ISO/DTR 27327-3 - Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

Release Date:09-Oct-2026
English language (40 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/DTR 27327-3 - Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

Release Date:09-Oct-2026
English language (40 pages)
sale 15% off
sale 15% off

ISO/DTR 27327-3 is an ISO Technical Report on fans - air curtain units, Part 3, about research tests to determine energy effectiveness. It brings together laboratory test work, simulation studies, and calculation methods used to assess how an air curtain unit reduces heat transfer across an open doorway. It is aimed at people evaluating, developing, or studying air curtain units, especially test laboratories, manufacturers, and technical specialists.

What does ISO/DTR 27327-3 specify?

ISO/DTR 27327-3 reports a laboratory approach for measuring the energy effectiveness of an air curtain unit when it is installed across an open doorway. The document says the method is not for design, production, or field testing, so it is best read as research support rather than a product conformity test.

The document is organized into:

  • Clause 1 - Scope
  • Clause 2 - Normative references
  • Clause 3 - Terms, definitions and symbols
  • Clause 4 - Independent Research Facility (IRF) climate chamber (lab) test
  • Clause 5 - Simulations
  • Clause 6 - Conclusion
  • Bibliography

There are no annexes in the document. In practice, the structure tells the reader that the technical focus is on one laboratory method, the calculations behind it, and several simulation studies used to compare against the lab work.

What are the key requirements of ISO/DTR 27327-3?

ISO/DTR 27327-3 does not set a compliance regime, but it does describe the research method in enough detail to let others reproduce the work and compare results. The most important points are in Clause 4, with supporting simulation material in Clause 5.

  • Use a dual-climate chamber with a doorway between the cells. Clause 4 places an air curtain unit above a door opening between a cold cell and a warm cell. The test conditions used in the report are 6.7 °C in the cold cell and 21 °C in the warm cell, with a 2 m by 2.3 m door opening. In practice, this means the method is about doorway separation, not general room ventilation.

  • Measure the temperature field in both cells and at the doorway. Clause 4 uses 27 thermocouples in each climate cell and 5 thermocouples in the door frame, plus other sensors for air curtain operation and chamber conditions. This matters because the method depends on comparing the average chamber temperatures and the way they change when the door is opened.

  • Run the test with the door open for a fixed time. The report says steady conditions cannot be maintained with the door open, so the method uses a timed open period instead. The door is opened 20 seconds after the air curtain unit fans start, kept open for 8 minutes, and then closed again. In practice, the fixed timing makes repeated tests comparable.

  • Calculate climate separation effectiveness from the energy difference with and without the ACU. Clause 4 defines climate separation effectiveness, ECS, as the proportional reduction in heat loss through the doorway when the air curtain unit operates. The energy with the ACU includes the ACU’s own energy use. For a reader, this means the result is not just about blocking transfer, but about net effect, including operating the device.

  • Use the cold cell energy balance as the main basis for the calculation. The report says the heat transfer through the doorway is determined from the cold climate cell because the ACU can disturb conditions in the warm cell. This is important in practice because it shows where the most reliable data are taken from in the test set-up.

  • Allow for changing temperature difference during the open-door period. The report explains that temperature cannot be held perfectly constant while the door is open, so it compares three values for the no-ACU case: a measured value, a calculated value at a nominal temperature difference of 14.3 K, and a calculated value based on the measured average temperature difference. In practice, that tells the reader the method is sensitive to chamber stability.

  • Use the reported research results as supporting evidence, not as a universal rule. Clause 5 reviews CFD and whole-building energy studies from different groups, including TRNSYS, CONTAM, EnergyPlus, ANSYS FLUENT, ANSYS CFX, and Autodesk Simulation 2015. These studies are used to compare simulation with lab data and to explore how air curtain units affect building energy use. For a user, this means the document is collecting evidence for a test method that is still being developed.

What terms does ISO/DTR 27327-3 define?

ISO/DTR 27327-3 defines a small set of core terms and symbols that are central to the lab method and the simulations.

  • Air curtain unit effectiveness - the ratio based on the difference between energy loss without an air curtain unit and energy loss with one, divided by the loss without the air curtain unit.
  • Climate separation effectiveness (ECS) - the percentage form used in the report to show how much the air curtain unit reduces thermal exchange across the doorway.
  • Air curtain unit (ACU) - a device mounted above a doorway to create a protective air stream across the opening.
  • Independent Research Facility (IRF) - the dual-climate laboratory set-up used for the physical tests described in Clause 4.
  • Computational Fluid Dynamics (CFD) - a simulation method used in Clause 5 to model air movement, temperature distribution, and doorway infiltration.
  • Particle image velocimetry (PIV) - a measurement technique used in the validation work to observe air flow patterns in the test opening.
  • ΔE - the energy difference used to compare the doorway heat transfer with and without an ACU over the test period.

Who uses ISO/DTR 27327-3?

ISO/DTR 27327-3 is used by people working on air curtain unit performance, doorway energy transfer, and related simulation work. The document is especially relevant to:

  • manufacturers of air curtain units
  • testing laboratories and research facilities
  • HVAC and building-energy engineers
  • CFD analysts and energy modelers
  • standards developers and technical committees
  • quality managers and buyers who need to understand what this research method does and does not cover

In practice, these users apply it to set up lab tests, compare ACU designs, validate simulation models, and discuss whether a doorway solution is likely to reduce energy loss in use.

What changed in ISO/DTR 27327-3 from the previous edition?

ISO/DTR 27327-3 does not identify a previous edition or replacement document in the provided text. The document does say it collects research data to support future development of a test method for energy effectiveness of air curtain units.

Which standards are used with ISO/DTR 27327-3?

ISO/DTR 27327-3 lists no normative references in Clause 2. The foreword refers readers to the ISO/IEC Directives, Parts 1 and 2, for drafting and editorial practice, but those are not part of the document’s technical requirements. The text also mentions ISO’s online terminology resources, but not companion standards that are required for use with this report.

What does the ISO/DTR 27327-3 document contain?

ISO/DTR 27327-3 contains the research record behind a doorway energy-effectiveness test for air curtain units. It includes the dual-climate chamber layout, thermocouple placement, measured parameters, and the energy-balance approach used to calculate ECS. It also gives the measurement conditions, such as the chamber temperatures, open-door duration, sampling interval, and unheated ACU operation.

The document then expands into simulation-based studies. These cover whole-building CFD and energy modelling, as well as detailed lab replications carried out by Mars Air Systems and Berner International. The figures and tables show temperature profiles, velocity cut-planes, airflow comparisons, and the calculated energy values used to compare ACU-on and no-ACU cases.

For practical use, the document is most helpful as a technical backgrounder. It shows what was measured, how the calculations were made, how CFD was used to check the laboratory work, and where the reported uncertainties and limitations lie.

Buy Documents

Draft

ISO/DTR 27327-3 - Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

Release Date:09-Oct-2026
English language (40 pages)
sale 15% off
sale 15% off
Draft

REDLINE ISO/DTR 27327-3 - Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

Release Date:09-Oct-2026
English language (40 pages)
sale 15% off
sale 15% off

Get Certified

Connect with accredited certification bodies for this standard

Institut za varilstvo d.o.o. (Welding Institute)

Slovenia's leading welding institute since 1952. ISO 3834, EN 1090, pressure equipment certification, NDT personnel, welder qualification. Only IIW Au

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

ISO/DTR 27327-3 is a draft published by the International Organization for Standardization (ISO). Its full title is "Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness". This standard covers: Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

Fans — Air curtain units — Part 3: Research tests to determine energy effectiveness

ISO/DTR 27327-3 is classified under the following ICS (International Classification for Standards) categories: 23.120 - Ventilators. Fans. Air-conditioners. The ICS classification helps identify the subject area and facilitates finding related standards.

ISO/DTR 27327-3 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and symbols
  • 3.1 Terms and definitions
  • 3.1.1 air curtain unit effectiveness
  • 3.2 Symbols
  • 4 Independent research facility (IRF) climate chamber (lab) test
  • 4.1 Introduction
  • 4.2 Experimental setup
  • 01 A.L.B 10 M.L.B 19 V.L.B 28 D.B.2 33 V.R.B 42 M.R.B 51 A.R.B
  • 02 A.M.B 11 M.M.B 20 V.M.B 29 D.B.1 34 V.M.B 43 M.M.B 52 A.M.B
  • 03 A.R.B 12 M.R.B 21 V.R.B 30 D.M. 35 V.L.B 44 M.L.B 53 A.L.B
  • 04 A.L.M 13 M.L.M 22 V.L.M 31 D.O.2 36 V.R.M 45 M.R.M 54 A.R.M
  • 05 A.M.M 14 M.M.M 23 V.M.M 32 D.O.1 37 V.M.M 46 M.M.M 55 A.M.M
  • 06 A.R.M 15 M.R.M 24 V.R.M 38 V.L.M 47 M.L.M 56 A.L.M
  • 07 A.L.O 16 M.L.O 25 V.L.O 39 V.R.O 48 M.R.O 57 A.R.O
  • 08 A.M.O 17 M.M.O 26 V.M.O 40 V.M.O 49 M.M.O 58 A.M.O
  • 09 A.R.O 18 M.R.O 27 V.R.O 41 V.L.O 50 M.L.O 59 A.L.O
  • 4.3 Measuring method
  • 1 ACU
  • 4.4 Measuring conditions
  • 4.5 Results
  • 5 Simulations
  • 5.1 General
  • 5.2 Whole building CFD simulation, energy modelling, and lab validation
  • 1 ND: Yag laser
  • 1 ACU experimental data – 13,75 meter per second outlet air velocity
  • 2 ACU experimental data – 9,1 meter per second outlet air velocity
  • 4 ACU CFD data – 13,75 meter per second outlet air velocity
  • 5 ACU CFD data – 9,1 meter per second outlet air velocity
  • 9 ACU – 9,1 meters per second CFD versus experimental correlation
  • 10 ACU - 9,1 meters per second CFD versus experimental correlation
  • 5.3 IRF lab CFD modelling performed by Mars Air Systems, LLC
  • 1 Q Heat removed by cooler
  • 2 Q Heat introduced by heater
  • 3 Q Heat introduced by fan
  • 4 Q Heat flow across cells due to pressure differential
  • 5 Q Heat introduced through interior walls and door
  • 6 Q Heat introduced through exterior walls
  • 7 T Climate cell 1 (6,7 °C)
  • 8 T Climate cell 2 (21 °C)
  • 9 Q Heat introduced by cooler
  • 1 Avg. cold cell temp. (°C)
  • 2 Recovery rate
  • 1 Avg. warm cell temp. (°C)
  • 2 Recovery rate
  • 1 T , cold cell (6,7 °C)
  • 2 T , warm cell (21 °C)
  • 1 T , temperature at cold cell conditioner inlet
  • 2 T , temperature at cold cell conditioner outlet (no air curtain)
  • 3 E , energy spent during the first 8 minutes. door open: air curtain OFF = 2 305 kJ
  • 4 E , energy spent during the recovery. door close: air curtain OFF = 761 kJ
  • 1 T , temperature at cold cell conditioner outlet (with air curtain)
  • 2 T , temperature at cold cell conditioner outlet (no air curtain)
  • 1 T , temperature at cold cell conditioner outlet (with air curtain)
  • 2 T , temperature at cold cell conditioner outlet (no air curtain)
  • 5.4 IRF lab CFD modelling performed by Berner International, LLC
  • 6 Conclusion
  • Bibliography

Introduction

This document collects research data that can support the future development of a test method for the energy effectiveness of air curtain units. In large part, air curtain unit are marketed as devices for saving energy at doorway entrances and, as such, a test method is required to measure the value of the effectiveness of an air curtain unit in saving energy at the doorway.

In various parts of the world legislation exists or is being drafted to promote energy saving in buildings. In Europe, the Energy Performance of Buildings Directive lays down the template requirement for EU member states to produce their energy saving regulations such as Part L in the UK, EnEV in Germany, EPN score in The Netherlands or RT2012 in France. In the United States of America, the ASHRAE Standard 90.1 provides details of permitted entrance systems for buildings but air curtain units are currently omitted from this 1) regulation. A number of US air curtain unit manufacturers commissioned a CFD study in 2013 to provide evidence that air curtain unit technology warrants inclusion in the energy codes as a permitted entrance system. In Europe, the impetus has been to develop laboratory-based test methodologies to physically measure the energy effectiveness of air curtain units.

1) Through AMCA, US air curtain unit manufacturers commissioned Dr Wang of Concordia University, Montréal to carry out the study.

FINAL DRAFT Technical Report ISO/DTR 27327-3:2026(en) Fans — Air curtain units — Part 3:

Research tests to determine energy effectiveness

1 Scope

This document reports data for a method of laboratory testing of an air curtain unit to determine its energy effectiveness when used across an open doorway.

This document is not applicable for the determination of energy effectiveness for design, production or field testing.

2 Normative references

There are no normative references in this document.

3 Terms, definitions and symbols

3.1 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https:// www .iso .org/ obp
  • IEC Electropedia: available at https:// www .electropedia .org/

3.1.1 air curtain unit effectiveness

ratio described by the difference in energy loss through an opening without and with the use of an air curtain unit divided by the energy loss without the air curtain unit Note 1 to entry: The energy loss with the use of the air curtain unit includes energy consumption of the air curtain unit.

3.2 Symbols

Symbol Description SI units b Width of door opening m c Specific heat of air kJ/kg-K p E Climate separation effectiveness dimensionless CS E Energy through door opening without ACU w/o ACU E Energy through door opening with ACU withACU h Height of door opening m ṁ Air mass flow rate kg/s Q Heat flow kW

ISO/DTR 27327-3:2026(en) Symbol Description SI units Q Heat in/out from device (cooler or heater)/ environment W x-y

ρ Air density in cold climate cell kg/m

ρ Air density in warm climate cell kg/m

ρ Average air density kg/m avg ΔT Temperature difference K u Outlet air velocity of ACU m/s

4 Independent research facility (IRF) climate chamber (lab) test

4.1 Introduction

A method was developed to measure the energy effectiveness of air curtain units for the purpose of climate separation. Two climate chambers were used with different temperatures separated from each other by a solid wall with a door opening in it. Above the door opening an air curtain unit was installed. Energy flows through the door opening were measured with and without an air curtain unit. Measurements showed that an air curtain unit can reduce the energy exchange through an unprotected open door to up to 80 %.

4.2 Experimental setup

The purpose of the following method is to determine the climate separation effectiveness of an air curtain unit across a door opening.

The measured/calculated heat loss through the door opening is a measure of the so-called climate separation effectiveness of an air curtain unit.

The measurements were made in the dual-climate room. The test facility consists of two separated climate cells in which a particular climate can be established and maintained independently of each other. In this case a temperature of 6,7 [°C] representing the average outdoor dry bulb temperature in The Netherlands was set for one of the climate cells and a temperature of 21 [°C] to represent the indoor condition in the other. A manually operated door (w x h = 2 x 2,3 [m]) was fitted in the wall between the two climate cells and the air curtain unit positioned above this door in the warm cell. See the photos in Figure 1.

a) situation viewed from the warm climate cell b) Situation viewed from the warm climate cell with door closed with door open Figure 1 — Climate cells The vertical thin wires visible in the photos are the thermocouples. Twenty seven thermocouples were fitted in each climate cell in three vertical planes with 3 x 3 = 9 thermocouples in each plane. Five thermocouples were fitted on the cold side of the door opening. This is shown diagrammatically in Figure 2 including the distance to the walls and the distances between the thermocouples.

ISO/DTR 27327-3:2026(en) The thermocouples had two functions:

  • when the door was closed: to determine the average temperature in the climate cells;
  • when the door was open: to record the change in temperature and the distribution of temperature in the climate cells and in the door opening.

Key Thermocouple locations Cold climate cell Door Warm climate cell # Loc. # Loc. # Loc. # Loc. # Loc. # Loc. # Loc.

01 A.L.B 10 M.L.B 19 V.L.B 28 D.B.2 33 V.R.B 42 M.R.B 51 A.R.B

02 A.M.B 11 M.M.B 20 V.M.B 29 D.B.1 34 V.M.B 43 M.M.B 52 A.M.B

03 A.R.B 12 M.R.B 21 V.R.B 30 D.M. 35 V.L.B 44 M.L.B 53 A.L.B

04 A.L.M 13 M.L.M 22 V.L.M 31 D.O.2 36 V.R.M 45 M.R.M 54 A.R.M

05 A.M.M 14 M.M.M 23 V.M.M 32 D.O.1 37 V.M.M 46 M.M.M 55 A.M.M

06 A.R.M 15 M.R.M 24 V.R.M 38 V.L.M 47 M.L.M 56 A.L.M

07 A.L.O 16 M.L.O 25 V.L.O 39 V.R.O 48 M.R.O 57 A.R.O

08 A.M.O 17 M.M.O 26 V.M.O 40 V.M.O 49 M.M.O 58 A.M.O

09 A.R.O 18 M.R.O 27 V.R.O 41 V.L.O 50 M.L.O 59 A.L.O

Figure 2 — Positioning of the thermocouples in the climate cells and in the door opening Table 1 shows the parameters that were measured and saved using the data acquisition system

ISO/DTR 27327-3:2026(en) Table 1 — Parameters measured List of parameters position number unit type of signal T-thermocouples matrix in cell 1 27 [°C] mV T-supply and return glycol cell 1 2 [°C] mV T-thermocouples matrix in cell 2 27 [°C] mV T-supply and return glycol cell 2 2 [°C] mV T-thermocouples in door frame 5 [°C] mV T-discharge of air curtain unit 2 [°C] mV T-Venturi tube for reduced pressure 2 [°C] mV T-water input to air curtain unit 1 [°C] mV T-water output from air curtain unit 1 [°C] mV T-supply glycol duo1 on pipe 1 [°C] mV T-return glycol duo1 on pipe 1 [°C] mV T-external 1 [°C] mV T-internal (lab) 1 [°C] mV Power transport fans cell 1 1 [W] mA Power supplementary heaters + excess pressure fan cell 1 1 [W] mA & pulse Power transport fans cell 2 1 [W] mA Power supplementary heater cell 2 1 [W] mA & pulse Power heater cell 2 1 [W] mA & pulse RH 1 [%] V Pressure difference across pressure channel monitor 1 [Pa] V Pressure difference across door frame 1 [Pa] V Ambient pressure 1 [kPa] V Power consumption of air curtain unit 1 [W] V

Water flow to air curtain unit 1 [m /h] pulse Total number of parameters 84

4.3 Measuring method

The method used to determine the climate effectiveness is still under development and is, therefore, not yet a standard method.

The method used is based on determining the amount of heat transfer through the open door in situations with and without use of the air curtain unit. Previous tests have shown that when the door is open a constant temperature in the climate cells cannot be maintained so that it is not possible to take measurements under stationary air conditions. Therefore, measurements were made for a set 'open time' of the door, after which the door was closed and the initial temperatures in the climate cells were restored. In this case the 'open time' for the door was set at 8 minutes.

The amount of heat transferred through the door opening was determined from the energy balance of the cold climate cell 1. This gives more precise and accurate readings because the air curtain unit in the warm climate cell 2 causes disturbances.

ISO/DTR 27327-3:2026(en) The difference in heat loss (= energy) between the situation with and without the air curtain unit is a measure of the so-called climate separation effectiveness (E ) of an air curtain unit. The E is defined as:

CS CS EE E wo/ ACUwith ACU withACU E  1 CS E E wo//ACU woACU where E is the climate separation effectiveness [-]; CS E is the energy (= heat loss) through the door opening without the air curtain unit [kJ]; w/out ACU E is the energy (= heat loss) through the door opening with the air curtain unit [kJ]. with ACU All energy flows Q from climate cell 1 are indicated with an arrow (→) in Figure 3. Key

1 ACU

2 air out 3 climate cell 1: 6,7 °C 4 climate cell 2: 21 °C 5 air supply 6 Q out-cooler 7 Q in-fan 8 Q in-heater 9 Q in -tr: int 10 Q in-open door 11 Q in -tr: ext Figure 3 — Diagram showing the energy flows in climate cell 1

ISO/DTR 27327-3:2026(en) When the door is closed a stationary situation is formed in which:

QQQQ QQ Q out in out-cooler in-heater in-fan in-tr;extin-tr;iint.

where Q is the heat removal from climate cell 1 cooling system [W]; out-cooler Q is the heat supply from a separate auxiliary heater [W]; (NOTE heater is used to reheat supply in-heater air from the cooler chamber as it is returned to initial conditions so that E can be out-cooler measured more precisely); Q is the heat supply from the motor of the climate system transport fan [W]; in-fan Q is the heat supply from the surroundings by transmission through the walls [W]; in-tr;ext Q is the heat supply from the warm climate cell 2 via transmission through the dividing wall and in-tr;int the door that can be opened [W].

The electrical power consumption is measured for Q and Q . Q , Q , Q , are in-heater in-fan out-cooler in-tr;ext in-tr;int calculated from air volume and temperature difference.

During the situation with 'open door' there is an exchange of air, i.e. warm air flows from climate cell 2 to climate cell 1 and in the reverse direction just as much cold air must flow from climate cell 1 to climate cell 2 because no air is lost. In Figure 3 Q represents the flow of heat [W] from climate cell 2 to climate in-open door cell 1 resulting in a net loss of energy [kJ] from climate cell 2 during the 'open time' of the door. After closing the door this energy has to be removed by cooling in order to restore the desired original temperature in climate cell 1 and thus restore the original stationary situation. As the door opening becomes better protected by the air curtain the heat loss will be reduced and less cooling energy will be required to restore the original situation.

In this project E was determined by taking readings while three different values for E were with ACU w/o ACU used for calculating E :

CS a) 1 - ΔE (ΔE without air curtain, measured) without ACU-measured This is a value that had been obtained from earlier measurements taken during research for the VLA (Vereniging Leveranciers Luchttechnische Apparaten, the Association of Suppliers of Technical Air- Conditioning Appliances). The measured value for an 'open time' of 8 min is -6 134 [kJ]. b) 2 - ΔE (ΔE without air curtain at temp. difference of 1,3 K) without ACU-ΔT14.3K This is a calculated value at a temperature difference ΔT of 21 °C – 6,7 °C = 14,3 [K] between the climate cells. The calculated value for an 'open time' of 8 min is -8 390 [kJ]. This is a calculated value using Formula 1.

c) 3 - ΔE (ΔE without air curtain at measured temp. difference) This is a calculated without ACU-ΔTaveraged value for the actual temperature difference ΔT between the climate cells measured (average of 27 thermocouples) while taking the readings with the air curtain. This is a calculated value using Formula 1.

The theoretical values 2 and 3 have been added because it was found that when the door was open the temperatures in the climate cells could not be kept constant. This affects the temperature difference between the two climate cells and therefore also the driving force for the flow of energy through the door opening and consequently the calculated E value.

CS For the theoretical calculation, Formulae (1), (2) and (3) (below) were used.

Qc bhUTUg/hT T (1) 12pc c

mT(,0480,)004 bh h 1 / (2) av 01

ISO/DTR 27327-3:2026(en)

QmcT (3) p where Q is the heat flow through the door opening [kW]; ṁ is the air mass flow through the door opening [kg/s];

ρ is the density of the air in the cold climate cell = 1,257 [kg/m ];

ρ is the density of the air in the warm climate cell = 1,197 [kg/m ];

ρ is the average density of the air = 1,227 [kg/m ]; av

c is the specific heat of air = 1,006 [kJ/kg K]; p b is the width of the door opening = 2 [m]; h is the height of the door opening = 2,3 [m]; ΔT is the temperature difference between the two climate cells [K].

This gives a value for Q ~ 15,0 [kW] (= 3,3 [W/m ] door opening) at the temperatures of 21 °C and 6,7 [°C]. The value for the 'open time' of 8 minutes is 7 198 [kJ].

The main points of the method used for measuring E were as follows. with ACU - When the temperatures in the climate cells were stable and the situation was stationary the fans of the air curtain unit were started and the door opened about 20 seconds later. The door was then closed again after 8 minutes. Immediately after closing the door the fans of the air curtain unit were switched off. - All the energy flows [J] for the various energy terms shown in Figure 3 (Q , Q , Q , Q out-cooler in-heater in-fan inand Q were determined for each test. The total amount of energy needed for cooling [J] for the tr;ext in-tr;int length of the test was determined by multiplying the stationary energy flow Q [W = J/s] by the out-cooler time [s].

  • Average values per set of readings were used for the calculation, i.e. each scan was regarded as a stationary period.
  • These incoming and outgoing energy flows for all the scans were summed for the whole of the test period. The difference between outgoing and incoming energy is the additional cooling energy required to remove the heat flowing in from climate cell 2 by cooling (E ). This means that for the situation in-open door without the air curtain unit E = E and for the situation with the air curtain unit E in-open door w/o ACU in-open = E .

door with ACU

4.4 Measuring conditions

The measurements were made under the following conditions:

  • Air curtain unit operated in unheated mode.
  • Temperatures of climate cells: climate cell 1: 6,7 [°C] and climate cell 2: 21 [°C];
  • Door opened 20 [s] after switching on the air curtain unit fans
  • ‘Open time’ of door: 8 minutes 2.
  • U-value of climate cells: 0,3 [W/m K] 2.
  • U-value of dividing door: 3,06 [W/m K]
  • Readings taken every 5 seconds and averages of the measured values for two scans saved every 10 seconds
  • Absolute humidity was the same in both climate cells so that there was no vapour pressure difference and therefore no driving force from this. This means that the climate installation cooler only had to cool sensible energy.

ISO/DTR 27327-3:2026(en)

4.5 Results

Figure 4 shows a typical profile from a series of energy effectiveness measurements of a properly sized air curtain unit.

Key E [%] climate separation efficiency, expressed in percent CS U [m/s] ACU outlet air velocity, expressed in meters per second

NOTE These results are based on an ambient outlet temperature. Figure 4 — Climate separation efficiency (E ) as function of the outlet air velocity of the ACU CS The readings are connected by a dotted line on the graphs to show the trends more clearly. It is emphasized that the dotted line only connects the measured points. The variation between two readings can therefore be different. This applies particularly for low values of outlet air velocity.

5 Simulations

5.1 General

Studies of air curtain unit effectiveness continue to be performed using computer simulation software. From the Computational Fluid Dynamics analysis (CFD) of unit performance to the study of entire building energy use using a combination of CFD and energy modelling software, studies are being performed to determine if there is a correlation between laboratory experiments and computer simulations.

5.2 Whole building CFD simulation, energy modelling, and lab validation

5.2.1 Vestibules vs. air curtain units

Vestibules might not to cater to building owners’ taste due to the concerns over space and construction cost. A vestibule could cost anywhere from $20 000 to $60 000. In addition, a vestibule becomes ineffective when both entrance doors open simultaneously during heavy traffic periods so as to allow cold outdoor air to penetrate. Air curtain units, which are typically mounted above doorways, separate indoor and outdoor

ISO/DTR 27327-3:2026(en) temperatures with a stream of air strategically engineered to strike the floor with a particular velocity and position. The air prevents outdoor air infiltration while also permitting an unobstructed pedestrian entryway. An air curtain unit for a single six-foot-wide entrance/exit opening is often less than $6 000 plus installation costs. It also helps to block flying insects, dust, wind, cold/warm, and ambient moisture to achieve a better indoor comfort. Furthermore, building entrances equipped with air curtain units are believed to be more energy efficient than the entrances with single doors and with vestibules as well.

5.2.2 Study investigation

Since 2013, the team of Dr. Liangzhu (Leon) Wang at Concordia University has investigated the energy saving impact of air curtain unit doors (i.e. building entrances fitted with air curtain units) on commercial building whole energy usages compared to single doors (i.e. entrances without air curtain units or vestibules) and vestibule doors (i.e. entrances with vestibules). Three phases of studies have been conducted.

5.2.3 Phase I & II
5.2.3.1 General

In 2013, the first study (Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy [1] Use) was completed. Following in 2016, the second study (Energy Saving Impact of Air Curtain Doors in [2] Commercial Buildings) was finished. Together they conducted about 340 computational fluid dynamics ® 2) (CFD) simulations using ANSYS FLUENT 14.0 to model an air curtain unit under different settings of outdoor and indoor pressure and temperature differences by using the standard k-ε turbulence model. Both winter and summer operational modes of air curtain unit were considered.

...

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms, definitions and symbols
  • 3.1 Terms and definitions
  • 3.1.1 air curtain unit effectiveness
  • 3.2 Symbols
  • 4 Independent Research Facilityresearch facility (IRF) climate chamber (lab) test
  • 4.1 Introduction
  • 4.2 Experimental setup
  • 01 A.L.B 10 M.L.B 19 V.L.B 28 D.B.2 33 V.R.B 42 M.R.B 51 A.R.B
  • 02 A.M.B 11 M.M.B 20 V.M.B 29 D.B.1 34 V.M.B 43 M.M.B 52 A.M.B
  • 03 A.R.B 12 M.R.B 21 V.R.B 30 D.M. 35 V.L.B 44 M.L.B 53 A.L.B
  • 04 A.L.M 13 M.L.M 22 V.L.M 31 D.O.2 36 V.R.M 45 M.R.M 54 A.R.M
  • 05 A.M.M 14 M.M.M 23 V.M.M 32 D.O.1 37 V.M.M 46 M.M.M 55 A.M.M
  • 06 A.R.M 15 M.R.M 24 V.R.M 38 V.L.M 47 M.L.M 56 A.L.M
  • 07 A.L.O 16 M.L.O 25 V.L.O 39 V.R.O 48 M.R.O 57 A.R.O
  • 08 A.M.O 17 M.M.O 26 V.M.O 40 V.M.O 49 M.M.O 58 A.M.O
  • 09 A.R.O 18 M.R.O 27 V.R.O 41 V.L.O 50 M.L.O 59 A.L.O
  • 4.3 Measuring method
  • 1 E 5is the energy (= heat loss) through the door opening
  • 2 Air Q is the energy (= heat loss) through the door opening with the air
  • 3 Climate cell 1: 6.7 °C 7 Qin-fan 11 Qin-tr:ext
  • 4 Climate cell 2: 21 °C 8 Q
  • 1 ACU
  • 6 Qout-cooler
  • 7 Qin-fan
  • 8 Qin-heater
  • 4.4 Measuring conditions
  • 4.5 Results
  • 5 Simulations
  • 5.1 General
  • 5.2 Whole building CFD simulation, energy modelling, and lab validation
  • 2 Door 6 Inside 10 Camera field of view
  • 3 Nozzle 7 Air curtain unit 11 2 nozzles inside ACU
  • 4 Person model 8 Nozzle
  • 1 ND: Yag laser
  • 1 ACU experimental data – 13,75 meter per second outlet air velocity
  • 2 ACU experimental data – 9,1 meter per second outlet air velocity
  • 3 Single door experimental
  • 4 ACU CFD data – 13,75 meter per second outlet air velocity
  • 5 ACU CFD data – 9,1 meter per second outlet air velocity
  • 6 Single door CFD
  • 7 Single door (Yuill, 1996)
  • 8 Vestibule (Yuill, 1996)
  • 9 ACU – 9,1 meters per second CFD versus experimental correlation
  • 10 ACU - 9,1 meters per second CFD versus experimental correlation
  • 1 ACU experimental data – 13,75 meter per second outlet air velocity
  • 2 ACU experimental data – 9,1 meter per second outlet air velocity
  • 4 ACU CFD data – 13,75 meter per second outlet air velocity
  • 5 ACU CFD data – 9,1 meter per second outlet air velocity
  • 9 ACU – 9,1 meters per second CFD versus experimental correlation
  • 10 ACU - 9,1 meters per second CFD versus experimental correlation
  • 5.3 IRF lab CFD modelling performed by Mars Air Systems, LLC
  • 1 Q₁Q1 Heat removed by cooler
  • 2 Q₂Q Heat introduced by heater
  • 3 Q₃Q3 Heat introduced by fan
  • 4 Q₄Q Heat flow across cells due to pressure differential
  • 5 Q₅Q5 Heat introduced through interior walls and door
  • 6 Q₆Q Heat introduced through exterior walls
  • 7 T₁T1 Climate cell 1 (6,7 °C)
  • 8 T₃T Climate cell 2 (21 °C)
  • 9 Q9 Heat introduced by cooler
  • 1 Cold cell conditioner Inlet (6.7 °C at 1.83 m/s)
  • 2 Pressure conditioner outlet
  • 3 Pressure conditioner inlet
  • 4 Warm cell conditioner inlet (21 °C at 4.00 m/s)
  • 5 Cold cell
  • 6 Warm Cell
  • 7 Air curtain unit intake
  • 8 Air curtain unit outlet
  • 9 Cold conditioner outlet
  • 10 Warm conditioner outlet
  • 11 Front view
  • 12 Side View
  • 1 Avg. cold cell temp. (°C)
  • 2 Recovery rate
  • 1 Avg. warm cell temp. (°C)
  • 2 Recovery rate
  • 1 Avg. cold cell temp. (°C) 1 Avg. warm cell temp. (°C)

Introduction

The need for this This document has been apparent for a number of years. This Technical Reportcollects research data that can serve assupport the basisfuture development of a test method for the standard ISO 27327-3. energy effectiveness of air curtain units. In large part, air curtain unit are marketed as devices for saving energy at doorway entrances and, as such, a test method is required to measure the value of the effectiveness of an air curtain unit in saving energy at the doorway. In various parts of the world legislation exists or is being drafted to promote energy saving in buildings. In Europe, the Energy Performance of Buildings Directive lays down the template requirement for EU member states to produce their energy saving regulations such as Part L in the UK, EnEV in Germany, EPN score in The Netherlands or RT2012 in France. In the United States of America, the ASHRAE Standard 90.1 provides details of permitted entrance systems for buildings but air curtain units are currently omitted from this regulation. Through AMCA aA number of US air curtain unit manufacturers commissioned Dr Wang of Concordia 1) University, Montréal to carry out a CFD study in 2013 to provide evidence that air curtain unit technology should be includedwarrants inclusion in the energy codes as a permitted entrance system. In Europe, the impetus has been to develop laboratory -based test methodologies to physically measure the energy effectiveness of air curtain units.

1) Through AMCA, US air curtain unit manufacturers commissioned Dr Wang of Concordia University, Montréal to carry out the study.

ISO #####-#:####(X/DTR 27327-3:(en) Fans — Air curtain units — Part 3:

Research tests to determine energy effectiveness

1 Scope

This document establishesreports data for a method of laboratory testing of an air curtain unit to determine theits energy effectiveness of the unit when used across an open doorway. ISO TR 27327This document is not applicable for establishingthe determination of energy effectiveness for design, production or field testing.

2 Normative references

There are no normative references in this document.

3 Terms, definitions and symbols

3.1 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obphttps://www.iso.org/obp
  • IEC Electropedia: available at https://www.electropedia.org/https://www.electropedia.org/

3.1.1 air curtain unit effectiveness

ratio described by the difference in energy loss through an opening without and with the use of an air curtain unit divided by the energy loss without the air curtain unit Note 1 to entry: The energy loss with the use of the air curtain unit includes energy consumption of the air curtain unit.

3.2 Symbols

A list of symbols used is:

Symbol Description SI units b Width of door opening m cp Specific heat of air kJ/kg-K ECS Climate separation effectiveness dimensionless E Energy through door opening without ACU w/o ACU EwithACU Energy through door opening with ACU h Height of door opening m ṁ Air mass flow rate kg/s Q Heat flow kW

ISO #####-#:####(X/DTR 27327-3:(en) Symbol Description SI units Qx-y Heat in/out from device (cooler or heater)/ environment W

ρ1 Air density in cold climate cell kg/m

ρ0 Air density in warm climate cell kg/m

ρ Average air density kg/m avg ΔT Temperature difference K u Outlet air velocity of ACU m/s

4 Independent Research Facilityresearch facility (IRF) climate chamber (lab) test

4.1 Introduction

A method was developed to measure the energy effectiveness of air curtain units for the purpose of climate separation. Two climate chambers were used with different temperatures separated from each other by a solid wall with a door opening in it. Above the door opening an air curtain unit was installed. Energy flows through the door opening were measured with and without an air curtain unit. Measurements showed that an air curtain unit can reduce the energy exchange through an unprotected open door to up to 80 %.

4.2 Experimental setup

The purpose of the following method is to determine the climate separation effectiveness of an air curtain unit across a door opening.

The measured/calculated heat loss through the door opening is a measure of the so-called climate separation effectiveness of an air curtain unit.

The measurements were made in the dual-climate room. The test facility consists of two separated climate cells in which a particular climate can be established and maintained independently of each other. In this case a temperature of 6,7 [°C] representing the average outdoor dry bulb temperature in The Netherlands was set for one of the climate cells and a temperature of 21 [°C] to represent the indoor condition in the other. A manually operated door (w x h = 2 x 2,3 [m]) was fitted in the wall between the two climate cells and the air curtain unit positioned above this door in the warm cell. See the photos in Figure 1.Figure 1 .

ISO #####-#:####(X/DTR 27327-3:(en)

a) – situation viewed from the warm climate cell with b) – Situation viewed from the warm climate cell with door Inserted Cells door closed open Figure 1 –— Climate cells The vertical thin wires visible in the photos are the thermocouples. Twenty seven thermocouples were fitted in each climate cell in three vertical planes with 3 x 3 = 9 thermocouples in each plane. Five thermocouples were fitted on the cold side of the door opening. This is shown diagrammatically in Figure 2Figure 2 including the distance to the walls and the distances between the thermocouples.

The thermocouples had two functions:

  • Whenwhen the door was closed: to determine the average temperature in the climate cells ;
  • Whenwhen the door was open: to record the change in temperature and the distribution of temperature in the climate cells and in the door opening.

Fig 2 Key:

ISO #####-#:####(X/DTR 27327-3:(en)

Key Thermocouple locations Cold climate cell Door Warm climate cell # Loc. # Loc. # Loc. # Loc. # Loc. # Loc. # Loc.

01 A.L.B 10 M.L.B 19 V.L.B 28 D.B.2 33 V.R.B 42 M.R.B 51 A.R.B

02 A.M.B 11 M.M.B 20 V.M.B 29 D.B.1 34 V.M.B 43 M.M.B 52 A.M.B

03 A.R.B 12 M.R.B 21 V.R.B 30 D.M. 35 V.L.B 44 M.L.B 53 A.L.B

04 A.L.M 13 M.L.M 22 V.L.M 31 D.O.2 36 V.R.M 45 M.R.M 54 A.R.M

05 A.M.M 14 M.M.M 23 V.M.M 32 D.O.1 37 V.M.M 46 M.M.M 55 A.M.M

06 A.R.M 15 M.R.M 24 V.R.M 38 V.L.M 47 M.L.M 56 A.L.M

07 A.L.O 16 M.L.O 25 V.L.O 39 V.R.O 48 M.R.O 57 A.R.O

08 A.M.O 17 M.M.O 26 V.M.O 40 V.M.O 49 M.M.O 58 A.M.O

09 A.R.O 18 M.R.O 27 V.R.O 41 V.L.O 50 M.L.O 59 A.L.O

Figure 2 -— Positioning of the thermocouples in the climate cells and in the door opening

Table 1Table 1 shows the parameters that were measured and saved using the data acquisition system Table 1 — Parameters measured List of parameters position number unit type of signal T-thermocouples matrix in cell 1 27 [°C] mV

ISO #####-#:####(X/DTR 27327-3:(en) T-supply and return glycol cell 1 2 [°C] mV T-thermocouples matrix in cell 2 27 [°C] mV T-supply and return glycol cell 2 2 [°C] mV T-thermocouples in door frame 5 [°C] mV T-discharge of air curtain unit 2 [°C] mV T-Venturi tube for reduced pressure 2 [°C] mV T-water input to air curtain unit 1 [°C] mV T-water output from air curtain unit 1 [°C] mV T-supply glycol duo1 on pipe 1 [°C] mV T-return glycol duo1 on pipe 1 [°C] mV T-external 1 [°C] mV T-internal (lab) 1 [°C] mV Power transport fans cell 1 1 [W] mA Power supplementary heaters + excess pressure fan cell 1 1 [W] mA & pulse Power transport fans cell 2 1 [W] mA Power supplementary heater cell 2 1 [W] mA & pulse Power heater cell 2 1 [W] mA & pulse RH 1 [%] V Pressure difference across pressure channel monitor 1 [Pa] V Pressure difference across door frame 1 [Pa] V Ambient pressure 1 [kPa] V Power consumption of air curtain unit 1 [W] V

Water flow to air curtain unit 1 [m /h] pulse Total number of parameters 84

4.3 Measuring method

The method used to determine the climate effectiveness is still under development and is, therefore, not yet a standard method.

The method used is based on determining the amount of heat transfer through the open door in situations with and without use of the air curtain unit. Previous tests have shown that when the door is open a constant temperature in the climate cells cannot be maintained so that it is not possible to take measurements under stationary air conditions. Therefore, measurements were made for a set 'open time' of the door, after which the door was closed and the initial temperatures in the climate cells were restored. In this case the 'open time' for the door was set at 8 minutes.

The amount of heat transferred through the door opening was determined from the energy balance of the cold climate cell 1. This gives more precise and accurate readings because the air curtain unit in the warm climate cell 2 causes disturbances.

ISO #####-#:####(X/DTR 27327-3:(en)

The difference in heat loss (= energy) between the situation with and without the air curtain unit is a measure of the so-called climate separation effectiveness (E ) of an air curtain unit. The E is defined as:

CS CS 𝐸 − 𝐸 𝐸 w/o ACU with ACU with ACU 𝐸 = = 1 − CS 𝐸 𝐸 w/o ACU w/o ACU where 𝐸 − 𝐸 𝐸 w/o ACU 𝑤𝑖𝑡ℎ 𝐴𝐶𝑈 with ACU 𝐸 = = 1 − 𝐶𝑆 𝐸 𝐸 𝑤/𝑜 𝐴𝐶𝑈 w/o ACU

in which:

E is climate separation effectiveness [-] CS E is energy (= heat loss) through the door opening without the air curtain unit [kJ] w/out ACU

E is energy (= heat loss) through the door opening with the air curtain unit [kJ] with ACU

All energy flows Q from climate cell 1 are indicated with an arrow (→) in Figure 3:

KeE is the climate separation effectiveness [-]; CS Inserted Cells y Inserted Cells Air supply 9 Q in-tr:int

1 E 5is the energy (= heat loss) through the door opening

w/out ACU Deleted Cells without the air curtain unit [kJ]; Deleted Cells 6 Q 10 out-cooler

2 Air Q is the energy (= heat loss) through the door opening with the air

in-open door Deleted Cells OutEwith curtain unit [kJ].

Deleted Cells

ACU Deleted Cells

3 Climate cell 1: 6.7 °C 7 Qin-fan 11 Qin-tr:ext

Deleted Cells

4 Climate cell 2: 21 °C 8 Q

in-heater

ISO #####-#:####(X/DTR 27327-3:(en)

Figure 3 -All energy flows Q from climate cell 1 are indicated with an arrow (→) in Error! Reference source not found..

Key

1 ACU

2 air out 3 climate cell 1: 6,7 °C 4 climate cell 2: 21 °C 5 air supply

6 Qout-cooler

7 Qin-fan

8 Qin-heater

9 Q in-tr:int 10 Q in-open door 11 Q in-tr:ext Figure 3 — Diagram showing the energy flows in climate cell 1

When the door is closed a stationary situation is formed in which:

Q = Q → 𝑄 = 𝑄 → 𝑄 = 𝑄 + 𝑄 + 𝑄 + 𝑄 out in 𝑜𝑢𝑡 𝑖𝑛 𝑜𝑢𝑡−𝑐𝑜𝑜𝑙𝑒𝑟 𝑖𝑛−ℎ𝑒𝑎𝑡𝑒𝑟 𝑖𝑛−𝑓𝑎𝑛 𝑖𝑛−𝑡𝑟;𝑒𝑥𝑡 𝑖𝑛−𝑡𝑟;𝑖𝑛𝑡.

where Q = Q + Q + Q + Q .

out-cooler in-heater in-fan in-tr;ext in-tr;int

where:

Q is the heat removal from climate cell 1 cooling system [W] ]; out-cooler Qin-heater is the heat supply from a separate auxiliary heater; [Note: [W]; (NOTE heater is used to reheat supply air from the cooler chamber as it is returned to initial conditions so that Eout-cooler can be measured more precisely] [W] ); Qin-fan is the heat supply from the motor of the climate system transport fan [W]];

ISO #####-#:####(X/DTR 27327-3:(en) Q is the heat supply from the surroundings by transmission through the walls [W] ]; in-tr;ext Qin-tr;int is the heat supply from the warm climate cell 2 via transmission through the dividing wall and the door that can be opened [W] ].

The electrical power consumption is measured for Q and Q . Q , Q , Q , are calculated in-heater in-fan out-cooler in-tr;ext in-tr;int from air volume and temperature difference.

During the situation with 'open door' there is an exchange of air, i.e. warm air flows from climate cell 2 to climate cell 1 and in the reverse direction just as much cold air must flow from climate cell 1 to climate cell 2 because no air is lost. In Figure 3In Error! Reference source not found. Q represents the flow of heat in-open door [W] from climate cell 2 to climate cell 1 resulting in a net loss of energy [kJ] from climate cell 2 during the 'open time' of the door. After closing the door this energy has to be removed by cooling in order to restore the desired original temperature in climate cell 1 and thus restore the original stationary situation. As the door opening becomes better protected by the air curtain the heat loss will be reduced and less cooling energy will be required to restore the original situation.

In this project E was determined by taking readings while three different values for E were used with ACU w/o ACU for calculating ECS:

a) 1. - ΔEwithout ACU-measured (ΔE without air curtain, measured) This is a value that had been obtained from earlier measurements taken during research for the VLA (Vereniging Leveranciers Luchttechnische Apparaten, the Association of Suppliers of Technical Air- Conditioning Appliances). The measured value for an 'open time' of 8 min is -6 134 [kJ].

b) 2. - ΔE (ΔE without air curtain at temp. difference of 1,3 K) without ACU-ΔT14.3K This is a calculated value at a temperature difference ΔT of 21 °C – 6,7 °C = 14,3 [K] between the climate cells. The calculated value for an 'open time' of 8 min is -8 390 [kJ]. This is a calculated value using equation 1.Error! Reference source not found..

c) 3. - ΔE (ΔE without air curtain at measured temp. difference) This is a without ACU-ΔT averagedΔTaveraged calculated value for the actual temperature difference ΔT between the climate cells measured (average of 27 thermocouples) while taking the readings with the air curtain. This is a calculated value using equation 1. Formula (1).

The theoretical values 2 and 3 have been added because it was found that when the door was open the temperatures in the climate cells could not be kept constant. This affects the temperature difference between the two climate cells and therefore also the driving force for the flow of energy through the door opening and consequently the calculated E value.

CS

ISO #####-#:####(X/DTR 27327-3:(en) For the theoretical calculation, formulas (1), (2)Error! Reference source not found., Error! Reference source not found. and (3)Error! Reference source not found. (below) were used. 1 1 𝑄 = 𝜌 ∙ 𝑐 ∙⋅ 𝑐 ⋅ 𝑏 ∙⋅ ℎ ∙ ∙ 𝑈 ∙ ∆𝑇𝑈 =⋅ ⋅ 𝑈 ⋅ 𝛥𝑇𝑈 ⋅ =⋅ 𝑔 ∙ ℎ ∙ ∆𝑇⁄𝑇 𝑔 ⋅ ℎ ⋅ 𝛥𝑇/𝑇 1 𝑝 𝑝 𝑐 𝑐 𝑐 𝑐 √ 2 √ 2 5 5 (1)

𝑚̇𝑚 = (0. ,48 + 0. ,004 ∙ ∆𝑇) ∙ 𝑏 ∙ ℎ ∙ ℎ ∙ 𝜌 ∙ 1 − 𝜌 ⁄𝜌 ⋅ 𝛥𝑇) ⋅ 𝑏 ⋅ ℎ ⋅ ℎ ⋅ 𝜌 ⋅ 1 − 𝜌 /𝜌 √ 𝑎𝑣 √ 0 1 √ av √ 0 1 (2) 𝑄 = 𝑚̇∙ 𝑐 ∙ ∆𝑇 𝑝

𝑚˙ ⋅ 𝑐 ⋅ 𝛥𝑇 𝑝 (3)

where Q is the heat flow through the door opening [kW]]; ṁ is the air mass flow through the door opening [kg/s]];

ρ is the density of the air in the cold climate cell = 1.,257 [kg/m ] ];

ρ0 is the density of the air in the warm climate cell = 1.,197 [kg/m ] ];

ρ is the average density of the air = 1.,227 [kg/m ] ]; av

cp is the specific heat of air = 1.,006 [kJ/kg K] ]; b is the width of the door opening = 2 [m] ]; h is the height of the door opening = 2.,3 [m] ]; ΔT is the temperature difference between the two climate cells [K] ].

This gives a value for Q ~ 15,0 [kW] (= 3,3 [W/m ] door opening) at the temperatures of 21 °C and 6,7 [°C]. The value for the 'open time' of 8 minutes is 7 198 [kJ].

The main points of the method used for measuring E were as follows. with ACU

  • When the temperatures in the climate cells were stable and the situation was stationary the fans of the air curtain unit were started and the door opened about 20 seconds later. The door was then closed again after 8 minutes. Immediately after closing the door the fans of the air curtain unit were switched off.
  • All the energy flows [J] for the various energy terms shown in Figure 5Figure 3 (Q , Q , Q , out-cooler in-heater in-fan Q and Q were determined for each test. The total amount of energy needed for cooling [J] for the in-tr;ext in-tr;int length of the test was determined by multiplying the stationary energy flow Q [W = J/s] by the time out-cooler [s].
  • Average values per set of readings were used for the calculation, i.e. each scan was regarded as a stationary period.

ISO #####-#:####(X/DTR 27327-3:(en) - These incoming and outgoing energy flows for all the scans were summed for the whole of the test period. The difference between outgoing and incoming energy is the additional cooling energy required to remove the heat flowing in from climate cell 2 by cooling (E ). This means that for the situation without the in-open door air curtain unit Ein-open door = Ew/o ACU and for the situation with the air curtain unit Ein-open door = Ewith ACU.

4.4 Measuring conditions

The measurements were made under the following conditions:

  • Air curtain unit operated in unheated mode.
  • Temperatures of climate cells: climate cell 1: 6,7 [°C] and climate cell 2: 21 [°C];
  • Door opened 20 [s] after switching on the air curtain unit fans
  • ‘Open time’ of door: 8 minutes 2.
  • U-value of climate cells: 0,3 [W/m K] 2.
  • U-value of dividing door: 3,06 [W/m K]
  • Readings taken every 5 seconds and averages of the measured values for two scans saved every 10 seconds
  • Absolute humidity was the same in both climate cells so that there was no vapour pressure difference and therefore no driving force from this. This means that the climate installation cooler only had to cool sensible energy.

4.5 Results

Figure 4Figure 4 shows a typical profile from a series of energy effectiveness measurements of a properly sized air curtain unit.

Outlet temperature: Ambient

2.0 3.0 4.0 5.0 6.0 7.0 8.0

U [m/s]

E [%] CS

ISO #####-#:####(X/DTR 27327-3:(en)

Key Climate separation efficiency, expressed in percent E CS

U0 ACU outlet air velocity, expressed in meters per second NOTE These results are based on an ambient outlet temperature

Key ECS [%] climate separation efficiency, expressed in percent U0 [m/s] ACU outlet air velocity, expressed in meters per second NOTE These results are based on an ambient outlet temperature. Figure 4 –- The climate— Climate separation efficiency (E ) as function of the outlet air velocity of CS the ACU The readings are connected by a dotted line on the graphs to show the trends more clearly. It is emphasized that the dotted line only connects the measured points. The variation between two readings can therefore be different. This applies particularly for low values of outlet air velocity.

ISO #####-#:####(X/DTR 27327-3:(en)

5 Simulations

5.1 General

Studies of air curtain unit effectiveness continue to be performed using computer simulation software. From the Computational Fluid Dynamics analysis (CFD) of unit performance to the study of entire building energy use using a combination of CFD and energy modelling software, studies are being performed to determine if there is a correlation between laboratory experiments and computer simulations.

...