ISO 13347-4:2025
(Main)Fans — Determination of fan sound power levels under standardized laboratory conditions — Part 4: Sound intensity method
Fans — Determination of fan sound power levels under standardized laboratory conditions — Part 4: Sound intensity method
This document specifies a method to measure sound power by using sound intensity measurements on a measurement surface which encloses the sound source. This document provides guidelines on the acoustical environment, ambient noise, measurement surface, and number of measurements. The installation categories are generally designed to represent the physical orientation of a fan installed in accordance with ISO 5801, ISO 13350 and also defined in ISO 13349-1. This document is applicable to fans defined in ISO 5801 and ISO 13349-1. This document is limited to the determination of airborne sound emission for the specified installation categories. Vibration is not measured, nor is the sensitivity of airborne sound emission to vibration effects determined. The sizes of the fan, which can be tested in accordance with this document are limited only by the practical aspects of the test installations.
Ventilateurs - Détermination des niveaux de puissance acoustique des ventilateurs dans des conditions de laboratoire standardisées — Partie 4: Méthode de l'intensité acoustique
Le présent document spécifie la puissance acoustique au moyen de mesurages de l'intensité acoustique, sur une surface de mesure qui enveloppe la source sonore. Le présent document fournit des lignes directrices relatives à l'environnement acoustique, au bruit ambiant, à la surface de mesure et au nombre de mesurages. Les catégories d'installations sont généralement conçues pour représenter l'orientation physique d'un ventilateur installé conformément à l'ISO 5801, l'ISO 13350, et également définies dans l'ISO 13349-1. Le présent document est applicable aux ventilateurs définis dans les ISO 5801 et l'ISO 13349-1. Le présent document se limite à la détermination de l'émission de son aérien pour les catégories d'installations spécifiées. Les vibrations ne sont pas mesurées, et la sensibilité de l'émission de son aérien aux effets des vibrations n'est pas déterminée. Les tailles de ventilateurs qu'il est possible de soumettre à l'essai conformément au présent document sont uniquement limitées par les aspects pratiques des installations d'essai.
General Information
Relations
Standards Content (Sample)
International
Standard
ISO 13347-4
Second edition
Fans — Determination of fan sound
2025-07
power levels under standardized
laboratory conditions —
Part 4:
Sound intensity method
Ventilateurs industriels — Détermination des niveaux de
puissance acoustique des ventilateurs dans des conditions de
laboratoire standardisées —
Partie 4: Méthode de l'intensité acoustique
Reference number
© ISO 2025
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
Contents Page
Foreword .v
Introduction .vi
1 Scope . 1
2 Normative references . 1
3 Terms, definitions and symbols . 2
3.1 Terms and definitions .2
3.2 Symbols — fan sound power levels .3
3.3 Other symbols .3
4 Instruments and methods of test . 4
4.1 General .4
4.2 Reference sound source (RSS) . .5
4.3 Calibration and field check .5
4.4 Performance verification .6
4.5 Test method .6
5 Equipment and installation categories . 6
5.1 Test environment .6
5.1.1 Background noise .6
5.1.2 Nearby reflecting surfaces .7
5.1.3 Reverberation control . . .7
5.2 Fan installation .7
5.2.1 Installation categories . . .7
5.2.2 Aerodynamic performance .8
5.2.3 Mounting methods .8
5.2.4 Duct length .8
5.2.5 Fan total sound testing (installation category E) .9
5.2.6 Fan inlet total sound testing .11
5.2.7 Fan outlet total sound testing .14
5.2.8 Fan casing-radiated sound testing . 15
5.3 Measurement surface . 15
5.4 Reference sound source (RSS) . .18
6 Test method .18
6.1 General .18
6.2 Sampling of sound on the measurement surface .18
6.3 Number of measurements .19
6.4 Observations .19
6.4.1 Point of operation .19
6.4.2 Background sound level .19
6.4.3 Sound intensity .19
6.4.4 Field indicators and qualification requirements . 20
6.4.5 Test conditions . 20
6.4.6 Information to be recorded . 20
7 Calculations .22
7.1 Surface average level . 22
7.2 Reference sound source adjustment, R . 23
W
7.3 Sound power level, L . 23
W
8 Report and results.24
8.1 Uncertainty of results .24
8.2 Presentation of results .24
8.3 Results . .24
8.4 Minimum information to be reported .24
Annex A (informative) Indicators for use in case of difficulty .26
iii
Annex B (normative) Alternative procedure for testing of large fan equipment .27
Annex C (normative) Radiation of sound by fan casing .28
Bibliography .30
iv
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 117, Fans.
This second edition cancels and replaces the first edition (ISO 13347-4:2004), which has been technically
revised. It also incorporates the Technical Corrigendum ISO 13347-4:2004/Cor 1:2006.
The main changes are as follows:
— inclusion of acoustic methods for installation category E fans;
— symbols harmonized with those used in ISO 5801 and other ISO standards listed as normative references [2];
— closer alignment with the superordinate ISO 9614 series relating to sound intensity measurement;
— editorial revisions.
A list of all parts in the ISO 13347 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
v
Introduction
This document establishes a method for determining the sound power level of a fan. The method is
reproducible in all laboratories which are qualified according to the requirements of this document.
The method specified in this document employs standard sound measurement instrumentation. The test
set-ups are generally designed to represent the physical orientation of a fan as installed, in accordance with
ISO 5801 or ISO 13350.
Since sound power levels are considered independent of the acoustic environment around the fan, a
good comparison can be made between two or more fans proposed for any specific air performance
condition. Moreover, these values establish an accurate base for estimating the acoustical outcome of the
fan installation in terms of sound pressure levels. A successful estimate of sound pressure levels requires
extensive information on the fan and the environment in which it is to be located.
It is often advantageous for the equipment user to employ acoustical consultation to ensure that all factors
which affect the final sound pressure levels are considered. More detailed information on the complexity of
this situation may be found in acoustic textbooks.
This document has been developed in response to the need for a reliable and accurate enveloping surface
method for determining the sound power levels of fan equipment. Where possible, it has been based on
existing National standards and combines state-of-the-art with practical considerations.
NOTE The bibliography contains further references for those wishing to explore this subject in greater detail (see
References [1] to [7]).
vi
International Standard ISO 13347-4:2025(en)
Fans — Determination of fan sound power levels under
standardized laboratory conditions —
Part 4:
Sound intensity method
1 Scope
This document specifies a method to measure sound power by using sound intensity measurements on a
measurement surface which encloses the sound source. This document provides guidelines on the acoustical
environment, ambient noise, measurement surface, and number of measurements. The installation
categories are generally designed to represent the physical orientation of a fan installed in accordance with
ISO 5801, ISO 13350 and also defined in ISO 13349-1.
This document is applicable to fans defined in ISO 5801 and ISO 13349-1. This document is limited to
the determination of airborne sound emission for the specified installation categories. Vibration is not
measured, nor is the sensitivity of airborne sound emission to vibration effects determined.
The sizes of the fan, which can be tested in accordance with this document are limited only by the practical
aspects of the test installations.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
ISO 5136, Acoustics — Determination of sound power radiated into a duct by fans and other air-moving devices
— In-duct method
ISO 5801, Fans — Performance testing using standardized airways
ISO 9614-1, Acoustics — Determination of sound power levels of noise sources using sound intensity — Part 1:
Measurement at discrete points
ISO 9614-2, Acoustics — Determination of sound power levels of noise sources using sound intensity — Part 2:
Measurement by scanning
ISO 13347-1, Fans — Determination of fan sound power levels under standardized laboratory conditions —
Part 1: General overview
ISO 13349-1, Fans — Vocabulary and definitions of categories — Part 1: Vocabulary
ISO 13350, Fans — Performance testing of jet fans
IEC 1043, Electroacoustics; Instruments for the measurement of sound intensity; measurement with pairs of
pressure sensing microphones
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 5801, ISO 13349-1 and the
following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
NOTE Some definitions have been expanded to fit the specific needs of this document. Further acoustic definitions
can be found in ISO 13347-1.
3.1.1
fan inlet
opening, usually circular or rectangular, through which the air first enters the fan casing
Note 1 to entry: If the fan is provided with an inlet-connecting flange or spigot, the fan inlet dimensions are measured
inside this connection. The inlet area is the gross area measured inside this flange, i.e. no deductions are made for
blockages, such as motors and bearing supports.
Note 2 to entry: When the inlet area is not clearly defined, agreement can be reached between the parties to the
contract.
Note 3 to entry: The fan inlet is defined by the airflow, when you reverse the airflow, what was previously the outlet,
now becomes the inlet
[SOURCE: ISO 13349-1:2022, 3.7.1]
3.1.2
fan outlet
opening, usually circular or rectangular, through which the air finally leaves the fan casing
Note 1 to entry: If the fan is provided with an outlet connecting flange or spigot, the fan outlet dimensions are
measured inside this connection. When the fan is delivered with a diffuser and the performance is quoted with this
fitted, the area of the fan outlet may be taken as equal to the outlet area of the diffuser.
Note 2 to entry: Fan outlet area is, by convention, taken as the gross area in the outlet plane inside the casing, without
deduction for motor, fairings or other obstructions. When the outlet area is not clearly defined, agreement can be
reached between the parties to the contract.
Note 3 to entry: The fan outlet is defined by the airflow, when you reverse the airflow, what was previously the inlet,
now becomes the outlet
[SOURCE: ISO 13349-1:2022, 3.7.2]
3.1.3
inlet sound power level
sound power level of a fan determined at the fan inlet (3.1.1) in a specified installation category A, B, C, D or E
3.1.4
outlet sound power level
sound power level of a fan determined at the fan outlet (3.1.2) in a specified installation category A, B, C, D or E
3.1.5
casing sound power level
sound power level radiated from a fan casing
Note 1 to entry: If the fan drive is external to the fan casing, the casing sound power shall include the sound power
generated by and radiated from the fan drive
Note 2 to entry: When cataloguing a range of fans, it is not always possible to include the motor noise, as this will vary
according to the power and type of motor selected. Motor noise may then be omitted, provided this fact is clearly stated.
3.2 Symbols — fan sound power levels
Considering all possible combinations for installation conditions specified in ISO 13347-1, seventeen
different sound power level (L ) descriptions are defined in Table 1, for example L .
W W (A,in)
Table 1 — Sound power levels
Number Subscript Description
1 (A,in) free-inlet sound power level, installation category A.
2 (A,in + cas) free-inlet sound power level plus radiated noise; installation category A.
3 (A,out) free-outlet sound power level; installation category A.
4 (A,out + cas) free-outlet sound power level plus radiated noise; installation category A.
5 (B,in) free-inlet sound power level; installation category B.
6 (B,in+cas) free-inlet sound power level plus casing-radiated noise; installation category B.
7 (B,out) ducted outlet sound power level; installation category B.
8 (C,in) ducted inlet sound power level; installation category C.
9 (C,out) free-outlet sound power level; installation category C.
10 (C,out+cas) free-outlet sound power level plus casing-radiated noise; installation category C.
11 (D,in) ducted inlet sound power level; installation category D.
12 (D,out) ducted outlet sound power level; installation category D.
13 (D,cas) casing-radiated sound power level; installation category D.
14 (E,in) non-ducted inlet sound power level; installation category E.
15 (E,out) non-ducted outlet sound power level; installation category E.
16 (E,cas) casing-radiated sound power level; installation category E.
17 (E,tot) total sound power level of a fan, installation category E (includes the contributions from
the inlet, outlet, fan casing and drive).
All of the symbols in this table may be used to indicate levels in one-third octave or octave frequency bands as well as
overall sound power levels and A-weighted sound power levels, provided that the sound power to which the symbols
relate is clearly defined.
Where noise from the drive may contribute to the noise radiated from a casing then this should be clearly stated by
the addition of + dr, e.g. L
WD(),casd+ r
NOTE 1 Not all of the above levels need to be measured for a particular fan.
NOTE 2 For installation category E, the inlet, outlet and casing-radiated sound power level can be established using
sound intensity methods (this document) or in some circumstances, methods using ISO 13347-3.
3.3 Other symbols
For consistency and mutual understanding, it is recommended that the symbols and units shown in Table 2
be used in reporting and calculation.
Table 2 — Symbols and units
Symbol Term SI unit
a, b, c Measurement surface dimensions m
c speed of sound m/s
D quality indicator for sound field directivity dB
D quality indicator for reverberation or reflection dB
E adjustment to sound power level for duct end correction(s) dB
W
E duct inlet end correction dB
W,i
TTabablele 2 2 ((ccoonnttiinnueuedd))
Symbol Term SI unit
E duct outlet end correction dB
W,o
d duct diameter m
d equivalent duct diameter (of rectangular duct) m
e
I sound intensity W/m
W/m
surface average sound intensity
I
I sound intensity I at measurement location n W/m
n
2 −12 2 2
I reference intensity, re 1 pW/m (1 × 10 W/m ) W/m
ref
dB
surface average sound intensity level
L
i
dB
L surface average level of the unsigned sound intensity
i
L fan sound intensity level dB
if
dB
surface average fan sound intensity level
L
if
L RSS sound intensity level dB
iq
dB
L
surface average RSS sound intensity level
iq
-5
L sound pressure level, re 20 µPa (2 x 10 Pa) dB
p
dB
L surface average sound pressure level
p
L recorded sound pressure level of background (noise) as measured over the normal mi- dB
pb
crophone path/position
dB
L surface average of background sound pressure level
pb
-12
L sound power level, re 1 pW (1 x 10 W) dB
W
L sound power level determined without end correction adjustment dB
W,m
L inlet sound power level determined with end correction adjustment dB
W,i
L inlet sound power level determined without end correction adjustment dB
W,m,i
L outlet sound power level determined with end correction adjustment dB
W,o
L outlet sound power level determined without end correction adjustment dB
W,m,o
L Sound power level of the reference sound source (RSS) obtained from the RSS calibration dB
W,q
l duct length m
R sound power level reference source adjustment dB
W
r radius m
ρ density kg/m
S measurement surface area m
S cross-sectional area of inlet at measurement area m
i
S cross-sectional area of outlet at measurement area m
o
2 2
S reference area, 1 m m
ref
z elevation m
4 Instruments and methods of test
4.1 General
Full details of the instrumentation and its requirements are given in ISO 13347-1. Particular requirements
for this document are given in the following subclauses. A sound intensity measurement instrument and
probe that meet the requirements of IEC 1043 shall be used. For sound intensity measurements, the use of
two or more different configurations of the intensity probe, or different probes, may be required to cover
the entire frequency range in conformance with Table 3.
Table 3 — Tolerances for the instrumentation system
One-third octave band Tolerance
centre frequency
dB
Hz
50 to 80 ±1,5
100 to 4 000 ±1,0
5 000 to 8 000 ±1,5
10 000 ±2,0
12 500 ±3,0
4.2 Reference sound source (RSS)
The RSS should periodically be used to qualify the performance of the sound intensity measurement system
and personnel, and to determine a sound power level adjustment for the specific site conditions. To be
used for these purposes, the RSS shall be of an appropriate type, be calibrated accurately and be properly
maintained. The RSS shall be in accordance with the requirements specified in ISO 13347-1.
The useful frequency range for accurate sound intensity measurements is dependent upon the character of
the sound field. Care should be taken to verify that sound intensity measurements are accurate in the actual
measurement environment.
4.3 Calibration and field check
The instrument, including the probe, shall comply with IEC 1043 and be verified regularly in a laboratory.
The calibrator shall be checked at least once every year to verify that its output has not changed. In addition,
an electrical calibration of the instrumentation system over the entire frequency range of interest shall be
performed periodically, at intervals of not more than one year.
Before each sound power determination, the following calibration checks shall be performed. A calibration
check of the entire measuring system at one or more frequencies within the frequency range of interest
shall be made for each microphone. An acoustical calibrator conforming to IEC 1043 shall be used for this
purpose.
In addition to the calibration check, the field check procedure for sound intensity measurement specified by
the manufacturer shall be performed. If no field check procedure is specified, the following procedure shall
be performed.
The intensity probe shall be placed on the measurement surface, oriented normal to the surface, at a position
where the noise is characteristic for the fan equipment under test. The sound intensity shall be measured.
The intensity probe shall be rotated through 180° and placed with its acoustical centre in the same position
as the initial measurement. The sound intensity shall be measured again. The intensity probe should be
mounted on a stand or other mechanical device so that its acoustical centre retains the same position when
the probe is rotated. For the octave band with the highest level, the absolute difference between the two
levels shall be less than the value in Table 4 for the measuring equipment to be acceptable. The two sound
intensities shall be of opposite sign.
Table 4 — Tolerances for difference in sound intensity levels for field check
Octave band Difference
centre frequency
dB
Hz
63 to 125 1,5
250 to 4 000 1,0
8 000 1,5
4.4 Performance verification
Periodically, the performance of the instrumentation system may be verified by determining the sound
power of a reference sound source using the procedures specified in ISO 13347-1.
The sound power level determined for the reference source shall differ from its calibrated value over the
frequency range of interest by no more than the tolerances given in Table 5.
Table 5 — Tolerances for sound power level determined for reference sound source
Octave band Tolerance
centre frequency
dB
Hz
63 ±5,0
125 ±3,0
250 to 500 ±2,0
1 000 to 4 000 ±1,5
8 000 ±2,5
4.5 Test method
The basis of the test method originated in ISO 9614-1 and ISO 9614-2. The test method covers a wider
frequency range and contains requirements somewhat more specific and restrictive than those of
ISO 9614-1 and ISO 9614-2, and also provides for sound power level adjustments as described below. With
the exception of the adjustments, however, measurements made in conformance with this test method will
be in conformance with ISO 9614-1 and ISO 9614-2 over their common frequency range.
The basic requirement is the measurement of the sound intensity distribution around the fan. A measurement
surface is defined which encloses the entire fan, fan inlet, or fan outlet, depending upon the objective of the
test. A set of sound intensity measurements is made about this surface. The results of these measurements
are compared with a set containing half the number of measurements, to ensure the adequacy of the number
of measurements and the accuracy of the data. The sound power level is calculated using the surface area
and the measured sound intensity data. Adjustments shall be made for duct-end corrections, if required, and
based on measurements of a calibrated RSS.
Prior to sound intensity measurements on the source of interest, the sound intensity measurement
instrumentation and personnel are to be qualified by conducting measurements about an RSS.
The sound power levels resulting from the test method can be expected to be identical to those that would
be produced using ISO 13347-2, within the uncertainty of both methods, to the extent that each method is
applicable and that the installations tested are identical. It should be noted that the present method differs
substantially from ISO 13347-2 in both the test environment requirements and the measured quantities.
5 Equipment and installation categories
5.1 Test environment
5.1.1 Background noise
Sound power determination using intensity measurements is inherently less sensitive to background noise
than are methods based on sound pressure measurements (such as ISO 13347-2), although an excessive
amount of background noise will not permit accurate sound power determination by any method. In general,
background noise should not be a problem in using the present method provided that, on the measurement
surface, the sound pressure level of background noise does not exceed the sound pressure level of direct
sound from the fan equipment of interest.
If the background noise is excessive, it is possible that sound power determination according to the
procedures of this document cannot be carried out. For additional information on background noise
monitoring, see 6.4.2.
5.1.2 Nearby reflecting surfaces
If the presence of a nearby reflecting surface interferes with sampling of sound intensity on the measurement
surface, it is possible that sound power determination according to the procedures of this standard cannot
be carried out. To evaluate whether a nearby reflecting surface is in fact the cause of the difficulty, the
procedure of Annex A is recommended.
5.1.3 Reverberation control
In addition to the difficulties associated with nearby reflecting surfaces, diffuse reverberant sound at the
measurement surface can limit the accuracy of sound intensity measurements if this sound is excessive.
In general, reverberant sound should not be a problem in using this standard provided that, on the
measurement surface, the sound pressure level of reverberant sound does not exceed the sound pressure
level of direct sound from the fan equipment of interest.
Excessive reverberation usually can be controlled by introducing a modest amount of sound absorbing
material at the boundaries of an acoustically “hard” (reflective) room. Alternatively, it may be possible
to reduce the relative strength of the reverberant sound by moving the measurement surface closer to
the sound source of interest within the limits of this document, i.e. increasing the direct sound from the
source. Application of this document in a reverberation chamber qualified for use with ISO 13347-2 is
not recommended without use of either supplemental absorption material or special care in defining the
measurement surface, or both.
If reverberant sound is excessive, it is possible that sound power determination according to the procedures
of this document cannot be carried out. To evaluate whether excessive reverberant sound is in fact the cause
of difficulty, the procedure of Annex A is recommended.
5.2 Fan installation
5.2.1 Installation categories
The fan installation conditions conform to the five categories of installation categories specified in
ISO 13349-1.
a) Category A b) Category B
c) Category C d) Category D e) Category E
Figure 1 — Installation categories
— Category A: installation with free inlet and free outlet with a partition (see Figure 1 a).
— Category B: installation with free inlet and ducted outlet (see Figure 1 b).
— Category C: installation with ducted inlet and free outlet (see Figure 1 c).
— Category D: installation with ducted inlet and ducted outlet (see Figure 1 d).
— Category E: free inlet and free outlet without partition (see Figure 1 e).
These installation categories fall into two general test configurations. The first configuration is for a free-
standing unit that would be placed entirely in the test room (see Figure 2). Results of this arrangement yield
the total sound power level (L or L ) of the test unit. The second configuration is for those units that
W,m W
would be tested with a chamber or two-room system and where only the inlet or outlet would discharge
sound into the test room (see Figures 3 or 4).
This arrangement results in ratings of inlet (L or L ) or outlet (L or L ) sound power level only.
W,m,i W,i W,m,o W,o
Note that the subscript «m» indicates that the sound power level is determined from measurements using
a installation category not requiring an end correction adjustment, while values without the subscript «m»
are determined by applying an end correction to measurements on a ducted installation category.
The choice of which installation category is used for a particular fan will depend on the way a product is
expected to be rated and applied in the field.
5.2.2 Aerodynamic performance
Where aerodynamic performance tests are necessary to determine the point of operation of the fan, these
shall be performed as specified in ISO 5801 or ISO 13350.
5.2.3 Mounting methods
Vibration is known to influence airborne sound emission. Vibration effects may be minimised by resilient
mounting of the fan and vibration isolation of any duct used.
The method of mounting fans, of connecting them to non-integral drivers, and of connecting them to
aerodynamic performance test facilities is not specified. Any conventional method may be used, including
vibration isolation devices and short flexible connectors. Other than these, sound and vibration absorptive
material shall not be incorporated in the test fan unless it is a standard part of the unit. Ducts shall be of
metal or other rigid, dense non-absorptive material, and have no exposed sound absorption material on the
interior or exterior surfaces.
The driving motor and drive, when not an integral part of the fan, may be damped or enclosed in any manner
that does not expose sound absorption material within the measurement surface. When the driving motor
and drive are an integral part of the test unit, they shall not be treated in any manner, and normal belt
tensions, bearings and lubricants shall be used.
5.2.4 Duct length
The length of duct shown in Figures 3 and 4 is consistent with the procedures of ISO 5801. Care shall be
exercised to ensure that no duct resonance exists in close proximity to specific frequencies of interest, e.g.,
blade passage frequency.
In chamber or two-room set-ups, the length of duct shall be consistent with acceptable practices from
ISO 5801, which are necessary to accurately establish the point of rating.
Key
1 fan 3 test bench
2 airflow 4 enveloping test measurement surface
Figure 2 — Fan total sound testing (installation category E)
5.2.5 Fan total sound testing (installation category E)
Figure 2 shows the installation category used with a non-ducted inlet and non-ducted outlet (jet) fan
arrangement to establish the fan's total sound power. The total sound power thus consists of three
components: The sound power at the inlet (see 5.2.6), the sound power at the outlet (see 5.2.7) and the sound
power emitted via the fan housing (including attachments, e.g. silencers) (see 5.2.8). The duct end correction
can be taken from Table 6.
Table 6 — Duct end correction for fan total sound testing
Installation type E Sound power level
W
dB
E: Non-ducted inlet 0 L
W (E,tot)
Non-ducted outlet
This test procedure and the above calculations are based on the following assumption that resonances are
not present on either the fan structure, supporting devices, test bench, or driving devices that provide any
significant pure tones that may add to the fan recorded sound levels.
Appurtenances attached to the fan are considered as part of the fan and shall be contained within the test
measurement surface.
a) Installation category A b) Installation category B
c) Installation category C
d) Installation category D
e) Installation category E
Key
1 fan 4 simplified anechoic termination
2 test room 5 transmission element
3 common part 6 measurement surface
a
May require acoustical treatment.
Figure 3 — Fan inlet sound testing
5.2.6 Fan inlet total sound testing
Figure 3 a) to e) shows the installation category to determine sound power on the fan inlet and Table 7 the
corresponding end duct corrections.
Table 7 — Duct end corrections for fan inlet total sound testing
Installation type E Sound power level
W,i
dB
A: Free inlet 0 L
W (A,in)
Free outlet
B: Free inlet 0 L
W (B,in)
Ducted outlet
C: Ducted inlet E L
W,i W (C,in)
Free outlet
D: Ducted inlet E L
W,i W (D,in)
Ducted outlet
E: Non-ducted inlet 0 L
W (E,in)
Non-ducted outlet
This test procedure and calculations are based on the following assumptions.
a) Acoustical energy in an outlet duct which terminates in a second room or chamber does not contribute
to fan test sound pressure levels. This requires adequate transmission loss between adjoining rooms
and the addition of absorptive material within a chamber to absorb this energy.
b) Adequate absorption takes place at the discharge of a duct in a second room or chamber so that any
energy passing down that duct is adequately attenuated.
c) Duct construction is such that the transmission loss through the duct wall is large enough to eliminate
any addition to measured room sound pressure levels.
d) No resonance is present on either the fan structure, supporting devices or driving devices that provide
any significant pure tones that may add to the recorded fan sound pressure levels.
a) Installation category A b) Installation category B
c) Installation category C
d) Installation category D
e) Installation category E
Key
1 fan 4 transmission element
2 test room 5 simplified anechoic termination
3 common part 6 measurement surface
a
May require acoustical treatment.
Figure 4 — Fan outlet sound testing
5.2.7 Fan outlet total sound testing
Figure 4 a) to e) shows the installation category to determine total sound power on the fan outlet and Table 8
the corresponding end duct corrections.
Table 8 — Duct end corrections for fan outlet total sound testing
Installation type E Sound power level
W,o
dB
A: Free inlet 0 L
W (A,out)
Free outlet
B: Free inlet E L
W,o W (B,out)
Ducted outlet
C: Ducted inlet 0 L
W (C,out)
Free outlet
D: Ducted inlet E L
W,o W (D,out)
Ducted outlet
E: Non-ducted inlet 0 L
W (E,out)
Non-ducted outlet
This test procedure and calculations are based on the following assumptions.
a) Acoustical energy in an inlet duct which terminates in a second room or chamber does not contribute to
fan test sound pressure levels. This requires adequate transmission loss between adjoining rooms and
the addition of absorptive material within a chamber to absorb this energy.
b) Adequate absorption takes place at the discharge of a duct in a second room or chamber so that any
energy passing down that duct is adequately attenuated.
c) Duct construction is such that the transmission loss through the duct wall is large enough to eliminate
any addition to measured room sound pressure levels.
d) No resonances is present on either the fan structure, supporting devices or driving devices that provide
any significant pure to
...
Norme
internationale
ISO 13347-4
Deuxième édition
Ventilateurs industriels —
2025-07
Détermination des niveaux
de puissance acoustique des
ventilateurs dans des conditions de
laboratoire standardisées —
Partie 4:
Méthode de l'intensité acoustique
Fans — Determination of fan sound power levels under
standardized laboratory conditions —
Part 4: Sound intensity method
Numéro de référence
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2025
Tous droits réservés. Sauf prescription différente ou nécessité dans le contexte de sa mise en œuvre, aucune partie de cette
publication ne peut être reproduite ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique,
y compris la photocopie, ou la diffusion sur l’internet ou sur un intranet, sans autorisation écrite préalable. Une autorisation peut
être demandée à l’ISO à l’adresse ci-après ou au comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Case postale 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Genève
Tél.: +41 22 749 01 11
E-mail: copyright@iso.org
Web: www.iso.org
Publié en Suisse
ii
Sommaire Page
Avant-propos .v
Introduction .vi
1 Domaine d'application . 1
2 Références normatives . 1
3 Termes et définitions, symboles et unités . 2
3.1 Termes et définitions .2
3.2 Symboles — Niveaux de puissance acoustique du ventilateur .3
3.3 Autres symboles .4
4 Appareillage et méthodes d'essai . 5
4.1 Généralités .5
4.2 Source sonore de référence (RSS) .5
4.3 Étalonnage et contrôle sur site .5
4.4 Vérification des performances .6
4.5 Méthode d'essai .6
5 Équipement et catégories d'installation . . 7
5.1 Environnement d'essai .7
5.1.1 Bruit de fond .7
5.1.2 Surfaces réfléchissantes avoisinantes .7
5.1.3 Contrôle de la réverbération .7
5.2 Installation du ventilateur .8
5.2.1 Catégories d'installation . .8
5.2.2 Essai aérodynamique .8
5.2.3 Méthodes de montage .9
5.2.4 Longueur du conduit .9
5.2.5 Essai acoustique global du ventilateur (catégorie d'installation E) .10
5.2.6 Essai acoustique total de l'aspiration du ventilateur . 12
5.2.7 Essai acoustique total du refoulement du ventilateur .14
5.2.8 Essai de son rayonné par l'enveloppe du ventilateur .16
5.3 Surface de mesure .16
5.4 Source sonore de référence (RSS) .19
6 Méthode d'essai . 19
6.1 Généralités .19
6.2 Échantillonnage du son sur la surface de mesure .19
6.3 Nombre de mesurages . 20
6.4 Observations . 20
6.4.1 Point de fonctionnement . 20
6.4.2 Niveau de bruit de fond. 20
6.4.3 Intensité acoustique .21
6.4.4 Indicateurs de champ et exigences de qualification .21
6.4.5 Conditions d'essai .21
6.4.6 Informations à enregistrer . 22
7 Calculs .23
7.1 Niveau moyen surfacique . 23
7.2 Ajustement de la source sonore de référence, R .24
W
7.3 Niveau de puissance acoustique, L . 25
W
8 Rapport et résultats .25
8.1 Incertitude des résultats . 25
8.2 Présentation des résultats . 25
8.3 Résultats . 25
8.4 Informations minimales à consigner . 26
Annexe A (informative) Indicateurs à utiliser en cas de problème .28
iii
Annexe B (normative) Mode opératoire de remplacement pour l'essai de systèmes de
ventilateurs de grande taille .29
Annexe C (normative) Son rayonné par l'enveloppe du ventilateur .31
Bibliographie .33
iv
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux
de normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général
confiée aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire
partie du comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (IEC) en ce qui concerne la normalisation électrotechnique.
Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont
décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier, de prendre note des différents
critères d'approbation requis pour les différents types de documents ISO. Le présent document a
été rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir
www.iso.org/directives).
L’ISO attire l’attention sur le fait que la mise en application du présent document peut entraîner l’utilisation
d’un ou de plusieurs brevets. L’ISO ne prend pas position quant à la preuve, à la validité et à l’applicabilité de
tout droit de propriété revendiqué à cet égard. À la date de publication du présent document, l’ISO n'avait pas
reçu notification qu’un ou plusieurs brevets pouvaient être nécessaires à sa mise en application. Toutefois,
il y a lieu d’avertir les responsables de la mise en application du présent document que des informations
plus récentes sont susceptibles de figurer dans la base de données de brevets, disponible à l'adresse
www.iso.org/brevets. L’ISO ne saurait être tenue pour responsable de ne pas avoir identifié tout ou partie de
tels droits de propriété.
Les appellations commerciales éventuellement mentionnées dans le présent document sont données pour
information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer un engagement.
Pour une explication de la nature volontaire des normes, la signification des termes et expressions
spécifiques de l'ISO liés à l'évaluation de la conformité, ou pour toute information au sujet de l'adhésion de
l'ISO aux principes de l’Organisation mondiale du commerce (OMC) concernant les obstacles techniques au
commerce (OTC), voir www.iso.org/avant-propos.
Le présent document a été élaboré par le comité technique ISO/TC 117, Ventilateurs.
Cette deuxième édition annule et remplace la première édition (ISO 13347-4:2004), qui a fait l’objet d’une
révision technique. Elle incorpore également le Rectificatif technique ISO 13347-4:2004/Cor 1:2006.
Les principales modifications sont les suivantes:
— inclusion de méthodes acoustiques pour les ventilateurs de catégorie d’installation E;
— harmonisation des symboles avec ceux utilisés dans l’ISO 5801 et dans les autres normes citées en
[2]
références normatives ;
— alignement plus proche avec la série de normes superordonnée ISO 9614 relative à la mesure de l’intensité
acoustique;
— révisions rédactionnelles.
Une liste de toutes les parties de la série ISO 13347 se trouve sur le site web de l’ISO.
Il convient que l’utilisateur adresse tout retour d’information ou toute question concernant le présent
document à l’organisme national de normalisation de son pays. Une liste exhaustive desdits organismes se
trouve à l’adresse www.iso.org/fr/members.html.
v
Introduction
Le présent document établit une méthode de détermination du niveau de puissance acoustique d'un
ventilateur. La méthode est reproductible dans tous les laboratoires qualifiés conformément aux exigences
du présent document.
La méthode emploie un appareillage de mesure acoustique type. Les installations d'essai sont généralement
conçues pour représenter l'orientation physique d'un ventilateur tel qu’installé, conformément à l'ISO 5801
ou à l'ISO 13350.
Puisque les niveaux de puissance acoustique sont considérés comme étant indépendants de l'environnement
acoustique autour du ventilateur, il est possible d'effectuer une comparaison correcte entre deux ou plusieurs
ventilateurs, proposés pour toute condition de performance d'aérage spécifique. De plus, ces valeurs
établissent une base précise pour l'estimation des résultats acoustiques de l'installation du ventilateur,
en termes de niveaux de pression acoustique. Une estimation réussie des niveaux de pression acoustique
requiert des informations détaillées sur le ventilateur et l’environnement dans lequel il est placé.
Il est souvent avantageux pour l'utilisateur de l'équipement d'utiliser une consultation acoustique afin
de garantir que tous les facteurs qui influencent les niveaux de pression acoustique finaux sont pris en
considération. Des informations plus détaillées sur la complexité de cette situation peuvent être trouvées
dans des ouvrages traitant d'acoustique.
Le présent document a été élaboré en vue de répondre au besoin d'une méthode par surface enveloppante,
fiable et précise pour déterminer les niveaux de puissance acoustique des systèmes de ventilateurs. Dans la
mesure du possible, il est basé sur des Normes nationales existantes et combine l'état actuel des réalisations
et des considérations pratiques.
NOTE La bibliographie contient davantage de références pour ceux qui souhaitent explorer ce sujet plus en détails
(voir les Références [1] à [7]).
vi
Norme internationale ISO 13347-4:2025(fr)
Ventilateurs industriels — Détermination des niveaux de
puissance acoustique des ventilateurs dans des conditions de
laboratoire standardisées —
Partie 4:
Méthode de l'intensité acoustique
1 Domaine d'application
Le présent document spécifie la puissance acoustique au moyen de mesurages de l'intensité acoustique, sur
une surface de mesure qui enveloppe la source sonore. Le présent document fournit des lignes directrices
relatives à l'environnement acoustique, au bruit ambiant, à la surface de mesure et au nombre de mesurages.
Les catégories d'installations sont généralement conçues pour représenter l'orientation physique d'un
ventilateur installé conformément à l'ISO 5801, l'ISO 13350, et également définies dans l'ISO 13349-1.
Le présent document est applicable aux ventilateurs définis dans les ISO 5801 et l'ISO 13349-1. Le présent
document se limite à la détermination de l'émission de son aérien pour les catégories d'installations
spécifiées. Les vibrations ne sont pas mesurées, et la sensibilité de l'émission de son aérien aux effets des
vibrations n'est pas déterminée.
Les tailles de ventilateurs qu'il est possible de soumettre à l'essai conformément au présent document sont
uniquement limitées par les aspects pratiques des installations d'essai.
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent document. Pour les
références datées, seule l'édition citée s'applique. Pour les références non datées, la dernière édition de la
publication à laquelle il est fait référence s'applique (y compris tous les amendements).
ISO 5136, Acoustique — Détermination de la puissance acoustique rayonnée dans un conduit par des ventilateurs
et d'autres systèmes de ventilation — Méthode en conduit
ISO 5801, Ventilateurs — Essais aérauliques sur circuits normalisés
ISO 9614-1, Acoustique — Détermination par intensimétrie des niveaux de puissance acoustique émis par les
sources de bruit — Partie 1: Mesurages par points
ISO 9614-2, Acoustique — Détermination par intensimétrie des niveaux de puissance acoustique émis par les
sources de bruit — Partie 2: Mesurage par balayage
ISO 13347-1, Ventilateurs industriels — Détermination des niveaux de puissance acoustique des ventilateurs
dans des conditions de laboratoire normalisées — Partie 1: Présentation générale
ISO 13349-1, Ventilateurs — Vocabulaire et définitions des catégories — Partie 1: Vocabulaire
ISO 13350, Ventilateurs — Essai de performance des ventilateurs accélérateurs
IEC 1043, Électroacoustique — Instruments pour la mesure de l’intensité acoustique — Mesure au moyen d’une
paire de microphones de pression
3 Termes et définitions, symboles et unités
3.1 Termes et définitions
Pour les besoins du présent document, les termes et définitions donnés dans l'ISO 5801, et l'ISO 13349-1,
ainsi que les suivants s'appliquent.
L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation,
consultables aux adresses suivantes:
— ISO Online browsing platform: disponible à l'adresse https:// www .iso .org/ obp
— IEC Electropedia: disponible à l'adresse https:// www .electropedia .org/
NOTE Certaines définitions ont été élargies pour s'adapter aux besoins spécifiques du présent document. D'autres
définitions acoustiques peuvent être trouvées dans l'ISO 13347-1.
3.1.1
ouïe d'aspiration du ventilateur
orifice, généralement circulaire ou rectangulaire, par lequel l'air pénètre dans l'enveloppe du ventilateur
Note 1 à l'article: Lorsque le ventilateur est muni d'une bride ou d'une manchette d'aspiration, les dimensions de
l'ouïe d'aspiration du ventilateur sont mesurées à l'intérieur de cet élément. L'aire de l'ouïe d'aspiration est l'aire brute
mesurée à l'intérieur de la bride, c'est-à-dire qu'aucune déduction ne doit être faite pour les obstacles tels que les
moteurs, les supports de paliers, etc.
Note 2 à l'article: Quand l'aire de l'ouïe d'aspiration n'est pas clairement définie, un accord peut être conclu entre les
parties prenantes au contrat.
Note 3 à l'article: l'ouïe d'aspiration du ventilateur est définie par le flux d'air; lorsque le flux d'air est inversé, ce qui
était auparavant le refoulement, devient maintenant l’aspiration.
[SOURCE: ISO 13349-1:2022, 3.7.1]
3.1.2
ouïe de refoulement du ventilateur
orifice, généralement circulaire ou rectangulaire, par lequel l'air quitte l'enveloppe du ventilateur
Note 1 à l'article: Lorsque le ventilateur est muni d'une bride ou d'une manchette de refoulement, les dimensions de
l'ouïe de refoulement du ventilateur sont mesurées à l'intérieur de cet élément. Quand le ventilateur est livré avec un
diffuseur et que la performance est indiquée avec ce diffuseur monté, l’aire de l'ouïe de refoulement du ventilateur
peut être considérée comme étant égale à l'aire de l'ouïe de refoulement du diffuseur.
Note 2 à l'article: L'aire de l'ouïe de refoulement du ventilateur est, par convention, considérée comme la surface
brute dans le plan de refoulement à l'intérieur de l'enveloppe, sans déduction pour le moteur, carénages ou autres
obstructions. Quand l'aire de l'ouïe de refoulement n'est pas clairement définie, un accord peut être conclu entre les
parties prenantes au contrat.
Note 3 à l'article: l'ouïe de refoulement du ventilateur est définie par le flux d'air; lorsque le flux d'air est inversé, ce qui
était auparavant l’aspiration, devient maintenant le refoulement.
[SOURCE: ISO 13349-1:2022, 3.7.2]
3.1.3
niveau de puissance acoustique de l'aspiration
niveau de puissance acoustique d'un ventilateur, déterminé à l’aspiration du ventilateur (3.1.1), selon une
catégorie d'installation spécifiée, A, B, C, D ou E
3.1.4
niveau de puissance acoustique du refoulement
niveau de puissance acoustique d'un ventilateur, déterminé au refoulement du ventilateur (3.1.2), selon une
catégorie d'installation spécifiée, A, B, C, D ou E
3.1.5
niveau de puissance acoustique de l'enveloppe
niveau de puissance acoustique rayonné par l'enveloppe d'un ventilateur
Note 1 à l'article: Si l'entraînement du ventilateur se situe à l'extérieur de l'enveloppe, la puissance acoustique de
l’enveloppe doit inclure la puissance acoustique générée et rayonnée par l'entraînement du ventilateur.
Note 2 à l'article: Lors du catalogage d'une série de ventilateurs, il n'est pas toujours possible d'inclure le bruit du
moteur, étant donné que ce dernier varie selon la puissance et le type de moteur choisi. Le bruit du moteur peut donc
être omis, à condition que ce fait soit clairement énoncé.
3.2 Symboles — Niveaux de puissance acoustique du ventilateur
Étant donné toutes les combinaisons possibles relatives aux conditions d'installation et spécifiées dans
l'ISO 13347-1, dix-sept descriptions de niveaux de puissance acoustique (L ) différents sont définies dans le
W
Tableau 1, par exemple L (A,in).
W
Tableau 1 — Niveaux de puissance acoustique
Numéro Suffixe Description
1 (A,in) niveau de puissance acoustique de l'aspiration libre; catégorie d'installation A.
niveau de puissance acoustique de l’aspiration libre plus bruit rayonné; catégorie d'ins-
2 (A,in + cas)
tallation A.
3 (A,out) niveau de puissance acoustique du refoulement libre; catégorie d'installation A.
niveau de puissance acoustique du refoulement libre, plus bruit rayonné; catégorie
4 (A,out + cas)
d'installation A.
5 (B,in) niveau de puissance acoustique de l'aspiration libre; catégorie d'installation B.
niveau de puissance acoustique de l’aspiration libre plus le bruit rayonné par l'enveloppe;
6 (B,in+cas)
catégorie d'installation B.
7 (B,out) niveau de puissance acoustique de la refoulement en conduit; catégorie d'installation B.
8 (C,in) niveau de puissance acoustique de l’aspiration en conduit; catégorie d'installation C.
9 (C,out) niveau de puissance acoustique de la refoulement libre; catégorie d'installation C.
10 (C,out+cas) niveau de puissance acoustique de la refoulement libre plus le bruit rayonné par l'enve-
loppe; catégorie d'installation C.
11 (D,in) niveau de puissance acoustique de l'aspiration en conduit; catégorie d'installation D.
12 (D,out) niveau de puissance acoustique de la refoulement en conduit; catégorie d'installation D.
13 (D,cas) niveau de puissance acoustique rayonnée par l'enveloppe; catégorie d'installation D.
14 (E,in) niveau de puissance acoustique de l'aspiration non en conduit; catégorie d'installation E.
15 (E,out) niveau de puissance acoustique de la sortie non en conduit; catégorie d'installation E.
16 (E,cas) niveau de puissance acoustique rayonné par l’enveloppe; catégorie d’installation E.
17 (E,tot) niveau de puissance acoustique total d’un ventilateur, catégorie d'installation E (inclut
les contributions de l'aspiration, de la sortie, de l'enveloppe et de l'entraînement du
ventilateur).
Tous les symboles de ce tableau peuvent être utilisés pour indiquer les niveaux par bandes de fréquences d'un tiers
d'octave ou d'octave, ainsi que les niveaux de puissance acoustique globale et les niveaux de puissance acoustique
pondérés A, à condition que la puissance acoustique à laquelle les symboles se rapportent soit clairement définie.
Lorsque le bruit de l'entraînement peut contribuer au bruit rayonné par une enveloppe, il convient de l'indiquer clai-
rement en ajoutant + dr, e.g. L
WD(),casd+ r
NOTE 1 Il n'est pas nécessaire de mesurer tous les niveaux ci-dessus pour un ventilateur particulier.
NOTE 2 Pour la catégorie d'installation E, le niveau de puissance acoustique à l’aspiration, au refoulement et rayonné
par l'enveloppe peut être établi à l'aide des méthodes d'intensité acoustique (présent document) ou, dans certaines
circonstances, à l'aide des méthodes utilisant l’ISO 13347-3.
3.3 Autres symboles
Dans un but de cohérence et de compréhension mutuelle, il est recommandé d'utiliser les symboles et unités
du Tableau 2 dans les rapports et les calculs.
Tableau 2 — Symboles, unités
Symbole Description Unité SI
a, b, c dimensions de la surface de mesure m
c vitesse du son m/s
D indicateur de qualité pour la directivité du champ acoustique dB
D indicateur de qualité pour la réverbération ou la réflexion dB
E ajustement du niveau de puissance acoustique pour la (les) correction(s) d'extrémité dB
W
du conduit
E correction d'extrémité de l’aspiration en conduit dB
W,i
E correction d'extrémité du refoulement en conduit dB
W,o
d diamètre du conduit m
d diamètre du conduit équivalent (du conduit rectangulaire) m
e
I intensité acoustique W/m
W/m
intensité acoustique moyenne surfacique
I
I intensité acoustique I à l'emplacement de mesure n W/m
n
2 −12 2 2
I intensité de référence, référence 1 pW/m (1 × 10 W/m ) W/m
ref
dB
niveau d'intensité acoustique moyen surfacique
L
i
dB
L niveau moyen surfacique de l'intensité acoustique non signé
i
L niveau d'intensité acoustique du ventilateur dB
if
dB
niveau d'intensité acoustique moyen surfacique du ventilateur
L
if
L niveau d'intensité acoustique de la source sonore de référence dB
iq
dB
L niveau d'intensité acoustique moyen surfacique de la source sonore de référence
iq
−5
L niveau de pression acoustique, référence 20 µPa (2 x 10 Pa) dB
p
dB
L niveau de pression acoustique moyen surfacique
p
L niveau de pression acoustique enregistré du bruit de fond de la salle tel que mesuré sur dB
pb
la trajectoire/position microphonique normale
dB
L niveau de pression acoustique moyen surfacique du bruit de fond
pb
−12
L niveau de puissance acoustique, référence 1 pW (1 x 10 W) dB
W
L niveau de puissance acoustique déterminé sans ajustement de correction d'extrémité dB
W,m
L niveau de puissance acoustique de l'aspiration déterminé avec ajustement de correction dB
W,i
d'extrémité
L niveau de puissance acoustique de l'aspiration déterminé sans ajustement de correction dB
W,m,i
d'extrémité
L niveau de puissance acoustique de la sortie déterminé avec ajustement de correction dB
W,o
d'extrémité
L niveau de puissance acoustique de la sortie déterminé sans ajustement de correction dB
W,m,o
d'extrémité
L niveau de puissance acoustique de la source sonore de référence (RSS) obtenu à partir dB
W,q
de l'étalonnage RSS
l longueur du conduit m
R ajustement du niveau de puissance acoustique de la source de référence dB
W
r rayon m
TTabableleaauu 2 2 ((ssuuiitte)e)
Symbole Description Unité SI
ρ densité kg/m
S aire de la surface de mesure m
S aire transversale de l'aspiration au niveau de l'aire de mesure m
i
S aire transversale de la sortie au niveau de l'aire de mesure m
o
2 2
S aire de référence, 1 m m
ref
z élévation m
4 Appareillage et méthodes d'essai
4.1 Généralités
La description détaillée de l'appareillage de mesure et des exigences associées est fournie dans l'ISO 13347-1.
Les exigences spécifiques concernant le présent document sont fournies dans les paragraphes ci-après. Un
instrument de mesure de l'intensité acoustique et une sonde conformes aux exigences de l’IEC 1043 doivent
être utilisés. Pour les mesurages de l'intensité acoustique, l'utilisation de deux configurations de la sonde
d'intensité différentes ou plus, ou encore de différentes sondes, peut être requise pour couvrir le domaine de
fréquences global conformément au Tableau 3.
Tableau 3 — Tolérances relatives à l'appareillage de mesure
Fréquence médiane des bandes Tolérance
de tiers d'octave
dB
Hz
50 à 80 ±1,5
100 à 4 000 ±1,0
5 000 à 8 000 ±1,5
10 000 ±2,0
12 500 ±3,0
4.2 Source sonore de référence (RSS)
Il convient que la source sonore de référence soit périodiquement utilisée pour qualifier les performances
du système de mesure de l'intensité acoustique et du personnel et pour déterminer un ajustement du niveau
de puissance acoustique destiné aux conditions spécifiques du site. À cette fin, la source sonore de référence
doit être du type approprié, étalonnée de façon précise et entretenue de façon adéquate. La source sonore de
référence doit être conforme aux exigences spécifiées dans l'ISO 13347-1.
Le domaine de fréquences utile pour les mesurages exacts de l'intensité acoustique dépend du caractère du
champ acoustique. Il convient de vérifier avec soin que les mesurages de l'intensité acoustique sont exacts
dans l'environnement de mesure réel.
4.3 Étalonnage et contrôle sur site
L’appareillage, y compris la sonde, doit être conforme à l’IEC 1043 et vérifié régulièrement dans un laboratoire.
Le calibreur doit être contrôlé au moins une fois par an afin de vérifier que sa sortie n'a pas changé. De plus,
un étalonnage électrique de l'appareillage de mesure sur l'ensemble du domaine de fréquences d'utilisation
doit être effectué périodiquement, à des intervalles ne dépassant pas un an.
Avant chaque détermination de la puissance acoustique, les contrôles d'étalonnage suivants doivent être
effectués. Un contrôle d'étalonnage de l'ensemble du système de mesure, à une ou plusieurs fréquences dans
le domaine de fréquences concerné, doit être effectué pour chaque microphone. À cette fin, un calibreur
acoustique conforme à l’IEC 1043 doit être utilisé.
Outre le contrôle d'étalonnage, un contrôle selon le mode opératoire de vérification sur le terrain pour le
mesurage de l'intensité acoustique, spécifié par le fabricant, doit être effectué. Si aucun mode opératoire
pour le contrôle sur le terrain n’est spécifié, le mode opératoire ci-après doit être respecté.
La sonde d'intensité doit être placée sur la surface de mesure, orientée perpendiculairement, à une position
où le bruit est caractéristique du système de ventilateur soumis à l'essai. L'intensité acoustique doit être
mesurée. La sonde d’intensité doit faire l'objet d'une rotation à 180° et être placée de sorte que son centre
acoustique se trouve à la même position que pour le mesurage initial. L'intensité acoustique doit être de
nouveau mesurée. Il convient que la sonde d'intensité soit montée sur un support ou un autre dispositif
mécanique de sorte que son centre acoustique reste dans la même position lors de la rotation. Pour la bande
d'octave avec le niveau le plus élevé, la différence absolue entre les deux niveaux doit être inférieure à la
valeur du Tableau 4 afin que l'équipement de mesure soit acceptable. Les deux intensités acoustiques doivent
être de signe opposé.
Tableau 4 — Tolérances relatives aux différences des niveaux d'intensité acoustique
pour la vérification sur le terrain
Fréquence médiane Différence
des bandes d'octave
dB
Hz
63 à 125 1,5
250 à 4 000 1,0
8 000 1,5
4.4 Vérification des performances
Les performances de l'appareillage de mesure peuvent être vérifiées périodiquement en déterminant
la puissance acoustique d'une source sonore de référence à l'aide des modes opératoires spécifiés dans
l'ISO 13347-1.
Le niveau de puissance acoustique déterminé pour la source de référence doit, par rapport à sa valeur
étalonnée sur le domaine de fréquences représentatif, rester dans les limites des tolérances fournies dans le
Tableau 5.
Tableau 5 — Tolérances relatives au niveau de puissance acoustique déterminé
pour la source sonore de référence
Fréquence médiane Tolérance
des bandes d'octave
dB
Hz
63 ±5,0
125 ±3,0
250 à 500 ±2,0
1 000 à 4 000 ±1,5
8 000 ±2,5
4.5 Méthode d'essai
La base de la méthode d'essai est issue de l'ISO 9614-1 et ISO 9614-2. La présente méthode d'essai couvre une
gamme de fréquences plus large et inclut des exigences en quelques sortes plus spécifiques et restrictives
que celles de l'ISO 9614-1 et de l'ISO 9614-2; elle fournit en outre des ajustements du niveau de puissance
acoustique, tels que décrits ci-après. A l'exception des ajustements, toutefois, les mesurages effectués
conformément à cette méthode d'essai respectent les exigences de l'ISO 9614-1 et de l'ISO 9614-2 sur leur
gamme de fréquences commune.
L'exigence élémentaire est le mesurage de la distribution de l'intensité acoustique autour du ventilateur. Une
surface de mesure qui enveloppe l'ensemble du ventilateur, l'aspiration du ventilateur ou sa sortie, selon
l'objectif de l'essai, est définie. Une série de mesurages de l'intensité acoustique est effectuée par rapport à
cette surface. Les résultats de ces mesurages sont comparés à une série contenant la moitié des mesurages
afin de garantir l'adéquation du nombre de mesurages et la précision des données. Le niveau de puissance
acoustique est calculé en utilisant l'aire de la surface et les données de l'intensité acoustique mesurée. Des
ajustements doivent être effectués pour les corrections d'extrémité du conduit, le cas échéant, sur la base
des mesurages d'une source sonore de référence étalonnée.
Avant de mesurer l'intensité acoustique sur la source concernée, l'appareillage de mesure de l'intensité
acoustique ainsi que le personnel sont à qualifier en effectuant des mesurages sur une source sonore de
référence.
Il peut être attendu que les niveaux de puissance acoustique issus de la méthode d'essai soient identiques
à ceux obtenus grâce à l'ISO 13347-2, dans les limites d'incertitude des deux méthodes et dans la mesure
où chaque méthode s'applique et les installations soumises à l'essai sont identiques. Il convient de noter
que la présente méthode diffère de façon substantielle de l'ISO 13347-2 quant aux exigences relatives à
l'environnement d'essai et aux grandeurs mesurées.
5 Équipement et catégories d'installation
5.1 Environnement d'essai
5.1.1 Bruit de fond
La détermination de la puissance acoustique à l'aide des mesurages d'intensité est par essence moins
sensible au bruit de fond que les méthodes basées sur les mesurages de la pression acoustique (telle que
l'ISO 13347-2), bien qu'aucune méthode ne permette une détermination précise de la puissance acoustique
lorsque le bruit de fond est excessif. De façon générale le bruit de fond ne doit pas constituer un problème en
ce qui concerne l'utilisation de la présente méthode, à condition que sur la surface de mesure, le niveau de
pression acoustique du bruit de fond ne soit pas supérieur au niveau de pression acoustique du son direct
issu du système de ventilateur concerné.
Si le bruit de fond est excessif, il est possible que la détermination de la puissance acoustique conformément
aux modes opératoires du présent document puisse ne pas être réalisable. Pour plus d'informations sur la
surveillance du bruit de fond, voir 6.4.2.
5.1.2 Surfaces réfléchissantes avoisinantes
Si la présence d'une surface réfléchissante avoisinante interfère avec l'échantillonnage de l'intensité
acoustique sur la surface de mesure, il est possible que la détermination de la puissance acoustique
conformément aux modes opératoires de la présente norme puisse ne pas être réalisable. Afin d'évaluer si
une surface réfléchissante avoisinante est effectivement à l'origine des difficultés, le mode opératoire de
l'Annexe A est recommandé.
5.1.3 Contrôle de la réverbération
Outre les difficultés associées aux surfaces réfléchissantes avoisinantes, un son réverbéré diffus et excessif
au niveau de la surface de mesure peut limiter la précision des mesurages de l'intensité acoustique. De façon
générale, le son réverbéré ne doit pas constituer un problème en ce qui concerne l'utilisation de la présente
norme, à condition que sur la surface de mesure, le niveau de pression acoustique du son réverbéré ne soit
pas supérieur au niveau de pression acoustique du son direct issu du système de ventilateur concerné.
Il est généralement possible de contrôler une réverbération excessive en introduisant une petite quantité de
matériau d'isolation phonique aux limites d'une salle acoustiquement «dure» (réfléchissante). De manière
alternative, il est possible de réduire la puissance relative du son réverbéré en rapprochant la surface de
mesure de la source sonore concernée, dans les limites permises par le présent document, c'est-à-dire en
augmentant le son direct issu de la source. L'application du présent document dans une salle réverbérante
qualifiée pour être utilisée avec l'ISO 13347-2 n'est pas recommandée sans utilisation de matériaux
absorbants supplémentaires ou si une attention particulière a été portée à la définition de la surface de
mesure, ou les deux.
Si le son réverbéré est excessif, il est possible que la détermination de la puissance acoustique conformément
aux modes opératoires du présent document ne soit pas réalisable. Afin d'évaluer si un son réverbéré excessif
est effectivement à l'origine des difficultés, le mode opératoire de l'Annexe A est recommandé.
5.2 Installation du ventilateur
5.2.1 Catégories d'installation
Les conditions d'installation du ventilateur sont conformes aux cinq catégories d'installation spécifiées dans
l'ISO 13349-2.
a) Catégorie A b) Catégorie B
c) Catégorie C d) Catégorie D e) Catégorie E
Figure 1 — Catégories d'installation
— Catégorie A: installation à aspiration libre et refoulement libre avec une paroi (voir Figure 1 a).
— Catégorie B: installation à aspiration libre et refoulement en conduit (voir Figure 1 b).
— Catégorie C: installation à aspiration en conduit et refoulement libre (voir Figure 1 c).
— Catégorie D: installation à aspiration en conduit et refoulement en conduit (voir Figure 1 d).
— Catégorie E: installation à aspiration libre et refoulement libre sans paroi (voir Figure 1 e).
Ces catégories d'installation se répartissent en deux configurations d'essai générales. La première
configuration est destinée à une unité autostable placée en intégralité dans la salle d'essai (voir Figure 2). Les
résultats issus de cette configuration fournissent le niveau de puissance acoustique total (L ou L ) de l'unité
Wm W
en essai. La seconde configuration concerne les unités soumises à l'essai avec une chambre ou un système à
deux salles, où uniquement l'aspiration ou la sortie émet un son dans la salle d'essai (voir Figures 3 ou 4).
Cette configuration fournit uniquement des valeurs du niveau de puissance acoustique de l'aspiration (L
W,m,i
ou L ) ou de la sortie (L ou L ). Il est à noter que l'indice «m» indique que le niveau de puissance
W,i W,m,o W,o
acoustique est déterminé à partir de mesurages utilisant une catégorie d'installation qui ne nécessite pas
d'ajustement de correction d'extrémité, alors que les valeurs sans indice «m» sont déterminées en appliquant
une correction d'extrémité aux mesurages effectués sur une catégorie d'installation en conduit.
Le choix de la catégorie d'installation, pour un ventilateur particulier, dépend des attentes au niveau de
l'évaluation du produit et de son application sur site.
5.2.2 Essai aérodynamique
Si des essais de performance aérodynamique sont nécessaires pour déterminer le point de fonctionnement
du ventilateur, ils doivent être effectués tel que spécifié dans l'ISO 5801 ou dans l'ISO 13350.
5.2.3 Méthodes de montage
Les vibrations sont connues pour influencer les émissions de son aérien. Les effets des vibrations peuvent
être réduits grâce à un montage résilient du ventilateur et l’isolement des vibrations de tout conduit utilisé.
La méthode de montage des ventilateurs, de connexion des ventilateurs à des organes moteurs non
incorporés et à des installations d'essai aérodynamique n'est pas spécifiée. Toute méthode conventionnelle
peut être utilisée, y compris des dispositifs antivibratiles et de courts raccords flexibles. D’autre part, les
matériaux absorbant le son et les vibrations ne doivent pas être incorporés au ventilateur d'essai, sauf s'ils
font partie de l'unité. Les conduits doivent être en métal ou constitués d'un autre matériau rigide, dense et
non absorbant et leurs surfaces intérieures ou extérieures ne doivent pas présenter de matériau absorbant
les sons.
Le moteur d'entraînement et la transmission, s'ils ne font pas partie intégrante du ventilateur, peuvent être
amortis ou encoffrés d'une façon qui permet d'éviter l'exposition de matériaux absorbant le son dans la
surface de mesure. Lorsque le moteur d'entraînement et la transmission font partie intégrante de l'unité
d'essai, ils ne doivent pas être traités, et des tensions de courroies normales, des coussinets et des lubrifiants
doivent être utilisés.
5.2.4 Longueur du conduit
La longueur du conduit présentée
...










Questions, Comments and Discussion