Devices to prevent pollution by backflow of potable water - Air gap with non-circular overflow (unrestricted) - Family A - Type B

This document specifies the characteristics and the requirements of air gap with non-circular overflow (unrestricted) Family A, Type B for nominal flow velocity not exceeding 3 m/s. Air gaps are devices for protection of potable water in water installations from pollution by backflow. This document applies to air gaps in factory-assembled products and to constructed air gaps in situ and specifies requirements and methods to verify and ensure compliance with this document during normal working use.
The fluid in the receiving vessel is assumed to have similar properties to water. Where this is not the case, additional care or tests could be required to verify the efficacy of the solution in practical use.
The AB device is intended to be used in potable water installations according to EN 806 (all parts).

Sicherungseinrichtungen zum Schutz des Trinkwassers gegen Verschmutzung durch Rückfließen - Freier Auslauf mit nicht kreisförmigem Überlauf (uneingeschränkt) - Familie A - Typ B

Dieses Dokument legt die Eigenschaften und Anforderungen für freie Ausläufe mit nicht kreisförmigem Überlauf (uneingeschränkt), Familie A, Typ B, für Nenn-Fließgeschwindigkeiten bis 3 m/s fest. Freie Ausläufe sind Sicherungseinrichtungen zum Schutz des Trinkwassers vor Verunreinigungen durch Rückfließen in Trinkwasser-Installationen. Dieses Dokument ist anwendbar für freie Ausläufe von werkseitig hergestellten Bauteilen sowie für vor Ort gebaute freie Ausläufe und legt Anforderungen und Verfahren fest, um im normalen Betrieb eine Übereinstimmung mit diesem Dokument zu überprüfen und sicherzustellen.
Es wird angenommen, dass die Flüssigkeit in dem zu versorgenden Behälter ähnliche Eigenschaften wie die Wasserversorgung aufweist. Ist dies nicht der Fall, könnten besondere Sorgfalt oder zusätzliche Prüfungen erforderlich sein, um die Wirksamkeit der Lösung im praktischen Einsatz sicherzustellen.
Die AB Einrichtung ist für die Verwendung in Trinkwasser-Installationen nach EN 806 (alle Teile) bestimmt.

Dispositifs de protection contre la pollution de l’eau potable par retour - Surverse avec trop-plein non-circulaire (totale) - Famille A - Type B

Ce document spécifie les caractéristiques et les exigences relatives aux surverses avec trop-plein non circulaire (totale) de la Famille A, Type B, pour des débits nominaux n’excédant pas 3 m/s. Les surverses sont des dispositifs destinés à protéger l’eau potable des installations d’eau contre la pollution par retour. Ce document s’applique à la fois aux surverses faisant partie de produits assemblés en usine et à celles réalisées sur site. Il spécifie les exigences et les méthodes permettant de vérifier et d’assurer la conformité au présent document dans des conditions de service normal.
Le fluide dans le réceptacle est supposé posséder des propriétés similaires à celles de l'eau. Lorsque ce n’est pas le cas, il peut se révéler nécessaire de redoubler d’attention ou de mener des essais supplémentaires afin de vérifier l’efficacité de la solution en pratique.
Le dispositif AB est destiné à être utilisé dans des installations d’eau potable conformément à l’EN 806 (toutes les parties).

Naprave za varovanje pred onesnaženjem pitne vode zaradi povratnega toka - Prosti iztok s prelivom nekrožne oblike (neoviran) - Družina A - Tip B

Ta dokument določa značilnosti in zahteve zračne reže z nekrožnim presežkom (neomejen) družine A, tipa B za nazivno hitrost pretoka, ki ne presega 3 m/s. Zračne reže so naprave za zaščito pitne vode v vodnih napeljavah pred onesnaženjem zaradi povratnega toka. Ta dokument se nanaša na zračne reže v tovarniško sestavljenih izdelkih in sestavljene zračne reže na mestu uporabe ter določa zahteve in metode za preverjanje in zagotavljanje skladnosti s tem dokumentom med običajno delovno rabo.
Tekočina v posodi za zbiranje naj bi imela enake lastnosti kot dovod vode. Če temu ni tako, je morda potrebna dodatna pozornost oziroma je treba izvesti preskuse za preverjanje učinkovitosti raztopine pri praktični uporabi.

General Information

Status
Published
Public Enquiry End Date
20-Jan-2022
Publication Date
10-Apr-2023
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
06-Apr-2023
Due Date
11-Jun-2023
Completion Date
11-Apr-2023

Relations

Effective Date
01-May-2023

Overview

EN 13077:2023 - Devices to prevent pollution by backflow of potable water: Air gap with non-circular overflow (unrestricted) - Family A, Type B (CEN) specifies design, performance and verification requirements for air gaps with non‑circular overflows used to protect potable water installations against backflow. It applies to both factory‑assembled devices and constructed in situ arrangements for nominal flow velocities up to 3 m/s. The document assumes the receiving fluid has properties similar to water; where it does not, additional verification is needed. The device is intended for potable water installations per EN 806.

Key Topics and Requirements

  • Scope and designation: Covers Family A, Type B air gaps with non‑circular overflow; designation includes name, EN reference, family/type and maximum flow rate (e.g., “Air gap, EN 13077, Family A, Type B, 14 l/min”).
  • Performance limits: Nominal flow velocity ≤ 3 m/s; tests performed at ambient temperature unless otherwise specified.
  • Geometric parameters:
    • Air gap distance (A) and height between spillover and critical water level (h) are fundamental for validation.
    • Overflow height (Ow) requirement: Ow ≥ 2D + h and never < 20 mm for single inlets (for multiple inlets Ow ≥ A + h and never < 20 mm).
    • Minimum proportions such as l ≥ 10·h are specified for effective protection.
  • Feed orifice and clearance:
    • Feed orifice diameter/bore (D) and radial clearance: a 2D radial clearance around the outlet is required; if < 2D or < 20 mm, a vacuum test per Annex B is required and radial clearance must be > D.
    • Flow direction must be downward into air, not more than 30° from vertical (validation methods depend on the angle).
  • Materials: All materials in contact with potable water must be safe and compatible with drinking water quality.
  • Overflow arrangements: Must discharge into free air; extensions are allowed if they remain unrestricted and validated (testing required if extensions used).
  • Verification: Compliance is verified by test or calculation per the standard. A vacuum test is specified where the overflow is the only air inlet or where geometric clearances require it.
  • Marking and documentation: Marking, symbolization and technical documentation requirements are defined.

Applications and Users

Practical applications include protection of sinks, tanks, process vessels, appliances and other potable water installations where a non‑circular overflow is used (laboratories, commercial kitchens, HVAC systems). Typical users:

  • Manufacturers of backflow protection devices and plumbing components
  • Plumbing and mechanical engineers, designers and specifiers
  • Installers and maintenance personnel for building water systems
  • Test laboratories and conformity assessors
  • Water utilities and regulatory authorities

Related Standards (if applicable)

  • EN 806 (all parts) - installations inside buildings conveying water for human consumption
  • EN 1717 - protection against pollution of potable water and general backflow prevention requirements
  • EN 806-1, EN 806-5 - referenced parts covering general specifications and operation/maintenance

Keywords: EN 13077:2023, air gap, non-circular overflow, backflow prevention, potable water, Family A Type B, CEN, EN 806, EN 1717.

Frequently Asked Questions

SIST EN 13077:2023 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Devices to prevent pollution by backflow of potable water - Air gap with non-circular overflow (unrestricted) - Family A - Type B". This standard covers: This document specifies the characteristics and the requirements of air gap with non-circular overflow (unrestricted) Family A, Type B for nominal flow velocity not exceeding 3 m/s. Air gaps are devices for protection of potable water in water installations from pollution by backflow. This document applies to air gaps in factory-assembled products and to constructed air gaps in situ and specifies requirements and methods to verify and ensure compliance with this document during normal working use. The fluid in the receiving vessel is assumed to have similar properties to water. Where this is not the case, additional care or tests could be required to verify the efficacy of the solution in practical use. The AB device is intended to be used in potable water installations according to EN 806 (all parts).

This document specifies the characteristics and the requirements of air gap with non-circular overflow (unrestricted) Family A, Type B for nominal flow velocity not exceeding 3 m/s. Air gaps are devices for protection of potable water in water installations from pollution by backflow. This document applies to air gaps in factory-assembled products and to constructed air gaps in situ and specifies requirements and methods to verify and ensure compliance with this document during normal working use. The fluid in the receiving vessel is assumed to have similar properties to water. Where this is not the case, additional care or tests could be required to verify the efficacy of the solution in practical use. The AB device is intended to be used in potable water installations according to EN 806 (all parts).

SIST EN 13077:2023 is classified under the following ICS (International Classification for Standards) categories: 13.060.20 - Drinking water; 23.060.99 - Other valves; 91.140.60 - Water supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 13077:2023 has the following relationships with other standards: It is inter standard links to SIST EN 13077:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase SIST EN 13077:2023 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2023
Nadomešča:
SIST EN 13077:2018
Naprave za varovanje pred onesnaženjem pitne vode zaradi povratnega toka -
Prosti iztok s prelivom nekrožne oblike (neoviran) - Družina A - Tip B
Devices to prevent pollution by backflow of potable water - Air gap with non-circular
overflow (unrestricted) - Family A - Type B
Sicherungseinrichtungen zum Schutz des Trinkwassers gegen Verschmutzung durch
Rückfließen - Freier Auslauf mit nicht kreisförmigem Überlauf (uneingeschränkt) - Familie
A - Typ B
Dispositifs de protection contre la pollution de l’eau potable par retour - Surverse avec
trop-plein non-circulaire (totale) - Famille A - Type B
Ta slovenski standard je istoveten z: EN 13077:2023
ICS:
13.060.20 Pitna voda Drinking water
23.060.99 Drugi ventili Other valves
91.140.60 Sistemi za oskrbo z vodo Water supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 13077
EUROPEAN STANDARD
NORME EUROPÉENNE
March 2023
EUROPÄISCHE NORM
ICS 13.060.20 Supersedes EN 13077:2018
English Version
Devices to prevent pollution by backflow of potable water
- Air gap with non-circular overflow (unrestricted) -
Family A - Type B
Dispositifs de protection contre la pollution de l'eau Sicherungseinrichtungen zum Schutz des Trinkwassers
potable par retour - Surverse avec trop-plein non- gegen Verschmutzung durch Rückfließen - Freier
circulaire (totale) - Famille A - Type B Auslauf mit nicht kreisförmigem Überlauf
(uneingeschränkt) - Familie A - Typ B
This European Standard was approved by CEN on 23 January 2023.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2023 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13077:2023 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 Designation. 7
5 Symbolization . 7
6 Materials . 7
7 Requirements . 7
7.1 General . 7
7.2 Characteristics and tests . 8
7.2.1 General . 8
7.2.2 General tolerances and measurements . 8
7.2.3 Accuracy of measuring instruments . 8
7.2.4 Measurements . 8
7.3 Water inlet device . 8
7.4 Overflow arrangements .10
7.5 Air gap distance A.12
7.5.1 General .12
7.5.2 Single supply .12
7.5.3 Multiple supplies .13
7.5.4 Backflow/back pressure .13
7.6 Verification .13
7.6.1 Procedure for verification by test .13
7.6.2 Procedures for verification by calculation .14
8 Marking .15
9 Technical documents .15
Annex A (informative) Relationship between h and l for air gap Family A, Type B with
rectangular overflow .16
Annex B (normative) Vacuum Test .17
B.1 Apparatus .17
B.2 Procedure.17
B.3 Requirement .18

European foreword
This document (EN 13077:2023) has been prepared by Technical Committee CEN/TC 164 “Water
supply”, the secretariat of which is held by AFNOR.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by September 2023, and conflicting national standards shall
be withdrawn at the latest by September 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 13077:2018.
The main changes compared to the previous edition are listed below:
a) terms and definitions have been amended;
b) Figure 1, Figure 4 and Figure 5 have been updated and redrawn;
c) Figure 6 has been added as an additional overflow arrangement;
d) the dimension D has been redefined;
e) 7.4 and 7.5 have been revised;
f) Annex B has been deleted.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
With respect to potential adverse effects on the quality of water intended for human consumption, caused
by the product covered by this document:
a) this document provides no information as to whether the product may be used without restriction
in any of the Member States of the EU or EFTA;
b) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national
regulations concerning the use and/or the characteristics of this product remain in force.
1 Scope
This document specifies the characteristics and the requirements of air gap with non-circular overflow
(unrestricted) Family A, Type B for nominal flow velocity not exceeding 3 m/s. Air gaps are devices for
protection of potable water in water installations from pollution by backflow. This document applies to
air gaps in factory-assembled products and to constructed air gaps in situ and specifies requirements and
methods to verify and ensure compliance with this document during normal working use.
The fluid in the receiving vessel is assumed to have similar properties to water. Where this is not the case,
additional care or tests could be required to verify the efficacy of the solution in practical use.
The AB device is intended to be used in potable water installations according to EN 806 (all parts).
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 806-1, Specifications for installations inside buildings conveying water for human consumption - Part 1:
General
EN 806-5:2012, Specifications for installations inside buildings conveying water for human consumption -
Part 5: Operation and maintenance
EN 1717, Protection against pollution of potable water in water installations and general requirements of
devices to prevent pollution by backflow
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 806-1 and EN 1717 and the
following apply.
3.1
air gap with non-circular overflow (unrestricted) Family A, Type B
permanent and vertical distance between the lowest point of the inlet orifice and the critical water level
of the receiving vessel having an overflow which is non-circular in design
Note 1 to entry: See Figure 1 for the design principle.
a) Air gap with non-circular overflow b) Internal non-circular overflow arrangement
Key
1 Cw ≤ 20 mm
2 Ow ≥ 2D + h and never < 20 mm (single inlet)
Ow ≥ A + h and never < 20 mm (multiple inlets)
3 l ≥ 10 h
Figure 1 — Design principle
3.2
spillover level
level at which water will start to overflow the receiving vessel with all outlets closed
3.3
critical water level
physical or piezometric level of the liquid reached in any part of the appliance 2 s after closing the water
inlet starting from maximum level
3.4
dimension h
height between the spillover level and the critical water level
Note 1 to entry: See 7.6 for measurement and calculation. For example, see Annex A.
3.5
maximum level
highest water level H reached above the spillover level with flow rate Q applied and all outlets closed
3.6
diameter of feed pipe outlet orifice (bore D)
internal diameter size of the outlet feed orifice (or calculated from the equivalent cross sectional area)
3.7
unrestricted
during fault condition, the water pathway to the overflow (of the receiving vessel) is not compromised
including through the overflow itself
4 Designation
An air gap with non-circular overflow (unrestricted) Family A, Type B is designated by:
— name;
— reference to this document, EN 13077;
— family and type;
— maximum permitted flow rate (Q).
EXAMPLE Air gap, EN 13077, Family A, Type B, 14 l/min.
5 Symbolization
The graphic representation of the air gap with non-circular overflow (unrestricted) Family A, Type B is
as follows (see Figure 2).
Figure 2 — Graphic symbol
6 Materials
All materials coming into contact with water intended for human consumption shall present no health
risk nor cause any change of the drinking water in terms of quality, appearances, smell or taste. All
materials shall be compatible among themselves and with the water supplied and with the fluids or
substances that can come into contact with them.
There are no special requirements concerning the materials downstream of the feed orifice provided they
do not have any harmful effect on the upstream part or the overflow arrangement.
7 Requirements
7.1 General
The protection assembly comprises three parts:
— water inlet device;
— receiving vessel (container);
— non-circular overflow.
7.2 Characteristics and tests
7.2.1 General
Performance tests shall be carried out on the device as installed in accordance with the manufacturer’s
technical documents. If not specified, all tests shall be performed with water at an ambient temperature.
7.2.2 General tolerances and measurements
— flow rate and pressure: ±2 % of the value specified;
— temperature: ±5 °C of the value specified;
+10
— time: % of the value specified.
−0
7.2.3 Accuracy of measuring instruments
All the measuring instruments shall have an error limit of ±2 % of the measured value.
7.2.4 Measurements
All measurements shall be in mm or l/min unless otherwise specified.
7.3 Water inlet device
Any device controlling the supply of water into a receiving vessel shall be securely attached to the vessel.
Every feed pipe supplying water to such a valve assembly or other device shall be fixed in its position to
prevent it from moving or buckling and to maintain a 2D radial clearance around the outlet. If a 2D with
a minimum of 20 mm clearance is not present, in addition to the air gap validation a vacuum test i
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

The article discusses the specifications and requirements of an air gap device with a non-circular overflow for preventing pollution by backflow of potable water. The device belongs to Family A, Type B and is designed for a maximum flow velocity of 3 m/s. Air gaps are used to protect water installations from contamination. The document applies to both pre-assembled and constructed air gaps and provides guidelines for ensuring compliance during normal use. In cases where the fluid properties in the receiving vessel differ from the water supply, additional precautions or tests may be necessary to ensure the effectiveness of the solution.

記事のタイトル:SIST EN 13077:2023 - 飲料水の逆流による汚染を防ぐ装置 - 非円形オーバーフロー(制限なし)を備えたエアギャップ - Family A - タイプB 記事の内容:この文書では、最大流速が3 m/s以下の場合に使用される、飲料水の逆流による汚染を防ぐための非円形オーバーフロー(制限なし)エアギャップ、Family A、タイプBの特性と要件を規定しています。エアギャップは、水設備における飲料水の汚染を防ぐための装置です。この文書は、工場で組み立てられた製品に使用されるエアギャップおよび現地で建設されたエアギャップに適用され、正常な使用時にこの文書の順守を確認および保証するための要件と検証方法を定義しています。 受け取り容器内の流体は、水供給と類似した特性を持つと仮定されています。これが該当しない場合、実際の使用で解決策の有効性を確認するために追加の注意や試験が必要になる可能性があります。

記事タイトル:SIST EN 13077:2023- 噴流防止装置 - 非円形オーバーフロー(制約なし)を備えたエアギャップ - Family A - Type B 記事内容:この文書は、名目流速が3 m/sを超えないエアギャップの特性と要件を規定します。エアギャップは、水回り設備における逆流による飲料水の汚染を防ぐための装置です。この文書は、工場組み立ての製品および現地で構築されたエアギャップに適用され、正常な使用中にこの文書の遵守を確認および保証するための要件と方法を定義します。 受信容器の流体は、水供給と類似した性質を持つものとします。そうでない場合は、実用上の使用における解決の有効性を確認するために、追加の注意やテストが必要な場合があります。

기사 제목: SIST EN 13077:2023 - 식수 백류에 의한 오염을 방지하기 위한 장치 - 비원형 오버플로우가 있는 에어갭 (제한 없음) - A 계열 - B형 기사 내용: 본 문서는 맥론 유속이 3 m/s를 초과하지 않는 상황에서 형제 A, B형의 비원형 오버플로우가 있는 에어갭의 특성과 요구사항을 명시한다. 에어갭은 음용수의 오염을 방지하기 위한 장치로서 수도 설치물에서의 백류에 의한 오염을 막는다. 본 문서는 공장에서 조립된 제품에 적용되는 에어갭과 현장에서 구성된 에어갭에 대한 요구사항 및 준수를 검증하고 보증하기 위한 방법을 정의한다. 수신 용기의 유체는 수도 공급과 유사한 특성을 갖는 것으로 가정한다. 그렇지 않은 경우, 실제 사용에서 솔루션의 효능을 검증하기 위해 추가적인 조치나 시험이 필요할 수 있다.

The article is about the specifications and requirements for an air gap device, specifically the air gap with non-circular overflow (unrestricted) Family A, Type B. This device is used to prevent pollution of potable water in water installations due to backflow. The document applies to both factory-assembled air gaps and those constructed on-site. It defines the requirements and methods to ensure compliance with the document during normal use. It also mentions that if the fluid in the receiving vessel has different properties from the water supply, additional tests or precautions may be necessary to verify the effectiveness of the device.

기사 제목: SIST EN 13077:2023 - 식수 역류에 의한 오염 방지 장치 - 비원형 넘치기(제한 없음)를 갖춘 공기 간격 - 가족 A - B형 기사 내용: 이 문서는 최대 유속이 3m/s를 초과하지 않는 명목 유속용 공기 간격을 위한 비원형 넘치기(제한 없음) 공기 간격 가족 A, B형의 특성과 요구 사항을 명시합니다. 공기 간격은 식수 설비 내에서 식수의 역류에 의한 오염을 방지하기 위한 장치입니다. 이 문서는 공장 조립 제품에 사용되는 공기 간격과 현장에서 만들어진 공기 간격에 적용되며, 정상 작동 시 이 문서를 준수하는 요건과 검증 및 보증하기 위한 방법을 정의합니다. 수령용 용기 내의 유체는 수도 공급과 유사한 특성을 가진 것으로 가정됩니다. 이 경우, 실제 사용에서 솔루션의 효과를 검증하기 위해 추가적인 주의 또는 테스트가 필요할 수 있습니다.