ASTM F710-22
(Practice)Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
ABSTRACT
This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring.
SCOPE
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
- Status
- Published
- Publication Date
- 14-Dec-2022
- Technical Committee
- F06 - Resilient Floor Coverings
- Drafting Committee
- F06.40 - Practices
Relations
- Effective Date
- 15-Dec-2023
- Effective Date
- 01-Nov-2023
- Effective Date
- 01-Aug-2023
- Effective Date
- 01-Jul-2020
- Effective Date
- 01-Apr-2020
- Effective Date
- 15-Jan-2020
- Effective Date
- 01-Dec-2019
- Effective Date
- 01-Mar-2019
- Effective Date
- 01-Feb-2019
- Effective Date
- 15-Dec-2018
- Effective Date
- 01-Aug-2018
- Effective Date
- 01-Jan-2018
- Effective Date
- 01-Sep-2017
- Effective Date
- 01-Sep-2017
- Effective Date
- 01-Dec-2016
Overview
ASTM F710-22 is the Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring, established by ASTM International. This standard provides procedures to assess the suitability of concrete floors before installing resilient flooring, such as vinyl, rubber, linoleum, and similar materials. It covers steps for cleaning, testing, repairing, and conditioning concrete substrates, with the goal of ensuring durable, high-performance resilient flooring installations. The standard emphasizes testing for moisture and pH, recommends the use of vapor retarders, and clarifies best practices for new and existing concrete floors. It also gives practical suggestions for mitigating risks related to moisture, alkalinity, surface irregularities, and contaminants, but does not address the structural adequacy of the slab itself.
Key Topics
- Assessment of Concrete Floors: Guidelines for determining if a concrete slab is suitable for resilient flooring.
- Surface Preparation: Requirements for surface cleanliness, flatness, smoothness, and repair of cracks, control joints, or other non-moving joints.
- Moisture and pH Testing: Procedures for measuring moisture vapor emission rates and pH levels to prevent flooring failure due to moisture or high alkalinity.
- Moisture Vapor Retarders: Mandate for permanent, effective vapor retarders under all on- or below-grade concrete floors.
- Cleaning Methods: Recommendations for removal of dust, residual adhesives, paint, oil, wax, and other contaminants through non-chemical means like scraping, vacuuming, or bead-blasting.
- Environmental Conditioning: Guidance on acclimating the installation area and materials regarding temperature and humidity for optimal installation conditions.
- Remediation and Repairs: Use of latex patching and underlayment compounds to correct irregularities, with attention to compressive strength and chemical compatibility.
- Safety Considerations: Notices regarding potential hazards when dealing with asbestos, lead-based paints, or crystalline silica during surface preparation.
Applications
- Flooring Contractors and Installers: Ensures best practices are followed for substrate preparation, maximizing performance and longevity of installations.
- Architects and Specifiers: Supports project design and specification of resilient flooring systems, including requirements for substrate moisture control and flatness.
- Facility Owners and Managers: Provides guidelines to minimize future flooring failures, moisture-related issues, and costly repairs.
- Manufacturers: Assures substrate conditions are within recommended ranges, reducing product claims and installation failures.
- New or Existing Commercial, Institutional, and Residential Projects: Applies to installation of resilient flooring over new or existing concrete slabs in diverse settings, with useful procedures adaptable for other finishes like carpet, wood flooring, or coatings.
- Renovation and Remediation Projects: Guides safe and effective removal of old flooring, adhesives, and contaminants, including historical buildings where hazardous materials may be present.
- Radiant Heated Slabs: Advises on resilient floor installation over heated slabs, including surface temperature limits.
Related Standards
- ASTM F1869: Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
- ASTM F2170: Test Method for Determining Relative Humidity in Concrete Floor Slabs Using In Situ Probes
- ASTM E1745: Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
- ASTM D4259: Practice for Preparation of Concrete by Abrasion Prior to Coating Application
- ASTM D4263: Test Method for Indicating Moisture in Concrete by the Plastic Sheet Method
- ACI 302.1R: Guide for Concrete Floor and Slab Construction
- ASTM F3191: Practice for Field Determination of Substrate Water Absorption for Substrates to Receive Resilient Flooring
- ASTM F141: Terminology Relating to Resilient Floor Coverings
Practical Value
Adhering to ASTM F710-22 ensures concrete floors are properly tested and prepared prior to resilient flooring installation, reducing the risk of moisture-related failures, adhesive issues, and floor covering defects. With clear procedures and references to complementary standards, it streamlines project workflows for construction professionals and improves the quality and resilience of finished flooring systems. Following this standard supports compliance with industry requirements, manufacturer recommendations, and long-term performance objectives.
Buy Documents
ASTM F710-22 - Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
REDLINE ASTM F710-22 - Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
Get Certified
Connect with accredited certification bodies for this standard

ICC Evaluation Service
Building products evaluation and certification.

QAI Laboratories
Building and construction product testing and certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
ASTM F710-22 is a standard published by ASTM International. Its full title is "Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring". This standard covers: ABSTRACT This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring. SCOPE 1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring. 1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring. 1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements. 1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring. 1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations. 1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes. 1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements. 1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
ABSTRACT This practice covers the procedure for determining the acceptability of concrete floors for the installation of resilient flooring. It also includes suggestions for ensuring that the constructed concrete floor is acceptable for such installations but does not cover tests for adequacy of the concrete floor to perform structural requirements. A permanent, effective moisture vapor retarder, of the specified thickness and permeance, is required under all on- or below-grade concrete floors. Concrete floors for resilient floorings should be permanently dry, clean, smooth, structurally sound, and free of substances that may prevent adhesive bonding. Surface cracks, grooves, depression, control joints or other non-moving joints, and other irregularities should be filled or smoothed with latex patching or a recommended underlayment compound. The surface of the floor should be cleaned by scraping, brushing, vacuuming, or any other method. All concrete slabs should be tested for moisture regardless of age or grade level while all concrete floors should be tested for pH before installing resilient flooring. SCOPE 1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring. 1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient flooring. 1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements. 1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring. 1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer's written instructions. Consult the individual manufacturer for specific recommendations. 1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints are not specifically intended to be included in the category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive such finishes. 1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements. 1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
ASTM F710-22 is classified under the following ICS (International Classification for Standards) categories: 91.060.30 - Ceilings. Floors. Stairs; 97.150 - Floor coverings. The ICS classification helps identify the subject area and facilitates finding related standards.
ASTM F710-22 has the following relationships with other standards: It is inter standard links to ASTM C109/C109M-23, ASTM D4397-16(2023), ASTM F141-23, ASTM E1155-20, ASTM C472-20, ASTM F141-12(2020), ASTM F2170-19a, ASTM F2170-19, ASTM F710-19, ASTM D4259-18, ASTM D4263-83(2018), ASTM F2170-18, ASTM F2170-17, ASTM F710-17, ASTM F2170-16b. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ASTM F710-22 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: F710 − 22
Standard Practice for
Preparing Concrete Floors to Receive Resilient Flooring
ThisstandardisissuedunderthefixeddesignationF710;thenumberimmediatelyfollowingthedesignationindicatestheyearoforiginal
adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.Asuperscript
epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This practice covers the determination of the acceptabil- 2.1 ASTM Standards:
ity of a concrete floor for the installation of resilient flooring. C109/C109M Test Method for Compressive Strength of
Hydraulic Cement Mortars (Using 2-in. or [50 mm] Cube
1.2 This practice includes suggestions for the construction
Specimens)
of a concrete floor to ensure its acceptability for installation of
C472 Test Methods for Physical Testing of Gypsum, Gyp-
resilient flooring.
sum Plasters, and Gypsum Concrete
1.3 This practice does not cover the adequacy of the
D4259 Practice for Preparation of Concrete by Abrasion
concrete floor to perform its structural requirements.
Prior to Coating Application
D4263 Test Method for Indicating Moisture in Concrete by
1.4 This practice covers the necessary preparation of con-
crete floors prior to the installation of resilient flooring. the Plastic Sheet Method
D4397 Specification for Polyethylene Sheeting for
1.5 This practice does not supersede in any manner the
Construction, Industrial, and Agricultural Applications
resilient flooring or adhesive manufacturer’s written instruc-
E1155 Test Method for Determining F Floor Flatness and
F
tions. Consult the individual manufacturer for specific recom-
F Floor Levelness Numbers
L
mendations.
E1486 Test Method for Determining Floor Tolerances Using
1.6 Although carpet tiles, carpet, wood flooring, coatings,
Waviness, Wheel Path and Levelness Criteria
films, and paints are not specifically intended to be included in
E1745 Specification for Plastic Water Vapor Retarders Used
the category of resilient floor coverings, the procedures in-
in Contact with Soil or Granular Fill under Concrete Slabs
cluded in this practice may be useful for preparing concrete
F141 Terminology Relating to Resilient Floor Coverings
floors to receive such finishes.
F710 Practice for Preparing Concrete Floors to Receive
1.7 This standard does not purport to address all of the Resilient Flooring
safety concerns, if any, associated with its use. It is the F1869 Test Method for Measuring Moisture Vapor Emission
responsibility of the user of this standard to establish appro- Rate of Concrete Subfloor Using Anhydrous Calcium
priate safety, health, and environmental practices and deter- Chloride
mine the applicability of regulatory limitations prior to use. F2170 Test Method for Determining Relative Humidity in
See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements. Concrete Floor Slabs Using in situ Probes
1.8 The values stated in inch-pound units are to be regarded F3191 Practice for Field Determination of Substrate Water
as standard. The values given in parentheses are mathematical Absorption (Porosity) for Substrates to Receive Resilient
conversions to SI units that are provided for information only Flooring
and are not considered standard.
NOTE 1—Specifications and test methods for cements and other related
1.9 This international standard was developed in accor- materials are found in ASTM Volume 04.01. Specifications and test
methods for concretes and related materials are found in ASTM Volume
dance with internationally recognized principles on standard-
04.02.
ization established in the Decision on Principles for the
2.2 ACI Guides:
Development of International Standards, Guides and Recom-
302.1R-06 Guide for Concrete Floor and Slab Construction
mendations issued by the World Trade Organization Technical
302.2R-06 Guide for Concrete Slabs that Receive Moisture-
Barriers to Trade (TBT) Committee.
Sensitive Flooring Materials
1 2
This practice is under the jurisdiction of ASTM Committee F06 on Resilient For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Floor Coverings and is the direct responsibility of Subcommittee F06.40 on contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Practices. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved Dec. 15, 2022. Published January 2023. Originally the ASTM website.
approved in 1981. Last previous edition approved in 2021 as F710–21. DOI: Available from American Concrete Institute (ACI), 38800 Country Club Dr.,
10.1520/F0710-22. Farmington Hills, MI 48331-3439, http://www.concrete.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F710 − 22
117R Standard Tolerances for Concrete Construction and shall be moisture-, mildew-, and alkali-resistant, and, for
Materials commercial installations, shall provide a minimum of 3000 psi
compressive strength after 28 days, when tested in accordance
2.3 Resilient Floor Covering Institute (RFCI):
with Test Method C109/C109M or Test Method C472, which-
Recommended Work Practices for the Removal of Resilient
ever is appropriate.
Floor Coverings
4.2.1 Joints such as expansion joints, isolation joints, or
2.4 Other Standards:
other moving joints in concrete slabs shall not be filled with
MASTERSPEC Guide Spec Section 03 30 00 “Cast-In-
patching compound or covered with resilient flooring. Consult
Place Concrete”
the resilient flooring manufacturer regarding the use of an
3. Terminology expansion joint covering system.
3.1 Definitions—For definitions of terms used in this
4.3 The surface of the floor shall be cleaned of all loose
practice, see Terminology F141.
material by scraping, brushing, vacuuming, or other methods,
or a combination thereof, as recommended by the resilient
3.2 Definitions of Terms Specific to This Standard:
flooring manufacturer, immediately before commencing instal-
3.2.1 design team, n—design professionals (including
lation of resilient flooring.
architects, designers, consultants, engineers and specifiers)
acting as a Team to provide planning, design, and construction
4.4 Many resilient floorings may not be installed over
administration services for a project; universally referred to as
concrete when residual asphalt adhesive residue is present.
the A/E (architect/engineer).
Consult the resilient flooring manufacturer’s written recom-
mendations concerning use of resilient flooring products in
3.2.2 mat, as in “mat test”,n—a sample of vapor-retardant
these situations.
sheet resilient floor finish material or equivalent.
3.2.3 moisture vapor emission, n—a term used by the
4.5 Concrete floors shall be smooth to prevent irregularities,
flooring industry in the U.S. to measure moisture emission
roughness, or other defects from telegraphing through the new
2 2
from concrete floors in lb/1000 ft · 24 h (56.51 µg/(s · m )
resilient flooring. The surface of concrete floors shall be flat to
using the anhydrous calcium chloride test.
within the equivalent of ⁄16 in. (3.9 mm) in 10 ft, (as described
in ACI 117R, or as measured by the method described in Test
4. General Guidelines
Method E1155 or any industry-recognized method specified)
and within the equivalent of 1/32 in. (0.8 mm) in 12 in.
4.1 The surface of concrete floors to receive resilient floor-
(305 mm). See X1.7 for more information regarding flatness
ing shall be dry, clean, smooth, and structurally sound. They
measurement methods.
shall be free of dust, solvent, paint, wax, oil, grease, residual
adhesive, adhesive removers, film-forming curing compounds,
4.6 Acclimation—Because of the role acclimation plays in a
silicate penetrating curing compounds, sealing, hardening, or
successful installation, most resilient flooring manufacturers
parting compounds, alkaline salts, excessive carbonation or
recommend or require that their flooring products, sundry
laitence, mold, mildew, and other foreign materials that might
supplies (adhesives, coatings, welding rods, underlayments,
affect the rate of moisture dissipation from the concrete, the
etc.) and the area to receive the resilient flooring are properly
adhesion of resilient flooring to the concrete or cause a
conditioned. Consult floor covering and sundry manufacturers
discoloration of the flooring from below. Non-chemical meth-
for appropriate ambient temperature, substrate surface tem-
ods for removal, such as abrasive cleaning or bead-blasting,
perature and ambient relative humidity ranges for the products
includingmethodsdescribedinPracticeD4259maybeusedon
to be installed and the geographic area where the job site is
existing slabs with deleterious residues.
located. When determining suitable installation conditions,
4.1.1 Warning—Hydraulic cement used in concrete con-
including dew point and potential surface condensation, suit-
struction may contain trace amounts of free crystalline silica.
able instrumentation shall be utilized to measure ambient
Prolonged exposure to airborne free crystalline silica may be a
temperature,percentofambientrelativehumidityandsubstrate
health hazard. Avoid actions that cause dust to become air-
surface temperature. General recommendations are for the
borne. Use local or general ventilation to control exposures
installation area and materials listed above to be maintained at
below applicable exposure limits.
a minimum of 65 °F (18.3 °C) and a maximum of 85 °F
4.1.2 Warning—See 7.1.1 and 7.1.2 for warnings regarding
(29.4 °C) for 48 h before, during and for 48 h after completion
asbestos and lead paint.
of the installation. Relative humidity level extremes should
4.2 Surface cracks, grooves, depressions, control joints or alsobeavoidedbecauseoftheirinfluenceonproperdryingand
curing of patching compounds and adhesives. General recom-
other non-moving joints, and other irregularities shall be filled
or smoothed with latex patching or underlayment compound mended humidity control level is between 35 – 55 %. If a
system other than the permanent HVAC source is utilized, it
recommended by the resilient flooring manufacturer for filling
or smoothing, or both. Patching or underlayment compound must provide proper control of both temperature and humidity
to recommended or specific levels for the appropriate time
duration.
Resilient Floor Covering Institute, 966 Hungerford Drive, Rockville, MD
4.6.1 Dew Point—All concrete slabs to receive resilient
20850.
flooring shall be evaluated for dew point regardless of age or
Available from MASTERSPEC,AIAMaster Systems, King Street Station, 225
Reinekers Lane, Suite 215, Alexandria, VA 22314-2875. grade level. For the required dew point limit, consult the
F710 − 22
written instructions from the manufacturer of the floor information. Floors containing lightweight aggregate or excess
covering(s), adhesive(s), patching/underlayment products, and water, and those which are allowed to dry from only one side,
if applicable, the moisture mitigation system. See Fig.A1.1 for such as concrete over a moisture vapor retarder or concrete on
dew point calculation chart. metal deck construction, may need a much longer drying time
4.6.2 If there is a conflict between the manufacturers’ and should not be covered with resilient flooring unless the
acceptable dew point temperature, it is the design team’s moisture vapor emission rate or the percentage of internal
responsibility to determine the appropriate level. relative humidity meets the manufacturer’s installation speci-
4.6.3 In the absence of written manufacturers’ guidelines, fications.
substrate surface must be at least 10 °F (5 °C) above dew point
6.2 The installation of a permanent below-slab vapor re-
with the ambient temperature rising. Example: If the ambient
tarder meeting the minimum performance requirements of
conditions are 70 °F and 65 % RH, the dew point is 57 °F.
SpecificationE1745isrequiredforallnewon-,orbelow-grade
Installation must not proceed unless the substrate surface
concrete floors over which resilient flooring materials are to be
temperature is at a minimum of 67 °F. See Fig. A1.1 for dew
installed. The use of such a material, provided that its integrity
point calculation chart. Dew point calculators are also freely
has not been compromised, retards the ingress of moisture
available on the Internet.
from the ground which otherwise can increase moisture levels
within the concrete which in turn can lead to flooring and
5. Testing Procedures
adhesiveproblems.Forresilientflooringinstallationsthevapor
5.1 Moisture Testing—All concrete slabs shall be tested for
retarder is to be installed in direct contact with the underside of
moisture regardless of age or grade level. For the preferred
the slab. For further information regarding below-slab vapor
moisture testing method and limits, consult the written instruc-
retarders refer to ACI 302.2R.
tions from the floor covering manufacturer, the adhesive
manufacturer, the patching/underlayment manufacturer, or
7. Preparation of Existing Concrete Floors
combination thereof. In the absence of manufacturer’s
7.1 The resilient flooring manufacturer shall be consulted
guidelines, refer to Table 1.
regarding the necessity of removal of old resilient flooring,
5.1.1 Consult the resilient flooring manufacturer, the adhe-
adhesive residue, paint, or other surface contaminants. If old
sive manufacturer, the underlayment manufacturer’s written
resilient flooring, paint, or adhesive residue is to be removed,
instructions, or combination thereof, for their acceptable test
follow 7.1.1 and 7.1.2:
methods. If these instructions are in conflict, the most stringent
7.1.1 Warning—Do not sand, dry sweep, dry scrape, drill,
requirements shall apply.
saw, beadblast, or mechanically chip or pulverize existing
5.2 pH and Alkalinity—See X1.4 for information about pH
resilient flooring, backing, lining felt, paint, asphaltic cutback
and alkalinity in concrete slabs.
adhesives, or other adhesives. These products may contain
asbestos fibers or crystalline silica. Avoid creating dust. Inha-
5.3 Substrate Water Absorption (Porosity)—All concrete
lation of such dust is a cancer and respiratory tract hazard.
slabs to receive resilient flooring shall be evaluated for
Smoking by individuals exposed to asbestos fibers greatly
substrate water absorption (porosity) regardless of age or grade
increases the risk of serious bodily harm. Unless positively
level. For the accepted criteria and method for determining
certain that the product is a nonasbestos-containing material,
substrate water absorption (porosity), consult the written in-
presume that it contains asbestos. Regulations may require that
structions from the manufacturer of the floor covering(s),
the material be tested to determine asbestos content. The
adhesive(s), patching/underlayment products, and if
Resilient Floor Covering Institute’s (RFCI’s) recommended
applicable, the moisture mitigation system.
work practices for removal of existing resilient floor coverings
5.3.1 If there is a conflict between the manufacturer’s
should be consulted for a defined set of instructions addressed
accepted criteria and method for determining substrate water
to the task of removing all resilient floor covering structures.
absorption (porosity), it is the design team’s responsibility to
7.1.2 Warning—Certain paints may contain lead. Exposure
determine the appropriate criteria and method.
to excessive amounts of lead dust presents a health hazard.
5.3.2 In the absence of written manufacturer’s guidelines,
Refer to applicable federal, state, and local laws and guidelines
substrate water absorption (porosity) shall be determined by
for hazard identification and abatement of lead-based paint
Practice F3191.
published by the U.S. Department of Housing and Urban
6. Preparation of New Concrete Floors
Development regarding appropriate methods for identifying
lead-based paint and removing such paint, and any licensing,
6.1 New concrete slabs shall be properly cured and dried or
certification, and training requirements for persons performing
treated before installation of resilient flooring. Drying time
lead abatement work.
before slabs are ready for moisture testing will vary depending
on atmospheric conditions and mix design. See X1.3 for more
7.2 Adhesive Removers—There are a number of commercial
adhesive removers that will properly remove adhesive residue
TABLE 1 ASTM Test Methods for Concrete Moisture Reading
Test Method Maximum Limit
2 2
Lead-Based Paint: Interim Guidelines for Hazard Identification and Abatement
F1869 3 lb/1000 ft (170 µg/m ) per 24 h
F2170 75 % in Public and Indian Housing, U.S. Department of Housing and Urban
Development, Washington, DC, 1990.
F710 − 22
from a subfloor, however, there are concerns that these prod- 8. Installation on Radiant Heated Floors
ucts may adversely effect the new adhesive and new floor
8.1 Most resilient flooring can be installed on radiant heated
covering. The Resilient Floor Covering Institute’s (RFCI’s)
slabs providing the maximum temperature of the surface of the
recommended work practices for removal of existing resilient
slab does not exceed 85 °F (29 °C) under any condition of use.
floor coverings and the resilient flooring manufacturer’s writ-
Consult the resilient flooring manufacturer for specific recom-
ten instructions should be consulted for a defined set of
mendations.
instructions which should be followed if existing adhesives
must be removed.
9. Keywords
7.3 Itistheprojectdesignteam’sresponsibilitytodetermine
9.1 adhesiveremovers;cement;concretefloors;installation;
the presence, quality, and location of a below-slab vapor
moisture; moisture vapor emissions; pH testing; preparation;
retarder. This information, along with the concrete slab mois-
resilient flooring; rubber; slabs
ture test results, will then be used by the design team to assess
the risk of a moisture-related flooring problem and determine
an appropriate approach.
ANNEX
(Mandatory Information)
A1. Dew Point
A1.1 Dew Point is the temperature at which moisture will A1.4 Example 2—If indoor air temperature is 75 °F and
condense on surfaces at a given Air Temperature and %
ambient relative humidity (RH) is 40%, the dew point would
Ambient Relative Humidity. As it relates to interior moisture
be 49 °F. If the substrate temperature measured at 60 °F, the
condensation, Dew Point is an important factor for ensuring
substratetemperaturewouldbe11°abovethedewpointandno
that proper conditions exist before and during substrate testing,
adjustments to the air temperature or ambient RH would be
preparations, and floor covering installations.
needed, so long as the installed products were capable of being
installed at: 75 °F air temperature, 40 % ambient relative
A1.2 Procedure for Calculating Dew Point—Starting at the
humidity (RH), and on a substrate surface of 60 °F tempera-
recorded Air Temperature reading in the left (green) column,
ture.
scroll directly across to the correct cell under the Ambient
Relative Humidity (blue row). The number where these two
A1.5 This information does not purport to cover all situa-
values intersect is the Dew Point.
tions that may be encountered in a field environment. Please
contact the flooring manufacturer, adhesive manufacturer, or
A1.3 Example 1—If the indoor air temperature is 80 °F and
combination thereof for any additional information if a ques-
the ambient relative humidity (RH) is 50%, the dew point
tion should arise.
would be 59 °F. If the substrate temperature measured at 63 °F,
the substrate temperature would be 4° above the dew point and
installation should not begin unless adjustments are made to
the air temperature or ambient relative humidity
F710 − 22
FIG. A1.1 Dew Point Calculation Chart
APPENDIXES
(Nonmandatory Information)
X1. CONCRETE COMPOSITION AND PRACTICES
X1.1 General—This brief information on concrete compo- (25 mm) or more of standard weight concrete, generally
sition and practices is provided to help specifiers, resilient 140 lb⁄ft (2241 kg/m ) or more, is used as a topping.
flooring installers, and resilient flooring manufacturers under-
X1.2 Water-Cement Ratio—The most important factor af-
stand the properties of concrete.Aconcrete slab is not an inert
fectingconcretepropertiesisthewater-cementratio.Thisisthe
substrate. It is a complex mixture of organic and inorganic
ratio of the mass of water to the mass of cement in a standard
substances whose properties and condition will affect the
volume of concrete. For a given concrete mix design, as the
performance of a floor covering placed on its surface. Surface
water-cement ratio is increased, most concrete properties are
flatness, strength, joints, alkalinity, permeability, and many
affected negatively. Of special interest to the floor covering
other concrete properties will have a significant effect on the
industry, compressive and flexural strengths are decreased,
long-term appearance and performance of resilient flooring.
permeability is increased, and drying times are lengthened.
X1.1.1 Concrete used for most floors is a mixture of
Moderate to moderately low water-cement ratios (0.40 to 0.45)
hydraulic cement, fine aggregate (sand), coarse aggregate
can be used to produce floor slabs that can easily be placed,
(stone), water and admixtures. In addition to these batch
finished, and dried, and which will have acceptable permeabil-
ingredients, chemical admixtures can be used to control the
ity to moisture. Floor slabs with water-cement ratios above
setting time, rate of strength development, workability, air
0.60 take an exceedingly long time to dry and cause adhesives
entrapment, and other properties of concrete. For example,
or floor coverings, or both, to fail due to high moisture
water-reducing admixtures can increase the slump of fresh
permeability.
concrete without adding additional water. Pozzolanic admix-
turessuchasflyashorgroundgranulatedblastfurnaceslagare X1.3 Curing and Drying New Concrete:
sometimes present as a partial replacement for the cement.
X1.3.1 Freshly placed concrete sets and gains strength by
X1.1.2 Lightweight concrete, less than 115 lb/ft the chemical reaction of water with the silicate and aluminate
(1841 kg⁄m ), may have such low compressive strength that it materials in the cement. As long as water is available during
is unsuitable for covering with resilient flooring unless 1 in. the planned curing period, the concrete will continue to gain
F710 − 22
strengthandde
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F710 − 21 F710 − 22
Standard Practice for
Preparing Concrete Floors to Receive Resilient Flooring
This standard is issued under the fixed designation F710; the number immediately following the designation indicates the year of original
adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A superscript
epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the determination of the acceptability of a concrete floor for the installation of resilient flooring.
1.2 This practice includes suggestions for the construction of a concrete floor to ensure its acceptability for installation of resilient
flooring.
1.3 This practice does not cover the adequacy of the concrete floor to perform its structural requirements.
1.4 This practice covers the necessary preparation of concrete floors prior to the installation of resilient flooring.
1.5 This practice does not supersede in any manner the resilient flooring or adhesive manufacturer’s written instructions. Consult
the individual manufacturer for specific recommendations.
1.6 Although carpet tiles, carpet, wood flooring, coatings, films, and paints aeare not specifically intended to be included in the
category of resilient floor coverings, the procedures included in this practice may be useful for preparing concrete floors to receive
such finishes.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use. See 4.1.1, 7.1.1, and 7.1.2 for specific warning statements.
1.8 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
C109/C109M Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50 mm] Cube Specimens)
C472 Test Methods for Physical Testing of Gypsum, Gypsum Plasters, and Gypsum Concrete
This practice is under the jurisdiction of ASTM Committee F06 on Resilient Floor Coverings and is the direct responsibility of Subcommittee F06.40 on Practices.
Current edition approved June 1, 2021Dec. 15, 2022. Published June 2021January 2023. Originally approved in 1981. Last previous edition approved in 20192021 as
ɛ1
F710–19–21. . DOI: 10.1520/F0710-21.10.1520/F0710-22.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F710 − 22
D4259 Practice for Preparation of Concrete by Abrasion Prior to Coating Application
D4263 Test Method for Indicating Moisture in Concrete by the Plastic Sheet Method
D4397 Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications
E1155 Test Method for Determining F Floor Flatness and F Floor Levelness Numbers
F L
E1486 Test Method for Determining Floor Tolerances Using Waviness, Wheel Path and Levelness Criteria
E1745 Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
F141 Terminology Relating to Resilient Floor Coverings
F710 Practice for Preparing Concrete Floors to Receive Resilient Flooring
F1869 Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
F2170 Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
F3191 Practice for Field Determination of Substrate Water Absorption (Porosity) for Substrates to Receive Resilient Flooring
NOTE 1—Specifications and test methods for cements and other related materials are found in ASTM Volume 04.01. Specifications and test methods for
concretes and related materials are found in ASTM Volume 04.02.
2.2 ACI Guides:
302.1R-06 Guide for Concrete Floor and Slab Construction
302.2R-06 Guide for Concrete Slabs that Receive Moisture-Sensitive Flooring Materials
117R Standard Tolerances for Concrete Construction and Materials
2.3 Resilient Floor Covering Institute (RFCI):
Recommended Work Practices for the Removal of Resilient Floor Coverings
2.4 Other Standards:
MASTERSPEC Guide Spec Section 03 30 00 “Cast-In-Place Concrete”
3. Terminology
3.1 Definitions—For definitions of terms used in this practice, see Terminology F141.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 design team, n—design professionals (including architects, designers, consultants, engineers and specifiers) acting as a Team
to provide planning, design, and construction administration services for a project; universally referred to as the A/E
(architect/engineer).
3.2.2 mat, as in “mat test”test”,—n—a sample of vapor-retardant sheet resilient floor finish material or equivalent.
3.2.3 moisture vapor emission—emission, n—a term used by the flooring industry in the U.S. to measure moisture emission from
2 2
concrete floors in lb/1000 ft · 24 h (56.51 μg/(s · m ) using the anhydrous calcium chloride test.
4. General Guidelines
4.1 The surface of concrete floors to receive resilient flooring shall be dry, clean, smooth, and structurally sound. They shall be
free of dust, solvent, paint, wax, oil, grease, residual adhesive, adhesive removers, film-forming curing compounds, silicate
penetrating curing compounds, sealing, hardening, or parting compounds, alkaline salts, excessive carbonation or laitence, mold,
mildew, and other foreign materials that might affect the rate of moisture dissipation from the concrete, the adhesion of resilient
flooring to the concrete or cause a discoloration of the flooring from below. Non-chemical methods for removal, such as abrasive
cleaning or bead-blasting, including methods described in Practice D4259 may be used on existing slabs with deleterious residues.
4.1.1 Warning—Hydraulic cement used in concrete construction may contain trace amounts of free crystalline silica. Prolonged
exposure to airborne free crystalline silica may be a health hazard. Avoid actions that cause dust to become airborne. Use local
or general ventilation to control exposures below applicable exposure limits.
4.1.2 Warning—See 7.1.1 and 7.1.2 for warnings regarding asbestos and lead paint.
Available from American Concrete Institute (ACI), 38800 Country Club Dr., Farmington Hills, MI 48331-3439, http://www.concrete.org.
Resilient Floor Covering Institute, 966 Hungerford Drive, Rockville, MD 20850.
Available from MASTERSPEC, AIA Master Systems, King Street Station, 225 Reinekers Lane, Suite 215, Alexandria, VA 22314-2875.
F710 − 22
4.2 Surface cracks, grooves, depressions, control joints or other non-moving joints, and other irregularities shall be filled or
smoothed with latex patching or underlayment compound recommended by the resilient flooring manufacturer for filling or
smoothing, or both. Patching or underlayment compound shall be moisture-, mildew-, and alkali-resistant, and, for commercial
installations, shall provide a minimum of 3000 psi compressive strength after 28 days, when tested in accordance with Test Method
C109/C109M or Test Method C472, whichever is appropriate.
4.2.1 Joints such as expansion joints, isolation joints, or other moving joints in concrete slabs shall not be filled with patching
compound or covered with resilient flooring. Consult the resilient flooring manufacturer regarding the use of an expansion joint
covering system.
4.3 The surface of the floor shall be cleaned of all loose material by scraping, brushing, vacuuming, or other methods, or a
combination thereof, as recommended by the resilient flooring manufacturer, immediately before commencing installation of
resilient flooring.
4.4 Many resilient floorings may not be installed over concrete when residual asphalt adhesive residue is present. Consult the
resilient flooring manufacturer’s written recommendations concerning use of resilient flooring products in these situations.
4.5 Concrete floors shall be smooth to prevent irregularities, roughness, or other defects from telegraphing through the new
resilient flooring. The surface of concrete floors shall be flat to within the equivalent of ⁄16 in. (3.9 mm) in 10 ft, (as described
in ACI 117R, or as measured by the method described in Test Method E1155 or any industry-recognized method specified) and
within the equivalent of 1/32 in. (0.8 mm) in 12 in. (305 mm). (305 mm). See X1.7 for more information regarding flatness
measurement methods.
4.6 Acclimation—Because of the role acclimation plays in a successful installation, most resilient flooring manufacturers
recommend or require that their flooring products, sundry supplies (adhesives, coatings, welding rods, underlayments, etc.) and the
area to receive the resilient flooring are properly conditioned. Consult floor covering and sundry manufacturers for appropriate
ambient temperature, substrate surface temperature and ambient relative humidity rangeranges for the products to be installed and
the geographic area where the job site is located. When determining suitable installation conditions, including dew point and
potential surface condensation, suitable instrumentation shall be utilized to measure ambient temperature, percent of ambient
relative humidity and substrate surface temperature. General recommendations are for the installation area and materials listed
above to be maintained at a minimum of 65 °F (18.3 °C) and a maximum of 85 °F (29.4 °C) (29.4 °C) for 48 h before, during
and for 48 h after completion of the installation. Relative humidity level extremes should also be avoided because of their influence
on proper drying and curing of patching compounds and adhesives. General recommended humidity control level is between 35
– 55 %. If a system other than the permanent HVAC source is utilized, it must provide proper control of both temperature and
humidity to recommended or specific levels for the appropriate time duration.
4.6.1 Dew Point—All concrete slabs to receive resilient flooring shall be evaluated for dew point regardless of age or grade level.
For the required dew point limit, consult the written instructions from the manufacturer of the floor covering(s), adhesive(s),
patching/underlayment products, and if applicable, the moisture mitigation system. See Fig. A1.1 for dew point calculation chart.
4.6.2 If there is a conflict between the manufacturers’ acceptable dew point temperature, it is the design team’s responsibility to
determine the appropriate level.
4.6.3 In the absence of written manufacturers’ guidelines, substrate surface must be at least 10 °F (5 °C) above dew point with
the ambient temperature rising. Example: If the ambient conditions are 70 °F and 65 % RH, the dew point is 57 °F. Installation
must not proceed unless the substrate surface temperature is at a minimum of 67 °F. See Fig. A1.1 for dew point calculation chart.
Dew point calculators are also freely available on the Internet.
5. Testing Procedures
5.1 Moisture Testing—All concrete slabs shall be tested for moisture regardless of age or grade level. For the preferred moisture
testing method and limits, consult the written instructions from the floor covering manufacturer, the adhesive manufacturer, the
patching/underlayment manufacturer, or combination thereof. In the absence of manufacturer’s guidelines, refer to Table 1.
F710 − 22
TABLE 1 ASTM Test Methods for Concrete Moisture Reading
Test Method Maximum Limit
2 2
F1869 3 lb/1000 ft (170 μg/m ) per 24 h
F2170 75 %
5.1.1 Consult the resilient flooring manufacturer, the adhesive manufacturer, the underlayment manufacturer’s written instructions,
or combination thereof, for their acceptable test methods. If these instructions are in conflict, the most stringent requirements shall
apply.
5.2 pH and Alkalinity—See X1.4 for information about pH and alkalinity in concrete slabs.
5.3 Substrate Water Absorption (Porosity)—All concrete slabs to receive resilient flooring shall be evaluated for substrate water
absorption (porosity) regardless of age or grade level. For the accepted criteria and method for determining substrate water
absorption (porosity), consult the written instructions from the manufacturer of the floor covering(s), adhesive(s), patching/
underlayment products, and if applicable, the moisture mitigation system.
5.3.1 If there is a conflict between the manufacturer’s accepted criteria and method for determining substrate water absorption
(porosity), it is the design team’s responsibility to determine the appropriate criteria and method.
5.3.2 In the absence of written manufacturer’s guidelines, substrate water absorption (porosity) shall be determined by Practice
F3191.
6. Preparation of New Concrete Floors
6.1 New concrete slabs shall be properly cured and dried or treated before installation of resilient flooring. Drying time before
slabs are ready for moisture testing will vary depending on atmospheric conditions and mix design. See X1.3 for more information.
Floors containing lightweight aggregate or excess water, and those which are allowed to dry from only one side, such as concrete
over a moisture vapor retarder or concrete on metal deck construction, may need a much longer drying time and should not be
covered with resilient flooring unless the moisture vapor emission rate or the percentage of internal relative humidity meets the
manufacturer’s installation specifications.
6.2 The installation of a permanent below-slab vapor retarder meeting the minimum performance requirements of Specification
E1745 is required for all new on-, or below-grade concrete floors over which resilient flooring materials are to be installed. The
use of such a material, provided that its integrity has not been compromised, retards the ingress of moisture from the ground which
otherwise can increase moisture levels within the concrete which in turn can lead to flooring and adhesive problems. For resilient
flooring installations the vapor retarder is to be installed in direct contact with the underside of the slab. For further information
regarding below-slab vapor retarders refer to ACI 302.2R.
7. Preparation of Existing Concrete Floors
7.1 The resilient flooring manufacturer shall be consulted regarding the necessity of removal of old resilient flooring, adhesive
residue, paint, or other surface contaminants. If old resilient flooring, paint, or adhesive residue is to be removed, follow 7.1.1 and
7.1.2:
7.1.1 Warning—Do not sand, dry sweep, dry scrape, drill, saw, beadblast, or mechanically chip or pulverize existing resilient
flooring, backing, lining felt, paint, asphaltic cutback adhesives, or other adhesives. These products may contain asbestos fibers or
crystalline silica. Avoid creating dust. Inhalation of such dust is a cancer and respiratory tract hazard. Smoking by individuals
exposed to asbestos fibers greatly increases the risk of serious bodily harm. Unless positively certain that the product is a
nonasbestos-containing material, presume that it contains asbestos. Regulations may require that the material be tested to determine
asbestos content. The Resilient Floor Covering Institute’s (RFCI’s) recommended work practices for removal of existing resilient
floor coverings should be consulted for a defined set of instructions addressed to the task of removing all resilient floor covering
structures.
7.1.2 Warning—Certain paints may contain lead. Exposure to excessive amounts of lead dust presents a health hazard. Refer to
applicable federal, state, and local laws and guidelines for hazard identification and abatement of lead-based paint published by
F710 − 22
the U.S. Department of Housing and Urban Development regarding appropriate methods for identifying lead-based paint and
removing such paint, and any licensing, certification, and training requirements for persons performing lead abatement work.
7.2 Adhesive Removers—There are a number of commercial adhesive removers that will properly remove adhesive residue from
a subfloor, however, there are concerns that these products may adversely effect the new adhesive and new floor covering. The
Resilient Floor Covering Institute’s (RFCI’s) recommended work practices for removal of existing resilient floor coverings and
the resilient flooring manufacturer’s written instructions should be consulted for a defined set of instructions which should be
followed if existing adhesives must be removed.
7.3 It is the project design team’s responsibility to determine the presence, quality, and location of a below-slab vapor retarder.
This information, along with the concrete slab moisture test results, will then be used by the design team to assess the risk of a
moisture-related flooring problem and determine an appropriate approach.
8. Installation on Radiant Heated Floors
8.1 Most resilient flooring can be installed on radiant heated slabs providing the maximum temperature of the surface of the slab
does not exceed 85 °F (29 °C) under any condition of use. Consult the resilient flooring manufacturer for specific
recommendations.
9. Keywords
9.1 adhesive removers; cement; concrete floors; installation; moisture; moisture vapor emissions; pH testing; preparation; resilient
flooring; rubber; slabs
ANNEX
(Mandatory Information)
A1. Dew Point
A1.1 Dew Point is the temperature at which moisture will condense on surfaces at a given Air Temperature and % Ambient
Relative Humidity. As it relates to interior moisture condensation, Dew Point is an important factor for ensuring that proper
conditions exist before and during substrate testing, preparations, and floor covering installations.
A1.2 Procedure for Calculating Dew Point—Starting at the recorded Air Temperature reading in the left (green) column, scroll
directly across to the correct cell under the Ambient Relative Humidity (blue row). The number where these two values intersect
is the Dew Point.
A1.3 Example 1—If the indoor air temperature is 80 °F and the ambient relative humidity (RH) is 50%, the dew point would be
59 °F. If the substrate temperature measured at 63 °F, the substrate temperature would be 4° above the dew point and installation
should not begin unless adjustments are made to the air temperature or ambient relative humidity
A1.4 Example 2—If indoor air temperature is 75 °F and ambient relative humidity (RH) is 40%, the dew point would be 49 °F.
If the substrate temperature measured at 60 °F, the substrate temperature would be 11° above the dew point and no adjustments
to the air temperature or ambient RH would be needed, so long as the installed products were capable of being installed at: 75 °F
air temperature, 40 % ambient relative humidity (RH), and on a substrate surface of 60 °F temperature.
Lead-Based Paint: Interim Guidelines for Hazard Identification and Abatement in Public and Indian Housing, U.S. Department of Housing and Urban Development,
Washington, DC, 1990.
F710 − 22
A1.5 This information does not purport to cover all situations that may be encountered in a field environment. Please contact the
flooring manufacturer, adhesive manufacturer, or combination thereof for any additional information if a question should arise.
APPENDIXES
(Nonmandatory Information)
X1. CONCRETE COMPOSITION AND PRACTICES
X1.1 General—This brief information on concrete composition and practices is provided to help specifiers, resilient flooring
installers, and resilient flooring manufacturers understand the properties of concrete. A concrete slab is not an inert substrate. It
is a complex mixture of organic and inorganic substances whose properties and condition will affect the performance of a floor
covering placed on its surface. Surface flatness, strength, joints, alkalinity, permeability, and many other concrete properties will
have a significant effect on the long-term appearance and performance of resilient flooring.
X1.1.1 Concrete used for most floors is a mixture of hydraulic cement, fine aggregate (sand), coarse aggregate (stone), water and
admixtures. In addition to these batch ingredients, chemical admixtures can be used to control the setting time, rate of strength
development, workability, air entrapment, and other properties of concrete. For example, water-reducing admixtures can increase
the slump of fresh concrete without adding additional water. Pozzolanic admixtures such as fly ash or ground granulated blast
furnace slag are sometimes present as a partial replacement for the cement.
3 3
X1.1.2 Lightweight concrete, less than 115 lb/ft (1841 (1841 kg kg/m⁄m ), may have such low compressive strength that it is
unsuitable for covering with resilient flooring unless 1 in. (25 mm) (25 mm) or more of standard weight concrete, generally 140
3 3
140 lb lb/ft⁄ft (2241 kg/m ) or more, is used as a topping.
FIG. A1.1 Dew Point Calculation Chart
F710 − 22
X1.2 Water-Cement Ratio—The most important factor affecting concrete properties is the water-cement ratio. This is the ratio of
the mass of water to the mass of cement in a standard volume of concrete. For a given concrete mix design, as the water-cement
ratio is increased, most concrete properties are affected negatively. Of special interest to the floor covering industry, compressive
and flexural strengths are decreased, permeability is increased, and drying times are lengthened. Moderate to moderately low
water-cement ratios (0.40 to 0.45) can be used to produce floor slabs that can easily be placed, finished, and dried, and which will
have acceptable permeability to moisture. Floor slabs with water-cement ratios above 0.60 take an exceedingly long time to dry
and cause adhesives or floor coverings, or both, to fail due to high moisture permeability.
X1.3 Curing and Drying New Concrete:
X1.3.1 Freshly placed concrete sets and gains strength by the chemical reaction of water with the silicate and aluminate materials
in the cement. As long as water is available during the planned curing period, the concrete will continue to gain strength and
decrease its permeability. Various ways concrete is cured i
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...