EN 60143-1:2015
(Main)Series capacitors for power systems - Part 1: General
Series capacitors for power systems - Part 1: General
IEC 60143-1:2015 applies both to capacitor units and capacitor banks intended to be used connected in series with an a.c. transmission or distribution line or circuit forming part of an a.c. power system having a frequency of 15 Hz to 60 Hz. The primary focus of this standard is on transmission application. The series capacitor units and banks are usually intended for high-voltage power systems. This standard is applicable to the complete voltage range. This standard does not apply to capacitors of the self-healing metallized dielectric type. The following capacitors, even if connected in series with a circuit, are excluded from this standard: - capacitors for inductive heat-generating plants (IEC 60110-1); - capacitors for motor applications and the like (IEC 60252 (all parts)); - capacitors to be used in power electronics circuits (IEC 61071); - capacitors for discharge lamps (IEC 61048 and IEC 61049). For standard types of accessories such as insulators, switches, instrument transformers, external fuses, etc. see the pertinent IEC standard. The object of this standard is: - to formulate uniform rules regarding performance, testing and rating; - to formulate specific safety rules; - to serve as a guide for installation and operation. This fifth edition cancels and replaces the fourth edition, published in 2004. This edition constitutes a technical revision. The main change with respect to the previous edition is that the endurance test has been replaced by an ageing test because voltage cycling is already performed in the cold duty test. The guide section has been expanded regarding long line correction and altitude correction. In addition the insulation tables and references to other standards have been updated. Keywords: a.c. transmission or distribution line, capacitor units and banks for high-voltage power systems
Condensateurs série destinés à être installés sur des réseaux - Partie 1: Généralités
L'IEC 60143-1:2015 s'applique aux condensateurs unitaires et aux batteries de condensateurs destinés à être raccordés en série sur une ligne de transport ou de distribution d'énergie faisant partie d'un réseau alternatif de fréquence comprise entre 15 Hz et 60 Hz. L'objectif principal de cette norme est de traiter des applications sur les réseaux de transport. Les condensateurs série et les batteries de condensateurs série sont habituellement destinés aux réseaux d'énergie à haute tension. La présente norme s'applique à toute la gamme de tensions. La présente norme ne s'applique pas aux condensateurs avec diélectrique métallisé du type autorégénérateur. Même s'ils sont connectés en série avec un circuit, les condensateurs suivants sont exclus de la présente norme: - condensateurs pour installations de production de chaleur par induction (IEC 60110-1); - condensateurs pour moteurs et similaires (IEC 60252 - toutes les parties); - condensateurs destinés à être utilisés dans les circuits électroniques de puissance (IEC 61071); - condensateurs pour lampes à décharge (IEC 61048 et IEC 61049). Pour les accessoires normalisés tels que les isolateurs, commutateurs, transformateurs de mesure, coupe-circuit externes, etc., se reporter à la norme IEC correspondante. La présente norme a pour objet: - de formuler des règles uniformes en ce qui concerne la qualité de fonctionnement, les essais et les caractéristiques assignées; - de formuler des règles spécifiques de sécurité; - de servir de guide pour l'installation et pour l'exploitation. Cette cinquième édition annule et remplace la quatrième édition parue en 2004. Cette édition constitue une révision technique. La modification majeure par rapport à la précédente édition concerne le fait que l'essai d'endurance a été remplacé par un essai de vieillissement dans la mesure où les cycles de fonctionnement en tension sont déjà réalisés au cours de l'essai de tenue au froid. La section guide a été étendue pour couvrir la correction de longue ligne et la correction d'altitude. De plus, les tableaux relatifs aux niveaux d'isolement et les références à d'autres normes ont été mis à jour. Mots clés: ligne de transport ou de distribution d'énergie, condensateurs séries destinés aux réseaux d'énergie à haute tension
Zaporedni kondenzatorji za elektroenergetske sisteme - 1. del: Splošno
Ta del standarda IEC 60143 velja za kondenzatorske enote in kondenzatorske baterije, namenjene za uporabo v zaporedni vezavi s prenosnim vodom ali razdelilnim omrežjem izmenične napetosti ali elementom, ki sklene tokokrog, izmeničnega napajalnega sistema s frekvenco med 15 in 60 Hz.
Ta standard se osredotoča predvsem na uporabo s prenosnimi vodi.
Zaporedne kondenzatorske enote in baterije so običajno namenjene za uporabo v visokonapetostnih napajalnih sistemih.
Ta standard velja za celoten razpon napetosti.
Ta standard se ne uporablja za kondenzatorje samoozdravljivega metaliziranega dielektričnega tipa. Naslednji kondenzatorji niso zajeti v tem standardu, tudi če so zaporedno vezani v tokokrog:
– kondenzatorji za induktivne obrate, ki proizvajajo toploto (IEC 60110-1);
– kondenzatorji za motorje in podobne namene (IEC 60252 (vsi deli));
– kondenzatorji za močnostne elektronske tokokroge (IEC 61071);
– kondenzatorji za razelektritvene sijalke (IEC 61048 in IEC 61049).
Za standardne tipe dodatne opreme, kot so izolatorji, stikala, instrumentni transformatorji, zunanje varovalke itd. glej ustrezni standard IEC.
OPOMBA 1 Dodatne zahteve za kondenzatorje, ki jih je treba zaščititi z notranjimi varovalkami, kot tudi zahteve za notranje varovalke najdete v standardu IEC 60143-3. Glej tudi dodatek C.
OPOMBA 2 Dodatne zahteve za kondenzatorje, ki jih je treba zaščititi z zunanjimi varovalkami, kot tudi zahteve za zunanje varovalke najdete v dodatkih A in C.
OPOMBA 3 Poseben standard za dodatno opremo za zaporedne kondenzatorje (iskrišča, varistorji, razelektritvene dušilke, dušilke za omejevanje toka, omejevalni upori, odklopniki itd.) IEC 60143-2 je bil leta 2012 revidiran in dopolnjen. Poseben standard za notranje varovalke za zaporedne kondenzatorje IEC 60143-3 je bil revidiran in dopolnjen leta 2013.
OPOMBA 4 Nekatere podatke o kondenzatorskih enotah in kondenzatorskih baterijah brez varovalk najdete v dodatku C.
Namen tega standarda je:
– določitev enotnih pravil glede zmogljivosti, preskušanja in ocenjevanja;
– določitev posebnih varnostnih pravil;
– zagotovitev navodil za namestitev in delovanje.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-december-2015
1DGRPHãþD
SIST EN 60143-1:2004
Zaporedni kondenzatorji za elektroenergetske sisteme - 1. del: Splošno
Series capacitors for power systems - Part 1: General
Ta slovenski standard je istoveten z: EN 60143-1:2015
ICS:
31.060.70 0RþQRVWQLNRQGHQ]DWRUML Power capacitors
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN 60143-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2015
ICS 31.060.70 Supersedes EN 60143-1:2004
English Version
Series capacitors for power systems - Part 1: General
(IEC 60143-1:2015)
Condensateurs série destinés à être installés sur des Reihenkondensatoren für Starkstromanlagen - Teil 1:
réseaux - Partie 1: Généralités Allgemeines
(IEC 60143-1:2015) (IEC 60143-1:2015)
This European Standard was approved by CENELEC on 2015-07-30. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 60143-1:2015 E
European foreword
The text of document 33/578/FDIS, future edition 5 of IEC 60143-1, prepared by IEC/TC 33 "Power
capacitors and their applications" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN 60143-1:2015.
The following dates are fixed:
(dop) 2016-04-30
• latest date by which the document has to be
implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2018-07-30
standards conflicting with the
document have to be withdrawn
This document supersedes EN 60143-1:2004.
The main change with respect to EN is that the endurance test has been replaced by an ageing test
because voltage cycling is already performed in the cold duty test. The guide section has been
expanded regarding long line correction and altitude correction. In addition the insulation tables and
references to other standards have been updated.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.
Endorsement notice
The text of the International Standard IEC 60143-1:2015 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
IEC 60060-2:2010 NOTE Harmonized as EN 60060-2:2011.
IEC 60110-1:1998 NOTE Harmonized as EN 60110-1:1998.
IEC 60252-1:2010 NOTE Harmonized as EN 60252-1:2011.
IEC 61048:2006 NOTE Harmonized as EN 61048:2006.
IEC 61049:1991 NOTE Harmonized as EN 61049:1993.
IEC 61071 NOTE Harmonized as EN 61071.
IEC 60270:2000 NOTE Harmonized as EN 60270:2001.
IEC 60909-0:2001 NOTE Harmonized as EN 60909-0:2001.
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60050 series International Electrotechnical Vocabulary - series
IEC 60060-1 2010 High-voltage test techniques -- Part 1: EN 60060-1 2010
General definitions and test requirements
IEC 60071-1 2006 Insulation co-ordination -- Part 1: EN 60071-1 2006
Definitions, principles and rules
IEC 60071-2 1996 Insulation co-ordination -- Part 2: EN 60071-2 1997
Application guide
IEC 60143-2 2012 Series capacitors for power systems -- Part EN 60143-2 2013
2: Protective equipment for series
capacitor banks
IEC 60143-3 1998 Series capacitors for power systems -- Part EN 60143-3 1998
3: Internal fuses
IEC 60143-4 2010 Series capacitors for power systems -- Part EN 60143-4 2010
4: Thyristor controlled series capacitors
IEC 60549 2013 High-voltage fuses for the external EN 60549 2013
protection of shunt capacitors
IEC 60871-1 2014 Shunt capacitors for a.c. power systems EN 60871-1 2014
having a rated voltage above 1 000 V -
Part 1: General
IEC 62271-1 2007 High-voltage switchgear and controlgear -- EN 62271-1 2008
Part 1: Common specifications
IEEE Std 693 - IEEE Recommended Practice for Seismic - -
Design of Substations
IEC 60143-1 ®
Edition 5.0 2015-06
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Series capacitors for power systems –
Part 1: General
Condensateurs série destinés à être installés sur des réseaux –
Partie 1: Généralités
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 31.060.70 ISBN 978-2-8322-2752-7
– 2 – IEC 60143-1:2015 © IEC 2015
CONTENTS
FOREWORD .6
1 Scope and object .8
2 Normative references .8
3 Terms and definitions .9
4 Service conditions . 15
4.1 Normal service conditions . 15
4.2 Ambient air temperature categories . 15
4.3 Abnormal service conditions . 16
4.4 Abnormal power system conditions . 16
5 Quality requirements and tests . 16
5.1 Test requirements for capacitor units . 16
5.1.1 General . 16
5.1.2 Test conditions . 16
5.1.3 Voltage limits as established by overvoltage protector . 17
5.1.4 Determination of protective level voltage U and U . 18
pl lim
5.2 Classification of tests . 18
5.2.1 General . 18
5.2.2 Routine tests . 18
5.2.3 Type tests . 19
5.2.4 Special test (ageing test) . 19
5.3 Capacitance measurement (routine test) . 19
5.3.1 Measuring procedure . 19
5.3.2 Capacitance tolerance . 20
5.4 Capacitor loss measurement (routine test) . 20
5.4.1 Measuring procedure . 20
5.4.2 Loss requirements . 21
5.4.3 Losses in external fuses . 21
5.5 Voltage test between terminals (routine test) . 21
5.6 AC voltage test between terminals and container (routine test) . 21
5.7 Test on internal discharge device (routine test) . 21
5.8 Sealing test (routine test) . 22
5.9 Thermal stability test (type test) . 22
5.9.1 Measuring procedure . 22
5.9.2 Capacitor loss measurement . 23
5.10 AC voltage test between terminals and container (type test) . 23
5.11 Lightning impulse voltage test between terminals and container (type test) . 24
5.12 Cold duty test (type test) . 24
5.13 Discharge current test (type test) . 25
6 Insulation level . 26
6.1 Insulation voltages . 26
6.1.1 Standard values . 26
6.1.2 Insulation to earth and between phases . 26
6.1.3 Insulation levels for insulators and equipment on the platform . 26
6.2 Creepage distance . 33
6.3 Air clearances . 34
7 Overloads, overvoltages and duty cycles . 38
IEC 60143-1:2015 © IEC 2015 – 3 –
7.1 Currents . 38
7.2 Transient overvoltages . 38
7.3 Duty cycles . 39
8 Safety requirements . 39
8.1 Discharge device . 39
8.2 Container connection . 39
8.3 Protection of the environment . 40
8.4 Other safety requirements . 40
9 Markings and instruction books . 40
9.1 Markings of the unit . 40
9.1.1 Rating plate . 40
9.1.2 Warning plate . 41
9.2 Markings of the bank . 41
9.2.1 Instruction sheet or rating plate . 41
9.2.2 Warning plate . 41
9.3 Instruction book . 41
10 Guide for selection of ratings, installation and operation . 42
10.1 General . 42
10.2 Reactance per line, rated reactance per bank and number of modules per
bank . 42
10.2.1 Capacitive reactance per line . 42
10.2.2 Number of series capacitor banks in a transmission line . 43
10.2.3 Number of modules in a capacitor bank . 44
10.2.4 Future requirements for series capacitors . 44
10.3 Current ratings for the bank . 44
10.3.1 General . 44
10.3.2 Typical bank overload and swing current capabilities . 45
10.3.3 Analysis to determine the continuous and emergency overload current
rating . 46
10.3.4 Analysis to determine the swing current rating . 46
10.4 Overvoltage protection requirements . 46
10.5 Voltage limitations during power system faults . 47
10.5.1 General . 47
10.5.2 Voltage limitation when the inductance between the primary
overvoltage protector and the capacitors is not significant . 47
10.5.3 Voltage limitation when the inductance between the primary
overvoltage protector and the capacitors is significant . 48
10.6 Protective and switching devices . 48
10.6.1 Capacitor fusing . 48
10.6.2 Other devices . 48
10.6.3 Connection diagrams . 48
10.7 Choice of insulation level . 49
10.7.1 Normal cases . 49
10.7.2 Altitude exceeding 1 000 m . 49
10.8 Long line correction . 50
10.9 Other application considerations . 51
10.9.1 General . 51
10.9.2 Ferro-resonance . 51
10.9.3 Sub-synchronous resonance . 51
– 4 – IEC 60143-1:2015 © IEC 2015
10.9.4 Relay protection of the power system . 51
10.9.5 Attenuation of carrier-frequency transmission . 52
10.9.6 Non-transposed transmission lines . 52
10.9.7 Power system harmonic currents . 52
10.9.8 TRV across line circuit-breakers . 52
10.9.9 Delayed line current zero crossing . 53
10.9.10 Prolonged secondary arc current . 53
Annex A (normative) Test requirements and application guide for external fuses and
units to be externally fused . 54
A.1 Overview . 54
A.2 Purpose . 54
A.3 Terms employed in Annex A . 54
A.4 Performance requirements . 54
A.5 Tests . 55
A.5.1 Tests on fuses . 55
A.5.2 Type tests on capacitor container . 55
A.6 Guide for coordination of fuse protection . 55
A.6.1 General . 55
A.6.2 Protection sequence . 55
A.7 Choice of fuses . 56
A.7.1 General . 56
A.7.2 Non current-limiting fuses . 56
A.7.3 Current-limiting fuses . 56
A.8 Information needed by the user of the fuses . 56
Annex B (informative) Economic evaluation of series capacitor bank losses . 57
Annex C (informative) Capacitor bank fusing and unit arrangement . 58
C.1 General . 58
C.2 Internally fused capacitor bank . 58
C.3 Externally fused capacitor bank . 58
C.4 Fuseless capacitor bank . 59
Annex D (informative) Examples of typical connection diagrams for large series
capacitor installations for transmission lines. 61
Annex E (informative) Precautions to be taken to avoid pollution of the environment
by polychlorinated biphenyls . 62
Bibliography . 63
Figure 1 – Typical nomenclature of a series capacitor installation . 12
Figure 2 – Classification of overvoltage protection . 17
Figure 3 – Time and amplitude limits for an overvoltage period waveform . 25
Figure 4 – Air clearance versus a.c. power frequency withstand voltage . 38
Figure 5 – Typical current-time profile of an inserted capacitor bank following the fault
and clearing of parallel line . 45
Figure C.1 – Typical connections between capacitor units in a segment or phase . 59
Figure C.2 – Typical connections between elements within a capacitor unit . 60
Figure D.1 – Diagrams for smaller banks . 61
Table 1 – Letter symbols for upper limit of temperature range . 15
IEC 60143-1:2015 © IEC 2015 – 5 –
Table 2 – Ambient air temperature in thermal stability test . 22
Table 3 – Standard insulation levels for range I (1 kV < U ≤ 245 kV) . 29
m
Table 4 – Standard insulation levels for range II (U > 245 kV) (1 of 2) . 30
m
Table 5 – Typical insulation levels for platform-to-ground insulators (1 of 2) . 32
Table 6 – Specific creepage distances . 34
Table 7 – Correlation between standard lightning impulse withstand voltages and
minimum air clearances . 36
Table 8 – Correlation between standard switching impulse withstand voltages and
minimum phase-to-earth air clearances . 37
(reproduced from IEC 60071-2:1996, Table A.2) . 37
Table 9 – Correlation between standard switching impulse withstand voltages and
minimum phase-to-phase air clearances . 37
Table 10 – Typical bank overload and swing current capabilities . 45
– 6 – IEC 60143-1:2015 © IEC 2015
INTERNATIONAL ÉLECTROTECHNICAL COMMISSION
____________
SERIES CAPACITORS FOR POWER SYSTEMS –
Part 1: General
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60143-1 has been prepared by IEC technical committee 33:
Power capacitors and their applications.
This fifth edition cancels and replaces the fourth edition, published in 2004. This edition
constitutes a technical revision.
The main change with respect to the previous edition is that the endurance test has been
replaced by an ageing test because voltage cycling is already performed in the cold duty test.
The guide section has been expanded regarding long line correction and altitude correction.
In addition the insulation tables and references to other standards have been updated.
IEC 60143-1:2015 © IEC 2015 – 7 –
The text of this standard is based on the following documents:
FDIS Report on voting
33/578/FDIS 33/580/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60143 series, published under the general title Series capacitors
for power systems, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC website under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
– 8 – IEC 60143-1:2015 © IEC 2015
SERIES CAPACITORS FOR POWER SYSTEMS –
Part 1: General
1 Scope and object
This part of IEC 60143 applies both to capacitor units and capacitor banks intended to be
used connected in series with an a.c. transmission or distribution line or circuit forming part
of an a.c. power system having a frequency of 15 Hz to 60 Hz.
The primary focus of this standard is on transmission application.
The series capacitor units and banks are usually intended for high-voltage power systems.
This standard is applicable to the complete voltage range.
This standard does not apply to capacitors of the self-healing metallized dielectric type.
The following capacitors, even if connected in series with a circuit, are excluded from this
standard:
– capacitors for inductive heat-generating plants (IEC 60110-1);
– capacitors for motor applications and the like (IEC 60252 (all parts));
– capacitors to be used in power electronics circuits (IEC 61071);
– capacitors for discharge lamps (IEC 61048 and IEC 61049).
For standard types of accessories such as insulators, switches, instrument transformers,
external fuses, etc. see the pertinent IEC standard.
NOTE 1 Additional requirements for capacitors to be protected by internal fuses, as well as the requirements for
internal fuses, are found in IEC 60143-3. See also Annex C.
NOTE 2 Additional requirements for capacitors to be protected by external fuses, as well as the requirements for
external fuses, are found in Annex A and Annex C.
NOTE 3 A separate standard for series capacitor accessories (spark-gaps, varistors, discharge reactors, current-
limiting damping reactors, damping resistors, circuit-breakers, etc.), IEC 60143-2, has been revised and was
completed in 2012. A separate standard for internal fuses for series capacitors, IEC 60143-3 has been revised and
was completed in 2013.
NOTE 4 Some information regarding fuseless capacitor units and fuseless capacitor banks is found in Annex C.
The object of this standard is:
– to formulate uniform rules regarding performance, testing and rating;
– to formulate specific safety rules;
– to serve as a guide for installation and operation.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document
and are indispensable for its application. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
NOTE If there is a conflict between this standard and a standard listed below, the text of IEC 60143-1 prevails.
IEC 60143-1:2015 © IEC 2015 – 9 –
IEC 60050 (all parts), International Electrotechnical Vocabulary (available at
www.electropedia.org)
IEC 60060-1:2010, High-voltage test techniques – Part 1: General definitions and test
requirements
IEC 60071-1:2006, Insulation co-ordination – Part 1: Definitions, principles and rules
IEC 60071-2:1996, Insulation co-ordination – Part 2: Application guide
IEC 60143-2:2012, Series capacitors for power systems – Part 2: Protective equipment for
series capacitor banks
IEC 60143-3:1998, Series capacitors for power systems – Part 3: Internal fuses
IEC 60143-4: 2010 Series capacitors for power systems – Part 4: Thyristor controlled series
capacitors
IEC 60549:2013, High-voltage fuses for the external protection of shunt capacitors
IEC 60871-1: 2014 Shunt capacitors for a.c power systems having a rated voltage above
1000V – Part 1: General
IEC 62271-1:2007, High-voltage switchgear and controlgear – Part 1: Common specifications
IEEE Std. 693:1997, IEEE Recommended Practice for Seismic Design of Substations
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
ambient air temperature (for capacitors)
temperature of air at the proposed location of the capacitor installation
3.2
bypass switch
device such as a switch or circuit-breaker used in parallel with a series capacitor and its
overvoltage protector to shunt line current for some specified time or continuously
Note 1 to entry: This device shall also have the capability of bypassing the capacitor during specified power
system fault conditions. The operation of the device is initiated by the capacitor bank control, remote control or by
an operator. The device may be mounted on the platform or on the ground near the platform. Besides bypassing
the capacitor, this device shall also have the capability of inserting the capacitor into a circuit carrying a specified
level of current.
3.3
capacitor
word used when it is not necessary to distinguish between the different meanings of the
words capacitor unit and the assembly of capacitors associated with a segment
3.4
capacitor unit
unit
assembly of one or more capacitor elements in the same container with terminals brought out
– 10 – IEC 60143-1:2015 © IEC 2015
[SOURCE: IEC 60050-436:1990, 436-01-04]
3.5
(capacitor) element
device consisting essentially of two electrodes separated by a dielectric
[SOURCE: IEC 60050-436:1990, 436-01-03]
3.6
capacitor losses
active power dissipated in the capacitor
Note 1 to entry: All loss-producing components should be included. For a unit, this includes losses from the
dielectric, discharge device, internal fuses (if applicable) and internal connections. For the bank, this includes
losses from the units, external fuses (if applicable) and busbars. See Annex B for additional discussion.
[SOURCE: IEC 60050-436:1990, 436-04-10]
3.7
cooling air temperature
temperature of cooling air measured at the hottest position in the capacitor assembly of a
segment, under rated current and steady-state conditions, midway between two units
Note 1 to entry: If only one unit is involved, it is the temperature measured at a point approximately 0,1 m away
from the capacitor container and at two-thirds of the height from its base.
3.8
degree of compensation
k
degree of series compensation, k (of a line section) is
/ X ) %
k = 100 (X
c L
where
X is the capacitive reactance of the series capacitor;
c
X is the total positive sequence inductive reactance of the transmission line section on
L
which the series capacitor is applied.
3.9
discharge device (of a capacitor)
device connected across the terminals of the capacitor or built into the capacitor unit,
capable of reducing the residual voltage across the capacitor effectively to zero after the
capacitor has been disconnected from the supply
Note 1 to entry: Further requirements on the size of the discharge device are found in 8.1.
[SOURCE: IEC 60050-436:1990, 436-03-15, modified (modified definition, addition of Note 1
to entry)]
3.10
external fuse (of a capacitor)
fuse connected in series with a capacitor unit or with a group of parallel units
3.11
fuseless capacitor bank
capacitor bank without any fuses, internal or external, constructed of parallel strings of
capacitor units. Each string consists of capacitor units connected in series
Note 1 to entry: See Annex C for an explanation of “string”.
IEC 60143-1:2015 © IEC 2015 – 11 –
3.12
highest voltage of a three-phase system
highest r.m.s. phase-to-phase voltage which occurs under normal operating conditions at any
time and at any point of the system
Note 1 to entry: It excludes voltage transients (such as those due to system switching) and temporary voltage
variations due to abnormal system conditions (such as due to faults or sudden disconnection of large loads).
3.13
highest voltage for equipment
U
m
highest r.m.s. value of phase-to-phase voltage for which the equipment is designed in respect
of its insulation as well as other characteristics which relate to this voltage in the relevant
equipment standards
Note 1 to entry: This voltage is the maximum value of the highest voltage of the system for which the equipment
may be used.
[SOURCE: IEC 60050-604:1987, 604-03-01]
3.14
insulation level
U
i
non-simultaneous combination of test voltages (power-frequency (U ) or switching impulse,
ipf
and lightning impulse) which characterizes the insulation of the capacitor with regard to its
capability of withstanding the electric stresses between terminals and earth, between phases
and between terminals and metalwork (e.g. platform) not at earth potential
3.15
internal fuse of a capacitor
fuse connected inside a capacitor unit, in series with an element or group of elements
[SOURCE: IEC 60050-436:1990, 436-03-16]
3.16
limiting voltage
U
lim
maximum peak of the power frequency voltage occurring between capacitor unit terminals
immediately before or during operation of the overvoltage protector, divided by 2
SEE: 5.1.4
Note 1 to entry: This voltage appears either during conduction of the varistor or immediately before ignition of the
spark gap.
3.17
line terminal
terminal to be connected to the power system
[SOURCE: IEC 60050-436:1990, 436-03-01, modified (modified definition)]
3.18
module (of a series capacitor)
switchable step of a series capacitor consisting of identical segments in each phase (see
Figure 1), which furthermore are also equipped with provisions for a common operation of the
bypass switch of each of these segments
– 12 – IEC 60143-1:2015 © IEC 2015
Note 1 to entry: The bypass switch of a module is normally operated on a three-phase basis. However, in some
applications for protection purposes, the bypass switch may be required to temporarily operate on an individual
phase basis.
Note 2 to entry: Figure 1 shows a typical nomenclature of a series capacitor installation.
SC installation
SC
Module 1 Module N
bank
9 9
Phase A
2-7
11 11
Segment A1 Segment AN
9 9
Phase B
Segment B1
Segment BN
9 9
Phase C
11 11
Segment C1 Segment CN
IEC
Key
1 assembly of capacitor units
2-7 main protective equipment (Figure 2c) and Annex D)
9 isolating disconnector
10 bypass disconnector
11 earth switch
NOTE 1 A SC Installation includes a SC Bank plus 9, 10 and 11.
NOTE 2 Most series capacitors are configured with a single module, unless the reactance and current
requirements result in a voltage across the bank that is impractical for the supplier to achieve with one module.
Normally each module has its own bypass switch, but a common bypass switch may be used for more than one
module. See clause 10.2.3 for additional details.
Figure 1 – Typical nomenclature of a series capacitor installation
3.19
overvoltage protector (of a series capacitor)
quick-acting device (usually MOV or a self triggered spark gap) which limits the voltage
across the capacitor to a permissible value when that value would otherwise be exceeded as
a result of a circuit fault or other abnormal power system conditions
3.20
power frequency withstand voltage
U
ipf
wet power frequency withstand voltage of bushings and insulators
IEC 60143-1:2015 © IEC 2015 – 13 –
3.21
protective level
U
pl
magnitude of the maximum peak of the power frequency voltage appearing across the
overvoltage protector during a power system fault
Note 1 to entry: The protective level may be expressed in terms of the actual peak voltage across a segment or
in terms of the per unit of the peak of the rated voltage across the capacitor (see 5.1.4, 10.4 and 10.5). This
voltage appears either during conduction of the varistor or immediately before ignition of the spark gap.
3.22
rated capacitance (of a capacitor)
C
N
capacitance value for which the capacitor has been designed
3.23
rated current of a capacitor
I
N
r.m.s. value of the alternating current for which the capacitor has been designed
[SOURCE: IEC 60050-436:1990, 436-01-13]
3.24
rated frequency (of a capacitor)
f
N
frequency of the system in which the capacitor is intended to be used
[SOURCE: IEC 60050-436:1990, 436-01-14, modified (modified definition)]
3.25
rated output (of a capacitor)
Q
N
reactive power derived from rated reactance and rated current
Note 1 to entry: For the bank, the rated three-phase reactive power rating in Mvar (Q ) is defined by the
N
equation:
Q = 3 × I × X
N N N
where
I is the rated current, in kA;
N
X is the rated reactance, in Ω.
N
3.26
rated reactance (of capacitor)
X
N
reactance of each phase of the series capacitor at rated frequency and 20 °C dielectric
temperature
3.27
rated voltage (of the bank)
power system phase-to-phase voltage for which the phase-to-ground insulation system is
designed
3.28
rated voltage (of a capacitor)
U
N
r.m.s. value of the voltage between the terminals, derived from rated reactance and rated
current U = X × I
N N N
– 14 – IEC 60143-1:2015 © IEC 2015
3.29
residual voltage (of a capacitor)
voltage remaining between terminals of a capacitor at a given time following disconnection of
the supply
3.30
segment (of a series capacitor)
single-phase assembly of groups of capacitors which has its own voltage-limiting devices and
relays to protect the capacitors from overvoltages and overloads
SEE: Figure 1
Note 1 to entry: Segments are not normally separated by isolating disconnectors. More than one segment can be
on the same insulated platform.
3.31
series capacitor bank (or bank)
three-phase assembly of capacitors with the associated protection and insulated support
structure
Note 1 to entry: The bank may include one or more modules (see Figure 1).
3.32
series capacitor installation
series capacitor bank and its accessories including the bypass and isolating disconnectors
[SOURCE: IEC 60050-436:1990, 436-01-07, modified (addition of "including the bypas
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...