SIGNIFICANCE AND USE
4.1 Designers and installers of waterproofing systems may consult this guide for a discussion of important elements of the use of cold liquid-applied waterproofing membranes and associated elements of construction. This guide is not intended to serve as a specification for waterproofing installation.  
4.2 Long-term performance of waterproofing with a separate wearing course is important because of the substantial difficulty in determining the location of leakage and in removing overlying materials to make repairs.  
4.3 Refer to Guide C1471/C1471M for application on below grade walls and vertical surfaces.
SCOPE
1.1 This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane that meets the criteria in Specification C836/C836M, in a waterproofing system subject to hydrostatic pressure for building decks over occupied space where the membrane is covered with a separate protective wearing course.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    14 pages
    English language

SIGNIFICANCE AND USE
4.1 The failure to correct membrane defects during and as soon as possible after its installation can cause premature failure of the membrane. Problems include design deficiencies, faulty application of the membrane system, and damage by subsequent trades.4 Roof designs incorporating a waterproof membrane under overburden such as a vegetative roof, insulation layer, wear-course, or topping slab greatly exacerbate the problem of leak locating.  
4.2 This guide describes methods for using electric conductance testing to locate breaches in waterproof membranes.5 The methods described include testing procedures designed to provide a part of the construction quality control of membrane installations.  
4.3 The methods described in this guide may also be used for integrity or forensic testing of existing waterproof membranes; specific limitations apply.  
4.4 The electric conductance methods described in this guide require a conductive substrate under the membrane to serve as a ground return path for the test currents. In roof assemblies where the membrane is installed over electric insulating material such as insulating foam or a protection board, or both, the electric path to any conductive deck is interrupted. The situation can be remedied by placing a conductive material directly under the membrane. The conductive material provides the return path for the test currents.
SCOPE
1.1 This guide describes standard procedures for using electrical conductance measurement methods to locate leaks in exposed or covered waterproof membranes.  
1.2 This guide addresses the need for a general technical description of the current methods and procedures that are used to test and verify the integrity of waterproof membranes.  
1.3 This guide is not intended to replace visual, infrared, or other methods of inspection. It is to be used in conjunction with other methods of roof inspection when specified.  
1.4 This guide recommends that the leak location equipment, procedures, and survey parameters used are calibrated to meet established minimum leak detection sensitivity. The leak detection sensitivity calibration should be verified on a regular basis according to the manufacturer’s recommendations.  
1.5 Leak location surveys can be used on waterproofing membranes installed in roofs, plaza decks, pools, water features, covered reservoirs, and other waterproofing applications.  
1.6 The procedures are applicable for membranes made of materials such as polyethylene, polypropylene, polyvinyl chloride, bituminous material, and other electrically insulating materials.  
1.7 This guide provides a general description of the equipment and methods for locating membrane breaches using electric conductance. Refer to the manufacturer’s instructions for the proper operation and use of the equipment described in this guide.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide is intended to be used in the selection and installation of chemical grout to seal leaks in concrete walls, floors, and ceilings. The procedure described in this guide focuses on the injection of through-wall cracks, but may be adapted to cold joints, control joints, voids associated with penetrations, and other voids contributing to water intrusion through concrete elements. This guide is intended to assist the building owner, owner’s representative, architect, engineer, contractor, or authorized inspector, or combinations thereof, during the selection, specification, or installation, or combinations thereof, of chemical grout for waterproofing repair.  
4.2 Prior to attempting any repair, it is important for all parties to have a clear and mutual understanding of the limitations of the repair and the iterative nature of the process. Injection of chemical grout does not affect the source of a leak. The repair obstructs the infiltration of water at a specific location only. The flow of water will be diverted elsewhere, and it is common for water to subsequently appear at a different location that was previously dry. A successful campaign at a given location can significantly reduce the amount of water infiltration, but may not fully prevent leakage. Given the nature of the materials and application technique, and depending on the conditions, the repairs should be periodically monitored and additional repair installations may be required.  
4.3 This guide is applicable to installations at below-grade walls and slabs. At above-grade elements, temperature variation on a daily or seasonal basis may lead to significant or more frequent changes, or both, in the width of a crack or joint. The use of injected chemical grout may be appropriate for many above-grade applications, but this guide does not specifically address installation of grout in dynamic cracks or joints.  
4.4 Cracks in below-grade walls may be a sign of structural distress. Prior to the i...
SCOPE
1.1 This guide describes the selection of materials, installation methods, and inspection required for sealing leaks at cracks in concrete building walls and slabs using chemical grout. The process discussed in this guide is a waterproofing repair in which voids in a concrete element are sealed with a reactive solution, installed by pressurized injection through drilled or surface-mounted ports.  
1.2 This guide does not address the use of chemical grout for waterproofing by curtain grouting or injection into preplaced permeable waterstop tubes. Injection of masonry elements presents additional factors beyond the scope of this guide. This guide does not address the use of injectable materials for structural repairs or for geotechnical applications such as soil stabilization.  
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide provides general procedures, information, guidelines, and precautions for the application of heat welded modified bituminous waterproofing systems used as part of a horizontal waterproofing system.  
4.2 This guide is not all-inclusive and is intended only to supplement detailed instructions from designers and system manufacturers.  
4.3 The horizontal deck or substrate referred to in this guide is reinforced cast-in-place structural concrete.
SCOPE
1.1 This guide presents application recommendations for the heat welding installation of multi-ply Styrene Butadiene Styrene (SBS) and Atactic Polypropylene (APP) modified bituminous systems to new, reinforced, cast-in-place structural concrete used as part of a horizontal waterproofing system over occupied spaces of buildings where covered by a separate wearing course.  
1.2 For the purpose of this guide, the substrate shall be structurally sound, sloped to drain, able to accept the weight of the membrane and other system materials, and meet the local building code requirements. Similarly, all components of the waterproofing system are assumed to comply with any federal, state, and local environmental regulations that may be in effect at the time of installation. Expansion joints, insulation, drainage layers, filter sheets, overburden, and the wearing surfaces are beyond the scope of this guide.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    4 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide provides information and guidelines for the selection and installation of drainage systems media that are in conjunction with waterproofing systems. This guide is intended to be used in conjunction with Guides C898/C898M, C981, C1471/C1471M, D5898/D5898M, and D6622/D6622M and to provide guidelines for the total waterproofing and drainage system.
SCOPE
1.1 This guide makes recommendations for the selection and application of prefabricated drainage media used in conjunction with waterproofing systems on horizontal and vertical surfaces. Drainage media considered include rigid and semi-rigid insulation boards and rigid materials including plastics. This guide considers drainage media as it relates to the performance of the waterproofing system, so its primary focus is draining water away from the membrane. This guide does not cover in detail other aspects or functions of drainage system performance such as efficiency of soil dewatering. The scope of this guide does not cover other drainage media including gravel and filter fabric systems that can be constructed. The scope of this guide does not cover drainage materials or drainage system designs used for vegetative roof systems. Vegetative roof systems require specialized designs.  
1.2 The committee with jurisdiction over this standard is not aware of any other comparable standards published by other organizations.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard may involve hazardous materials, operations and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    10 pages
    English language

SCOPE
1.1 This specification describes the required properties and test methods for a one or two-component, cold liquid-applied elastomeric-type membrane comprised of silyl-terminated polyether polymer, silyl-terminated polyurethane polymer, or a blend of the two polymers for waterproofing building decks and walls subjected to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.
Note 1: See Guides C898/C898M and C1471/C1471M for proper application of membrane.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    4 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is used to indicate a waterproofing membrane's ability to maintain its integrity while bridging a preexisting crack in the substrate at low ambient temperatures, when the membrane is least likely to be flexible.
SCOPE
1.1 This test method covers a laboratory procedure for determining the ability of a waterproofing membrane to bridge a crack in the substrate.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide is intended to be used in the selection and installation of waterstops in cast-in-place concrete construction. This guide is intended to assist the building owner, owner’s representative, architect, engineer, contractor, and/or authorized inspector during the specification and installation of waterstops.  
4.2 This guide is applicable to cast-in-place concrete construction. The use of this guide may not be appropriate for installation of waterstops in other types of concrete construction, including but not limited to, pneumatically applied (that is, shotcrete) and precast concrete construction.
SCOPE
1.1 This guide covers the use of waterstops within cast-in-place concrete construction. Waterstops are generally placed within static, non-moving construction joints in concrete to close off the joint to water, which may be under significant hydrostatic pressure. They are used as part of the overall waterproofing strategy for a building or other structure. Expansion and other types of moving joints may require the use of waterstops, which can accommodate the anticipated movement of the structure and are beyond the scope of this guide.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents: therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    4 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is used as a screening tool to determine the hydrostatic pressure to which a liquid-applied waterproofing membrane may be subjected without failing when stretched over a crack in the substrate. This test method discriminates between a membrane that is very resistant to hydrostatic pressure and one that is not. Because of the variability inherent in this test method, it is not recommended that this test method be used to set a numerical standard for hydrostatic pressure resistance. No prediction of durability at lower hydrostatic pressures can be made when using the results of this test method.
SCOPE
1.1 This test method describes a laboratory procedure for determining the resistance of a waterproofing membrane to hydrostatic pressure.  
1.2 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.3 There are no ISO standards similar or equivalent to this ASTM standard.  
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide outlines general installation procedures and precautions for the application of sodium bentonite needle-punched geotextile waterproofing systems.  
5.2 This guide is not all inclusive and is intended only to supplement detailed drawings and specifications from designers and the installation guidelines of manufacturers. Manufacturers of some of the systems addressed by this guide require proprietary products and special procedures not described in this guide. Manufacturers’ guidelines and details applicable for each site construction condition encountered on a project should therefore be considered in the application of this guide.
SCOPE
1.1 This guide covers general installation guidelines of waterproofing membranes produced as a composite of sodium bentonite contained within two interlocked needle-punched geotextiles for designers to consider when developing project-specific drawings and specifications. This guide covers construction applications where the waterproofing is applied to the positive side of below-grade cast-in-place concrete foundation walls, both backfilled and support of excavation (SOE) construction, and under concrete pressure slabs. This guide does not cover plaza deck construction applications, either split-slab construction or pavers on pedestals, or vegetated green roof waterproofing applications.  
1.2 This guide does not cover sodium bentonite waterproofing membranes produced with a corrugation paper carrier, bentonite bonded to a geomembrane, and spray-applied bentonite systems.  
1.3 For the purpose of this guide, concrete is assumed to be cast-in-place with a surface profile as recommended in Guide D5295/D5295M, consolidated in accordance with applicable guidelines in ACI 309, structurally sound, able to accept the weight of anticipated loads, and meets the local building code requirements. All components of the waterproofing system are assumed to comply with any federal, state, and local environmental regulations that may be in effect at the time of installation. Expansion joints, insulation, and drainage layers are beyond the scope of this guide.  
1.4 This guide does not cover sodium bentonite geotextile membranes installed on below-grade foundation walls and slabs constructed with masonry materials, precast concrete, or pneumatically applied concrete (that is, shotcrete).  
1.5 The values stated in SI units are to be regarded as standard. The unit values given in parentheses are for reference information only.  
1.6 Different sodium bentonite geotextile membranes have different materials of composition and construction which can affect physical properties. The procedures contained in this guide, therefore, may not be universally applicable to all sodium bentonite geotextile membranes under all field conditions.  
1.7 This guide does not purport to assign responsibilities of quality assurance or quality control. Specific quality assurance and quality control items should be addressed in project specifications and contract documents.  
1.8 This guide does not purport to include requirements for warranties associated with the waterproofing materials or installation.  
1.9 This guide does not purport to include all detailing techniques to address various conditions that can be encountered on construction projects.  
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.11 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    7 pages
    English language

ABSTRACT
This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane subject to intermittent hydrostatic pressure in a waterproofing system intended for installation on cast-in-place concrete vertical surfaces. Typical uses for these systems include planters and foundation walls with drainage system and others. The major components to be considered for a below grade building wall waterproofing system are the structural wall or substrate to be waterproofed, waterproofing membrane, membrane protection, and drainage system. The following considerations are detailed: (1) compatibility; (2) continuity; (3) substrate: strength, density and moisture content, admixtures, release and curing agents, finish, dryness, and joints; (4) waterproofing membrane: adhesion to substrate, terminations, and penetrations; (5) treatment and design of reinforced, unreinforced, and expansion joints; (6) protection course: impact resistance, compatibility, ancillary provisions, thermal insulation, and drainage composites; and (7) drainage system: drainage course, backfill, and drainage pipes. Illustrations of footing, treatment of vertical corners, and pipe penetration for the waterproofing system and treatment of reinforced and unreinforced joints are given.
SCOPE
1.1 This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane that meets the performance criteria specified in Specification C836/C836M, subject to intermittent hydrostatic pressure in a waterproofing system intended for installation on vertical cast-in-place concrete surfaces.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

ABSTRACT
This specification describes the required properties and test methods for cold liquid-applied elastomeric-type membranes for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill. After application by spreading or spraying, the membrane materials shall cure to form an elastomeric film capable of maintaining a seal against liquid water. Materials shall undergo appropriate tests and conform accordingly to the following requirements: hardness; weight loss; nonvolatile matter content; low temperature crack bridging; film thickness; adhesion-in-peel after water immersion; extensibility after heat aging; and storage stability.
SCOPE
1.1 This specification describes the required properties and test methods for a cold liquid-applied elastomeric-type membrane, one- or two-component, for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.  
Note 1: See Guides C898/C898M and C1471/C1471M for proper application of membrane.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    3 pages
    English language

SIGNIFICANCE AND USE
6.1 This test method is used to determine a membrane's ability to bridge a crack that forms after the membrane has been applied and allowed to cure.
SCOPE
1.1 This test method describes a laboratory procedure for determining extensibility for one- or two-component cold liquid-applied elastomeric waterproofing membranes.  
1.2 The values stated in SI units are to be regarded as the standard. The values in parentheses are for information only.  
1.3 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
4.1 A waterproofing membrane should maintain its watertight integrity for the life of the building in a continuously or intermittently moist environment and may be subject to continuous or intermittent hydrostatic pressure. It should resist chemicals that can harm the membrane and root growth. This guide lists minimum performance attributes required of waterproofing membranes applied to below-grade walls. Products not previously used as waterproofing membrane materials require additional tests beyond the scope of this guide. This guide is not intended for use on in-service waterproofing materials. Waterproofing membranes and other components should conform to ASTM product standards, if available.  
4.2 Limitations—Prior to use and in service, waterproofing may be exposed to a variety of conditions so no one test will provide evaluations related to performance for all exposures. Neither will all tests be necessary in all evaluations for specific exposures.
SCOPE
1.1 This guide lists test methods intended to establish a minimum level of acceptable performance attributes for reinforced or laminated waterproofing membranes applied to below-grade walls.  
1.2 This guide does not include cementitious, integral, or bentonite waterproofing systems.  
1.3 This guide does not include membranes applied under slabs on grade or on suspended slabs below grade or applied to soil retaining systems, water containment structures, or tunnels.  
1.4 It is not possible to establish a precise correlation between laboratory tests on waterproofing membranes and performance attributes after installation due to variations in chemicals in the soil, design, material, and installation.  
1.5 The values stated in either inch-pound or SI units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide describes the techniques used to test for watertightness of waterproofing installations on horizontal services having a slope not greater than 20 mm/m (2 % slope) (1/4 in./ft). See also ACI 515.  
5.2 The structural capacity of the substrate to which the waterproofing system is to be installed should be reviewed by a licensed structural engineer to verify that the loads associated with the use of procedures described in this guide do not exceed code and design restrictions. Lateral loads will be imposed on curbs or walls used for containment of the water during the test procedures and their effect should be accounted for. The effects of equipment, planters, or other movable objects present within the test area should be considered.
Note 1: Potable water weighs approximately 1000 kg/cubic m (62.3 lb per cubic ft) at 22 °C (71.6 °F) or 1 g/cm2/cm depth (5.19 lb/ft2 per in. depth).  
5.3 This guide describes a procedure to test for watertightness of waterproofing installations under ponded water with a short-term hydrostatic head measuring not more than 100 mm (4 in.).
Note 2: Increasing the amount of water forming a hydrostatic head beyond 100 mm (4 in.) of water may be considered provided the impact of increased loads on the substrate has been reviewed and approved by a licensed structural engineer.  
5.4 For the purposes of this guide, the installation of the waterproofing membrane and flashing should be completed and the materials fully cured. Manufacturers should specify a minimum time period for materials to cure prior to performing flood test, however, no testing should be performed during the first 24 h following installation of system materials (48 h min if materials are installed at a time when ambient temperatures are below 10 °C (50 °F)).  
5.5 The additional loads imposed upon the structure during the test period will affect the deflection of structural items. The effects shall be analyzed by a licensed structural engineer prior to p...
SCOPE
1.1 This guide provides the user with a method for testing the watertightness of waterproofing installations applied to horizontal surfaces having a slope not greater than 20 mm/m (2 % slope) (1/4 in. per ft).  
1.2 This guide is intended for waterproofing installation on parking garages and plaza deck type applications over habitable spaces or on elevated structures, but is not intended for use on building roofing systems. Applicable waterproofing membrane installations that may be tested using this guide are fully adhered or bonded sheet membranes, liquid or fluid-applied membranes, or loose-laid sheet membranes.  
1.3 The procedures presented here are not intended for use on those waterproofing installation applications that are for long-term water storage or continuously submerged environments, such as swimming pools, fountains, tank liners with hydrostatic pressure, or water storage units (storage period greater than 48 h).  
1.4 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    5 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide illustrates general details for below-grade and plaza waterproofing. It serves as a guide that will enable the designer to prepare complete waterproofing details for each specific condition that occurs on a project.
SCOPE
1.1 This guide covers details for typical conditions encountered in adhered sheet waterproofing on below-grade structures and plazas.  
1.2 This guide does not cover liquid-applied waterproofing.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    16 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide outlines general procedures for the storage and application of semi-rigid protection board to below-grade and below wearing surface waterproofing. The proper application is necessary to prevent damage to the waterproofing membrane during backfilling, paving, or other construction operations, as well as to minimize the effects of soil stresses.  
4.2 This guide is intended to supplement instructions from designers and manufacturers.
SCOPE
1.1 This guide lists minimum application and installation requirements for semi-rigid protection board when used as protection for below-grade or below wearing surface (like plaza decks) waterproofing.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 8.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    2 pages
    English language

SIGNIFICANCE AND USE
3.1 This test method tests the hydrostatic resistance of a waterproofing membrane and can be used to compare the hydrostatic resistance of waterproofing membranes.  
3.2 No correlation has been established between the performance in this test method and that in the field.
SCOPE
1.1 This test method measures the hydrostatic resistance of a waterproofing membrane under controlled laboratory conditions. This test method is not suitable for systems that rely on confinement of the seams by the backfill since backfill is not part of this test method.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    3 pages
    English language
  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide outlines general procedures and precautions for the application of fully adhered hot-applied built-up reinforced waterproofing systems.  
5.2 This guide is not all inclusive and is intended only to supplement detailed instructions from designers, and the recommendations of manufacturers. Manufacturers of some of the systems addressed by this guide require proprietary products and special procedures not described in this guide. Manufacturers' recommendations should therefore be considered in the application of this guide.  
5.3 For design guidelines, consult Guide C981.
SCOPE
1.1 This guide covers the minimum installation recommendations for fully adhered, hot-applied reinforced waterproofing systems on vertical and low-slope (plaza deck) surfaces.  
1.2 For the purpose of this guide, the substrate is assumed to be concrete or masonry, structurally sound, able to accept the weight of anticipated loads, and meets the local building code requirements. Similarly, all components of the waterproofing system are assumed to comply with any federal, state, and local environmental regulations that may be in effect at the time of installation. Expansion joints, insulation, drainage layers, and overburden are beyond the scope of this guide.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory requirements prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    4 pages
    English language
  • Guide
    4 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide provides information and guidelines for the selection of components and the design of a built-up bituminous membrane waterproofing system in building deck construction. Where the state of the art is such that criteria for particular conditions are not established or have numerous variables that require consideration, applicable portions of design considerations, Sections 5 – 16, serve as reference and guidance for selection by the designer of the system.
SCOPE
1.1 This guide describes the design of fully adhered built-up bituminous membrane waterproofing systems for plaza deck and promenade construction over occupied spaces of buildings where covered by a separate wearing course.  
1.2 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.  
1.3 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    18 pages
    English language
  • Guide
    18 pages
    English language

SIGNIFICANCE AND USE
4.1 The failure to correct membrane breaches during and after its installation can cause premature failure of the membrane and damage to the structure. Root causes may include design deficiencies, faulty application of the membrane system, product failure, material incompatibility, and damage by other trades. Roof designs incorporating a waterproof membrane under overburden must be tested for breaches before overburden is installed.  
4.2 This practice describes a low voltage (less than 50 V as defined by NFPA 70), dual sweep, scanning method using electronic leak detection to locate breaches in waterproof membranes. The method described includes testing procedures designed to provide a part of the quality assurance of roofing and waterproofing membranes.  
4.3 The methods described in this practice may also be used for forensic testing of existing roofing and waterproofing membranes; however, specific limitations apply that are described later.
SCOPE
1.1 This practice describes standard procedures for using an electronic scanning system to locate membrane breaches on both horizontal and vertical surfaces to locate potential leaks in exposed roofing and waterproofing membranes.  
1.2 This practice addresses the need for a detailed technical description of a scanning method and procedures that are used to test and verify the integrity of membranes.  
1.3 This practice is not intended to replace visual or other methods of inspection. It is to be used in conjunction with other methods of roof inspection when specified.  
1.4 This practice requires that the detection and location equipment, procedures, and survey parameters used are calibrated to meet established minimum leak detection sensitivity. The detection sensitivity calibration must be verified on a regular basis using the manufacturer’s procedures to assure maximum confidence in the results.  
1.5 Scanning surveys can be used on membranes installed on roofs, plaza decks, pools, water features, covered reservoirs, and other roofing and waterproofing applications.  
1.6 This practice is applicable for membranes made of electrically insulating materials and is used on certain moderately conductive membranes (see Test Method D4496).  
1.7 This practice provides a description of the scanning method and equipment for locating membrane breaches using electric conductance and is intended to be used in conjunction with the manufacturer’s instructions for the proper operation and use of the equipment.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Standard
    8 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide outlines general procedures for the storage and application of various prefabricated sheets made using modified bituminous materials and intended for use as below-grade and below-wearing-surface waterproofing.  
4.2 The substrate used for applications described in this guide shall be concrete or masonry.  
4.3 This application consists of a prefabricated reinforced modified bituminous sheet applied to a suitable substrate using a bituminous-based, cold-applied adhesive or mastic. Application rates given are typical for such installations.  
4.4 This guide is intended to supplement instructions from designers and manufacturers.
SCOPE
1.1 This guide lists application and installation requirements for fully adhered, cold-applied, prefabricated modified bituminous membrane waterproofing systems for below-grade or below-wearing-surface (such as plaza decks) vertical or horizontal applications.  
1.2 For the purposes of this application guide, the substrate is assumed to be structurally sound, sloped to drain (if new construction), and meeting the local building code requirements. Similarly, the system components are assumed to comply with all federal, state, and local requirements in effect at the time of installation.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This guide may involve hazardous materials, operations, and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory requirements prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    3 pages
    English language

SIGNIFICANCE AND USE
3.1 The success of a waterproofing application depends on, among other things, the type, smoothness, and cleanliness of the concrete surface being coated. This guide describes conditioning or repairing of the concrete surface by the removal or other constructive modification of those surface defects that can affect the performance of the waterproofing system. It covers surface preparation by mechanical, chemical, and blast cleaning methods in order to provide good adhesion between the waterproofing system and the concrete as well as the effect and control of various surface contaminants. It also addresses the evaluation of concrete moisture content to ensure optimal initial bond. (See also ACI 515.)  
3.2 This guide is not intended to offer guidelines for the selection of a suitable waterproofing system; the use of specific application techniques; or the design and installation of flashing, terminations, expansion joint details, etc. (For definitions of terms, see Terminology D1079.)  
3.3 This guide is not intended to offer guidelines for the control of water vapor drive through the concrete which could affect long term performance of the bond between the concrete and waterproofing.  
3.4 The recommended procedures described herein are minimums; the waterproofing materials manufacturer may require more strict or specific procedures for the preparation of concrete surfaces for the application of the manufacturer's specific system.
SCOPE
1.1 This guide provides recommendations for the preparation of concrete surfaces prior to the application of adhered (bonded) waterproofing.  
1.2 This guide is directed primarily toward installations of new concrete, but is also applicable for existing concrete installations. (See also ACI 116 and ACI 546.)  
1.3 This guide does not apply to loose laid systems, bentonite systems, lead, or the like.  
1.4 This guide does not apply to applications involving insulating concrete.  
1.5 This guide does not apply to applications involving lightweight structural concrete.
Note 1: Once installed, it is difficult to visually identify the difference between normal weight and lightweight concrete. It is recommended that a review of contract documents, concrete batch or delivery tickets or similar effort be performed to identify the concrete type.  
1.6 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.8 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

ABSTRACT
This specification covers the manufacture, testing, and physical requirements of two classes of asphalt based protection board used for protecting the integrity of below grade or below wearing surface waterproofing. Class A is made with asphalt saturated organic felt on the bottom and a coated or saturated non-woven glass felt on top, while Class B is made with glass fabrics both top and bottom. The boards shall be sampled for testing, and each class shall conform accordingly to specified individual values of the following physical properties: nominal thickness; puncture strength; water absorption; asphalt content; and resistance to decay.
SCOPE
1.1 This specification covers an asphalt based protection board used for protecting the integrity of below grade or below wearing surface waterproofing. The protection board protects the waterproofing system from backfill, surfacing, construction activities, and weathering conditions prior to backfilling or applying surfacing.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    2 pages
    English language

SIGNIFICANCE AND USE
4.1 The failure to correct membrane defects during and as soon as possible after its installation can cause premature failure of the membrane. Problems include design deficiencies, faulty application of the membrane system, and damage by subsequent trades.4 Roof designs incorporating a waterproof membrane under overburden such as a vegetative roof, insulation layer, wear-course, or topping slab greatly exacerbate the problem of leak locating.  
4.2 This guide describes methods for using electric conductance testing to locate breaches in waterproof membranes.5 The methods described include testing procedures designed to provide a part of the construction quality control of membrane installations.  
4.3 The methods described in this guide may also be used for integrity or forensic testing of existing waterproof membranes; specific limitations apply.  
4.4 The electric conductance methods described in this guide require a conductive substrate under the membrane to serve as a ground return path for the test currents. In roof assemblies where the membrane is installed over electric insulating material such as insulating foam or a protection board, or both, the electric path to any conductive deck is interrupted. The situation can be remedied by placing a conductive material directly under the membrane. The conductive material provides the return path for the test currents.
SCOPE
1.1 This guide describes standard procedures for using electrical conductance measurement methods to locate leaks in exposed or covered waterproof membranes.  
1.2 This guide addresses the need for a general technical description of the current methods and procedures that are used to test and verify the integrity of waterproof membranes.  
1.3 This guide is not intended to replace visual, infrared, or other methods of inspection. It is to be used in conjunction with other methods of roof inspection when specified.  
1.4 This guide recommends that the leak location equipment, procedures, and survey parameters used are calibrated to meet established minimum leak detection sensitivity. The leak detection sensitivity calibration should be verified on a regular basis according to the manufacturer’s recommendations.  
1.5 Leak location surveys can be used on waterproofing membranes installed in roofs, plaza decks, pools, water features, covered reservoirs, and other waterproofing applications.  
1.6 The procedures are applicable for membranes made of materials such as polyethylene, polypropylene, polyvinyl chloride, bituminous material, and other electrically insulating materials.  
1.7 This guide provides a general description of the equipment and methods for locating membrane breaches using electric conductance. Refer to the manufacturer’s instructions for the proper operation and use of the equipment described in this guide.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

ABSTRACT
This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane subject to intermittent hydrostatic pressure in a waterproofing system intended for installation on cast-in-place concrete vertical surfaces. Typical uses for these systems include planters and foundation walls with drainage system and others. The major components to be considered for a below grade building wall waterproofing system are the structural wall or substrate to be waterproofed, waterproofing membrane, membrane protection, and drainage system. The following considerations are detailed: (1) compatibility; (2) continuity; (3) substrate: strength, density and moisture content, admixtures, release and curing agents, finish, dryness, and joints; (4) waterproofing membrane: adhesion to substrate, terminations, and penetrations; (5) treatment and design of reinforced, unreinforced, and expansion joints; (6) protection course: impact resistance, compatibility, ancillary provisions, thermal insulation, and drainage composites; and (7) drainage system: drainage course, backfill, and drainage pipes. Illustrations of footing, treatment of vertical corners, and pipe penetration for the waterproofing system and treatment of reinforced and unreinforced joints are given.
SCOPE
1.1 This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane that meets the performance criteria specified in Specification C836/C836M, subject to intermittent hydrostatic pressure in a waterproofing system intended for installation on vertical cast-in-place concrete surfaces.  
1.2 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

ABSTRACT
This specification describes the required properties and test methods for cold liquid-applied elastomeric-type membranes for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill. After application by spreading or spraying, the membrane materials shall cure to form an elastomeric film capable of maintaining a seal against liquid water. Materials shall undergo appropriate tests and conform accordingly to the following requirements: hardness; weight loss; nonvolatile matter content; low temperature crack bridging; film thickness; adhesion-in-peel after water immersion; extensibility after heat aging; and storage stability.
SCOPE
1.1 This specification describes the required properties and test methods for a cold liquid-applied elastomeric-type membrane, one- or two-component, for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.  
Note 1: See Guide C898/C898M and Guide C1471/C1471M for proper application of membrane.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide outlines general procedures and precautions for the application of fully adhered hot-applied built-up reinforced waterproofing systems.  
5.2 This guide is not all inclusive and is intended only to supplement detailed instructions from designers, and the recommendations of manufacturers. Manufacturers of some of the systems addressed by this guide require proprietary products and special procedures not described in this guide. Manufacturers' recommendations should therefore be considered in the application of this guide.  
5.3 For design guidelines, consult Guide C981.
SCOPE
1.1 This guide covers the minimum installation recommendations for fully adhered, hot-applied reinforced waterproofing systems on vertical and low-slope (plaza deck) surfaces.  
1.2 For the purpose of this guide, the substrate is assumed to be concrete or masonry, structurally sound, able to accept the weight of anticipated loads, and meets the local building code requirements. Similarly, all components of the waterproofing system are assumed to comply with any federal, state, and local environmental regulations that may be in effect at the time of installation. Expansion joints, insulation, drainage layers, and overburden are beyond the scope of this guide.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory requirements prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    4 pages
    English language
  • Guide
    4 pages
    English language

SIGNIFICANCE AND USE
4.1 Designers and installers of waterproofing systems may consult this guide for a discussion of important elements of the use of cold liquid-applied waterproofing membranes and associated elements of construction. This guide is not intended to serve as a specification for waterproofing installation.  
4.2 Long-term performance of waterproofing with a separate wearing course is important because of the substantial difficulty in determining the location of leakage and in removing overlying materials to make repairs.  
4.3 Refer to Guide C1471/C1471M for application on below grade walls and vertical surfaces.
SCOPE
1.1 This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane that meets the criteria in Specification C836/C836M, in a waterproofing system subject to hydrostatic pressure for building decks over occupied space where the membrane is covered with a separate protective wearing course.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    14 pages
    English language
  • Guide
    14 pages
    English language
  • Guide
    14 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide is intended to be used in the selection and installation of chemical grout to seal leaks in concrete walls, floors, and ceilings. The procedure described in this guide focuses on the injection of through-wall cracks, but may be adapted to cold joints, control joints, voids associated with penetrations, and other voids contributing to water intrusion through concrete elements. This guide is intended to assist the building owner, owner’s representative, architect, engineer, contractor, or authorized inspector, or combinations thereof, during the selection, specification, or installation, or combinations thereof, of chemical grout for waterproofing repair.  
4.2 Prior to attempting any repair, it is important for all parties to have a clear and mutual understanding of the limitations of the repair and the iterative nature of the process. Injection of chemical grout does not affect the source of a leak. The repair obstructs the infiltration of water at a specific location only. The flow of water will be diverted elsewhere, and it is common for water to subsequently appear at a different location that was previously dry. A successful campaign at a given location can significantly reduce the amount of water infiltration, but may not fully prevent leakage. Given the nature of the materials and application technique, and depending on the conditions, the repairs should be periodically monitored and additional repair installations may be required.  
4.3 This guide is applicable to installations at below-grade walls and slabs. At above-grade elements, temperature variation on a daily or seasonal basis may lead to significant or more frequent changes, or both, in the width of a crack or joint. The use of injected chemical grout may be appropriate for many above-grade applications, but this guide does not specifically address installation of grout in dynamic cracks or joints.  
4.4 Cracks in below-grade walls may be a sign of structural distress. Prior to the i...
SCOPE
1.1 This guide describes the selection of materials, installation methods, and inspection required for sealing leaks at cracks in concrete building walls and slabs using chemical grout. The process discussed in this guide is a waterproofing repair in which voids in a concrete element are sealed with a reactive solution, installed by pressurized injection through drilled or surface-mounted ports.  
1.2 This guide does not address the use of chemical grout for waterproofing by curtain grouting or injection into preplaced permeable waterstop tubes. Injection of masonry elements presents additional factors beyond the scope of this guide. This guide does not address the use of injectable materials for structural repairs, or for geotechnical applications such as soil stabilization.  
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide provides information and guidelines for the selection and installation of drainage systems media that are in conjunction with waterproofing systems. This guide is intended to be used in conjunction with Guides C898/C898M, C981, C1471/C1471M, D5898/D5898M, and D6622 and to provide guidelines for the total waterproofing and drainage system.
SCOPE
1.1 This guide makes recommendations for the selection and application of prefabricated drainage media used in conjunction with waterproofing systems on horizontal and vertical surfaces. Drainage media considered include rigid and semi-rigid insulation boards and rigid materials including plastics. This guide considers drainage media as it relates to the performance of the waterproofing system, so its primary focus is draining water away from the membrane. This guide does not cover in detail other aspects or functions of drainage system performance such as efficiency of soil dewatering. The scope of this guide does not cover other drainage media including gravel and filter fabric systems that can be constructed. The scope of this guide does not cover drainage materials or drainage system designs used for vegetative roof systems. Vegetative roof systems require specialized designs.  
1.2 The committee with jurisdiction over this standard is not aware of any other comparable standards published by other organizations.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard may involve hazardous materials, operations and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    10 pages
    English language
  • Guide
    10 pages
    English language
  • Guide
    10 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is used to indicate a waterproofing membrane's ability to maintain its integrity while bridging a preexisting crack in the substrate at low ambient temperatures, when the membrane is least likely to be flexible.
SCOPE
1.1 This test method covers a laboratory procedure for determining the ability of a waterproofing membrane to bridge a crack in the substrate.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Standard
    3 pages
    English language
  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This test method is used as a screening tool to determine the hydrostatic pressure to which a liquid-applied waterproofing membrane may be subjected without failing when stretched over a crack in the substrate. This test method discriminates between a membrane that is very resistant to hydrostatic pressure and one that is not. Because of the variability inherent in this test method, it is not recommended that this test method be used to set a numerical standard for hydrostatic pressure resistance. No prediction of durability at lower hydrostatic pressures can be made when using the results of this test method.
SCOPE
1.1 This test method describes a laboratory procedure for determining the resistance of a waterproofing membrane to hydrostatic pressure.  
1.2 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.3 There are no ISO standards similar or equivalent to this ASTM standard.  
1.4 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Standard
    3 pages
    English language
  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide provides information and guidelines for the selection and installation of drainage systems media that are in conjunction with waterproofing systems. This guide is intended to be used in conjunction with Guides C898, C981, C1471, D5898, and D6622 and to provide guidelines for the total waterproofing and drainage system.
SCOPE
1.1 This guide makes recommendations for the selection and application of prefabricated drainage media used in conjunction with waterproofing systems on horizontal and vertical surfaces. Drainage media considered include rigid and semi-rigid insulation boards and rigid materials including plastics. The scope of this guide does not cover other drainage media including gravel and filter fabric systems that can be constructed. The scope of this guide does not cover drainage materials or drainage system designs used for vegetative roof systems. Vegetative roof systems require specialized designs.  
1.2 The committee with jurisdiction over this standard is not aware of any other comparable standards published by other organizations.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard may involve hazardous materials, operations and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    10 pages
    English language
  • Guide
    10 pages
    English language

ABSTRACT
This specification describes the required properties and test methods for cold liquid-applied elastomeric-type membranes for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill. After application by spreading or spraying, the membrane materials shall cure to form an elastomeric film capable of maintaining a seal against liquid water. Materials shall undergo appropriate tests and conform accordingly to the following requirements: hardness; weight loss; nonvolatile matter content; low temperature crack bridging; film thickness; adhesion-in-peel after water immersion; extensibility after heat aging; and storage stability.
SCOPE
1.1 This specification describes the required properties and test methods for a cold liquid-applied elastomeric-type membrane, one- or two-component, for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.  
Note 1: See Guide C898 and Guide C1471 for proper application of membrane.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide provides general procedures, information, guidelines, and precautions for the application of heat welded modified bituminous waterproofing systems used as part of a horizontal waterproofing system.  
4.2 This guide is not all-inclusive and is intended only to supplement detailed instructions from designers and system manufacturers.  
4.3 The horizontal deck or substrate referred to in this guide is reinforced cast-in-place structural concrete.
SCOPE
1.1 This guide presents application recommendations for the heat welding installation of multi-ply Styrene Butadiene Styrene (SBS) and Atactic Polypropylene (APP) modified bituminous systems to new, reinforced, cast in place structural concrete used as part of a horizontal waterproofing system over occupied spaces of buildings where covered by a separate wearing course.  
1.2 For the purpose of this guide, the substrate shall be structurally sound, sloped to drain, able to accept the weight of the membrane and other system materials, and meet the local building code requirements. Similarly, all components of the waterproofing system are assumed to comply with any federal, state, and local environmental regulations that may be in effect at the time of installation. Expansion joints, insulation, drainage layers, filter sheets, overburden, and the wearing surfaces are beyond the scope of this guide.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    4 pages
    English language
  • Guide
    4 pages
    English language

SIGNIFICANCE AND USE
4.1 The failure to correct membrane defects during and as soon as possible after its installation can cause premature failure of the membrane. Problems include design deficiencies, faulty application of the membrane system, and damage by subsequent trades.4 Roof designs incorporating a waterproof membrane under overburden such as a vegetative roof, insulation layer, wear-course, or topping slab greatly exacerbate the problem of leak locating.  
4.2 This guide describes methods for using electric conductance testing to locate breaches in waterproof membranes.5 The methods described include testing procedures designed to provide a part of the construction quality control of membrane installations.  
4.3 The methods described in this guide may also be used for integrity or forensic testing of existing waterproof membranes, specific limitations apply.  
4.4 The electric conductance methods described in this guide require a conductive substrate under the membrane to serve as a ground return path for the test currents. In roof assemblies where the membrane is installed over electric insulating material such as insulating foam or a protection board, or both, the electric path to any conductive deck is interrupted. The situation can be remedied by placing a conductive material directly under the membrane. The conductive material provides the return path for the test currents.
SCOPE
1.1 This guide describes standard procedures for using electrical conductance measurement methods to locate leaks in exposed or covered waterproof membranes.  
1.2 This guide addresses the need for a general technical description of the current methods and procedures that are used to test and verify the integrity of waterproof membranes.  
1.3 This guide is not intended to replace visual, infrared, or other methods of inspection. It is to be used in conjunction with other methods of roof inspection when specified.  
1.4 This guide recommends that the leak location equipment, procedures, and survey parameters used are calibrated to meet established minimum leak detection sensitivity. The leak detection sensitivity calibration should be verified on a regular basis according to the manufacturer’s recommendations.  
1.5 Leak location surveys can be used on waterproofing membranes installed in roofs, plaza decks, pools, water features, covered reservoirs and other waterproofing applications.  
1.6 The procedures are applicable for membranes made of materials such as polyethylene, polypropylene, polyvinyl chloride, bituminous material, and other electrically insulating materials.  
1.7 This guide provides a general description of the equipment and methods for locating membrane breaches using electric conductance. Refer to the manufacturer’s instructions for the proper operation and use of the equipment described in this guide.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    7 pages
    English language

SIGNIFICANCE AND USE
4.1 A waterproofing membrane should maintain its watertight integrity for the life of the building in a continuously or intermittently moist environment and may be subject to continuous or intermittent hydrostatic pressure. It should resist chemicals that can harm the membrane and root growth. This guide lists minimum performance attributes required of waterproofing membranes applied to below-grade walls. Products not previously used as waterproofing membrane materials require additional tests beyond the scope of this guide. This guide is not intended for use on in-service waterproofing materials. Waterproofing membranes and other components should conform to ASTM product standards, if available.  
4.2 Limitations—Prior to use and in service, waterproofing may be exposed to a variety of conditions so no one test will provide evaluations related to performance for all exposures. Neither will all tests be necessary in all evaluations for specific exposures.
SCOPE
1.1 This guide lists test methods intended to establish a minimum level of acceptable performance attributes for reinforced or laminated waterproofing membranes applied to below-grade walls.  
1.2 This guide does not include cementitious, integral, or bentonite waterproofing systems.  
1.3 This guide does not include membranes applied under slabs on grade or on suspended slabs below grade or applied to soil retaining systems, water containment structures, or tunnels.  
1.4 It is not possible to establish a precise correlation between laboratory tests on waterproofing membranes and performance attributes after installation due to variations in chemicals in the soil, design, material, and installation.  
1.5 The values stated in either inch-pound or SI units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    3 pages
    English language

SCOPE
1.1 This guide describes the use of a high solids content, cold liquid-applied elastomeric waterproofing membrane that meets the performance criteria specified in Specification C836, subject to intermittent hydrostatic pressure in a waterproofing system intended for installation on vertical cast-in-place concrete surfaces.  
1.2 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    6 pages
    English language
  • Guide
    6 pages
    English language

SIGNIFICANCE AND USE
3.1 The success of a waterproofing application depends on, among other things, the type, smoothness, and cleanliness of the concrete surface being coated. This guide describes conditioning or repairing of the concrete surface by the removal or other constructive modification of those surface defects that can affect the performance of the waterproofing system. It covers surface preparation by chemical and blast cleaning methods in order to provide good adhesion between the waterproofing system and the concrete as well as the effect and control of various surface contaminants. It also addresses the evaluation of concrete moisture content to ensure optimal initial bond. (See also ACI 515.)  
3.2 This guide is not intended to offer guidelines for the selection of a suitable waterproofing system; the use of specific application techniques; or the design and installation of flashing, terminations, expansion joint details, etc. (For definitions of terms, see Terminology D1079.)  
3.3 This guide is not intended to offer guidelines for the control of water vapor drive through the concrete which could affect long term performance of the bond between the concrete and waterproofing.  
3.4 The recommended procedures described herein are minimums; the waterproofing materials manufacturer may require more strict or specific procedures for the preparation of concrete surfaces for the application of the manufacturer's specific system.
SCOPE
1.1 This guide provides recommendations for the preparation of concrete surfaces prior to the application of adhered (bonded) waterproofing.  
1.2 This guide is directed primarily toward installations of new concrete, but is also applicable for existing concrete installations. (See also ACI 116 and ACI 546.)  
1.3 This guide does not apply to loose laid systems, bentonite systems, lead, or the like.  
1.4 This guide does not apply to applications involving insulating concrete.  
1.5 This guide does not apply to applications involving lightweight structural concrete.  
1.6 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    5 pages
    English language
  • Guide
    5 pages
    English language

SIGNIFICANCE AND USE
3.1 This test method tests the hydrostatic resistance of a waterproofing membrane and can be used to compare the hydrostatic resistance of waterproofing membranes.  
3.2 No correlation has been established between the performance in this test method and that in the field.
SCOPE
1.1 This test method measures the hydrostatic resistance of a waterproofing membrane under controlled laboratory conditions. This test method is not suitable for systems that rely on confinement of the seams by the backfill since backfill is not part of this test method.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Standard
    3 pages
    English language
  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide outlines general procedures for the storage and application of semi-rigid protection board to below grade and below wearing surface waterproofing. The proper application is necessary to prevent damage to the waterproofing membrane during backfilling, paving, or other construction operations, as well as to minimize the effects of soil stresses.  
4.2 This guide is intended to supplement instructions from designers and manufacturers.
SCOPE
1.1 This guide lists minimum application and installation requirements for semi-rigid protection board when used as protection for below grade or below wearing surface (like plaza decks) waterproofing.  
1.2 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this guide to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statement, see Section 8.

  • Guide
    2 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide illustrates general details for below grade and plaza waterproofing. It serves as a guide that will enable the designer to prepare complete waterproofing details for each specific condition that occurs on a project.
SCOPE
1.1 This guide covers details for typical conditions encountered in adhered sheet waterproofing on below grade structures and plazas.  
1.2 This guide does not cover liquid applied waterproofing.  
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.

  • Guide
    16 pages
    English language

SIGNIFICANCE AND USE
6.1 This test method is used to determine a membrane's ability to bridge a crack that forms after the membrane has been applied and allowed to cure.
SCOPE
1.1 This test method describes a laboratory procedure for determining extensibility for one- or two-component cold liquid-applied elastomeric waterproofing membranes.  
1.2 The values stated in SI units are to be regarded as the standard. The values in parentheses are for information only.  
1.3 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Standard
    3 pages
    English language

SIGNIFICANCE AND USE
5.1 This guide describes the techniques used to test for watertightness of waterproofing installations on horizontal services having a slope not greater than 20 mm/m (2 % slope) (1/4 in./ft). See also ACI 515.  
5.2 The structural capacity of the substrate to which the waterproofing system is to be installed should be reviewed by a licensed structural engineer to verify that the loads associated with the use of procedures described in this guide do not exceed code and design restrictions. Lateral loads will be imposed on curbs or walls used for containment of the water during the test procedures and their effect should be accounted for. The effects of equipment, planters, or other movable objects present within the test area should be considered.Note 1—Potable water weighs approximately 1000 kg/cubic m (62.3 lb per cubic ft) at 22°C (71.6°F) or 1 g/cm2/cm depth (5.19 lbs/ft 2  per in. depth).  
5.3 This guide describes a procedure to test for watertightness of waterproofing installations under ponded water with a short-term hydrostatic head measuring not more than 100 mm (4 in.).Note 2—Increasing the amount of water forming a hydrostatic head beyond 100 mm (4 in.) of water may be considered provided the impact of increased loads on the substrate has been reviewed and approved by a licensed structural engineer.  
5.4 For the purposes of this guide, the installation of the waterproofing membrane and flashing should be completed and the materials fully cured. Manufacturers should specify a minimum time period for materials to cure prior to performing flood test, however, no testing should be performed during the first 24 h following installation of system materials (48 h min if materials are installed at a time when ambient temperatures are below 10°C (50°F)).  
5.5 The additional loads imposed upon the structure during the test period will affect the deflection of structural items. The effects shall be analyzed by a licensed structural engineer prior to placemen...
SCOPE
1.1 This guide provides the user with a method for testing the watertightness of waterproofing installations applied to horizontal surfaces having a slope not greater than 20 mm/m (2% slope) (1/4 in. per ft).  
1.2 This guide is intended for waterproofing installation on parking garages and plaza deck type applications over habitable spaces or on elevated structures, but is not intended for use on building roofing systems. Applicable waterproofing membrane installations that may be tested using this guide are fully adhered or bonded sheet membranes, liquid or fluid applied membranes, or loose laid sheet membranes.  
1.3 The procedures presented here are not intended for use on those waterproofing installation applications that are for long-term water storage or continuously submerged environments, such as swimming pools, fountains, tank liners with hydrostatic pressure, or water storage units (storage period greater than 48 h).  
1.4 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.  
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    5 pages
    English language

SIGNIFICANCE AND USE
4.1 This guide provides information and guidelines for the selection of components and the design of a built-up bituminous membrane waterproofing system in building deck construction. Where the state of the art is such that criteria for particular conditions are not established or have numerous variables that require consideration, applicable portions of Design Considerations, Sections 5-16, serve as reference and guidance for selection by the designer of the system.
SCOPE
1.1 This guide describes the design of fully adhered built-up bituminous membrane waterproofing systems for plaza deck and promenade construction over occupied spaces of buildings where covered by a separate wearing course.  
1.2 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.  
1.3 The committee with jurisdiction over this standard is not aware of any comparable standards published by other organizations.  
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    18 pages
    English language

ABSTRACT
This specification describes the required properties and test methods for cold liquid-applied elastomeric-type membranes for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill. After application by spreading or spraying, the membrane materials shall cure to form an elastomeric film capable of maintaining a seal against liquid water. Materials shall undergo appropriate tests and conform accordingly to the following requirements: hardness; weight loss; nonvolatile matter content; low temperature crack bridging; film thickness; adhesion-in-peel after water immersion; extensibility after heat aging; and storage stability.
SCOPE
1.1 This specification describes the required properties and test methods for a cold liquid-applied elastomeric-type membrane, one- or two-component, for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.
Note 1—See Guide C898 and Guide C1471 for proper application of membrane.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

SCOPE
1.1 This specification covers flexible sheet made from ethylene-propylene-diene terpolymer (EPDM) intended for use in single-ply roofing membranes exposed to the weather. The tests and property limits used to characterize the sheet are values to ensure minimum quality for the intended use. The sheet may be non-reinforced, fabric- or scrim-reinforced, or fabric-backed vulcanized rubber sheet.
1.2 In-place roof system design criteria, such as fire resistance, field seaming strength, material compatibility, and uplift resistance, among others, are factors that must be considered but are beyond the scope of this specification.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.4 This standard may involve hazardous materials, operations, and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    4 pages
    English language

SIGNIFICANCE AND USE
This guide provides information and guidelines for the selection and installation of drainage systems media that are in conjunction with waterproofing systems. This guide is intended to be used in conjunction with Guides C898, C981, C1471, D5898, and D6622 and to provide guidelines for the total waterproofing and drainage system.
SCOPE
1.1 This guide makes recommendations for the selection and application of prefabricated drainage media used in conjunction with waterproofing systems on horizontal and vertical surfaces. Drainage media considered include rigid and semi-rigid insulation boards and rigid materials including plastics. The scope of this guide does not cover other drainage media including gravel and filter fabric systems that can be constructed. The scope of this guide does not cover drainage materials or drainage system designs used for vegetative roof systems. Vegetative roof systems require specialized designs.
1.2 The committee with jurisdiction over this standard is not aware of any other comparable standards published by other organizations.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.4 This standard may involve hazardous materials, operations and equipment. This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Guide
    9 pages
    English language

ABSTRACT
This specification describes the required properties and test methods for cold liquid-applied elastomeric-type membranes for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill. After application by spreading or spraying, the membrane materials shall cure to form an elastomeric film capable of maintaining a seal against liquid water. Materials shall undergo appropriate tests and conform accordingly to the following requirements: hardness; weight loss; nonvolatile matter content; low temperature crack bridging; film thickness; adhesion-in-peel after water immersion; extensibility after heat aging; and storage stability.
SCOPE
1.1 This specification describes the required properties and test methods for a cold liquid-applied elastomeric-type membrane, one- or two-component, for waterproofing building decks and walls subject to hydrostatic pressure in building areas to be occupied by personnel, vehicles, or equipment. This specification applies only to a membrane system that will be covered with a separate wearing course, traffic course, or backfill.
Note 1—See Guide C898 and Guide C1471 for proper application of membrane.  
1.2 There are no ISO standards similar or equivalent to this ASTM standard.
1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

  • Technical specification
    3 pages
    English language
  • Technical specification
    3 pages
    English language

Frequently Asked Questions

D08.22 is a Technical Committee within ASTM International. It is named "Waterproofing and Dampproofing Systems". This committee has published 111 standards.

D08.22 develops ASTM standards in the area of Information technology. Currently, there are 111 published standards from this technical committee.

ASTM is a standardization organization that develops and publishes standards to support industry, commerce, and regulatory requirements.

A Technical Committee (TC) in ASTM is a group of experts responsible for developing international standards in a specific technical area. TCs are composed of national member body delegates and work through consensus to create standards that meet global industry needs. Each TC may have subcommittees (SCs) and working groups (WGs) for specialized topics.

Loading...