment Directive 2014/68/EU, Article 2, indent (9).
3.12
maximum allowable pressure
PS
maximum pressure for which the pressure equipment is designed, as specified by the manufacturer, and
defined at a location specified by him, being either the connection of protective and/or limiting devices,
or the top of equipment or, if not appropriate, any point specified
Note 1 to entry PS corresponds to Pressure Equipment Directive 2014/68/EU, Article 2, indent (8).
3.13
maximum continuous rating
maximum continuous steam output that can be generated during continuous operation taking the
specified steam condition into consideration
3.14
internal steam cushion
steam filled space located within the steam boiler to accommodate changes in volume
3.15
external steam cushion
steam filled space located outside the steam boiler to accommodate changes in volume
3.16
gas cushion
gas-filled space to accommodate changes in volume
3.17
effective heat transfer
energy supply is on and
— for a hot water boiler, flow of water is greater than or equal to a specified minimum value or
— for a steam boiler, the start-up or steam valve is open and the temperature is greater than the
saturation temperature at ambient pressure
3.18
normal operation
automatic operation, with all regulating circuits and controls (open loops/closed loops) in automatic
mode and with the set points and parameters valid for normal operation
Note 1 to entry: Normal operation also includes the automatic switching on and off of the assigned actuators (e.g.
burner).
3.19
normal shut down
controlled switch off of the boiler either operated manually or automatically
3.20
make-up water
water which compensates for losses of water and steam from the system
Note 1 to entry: Definition from EN 12953-10:2003.
3.21
feed water
mixture of returned condensate and/or make up water supplied to the boiler inlet
Note 1 to entry: Definition from EN 12953-10:2003.
3.22
pressurization equipment
external system for keeping the hot water system pressure within the required pressure limits
Note 1 to entry: In order to prevent corrosion caused by oxygen infiltration, systems that prevent the system
water being in direct contact with air should be preferred.
3.23
boiler attendant
boiler operator skilled person appointed for operating the boiler plant
3.24
temperature monitoring of the furnace shell
measurement system for monitoring the temperature of the furnace shell in the area of the highest heat
flux
3.25
minimum flow rate
minimum flow of water in the piping required for hot water boilers and economisers to avoid overheating
of the boiler or economiser
3.26
cold start
starting the boiler from ambient pressure at room temperature to normal operating condition
4 General requirements for steam boilers and hot water boilers
4.1 Safeguards (safety valves) against excessive pressure
Each steam boiler and hot water boiler, except open vented hot water boiler, shall be equipped with
safeguards (safety valves) against excessive pressure in accordance with EN 12953-8:2001.
Superheaters and economizers shall be protected in accordance with EN 12953-8:2001. Where a
superheater or an economizer can be isolated a pressure gauge connection shall be provided.
NOTE For example, see Annex A (Figures A.5 and A.6).
4.2 Materials for valves, fittings, flanges and bolting
The conditions and requirements to select the material shall be in accordance with EN 12953-2:2012.
4.3 Protective systems
4.3.1 All limiters and their installation shall be designed in accordance with EN 12953-9:2024. Limiters
shall function independently of each other and of controls unless their safety function cannot be affected
by other such functions.
The protective systems shall be in accordance with EN 50156-1:2015.
4.3.2 The application design and installation of the electrical safety circuit as well as the electrical and
control equipment for the energy supply and its auxiliary equipment shall be in accordance with
EN 50156-1:2015.
A hazard analysis SIL classification shall be carried out for each limiting device function and appropriate
levels of functional safety implemented.
Typical Safety Integrity Level (SIL) requirements cannot be less than 2.
It shall be possible to stop the boiler by additional devices outside the boiler such as shut-off valve,
emergency stop device, fire detectors, etc.
4.3.3 Functional check of all limiters shall be possible at any time during operation e.g. by simulation
in accordance with operating instructions as specified in Clause 7.
4.3.4 When a limiter mentioned in this document activates, information shall be given to indicate which
limiter has activated.
4.3.5 After lock out, the steam boiler/hot water boiler shall be physically checked by the boiler
attendant (operator), before start-up (see 4.4.2).
4.3.6 Any valves that may isolate a limiter or monitoring device from the boiler system during normal
operation shall be prevented from unintended closure (e.g. by wire and seal, locked in open position or
position switches integrated in a safety circuit, etc.).
4.3.7 For purpose of function testing a bypassing of limiters at the boiler shall be allowed for a time not
exceeding:
— for both channels of a two channels water level limiter, 30 s;
— for one channel of a two channels water level limiter, 5 min;
— for a maximum pressure limiter if there is a second channel in operation (e.g. safety valve or second
pressure limiter), 5 min;
— for all other limiters, 5 min.
In all cases above:
— if the above times are exceeded, the energy supply shall be shut down and locked-out.
— the bypassing system which is implemented shall not alter the safety integrity level SIL of the safety
functions concerned.
4.4 Energy supply
4.4.1 General
The requirements for energy supply to steam boilers and hot water boilers shall be in accordance with
either EN 12953-7:2002 or EN 12953-12:2003 depending on fuel type.
The combustion process shall be completed within the furnace.
The energy supply shall be automatically controlled and in all operating stages rapidly adapted to the
variation of the heat demand. Steam pressure influences heat demand of steam boilers and hot water
boilers with internal steam cushion. For other hot water boilers, heat demand is influenced by flow
temperature.
NOTE For examples of steam and hot water boiler systems, see Annex A (Figures A.1 to A.4).
In the event of normal shutdown or lock out, residual heat accumulated in the furnace and flue-gas passes
shall not cause unacceptable metal or fluid temperatures (e.g. by evaporation of the water) in the steam
boiler/hot water generator.
This requirement is fulfilled:
a) if a fast acting combustion system is used e.g. oil, gas or pulverised fuel firing systems (except slag-
tap firing or heavy brickwork in the furnace or flue-gas passes) or electrical heated system; or
b) if it is proved that, after interruption of the energy supply from the full load steady-state condition,
the fluegas temperature at the highest point of the heating surface (HHS) falls to below 400 °C before
the water level has sunk from the lowest permissible water level (LWL) to 50 mm above the highest
point of the heating surface (HHS); or
c) if a reliable feed water supply is installed to ensure adequate cooling of the heating surfaces
in case of a sudden loss of essential operational parameters (see e.g. 5.4.4); or
d) if it is only heated with gases not exceeding a temperature of 400 °C; or
e) if, in case of fully flooded hot water generators, the water temperature does not exceed the maximum
allowable temperature (TS) with or without emergency cooling system and without release of
residual heat via the safety valve. The function of the emergency cooling system shall ensure that no
adverse side effects can occur.
In case of a combination of energy supply, highest requirements of this document shall be applied.
4.4.2 Start up
When a boiler is started-up locally or remotely after lockout or from cold condition (cold start), the boiler
attendant (operator) shall be present and remain with the boiler until it is operating correctly under
normal operation.
When designing the controls for the start-up sequence, it shall be taken into account the effective heat
transfer to avoid unacceptable local over heating or thermal stresses or other stresses of any pressurized
parts of the boiler or parts connected to the boiler, with particular regard to the heating up sequence and
flow rates. These controls shall be in the form of installed control systems and/or software and/or
operating instructions.
The manual or automatic start-up sequence shall consider as a minimum the following points which shall
be specified in the operating instructions:
a) lock out by limiters;
b) minimum flow of water for hot water boilers to avoid overheating and to reach effective heat transfer;
c) minimum temperature of water for hot water boilers to avoid corrosion;
d) minimum temperature of critical parts of boilers to avoid unacceptable thermal stresses;
e) steam output as a function of pressure of steam boilers to improve internal mixing (flow) and to avoid
thermal stresses (effective heat transfer);
f) sequence shall contain times (or pressures) and burner loads for a gentle start-up to avoid thermal
stresses;
g) additional energy supply requirements like e.g. maximum permitted low loads, minimum number of
burner steps for stepped burner or minimum burner adjustment time between low and high load for
infinitely variable burners.
NOTE For remote system, see informative Annex E.
4.4.3 Normal shutdown
The control sequence designed for normal shutdown shall involve the low load position of energy supply
before switching off the boiler.
4.5 Flue-gas heated economizers
Economizers shall be fitted with a temperature indicating device on the water outlet.
4.6 Drain and blowdown devices
4.6.1 Drain and blowdown equipment shall be installed to prevent accidents.
NOTE Drain and blowdown devices, see Annex D.
4.6.2 Each steam boiler shall be fitted with drain lines placed at, or as near as practicable to, the lowest
point of the steam boiler.
NOTE On some steam boilers, drain valves can be used for blowdown purposes.
4.6.3 Where lines from two or more steam boilers are connected to a common discharge, two valves
shall be fitted to each drain line, one being of a non-return type to prevent the contents of one steam
boiler passing to another.
4.6.4 The drain line between the steam boiler and the drain valve shall, if exposed to furnace heat, be
protected by brickwork or other insulating material so arranged that the pipe may be inspected and is
not constrained against expansion.
4.6.5 Taper-plug valves where fitted, shall be of the bolted cover type with separately packed glands
and shall not be used with design pressures over 13 bar.
4.6.6 Where drain or the steam boiler blowdown valves are not self closing or capable of being locked
in the closed position, a further shut-off device shall be installed in the line.
4.7 Water quality
4.7.1 The water quality shall be in accordance with EN 12953-10:2003 and operating instructions.
4.7.2 It shall be possible at any time during operation to safely take reliable samples of the boiler water,
feed-water, make-up water and if relevant the condensate and/or the recirculation water. Depending on
the temperature of the media the samples shall be taken through one or more sample coolers.
4.8 Water quality protection
4.8.1 Conductivity in steam boiler water
The boiler water conductivity shall be monitored to ensure the water quality remains within the
allowable limits prescribed by the operating instructions and EN 12953-10:2003.
If the limit values can be exceeded the following monitoring methods shall be used:
a) without manual (human) intervention ≤ 24 h or permanent supervision, the boiler water shall be
manually daily tested and appropriate actions shall be taken. If additional operation conditions shall
be considered according to EN 12953-3:2016, 5.5.4, at least a monitoring device shall be used as
specified in Annex F, which measures continuously and which shut down and locks out the energy
supply if the limits are exceeded.
b) without manual (human) intervention > 24 h and ≤ 72 h, a continuous monitoring device shall be
used as specified in Annex F. If the limit values are exceeded for more than the time specified in the
operating instructions, the boiler shall be shut down and the energy supply shall be locked out (based
on the result from the risk and hazard analysis the time delay to shut down may be extended).
c) without manual (human) intervention > 72 h, a hazard and risk analysis shall be carried out to
specify if a limiter according to EN 12953-9:2024 or a monitoring device shall be used. If the limit
values are exceeded for more than the time specified in the operating instructions, the boiler shall be
shut down and the energy supply shall be locked out (based on the result from the risk and hazard
analysis the time delay to shut down may be extended).
For operational aspects, it is recommended to
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...