EN ISO 3679:2004
(Main)Determination of flash point - Rapid equilibrium closed cup method (ISO 3679:2004)
Determination of flash point - Rapid equilibrium closed cup method (ISO 3679:2004)
ISO 3679:2004 specifies a method for the determination of the closed cup flash point of paints (including water-borne paints), varnishes, paint binders, adhesives, solvents, petroleum, and related products having closed cup flash points within the range of - 30 degrees Celsius to 300 degrees Celsius. When used in conjunction with the flash detector (A.1.6), ISO 3679:2004 is also suitable for the determination of the flash point of fatty acid methyl esters (FAME).
Bestimmung des Flammpunktes - Schnelles Gleichgewichtsverfahren mit geschlossenem Tiegel (ISO 3679:2004)
Diese Internationale Norm legt ein Verfahren zur Bestimmung des Flammpunktes im geschlossenen Tiegel von Beschichtungsstoffen (einschließlich wasserverdünnbare Beschichtungsstoffe), Bindemitteln für Beschichtungsstoffe, Klebstoffen, Lösemitteln, Mineralölerzeugnissen und verwandten Produkten für den Bereich zwischen -30 °C und 300 °C fest. Wird der Detektor (A.1.6) eingesetzt, so kann diese Internationale Norm auch für die Bestimmung der Flammpunkte von Fettsäuremethylestern (FAME) herangezogen werden.
Détermination du point d'éclair - Méthode rapide à l'équilibre en vase clos (ISO 3679:2004
L'ISO 3679:2004 spécifie une méthode de détermination du point d'éclair en vase clos des peintures (y compris les peintures à support aqueux), des vernis, des liants pour peintures, des adhésifs, des solvants, des produits pétroliers et des produits connexes, dont le point d'éclair est compris entre -30 °C et 300 °C. Lorsqu'elle est utilisée avec le détecteur d'éclair, l'ISO 3679:2004 convient aussi pour la détermination du point d'éclair des esters méthyliques d'acide gras (EMAG).
Določanje plamenišča - Hitra ravnotežna metoda v zaprti posodi (ISO 3679:2004)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2004
'RORþDQMHSODPHQLãþD+LWUDUDYQRWHåQDPHWRGDY]DSUWLSRVRGL,62
Determination of flash point - Rapid equilibrium closed cup method (ISO 3679:2004)
Bestimmung des Flammpunktes - Schnelles Gleichgewichtsverfahren mit
geschlossenem Tiegel (ISO 3679:2004)
Détermination du point d'éclair - Méthode rapide a l'équilibre en vase clos (ISO
3679:2004
Ta slovenski standard je istoveten z: EN ISO 3679:2004
ICS:
75.080 Naftni proizvodi na splošno Petroleum products in
general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
INTERNATIONAL ISO
STANDARD 3679
Third edition
2004-04-01
Determination of flash point — Rapid
equilibrium closed cup method
Détermination du point d'éclair — Méthode rapide à l'équilibre en vase
clos
Reference number
ISO 3679:2004(E)
©
ISO 2004
ISO 3679:2004(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.
© ISO 2004
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2004 – All rights reserved
ISO 3679:2004(E)
Contents Page
Foreword. iv
Introduction . v
1 Scope. 1
2 Normative references . 1
3 Terms and definitions. 1
4 Principle . 2
5 Reagents and materials. 2
6 Apparatus . 2
7 Apparatus preparation. 3
8 Sampling . 4
9 Sample handling . 4
10 Procedure . 4
11 Calculation. 6
12 Expression of results. 6
13 Precision . 6
14 Test report . 7
Annex A (normative) Flash point test apparatus . 8
Annex B (normative) Thermometer specifications . 13
Annex C (informative) Verification of apparatus . 14
Annex D (informative) Use of a cup insert . 17
Bibliography . 18
ISO 3679:2004(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO 3679 was prepared jointly by Technical Committees ISO/TC 28, Petroleum products and lubricants and
ISO/TC 35, Paints and varnishes.
This third edition cancels and replaces the second edition (ISO 3679:1983), which has been technically
revised.
iv © ISO 2004 – All rights reserved
ISO 3679:2004(E)
Introduction
This International Standard describes one of two closed cup equilibrium methods for the determination of the
flash point of paints, varnishes, paint binders, solvents, adhesives, petroleum and related products. When
[4]
selecting a method, it should therefore be read in conjunction with the second method, ISO 1523 . When
used in conjunction with the flash detector (A.1.6), this International Standard is also suitable for the
determination of the flash point of fatty acid methyl esters (FAME).
In both ISO 3679 and ISO 1523, the test is only carried out when the material under test and the air/vapour
mixture above the material in the test cup are approximately in temperature equilibrium.
The apparatus specified in this International Standard enables a similar test result to be determined using a
more rapid procedure and a smaller test portion (2 ml or 4 ml) than that required in ISO 1523. In addition, the
apparatus can be made portable to the extent of being suitable for on-site testing in addition to its more
normal use in laboratories.
Collaborative work (see [6] in the Bibliography) has shown that results obtained by these procedures are
comparable. The interpretation of flash point results obtained on solvent mixtures containing halogenated
hydrocarbons should be considered with caution, as these mixtures can give anomalous results (see [7] in the
Bibliography).
Flash point values are not a constant physical-chemical property of materials tested. They are a function of
the apparatus design, the condition of the apparatus used, and the operational procedure carried out. Flash
point can therefore only be defined in terms of a standard test method, and no general valid correlation can be
guaranteed between results obtained by different test methods or with test apparatus different from that
specified.
INTERNATIONAL STANDARD ISO 3679:2004(E)
Determination of flash point — Rapid equilibrium closed cup
method
WARNING — The use of this International Standard may involve hazardous materials, operations and
equipment. This International Standard does not purport to address all of the safety problems
associated with its use. It is the responsibility of the user of this International Standard to establish
appropriate safety and health practices and determine the applicability of regulatory limitations prior
to use.
1 Scope
This International Standard specifies a method for the determination of the closed cup flash point of paints
(including water-borne paints), varnishes, paint binders, adhesives, solvents, petroleum, and related products
having closed cup flash points within the range of − 30 °C to 300 °C. When used in conjunction with the flash
detector (A.1.6), this International Standard is also suitable for the determination of the flash point of fatty acid
methyl esters (FAME).
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
ISO 1513:1992, Paints and varnishes — Examination and preparation of samples for testing
ISO 3170:2004, Petroleum liquids — Manual sampling
ISO 3171:1988, Petroleum liquids — Automatic pipeline sampling
ISO 15528:2000, Paints, varnishes and raw materials for paints and varnishes — Sampling
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
flash point
lowest temperature of the test portion (as measured in the prescribed manner), corrected to a barometric
pressure of 101,3 kPa, at which application of a test flame causes the vapour of the test portion to ignite
momentarily and the flame to propagate across the surface of the liquid under the specified conditions of test
ISO 3679:2004(E)
4 Principle
A test portion of specified volume is introduced into the test cup, which is maintained at the temperature of the
estimated flash point of the material under test. After a specified time, a test flame is applied and the presence
or absence of a flash observed. Further tests, with fresh test portions at different temperatures, are carried out
until the flash point is determined to the sensitivity specified.
5 Reagents and materials
5.1 Cleaning solvent
An appropriate solvent for the removal of traces of the previous test portion from the test cup and cover.
NOTE The choice of solvent will depend upon the previous material tested and the tenacity of the residue. Low
volatility aromatic (benzene-free) solvents may be used to remove traces of oil, and mixed solvents such as toluene-
acetone-methanol may be effective for the removal of gum-type deposits.
5.2 Verification liquids
A series of certified reference materials (CRM) and/or secondary working standards (SWS) as described in
Annex C.
6 Apparatus
6.1 General
The apparatus is described in Annex A, and this includes the details of the test cup and cover assembly,
together with dimensions and special requirements. These are shown in Figure A.1 to Figure A.5. The
measurement of flash points over the whole range of − 30 °C to 300 °C may require more than one
instrument.
6.2 Syringes
6.2.1 2 ml syringe, adjusted to deliver 2,00 ml ± 0,05 ml and equipped, if required, with a needle suitable
for use with the apparatus at test temperatures up to and including 100 °C. When testing FAME, a 2 ml
sample is used at all temperatures.
6.2.2 5 ml syringe, adjusted to deliver 4,00 ml ± 0,10 ml and equipped, if required, with a needle suitable
for use with the apparatus at test temperatures above 100 °C. A 5 ml syringe is not required when testing
FAME.
6.3 Barometer, accurate to 0,1 kPa. Barometers precorrected to give sea-level readings, such as those
used at weather stations and airports, shall not be used.
6.4 Heating bath or oven (optional), for warming the samples, if required, and capable of controlling the
temperature to ± 5 °C. If an oven is used, it shall be intrinsically safe for hydrocarbon vapours.
It is recommended that the oven be of explosion-protected design.
6.5 Cooling bath or freezer (optional), for cooling the samples, if required, and capable of cooling the
sample to 10 °C below the expected flash point, and controlling the temperature to ± 5 °C. If a freezer is used,
it shall be of an explosion-protected design.
6.6 Draught shield (optional), if required to minimize draughts, fitted at the back and on two sides of the
instrument.
2 © ISO 2004 – All rights reserved
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.