oSIST prEN 50545-2:2027
(Main)Electrical apparatus for the detection and measurement of toxic and combustible gases in car parks and tunnels - Part 2: General performance requirements and test methods for gaseous and airborne pollution measurements in tunnels
- Abstract
This document applies to apparatus for the measurement of any of the following: carbon monoxide (CO), nitrogen monoxide (NO), nitrogen dioxide (NO2) and visibility for the purpose of integration into tunnel control systems. The three aforementioned gases are generically called “target gases” for the purpose of this document. These target gases and visibility comprise the target measurands.
This document specifies general requirements for construction and validation testing and describes the test methods that apply to fixed apparatus for the measurement of the concentration of the target gases and visibility in tunnels.
This document applies to apparatus for use in road tunnels and similar infrastructures, for example railway tunnels with diesel locomotives, loading areas for trucks and trafficked areas of underground bus stations.
This document also applies when an apparatus manufacturer makes any claims regarding superior performance that exceeds these minimum requirements. Any enhanced performance or features claimed by the manufacturer outside the scope of this standard cannot be claimed to be certified by this document.
This document applies to apparatus, including the sampling system if applicable.
This document does not specify requirements for apparatus to be installed in hazardous areas.
This document does not apply to applications already covered by the following standards:
— car parks, covered by EN 50545-1;
— domestic premises, covered by EN 50291-1;
— boats, craft, caravans or mobile homes, covered by EN 50291-2;
— workplace atmospheres, covered by EN 45544 series;
— emissions of heaters, covered by EN 50379 series;
— motor vehicles emissions, covered by ISO/PAS 3930;
— monitoring of the LEL level of combustible gases, covered by EN 60079-29-1.
This document does not apply to the following applications, locations and technologies:
— confined spaces;
— laboratory equipment;
— apparatus used to control industrial processes;
— portable and transportable apparatus;
— tunnel construction;
— monitoring of combustible gases or VOCs;
— monitoring for fire detection;
— non-trafficked areas in underground bus stations;
— mines.
- Status
- Not Published
- Public Enquiry End Date
- 31-Jan-2027
- Technical Committee
- I09 - Imaginarni 09
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 17-Nov-2026
- Due Date
- 06-Apr-2027
oSIST prEN 50545-2:2027 is a CENELEC draft European Standard for fixed electrical apparatus used in tunnels to measure carbon monoxide (CO), nitrogen monoxide (NO), nitrogen dioxide (NO2) and visibility for integration into tunnel control systems. It sets general performance requirements, construction rules, validation testing and laboratory and field test methods for manufacturers, test laboratories, and tunnel operators who specify or verify this equipment.
What does oSIST prEN 50545-2:2027 specify?
oSIST prEN 50545-2:2027 specifies requirements for fixed apparatus that measure the target gases - CO, NO and NO2 - and visibility in tunnels. It applies to road tunnels and similar infrastructures such as railway tunnels with diesel locomotives, truck loading areas and trafficked underground bus stations.
The scope includes the apparatus itself and, where applicable, the sampling system. It also applies when a manufacturer claims performance above the minimum requirements, but only the performance covered by this document can be treated as certified to it.
The standard excludes apparatus for hazardous areas and several other application families already covered elsewhere, including car parks, domestic premises, boats and caravans, workplace atmospheres, heater emissions, vehicle exhaust emissions, and monitoring of the lower explosive limit (LEL) of combustible gases. It also excludes confined spaces, laboratory equipment, industrial process control, portable and transportable apparatus, tunnel construction, combustible gases or VOCs, fire detection, non-trafficked underground bus areas and mines.
| Annex | What it covers |
|---|---|
| Annex A | Criteria for in-tunnel air quality |
| Annex B | Comments on the use of NO and NO2 standard test gases |
| Annex C | Particulate matter (PM) monitoring |
| Annex D | Scattered light monitors |
| Annex E | Field test equipment installation |
| Annex F | Paired t-test |
What are the key requirements of oSIST prEN 50545-2:2027?
oSIST prEN 50545-2:2027 focuses on how tunnel gas and visibility monitors are built, how they present data to tunnel systems, and how they are type tested and checked in the field. In practice, it tells a manufacturer what the unit must do, what the lab must test, and what an operator should expect from installed equipment.
Construction, interface and user information
Clause 4 requires the apparatus to detect the target gases and/or visibility in fixed tunnel installations and to provide an interface for tunnel control and monitoring systems. If the apparatus can take an automatic executive action in the absence of a tunnel control system, EN 50271 applies.
The construction requirements matter because tunnel equipment is exposed to corrosion, soot, dust and vibration. Clause 4.2 requires corrosion-resistant materials or coatings, protection against contamination of optical devices, stable mounting points, and low smoke zero halogen cables. Apparatus in trafficked areas must meet the required ingress protection, and the electronic parts must be at least IP66.
Clause 4.2.2 requires a linear transfer function between the measured concentration or visibility and the output signal. It also requires over-range and status signals to be defined, and analogue loops used for fault signalling to comply with NAMUR NE43. This is important for SCADA integration because the control system must distinguish measurement data from alarm and fault states.
Clause 4.3 defines the minimum operating modes in Table 1, including normal operation, maintenance, fault, manual calibration, autocalibration and warm-up. Clause 4.3.2 sets the measuring ranges in Table 2, and Clause 4.3.3 limits the cycle time for aspirated apparatus with multiple sampling points. This matters because operators need to know the measurable range and how quickly a multi-point unit can cycle through all points.
Clause 4.4 requires durable marking and a manual that covers installation, commissioning, calibration, routine checks, operating limits, fault signals, troubleshooting and replacement parts. For a buyer, this is the documentation needed to install, verify and maintain the equipment correctly.
Type testing and laboratory methods
Clause 5 says type testing is performed on two apparatus, and the lesser-performing unit defines the official result. Additional units may be used for wall mounting, impact, vibration, shock, corrosion, EMC and long-term stability tests.
The standard defines preparation and test conditions in detail so that results are comparable. It specifies how test gas is applied for diffusion, aspirated and open-path sensors, and how visibility surrogates are used for open-path systems, single-point systems and aspirated apparatus. Clause 5.6 sets standard conditions for gas concentration, voltage, temperature, pressure, humidity, stabilization time and installation.
Clause 6 gives the laboratory test methods. The most important ones are response time, repeatability, linearity, temperature, humidity, flow rate for aspirated apparatus, interfering gases, particulate matter interference, recovery from high gas concentrations, mechanical strength, corrosion, power supply variations, field calibration, multiple point selector testing, EMC and enclosure protection.
For visibility equipment, Annex D is especially important. It describes scattered light monitors and how they are adjusted against a transmission monitor by co-location in a test tunnel. That matters because visibility in road tunnels is reported as K-value, not directly as visual range, so the test setup has to link the optical method to a common reference.
Field testing and performance in service
Clause 7 covers field testing with two apparatus installed in a test tunnel and monitored by an independent body. The installation and spacing guidance in Annex E helps place the devices where tunnel air conditions are representative and the co-located units can be compared reliably.
The field test checks long-term stability, availability, zero measurement, span measurement, response time and reproducibility. The minimum certified maintenance interval is 3 months, availability must reach 98%, and the measured signals must be recorded continuously. That gives tunnel operators evidence that the device remains stable over time, not just under laboratory conditions.
Clause 7.8 requires a detailed test report, including tunnel location and traffic characteristics, ventilation type, slope, installation details and any interruptions. Annex F adds paired t-test guidance for the reproducibility evaluation.
What terms does oSIST prEN 50545-2:2027 define?
- aspirated apparatus - apparatus that draws air from the tunnel through a separate sampling system to the sensor.
- diffusion apparatus - apparatus that analyses tunnel air without using a separate sampling system.
- control unit (CU) - the part of the apparatus that receives and processes sensor signals and generates output functions.
- lower detectable limit - the smallest pollutant concentration that produces a signal equal to three times the standard deviation at zero.
- response time - the time from a step increase at the inlet to the point where the reading reaches the stated percentage of the final reading; here, 90%.
- transmission monitor - an apparatus that measures the attenuation of a light beam over a known path length and calculates K-value from the transmission.
- visibility surrogate - an optical element used as a test substitute for dust in visibility measurements, including optical filters and a scattered light test element.
- target gas - the gas measured in the tunnel, identified as a common pollutant in vehicle exhaust.
Who uses oSIST prEN 50545-2:2027?
oSIST prEN 50545-2:2027 is used by manufacturers of tunnel gas and visibility monitors, calibration and test laboratories, tunnel owners and operators, and system integrators for tunnel control systems. It is also relevant to quality and procurement teams who need to specify performance, installation and acceptance criteria.
The document applies to road tunnels and similar infrastructures, including railway tunnels with diesel locomotives, truck loading areas and trafficked underground bus stations. In practice, users apply it for type testing, field verification, maintenance planning, calibration, and acceptance of fixed monitoring equipment.
Which standards are used with oSIST prEN 50545-2:2027?
- EN 50271 - applies if the apparatus can perform an automatic executive action without a tunnel control system, especially where software or digital technology is involved.
- EN 60068-2-27 - provides the shock test method used for mechanical strength.
- EN IEC 60068-2-52 - provides the cyclic salt mist corrosion test.
- EN 60529 - provides the ingress protection code used for enclosure protection.
- EN 61010-1 - provides the general safety requirements used in the impact test reference.
- EN IEC 61326-1 - provides the EMC performance requirements, including the type 2 level used here.
- ISO 23431 - provides road tunnel air quality measurement methods and is referenced for operational calibration and maintenance.
- Namur NE43 - gives the signal level convention for fault information on digital transmitters.
- EN 50545-1 - the companion part for car parks, cited in the scope as the standard covering that application family.
- EN ISO 6142-1, EN ISO 6143, EN ISO 6144 and EN ISO 6145 series - provide standard methods for preparing calibration gas mixtures used in test gas preparation.
What does the oSIST prEN 50545-2:2027 document contain?
The document contains a full set of requirement tables and test methods for tunnel gas and visibility monitoring. Tables 1 and 2 define operating modes and measuring ranges, while Tables 3 to 9 define test gases, surrogates, tolerances, interference limits and recovery conditions.
It also contains two main calculation areas: the linearity calculation in Clause 6.4 and the field reproducibility calculation in Clause 7.7. These formulas are used to assess measurement error and agreement between two installed instruments.
Annexes A to F add practical guidance beyond the core requirements. They cover tunnel air quality criteria, the handling of NO and NO2 test gases, particulate matter context, the special calibration method for scattered light monitors, field installation guidance, and the paired t-test approach used in the field reproducibility assessment.
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
oSIST prEN 50545-2:2027 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Electrical apparatus for the detection and measurement of toxic and combustible gases in car parks and tunnels - Part 2: General performance requirements and test methods for gaseous and airborne pollution measurements in tunnels". This standard covers: This document applies to apparatus for the measurement of any of the following: carbon monoxide (CO), nitrogen monoxide (NO), nitrogen dioxide (NO2) and visibility for the purpose of integration into tunnel control systems. The three aforementioned gases are generically called “target gases” for the purpose of this document. These target gases and visibility comprise the target measurands. This document specifies general requirements for construction and validation testing and describes the test methods that apply to fixed apparatus for the measurement of the concentration of the target gases and visibility in tunnels. This document applies to apparatus for use in road tunnels and similar infrastructures, for example railway tunnels with diesel locomotives, loading areas for trucks and trafficked areas of underground bus stations. This document also applies when an apparatus manufacturer makes any claims regarding superior performance that exceeds these minimum requirements. Any enhanced performance or features claimed by the manufacturer outside the scope of this standard cannot be claimed to be certified by this document. This document applies to apparatus, including the sampling system if applicable. This document does not specify requirements for apparatus to be installed in hazardous areas. This document does not apply to applications already covered by the following standards: — car parks, covered by EN 50545-1; — domestic premises, covered by EN 50291-1; — boats, craft, caravans or mobile homes, covered by EN 50291-2; — workplace atmospheres, covered by EN 45544 series; — emissions of heaters, covered by EN 50379 series; — motor vehicles emissions, covered by ISO/PAS 3930; — monitoring of the LEL level of combustible gases, covered by EN 60079-29-1. This document does not apply to the following applications, locations and technologies: — confined spaces; — laboratory equipment; — apparatus used to control industrial processes; — portable and transportable apparatus; — tunnel construction; — monitoring of combustible gases or VOCs; — monitoring for fire detection; — non-trafficked areas in underground bus stations; — mines.
This document applies to apparatus for the measurement of any of the following: carbon monoxide (CO), nitrogen monoxide (NO), nitrogen dioxide (NO2) and visibility for the purpose of integration into tunnel control systems. The three aforementioned gases are generically called “target gases” for the purpose of this document. These target gases and visibility comprise the target measurands. This document specifies general requirements for construction and validation testing and describes the test methods that apply to fixed apparatus for the measurement of the concentration of the target gases and visibility in tunnels. This document applies to apparatus for use in road tunnels and similar infrastructures, for example railway tunnels with diesel locomotives, loading areas for trucks and trafficked areas of underground bus stations. This document also applies when an apparatus manufacturer makes any claims regarding superior performance that exceeds these minimum requirements. Any enhanced performance or features claimed by the manufacturer outside the scope of this standard cannot be claimed to be certified by this document. This document applies to apparatus, including the sampling system if applicable. This document does not specify requirements for apparatus to be installed in hazardous areas. This document does not apply to applications already covered by the following standards: — car parks, covered by EN 50545-1; — domestic premises, covered by EN 50291-1; — boats, craft, caravans or mobile homes, covered by EN 50291-2; — workplace atmospheres, covered by EN 45544 series; — emissions of heaters, covered by EN 50379 series; — motor vehicles emissions, covered by ISO/PAS 3930; — monitoring of the LEL level of combustible gases, covered by EN 60079-29-1. This document does not apply to the following applications, locations and technologies: — confined spaces; — laboratory equipment; — apparatus used to control industrial processes; — portable and transportable apparatus; — tunnel construction; — monitoring of combustible gases or VOCs; — monitoring for fire detection; — non-trafficked areas in underground bus stations; — mines.
oSIST prEN 50545-2:2027 is classified under the following ICS (International Classification for Standards) categories: 13.040.50 - Transport exhaust emissions; 13.320 - Alarm and warning systems. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN 50545-2:2027 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 45 5.6.8 Test installation
- 46 6 Laboratory test methods
- 47 6.1 General
- 48 6.2 Response time
- 49 6.3 Repeatability
- 50 6.4 Linearity
- 51 6.4.1 Linearity testing for gases
- 52 6.4.2 Linearity testing for visibility
- 53 6.4.3 Linearity calculation
- 54 6.5 Temperature
- 55 6.6 Humidity
- 56 6.7 Flow rate (for aspirated apparatus only)
- 57 6.8 Interfering gases
- 58 6.8.1 Testing Interfering Gases
- 59 6.8.2 Testing Particulate Matter Interference
- 60 6.9 Recovery from high gas concentrations
- 61 6.10 Mechanical strength
- 62 6.10.1 Wall mounting
- 63 6.10.2 Impact test
- 64 6.10.3 Vibration
- 65 6.10.4 Shock test
- 66 6.11 Corrosion test
- 67 6.12 Power supply variations
- 68 6.13 Field calibration
- 69 6.14 Testing of multiple point selector
- 70 6.15 Electromagnetic compatibility
- 71 6.16 Degrees of protection provided by enclosures
- 72 7 Field test
- 73 7.1 General
- 74 7.2 Long term stability test
- 75 7.3 Availability
- 76 7.4 Zero Measurement
- 77 7.5 Span Measurement
- 78 7.6 Response Time Measurement
- 79 7.7 Reproducibility
- 80 7.8 Test report
- 81 Annex A (informative) Criteria for In-tunnel Air Quality
- 82 A.1 General
- 83 A.2 PIARC Criteria (2019)
- 84 A.3 National Criteria for NO
- 85 A.4 Air quality criteria in road tunnels for occupational exposure
- 86 A.5 WHO ambient air quality guidelines for NO and CO
- 87 A.6 References
- 88 Annex B (informative) Comments on the use of NO and NO standard test gases for testing
- 89 B.1 General
- 90 B.2 NO gas testing
116 Introduction 117 With sustained road traffic and still significant emissions from vehicles, the main air quality pollutants 118 (exhaust and non-exhaust) need to be monitored in road tunnels. The objective of this document is to 119 ensure compliance with regulatory criteria for protecting the health of users, while also minimizing 120 ventilation requirements to reduce energy consumption.
121 Important developments in air quality sensors over the last two decades can help to meet this objective. 122 Road tunnel operators can now monitor concentrations of the main pollutants more accurately than in 123 the past, provided that they select and correctly install the right equipment. Two complementary 124 standards, ISO 23431 and this document now provide guidance when purchasing and using the 125 appropriate equipment. The ISO standard describes methods for determining air speed and flow 126 direction, CO, NO and NO2 concentrations and visibility in road tunnels using direct-reading instruments 127 and specifically excludes requirements relating to instrument conformance testing.
128 This document, prEN 50545-2 “General performance requirements and test methods for gaseous and 129 airborne pollution measurements in tunnels“ designates unique ranges and test levels for target gases 130 and visibility for the purpose of type testing, specifying minimum requirements. These ranges may be 131 adapted to national and/or local regulations.
132 1 Scope 133 This document applies to apparatus for the measurement of any of the following: carbon monoxide (CO), 134 nitrogen monoxide (NO), nitrogen dioxide (NO2) and visibility for the purpose of integration into tunnel 135 control systems. The three aforementioned gases are generically called “target gases” for the purpose 136 of this document. These target gases and visibility comprise the target measurands. 137 This document specifies general requirements for construction and validation testing and describes the 138 test methods that apply to fixed apparatus for the measurement of the concentration of the target gases 139 and visibility in tunnels.
140 This document applies to apparatus for use in road tunnels and similar infrastructures, for example 141 railway tunnels with diesel locomotives, loading areas for trucks and trafficked areas of underground 142 bus stations.
143 This document also applies when an apparatus manufacturer makes any claims regarding superior 144 performance that exceeds these minimum requirements. Any enhanced performance or features 145 claimed by the manufacturer outside the scope of this standard cannot be claimed to be certified by this 146 document.
147 This document applies to apparatus, including the sampling system if applicable.
148 This document does not specify requirements for apparatus to be installed in hazardous areas. 149 This document does not apply to applications already covered by the following standards:
150 — car parks, covered by EN 50545-1; 151 — domestic premises, covered by EN 50291-1; 152 — boats, craft, caravans or mobile homes, covered by EN 50291-2; 153 — workplace atmospheres, covered by EN 45544 series; 154 — emissions of heaters, covered by EN 50379 series; 155 — motor vehicles emissions, covered by ISO/PAS 3930; 156 — monitoring of the LEL level of combustible gases, covered by EN 60079-29-1.
157 This document does not apply to the following applications, locations and technologies:
158 — confined spaces; 159 — laboratory equipment; 160 — apparatus used to control industrial processes; 161 — portable and transportable apparatus; 162 — tunnel construction; 163 — monitoring of combustible gases or VOCs; 164 — monitoring for fire detection; 165 — non-trafficked areas in underground bus stations; 166 — mines.
167 2 Normative references 168 The following documents are referred to in the text in such a way that some or all of their content 169 constitutes requirements of this document. For dated references, only the edition cited applies. For 170 undated references, the latest edition of the referenced document (including any amendments) applies. 171 EN 50271, Electrical apparatus for the detection and measurement of combustible gases, toxic gases 172 or oxygen - Requirements and tests for apparatus using software and/or digital technologies 173 EN 60068-2-27, Environmental testing - Part 2-27: Tests - Test Ea and guidance: Shock (IEC 60068-2- 174 27) 175 EN IEC 60068-2-52, Environmental testing — Tests. Test Kb: Salt mist, cyclic (sodium chloride solution) 176 and guidance. Shock (IEC 60068-2-52) 177 EN 60529, Degrees of protection provided by enclosures (IP Code) (IEC 60529) 1 178 EN 61010-1:2010, Safety requirements for electrical equipment for measurement, control, and 179 laboratory use - Part 1: General requirements (IEC 61010-1) 180 EN IEC 61326-1, Electric equipment for measurement, control and laboratory use. EMC requirements 181 — General requirements (IEC 61326-1) 182 ISO 23431, Measurement of road tunnel air quality 183 Namur NE43, Standardization of the Signal Level for the Failure Information of Digital Transmitters 184 3 Terms and definitions 185 For the purposes of this document, the following terms and definitions apply.
186 ISO and IEC maintain terminology databases for use in standardization at the following addresses:
187 — ISO Online browsing platform: available at https://www.iso.org/obp 188 — IEC Electropedia: available at https://www.electropedia.org/ 189 3.1 190 apparatus 191 component necessary for measuring the target measurands, contained in one or more enclosures which 192 will be type tested according to this document 193 3.2 194 aspirated apparatus 195 apparatus that extracts air from the tunnel by a separate sampling system from single or multiple points, 196 consisting of a separate sampling system and the sensor 197 3.3 198 clean air 199 air which is free from gases or vapours and particles to which the equipment is sensitive or which 200 influence the performance of the equipment
As impacted by EN 61010-1:2010/A1:2019 and EN 61010-1:2010/A1:2019/AC:2019-04.
202 transit time 203 time a sample takes to travel from the sampling point to the point of measurement inside the sensor 204 3.5 205 co-location 206 measurement from the apparatus and a reference measurement system, sampling from the same 207 location (within 5 metres) over the same time period 208 3.6 209 control unit 210 CU 211 part of the apparatus that receives and processes the signals generated by the sensors and also 212 generates output functions 213 3.7 214 diffusion apparatus 215 apparatus that analyses air from the tunnel without using a separate sampling system 216 3.8 217 extinction coefficient 218 attenuation of light through a scattering and/or absorbing medium, described by the following function:
−k()λ⋅d 219 I()λ Ie⋅ (1) 0 220 where 221 I and I are the initial intensity and the intensity after a distance d of uniform, collimated light; 0 222 k is the extinction coefficient called K-value −1 −3 −1 223 Note 1 to entry: The K-value of a medium has the unit m (also commonly used 10 m ) and depends on 224 the wavelength spectrum of the light source. Here, the K-value is used as a measurable parameter to estimate the 225 visibility in a tunnel. A reduction of visibility in tunnels is primarily caused by light scattering and results in an 226 increased K-value.
227 3.9 228 fault 229 abnormal condition that may cause a reduction in, or loss of, the capability of a functional unit to perform 230 a required function 231 3.10 232 fault signal 233 audible, visible or other type of output, permitting, directly or indirectly, a warning or indication that there 234 is a fault 235 3.11 236 final reading 237 asymptotic measurement value given by the apparatus after a long period of time 238 3.12 239 fixed apparatus 240 apparatus that is intended to have all parts permanently installed 241 3.13 242 hazardous area 243 <potentially explosive atmosphere> atmosphere which could become explosive due to local and 244 operational conditions 245 Note 1 to entry: Operation in hazardous areas can require legislative measures for the approval, installation 246 and construction requirements of the apparatus.
247 3.14 248 indicator 249 means to provide visible and/or audible information 250 3.15 251 K-value 252 extinction coefficient 253 Note 1 to entry: See 3.8 extinction coefficient.
254 3.16 255 lower detectable limit 256 minimum pollutant concentration that produces a signal calculated as three times the standard deviation 257 at zero 258 Note 1 to entry: E.g. ISO 23431.
259 3.17 260 calibration mask 261 device that can be attached to the equipment to present a test gas to the sensor in a reproducible 262 manner 263 3.18 264 optical filter 265 <surrogates> optical element that attenuates the transmitted light intensity in the wavelength range 266 employed by the optical sensor 267 Note 1 to entry: Optical filters shall be used as well-defined surrogates for dust in transmission 268 monitors. They can be used for measuring both linearity and span in transmitted light monitors. 269 3.19 270 output signal 271 analogue or digital signal which is available at an output interface 272 3.20 273 particulate matter 274 PM 275 particles suspended in air, classified with diameters between 0,3 and 10 µm and measured and reported 276 as PM , PM (fine) and (PM -PM ) (coarse) 1 2.5 10 2.5 277 Note 1 to entry: Although particulate matter measurement devices are not covered in this standard, important 278 information is given in Annex C.
279 3.21 280 ppm 281 ppm v 282 parts per million 283 ratio expressing the units of volume of gaseous pollutant contained in 1 000 000 units of volume of 284 atmosphere 285 Note 1 to entry: It may equivalently be expressed as one million times the ratio of the partial pressure of 286 gaseous pollutant to the pressure of the atmosphere in which it is contained.
287 3.22 288 power supply 289 device that provides suitable power to the system or part thereof 291 reference wavelength 292 defined standard wavelenght 293 Note 1 to entry: As the K-value varies with wavelength, the measured K-value of a visibility apparatus depends 294 on the wavelength used by the device. To achieve standardized and comparable measurement values for the K- 295 value, these measured values need to be referenced to measurement apparatus using a defined standard 296 wavelength.
297 The reference wavelength for visibility measurement shall:
298 a) be within a range in which the human eye has a good spectral sensitivity; and 299 b) use commonly available light sources for the test instrument.
300 Note 2 to entry:
301 1. The 50 % range of the maximum spectral sensitivity is between 510 nm and 610 nm. 302 2. many technical applications use green light sources. Therefore, green light sources are available in many 303 different forms.
304 Note 3 to entry: A wavelength of 530 (±20) nm complies with these requirements and is the reference 305 wavelength for the tests in this standard.
306 3.24 307 response time 308 t x 309 time interval, with the apparatus in a warmed-up condition, between the time when a step increase in 310 concentration of a target measurand is produced at the apparatus inlet and the time when the response 311 reaches a stated percentage (x) of the final reading 312 Note 1 to entry: For an aspirated apparatus system, the response time is the sum of:
313 — the transit time of the sample (see definition 3.3); 314 — the response time of the sensor itself.
315 Note 2 to entry: This document refers to t as the time the device takes to reach 90 % of the final reading. 90 316 3.25 317 sampling system 318 means by which the sampled air is transferred to the sensor including accessories (e.g. filter, water trap) 319 3.26 320 scattered light monitor 321 apparatus that measures the intensity of scattered light 322 Note 1 to entry: The device contains a light source that illuminates a measurement volume. The particles in 323 the measurement volume scatter the light in various directions. The apparatus measures the intensity of light at a 324 defined angle or range of angles to the light beam. The intensity of the measured light is proportional to the K-value. 325 3.27 326 scattered light test element 327 <surrogates> optical element that scatters light 328 Note 1 to entry: Scattered light test elements shall be used as surrogates for dust in scattered light monitors. 329 A scattered light element is customized to the apparatus to be tested and provides a specific K-value in the 330 respective apparatus.
332 sensing element 333 part of the sensor which responds to the target measurand 334 3.29 335 sensor 336 assembly in which the sensing element is housed and that may also contain associated circuit 337 components 338 3.30 339 target gas 340 gas to be measured in the tunnel, having been identified as the most common pollutants present in the 341 exhaust of vehicles powered by combustion engines 342 3.31 343 test tunnel 344 tunnel in which two apparatus can be co-located at least temporarily for field tests and/or calibrations 345 (mainly regarding visibility) 346 Note 1 to entry: The test tunnel shall have an annual average daily traffic (AADT) on workdays over the test 347 period of greater than or equal to 5000/lane in unidirectional and greater than or equal to 3000/lane in bidirectional 348 tunnels. The percentage of heavy goods vehicles shall be at least 3 %. During the co-location test, visibility 349 conditions shall reach the values stated in Table 4 on at least two occasions.
350 3.32 351 transmission monitor 352 apparatus that measures the transmission along a known optical path length d of the tunnel atmosphere 353 by measuring the attenuation of a light beam along this path 354 Note 1 to entry: The transmission T is the ratio of the actually received light intensity at the end of the path (I) 355 to the known received light intensity of the light beam (I ) in a clean atmosphere and depends on the wavelength of 0 356 the light beam 357 T = I/I o -Kd 358 Note 2 to entry: Based on the equation T = e , the device calculates the K-value: K = -ln(T)/d. 359 3.33 360 visibility 361 K-value measured in road tunnels 362 Note 1 to entry: The visibility is usually a measure of the distance at which an object or light can be clearly 363 discerned from its background, however, this value cannot be measured directly in road tunnels. Therefore, the K- 364 value is measured and commonly called “visibility” in road tunnels.
365 3.34 366 visibility surrogate 367 optical element that comprises the optical filters as described in 3.17 and the scattered light test element 368 as described in 3.26 369 3.35 370 warm-up time 371 time starting immediately after an apparatus is switched (powered) on 372 Note 1 to entry: The duration of the warm-up time can be different for different device types and is stated by 373 the manufacturer of the device. During the warm-up time, the apparatus does not provide valid readings. Therefore, 374 the apparatus shall indicate a “data not valid” signal until it enters the measuring mode.
376 zero gas 377 gas (mixture) without any traces of the target gases 378 3.37 379 zero suppression 380 feature used to output a zero value when the reading is below a defined value 381 4 General requirements 382 4.1 Introduction 383 4.1.1 Purpose 384 The apparatus shall detect the presence of target gases and/or visibility in fixed installations for the 385 applications listed in chapter 1. Its function is to report the visibility and/or target gas concentrations. It 386 shall provide an interface to the tunnel control and monitoring system for transmission of these 387 measurements and for status and/or diagnostic data.
388 4.1.2 Software-controlled apparatus 389 Most tunnels are controlled by SCADA systems where the apparatus provides measurements and 390 signals into those systems. However, if the measuring apparatus makes an automatic executive action 391 regarding tunnel operations in the absence of a tunnel control system, it shall conform to EN 50271. 392 4.2 Construction requirements 393 4.2.1 General 394 As the apparatus or parts thereof are specifically intended for use in the presence of corrosive vapours, 395 gases or salt spray they shall be constructed of materials or protected by coatings known to be resistant 396 against corrosion (e.g. engineering plastics, anodized aluminium, stainless steel such as AISI 316 L, 397 AISI 316 Ti, etc.).
398 In particular, optical devices shall have integral protection against the influence of soot, dust or other 399 pollutants so as to minimize their effect on the measurements.
400 The apparatus shall be constructed to facilitate regular operation and performance checks. 401 Any adjustment devices shall be designed so as to discourage unauthorized or inadvertent interference 402 with the apparatus.
403 Apparatus mounted in the trafficked areas of the tunnel shall be constructed to provide the degree of 404 protection as defined in EN 60529, for all orientations of installation specified by the manufacturer in 405 provided documentation as defined in 4.4.2. The degree of protection for all electronic parts shall be at 406 least IP66.
407 The apparatus shall be provided with adequate mounting points to provide a stable long-term connection 408 to the tunnel structure.
409 Cables used within the apparatus shall be low smoke and zero halogen according to EN 50525-1. 410 4.2.2 Interface requirements 411 The measurement device shall deliver a linear relationship between the gas concentration and/or 412 visibility and the corresponding output signal (transfer function).
413 Over-range and status signals (e.g. fault or inhibit) shall be specified.
414 If analogue loops are used for purposes other than measurements such as raising a fault, the interface 415 shall comply with NAMUR NE 43.
416 4.2.3 Measuring function 417 4.2.3.1 General 418 The measurement device shall provide a data (not) valid and a fault status.
419 The apparatus shall measure the target gas volumetric concentrations and/or visibility (K-value) with 420 measuring range as specified in Table 2.
421 4.2.3.2 Visual indications 422 If visible indicator lights are provided, these shall be adequately labelled to show their functions and 423 shall be coloured as follows (in accordance with EN 60073):
424 — status indicating the need of calibration shall be coloured BLUE; 425 — equipment fault indicators shall be coloured YELLOW; 426 — power supply indicators shall be coloured GREEN.
427 4.2.4 Calibration equipment 428 The manufacturer shall provide calibration equipment adapted to the apparatus that shall be verified as 429 being appropriate for the calibration and type testing (see 6.15 and 6.16).
430 The device specific equipment for calibration shall be used for type testing of the apparatus. If applicable, 431 removal of any protective cover that could be mounted on the device is allowed.
432 4.3 Operational requirements 433 4.3.1 Introduction 434 The modes from Table 1 shall be defined as a minimum for the apparatus.
435 Table 1 — Functioning modes
Mode Mandatory/optional Data valid Fault Measurement output Normal operation Mandatory Yes No Yes
Maintenance Optional No No Yes
Fault Mandatory No Yes If available
Manual calibration Optional No No No
Autocalibration Optional Yes No Previous value maintained Warm up Optional No No No 436 4.3.2 Measuring range 437 The minimum measuring range for each measurand shall be as specified in Table 2.
438 Table 2 — Measuring range
Target gas Measuring Range Lower Detectable Limit CO 0 … 200 ppm 1,5 ppm
NO 0 … 2 ppm 20 ppb
NO 0 … 10 ppm 30 ppb
Target gas Measuring Range Lower Detectable Limit −3 −1 −3 −1
...