Fans - Efficiency classification for fans - Part 6: Calculation of the fan energy index

This document defines the calculation method for determining the fan energy index (FEI), which is an energy efficiency metric for fan duty points. This metric provides a standardized and consistent basis to compare fan energy performance across fan types and sizes at a given fan duty point. This document is applicable to fans driven by electric motors and fans without drives. It is not applicable to circulating fans or air curtains. The fan energy index can only be calculated for fan duty points above a minimum air power of 125 W (where air power is the product of volume flow rate and fan static pressure) or above a minimum volume flow rate of 2,0 m3/s.

Ventilateurs — Classification du rendement des ventilateurs — Partie 6: Calcul de l'indice énergétique des ventilateurs

Le présent document définit la méthode de calcul pour l’indice énergétique des ventilateurs (FEI), qui est un paramètre d’efficacité énergétique pour les points de fonctionnement des ventilateurs. Cette mesure fournit une base standardisée et cohérente pour comparer les performances énergétiques de ventilateurs de différents types et tailles à un point de fonctionnement de ventilateur donné. Le présent document s'applique aux ventilateurs entraînés par des moteurs électriques et aux ventilateurs sans entraînement. Il ne s'applique pas aux ventilateurs brasseurs d’air ou aux rideaux d'air. L'indice énergétique des ventilateurs ne peut être calculé que pour des points de fonctionnement des ventilateurs supérieurs à une puissance d'air minimale de 125 W où la puissance d'air est le produit du débit-volume et de la pression statique du ventilateur ou supérieurs à un débit‑volume minimal de 2,0 m3/s.

General Information

Status
Published
Publication Date
21-May-2024
Technical Committee
Drafting Committee
Current Stage
6060 - International Standard published
Start Date
22-May-2024
Due Date
23-Aug-2024
Completion Date
22-May-2024
Ref Project

Overview

ISO 12759-6:2024 defines the method to calculate the Fan Energy Index (FEI) - a standardized energy-efficiency metric for fan duty points. The FEI provides a consistent basis to compare energy performance across fan types and sizes at a given operating point. This part of the ISO 12759 series applies to fans driven by electric motors and to fans without drives, but it is not applicable to circulating fans or air curtains. FEI calculation is limited to duty points above a minimum air power of 125 W (air power = volume flow rate × fan static pressure) or above 2.0 m³/s volume flow.

Key Topics

  • Definition and scope of FEI - purpose, limits of applicability and minimum testable configurations.
  • Reference electrical input power - how to derive a reference shaft power and account for transmission, motor and motor controller efficiencies to establish a reference baseline.
  • Actual fan electrical input power - measurement requirements and methods for determining real input power at the duty point (including guidance on measurements and when to use tested motor data).
  • Transmission and motor considerations - treatment of direct-drive, belt-driven and other transmission types and their impact on FEI.
  • Measurement and calculation guidance - procedures referencing ISO 12759-2 for standard losses, ISO 5801 for performance testing, and annexed guidance for conversions (e.g., to other speeds and densities, Annex E).
  • Annexes addressing practical issues - informative annexes cover fan types and test configurations, FEI pressure basis, usage guidance, fan arrays, embedded fans, and measurement conversions.

Applications

Who uses ISO 12759-6:2024 and why:

  • Fan manufacturers - to report and compare energy performance consistently across product ranges.
  • Specifiers and consultants - to set efficiency requirements and select fans based on FEI at required duty points.
  • Test laboratories - to measure and calculate FEI following uniform methods.
  • Energy auditors and facility engineers - to compare retrofit or replacement options, and to quantify fan energy savings.
  • Regulators and standards bodies - to establish minimum performance bands or efficiency labeling programs based on FEI.

Practical value: FEI supports design and selection decisions that reduce operational energy use by evaluating fan performance across actual duty points rather than only at peak efficiency.

Related standards

  • ISO 12759-1 (General information for fans)
  • ISO 12759-2:2019 (Standard losses for drive components)
  • ISO 5801 (Fans - Performance testing using standardized airways)
  • ISO 13348, ISO 13349-1, ISO 13350 (Fan technical data and vocabulary)
  • IEC 60034 series (motor efficiency and test methods)

Keywords: ISO 12759-6:2024, fan energy index, FEI, fan efficiency, fan duty point, fan performance, fan testing, energy efficiency metric.

Standard
ISO 12759-6:2024 - Fans — Efficiency classification for fans — Part 6: Calculation of the fan energy index Released:22. 05. 2024
English language
40 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ISO 12759-6:2024 - Ventilateurs — Classification du rendement des ventilateurs — Partie 6: Calcul de l'indice énergétique des ventilateurs Released:22. 05. 2024
French language
45 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


International
Standard
ISO 12759-6
First edition
Fans — Efficiency classification
2024-05
for fans —
Part 6:
Calculation of the fan energy index
Ventilateurs — Classification du rendement des ventilateurs —
Partie 6: Calcul de l'indice énergétique des ventilateurs
Reference number
ISO 12759-6:2024(en)
© ISO 2024
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
ISO 12759-6:2024(en)
Contents  Page
Foreword .iv
Introduction .v
1  Scope . 1
2  Normative references . 1
3  Terms, definitions and symbols . 1
3.1 Terms and definitions .2
3.1.1 General terms .2
3.1.2 Impeller types .4
3.1.3 Fan types .5
3.2 Symbols .7
4  General . 7
4.1 Minimum testable configuration .7
4.2 FEI pressure basis .8
4.3 Appurtenances.8
4.4 Fans embedded in other equipment .9
5  Fan energy index . 9
5.1 General .9
5.2 Reference electrical input power .9
5.2.1 General .9
5.2.2 Reference shaft power .10
5.2.3 Reference transmission efficiency .11
5.2.4 Reference motor efficiency .11
5.2.5 Reference motor controller efficiency. 12
5.3 Actual fan electrical input power . 12
5.3.1 General . 12
5.3.2 Measurement of fan electrical input power . 13
5.3.3 Fan electrical input power calculation using ISO 12759-2 .14
5.3.4 Combined fan shaft power with tested motor or motor and controller .14
5.3.5 Fan electrical input power calculation for fans with motors of unknown
efficiency .16
6  Use of FEI . 17
6.1 Requirements for use of FEI .17
6.2 Published FEI values .17
Annex A (normative)  Fan types, test configurations and FEI pressure basis .18
Annex B (informative)  Usage of FEI .21
Annex C (informative)  Fan arrays .27
Annex D (informative)  Practical issues with embedded fans .29
Annex E  (informative)  Electrical power measurement — Calculation to other speeds and
densities .30
Annex F (informative)  Basis for the reference electrical input power calculations .36
Bibliography .40

iii
ISO 12759-6:2024(en)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO document should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 117, Fans.
A list of all parts in the ISO 12759 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.

iv
ISO 12759-6:2024(en)
Introduction
The fan industry is of a global nature, with a considerable degree of exporting and licensing. To ensure that
the defining fan performance characteristics are common throughout the world, a series of standards have
been developed. It is the belief of the industry that there is now a need for minimum efficiency standards to
be recognized.
To encourage their implementation, a classification system is proposed which incorporates a series of
efficiency bands. With improvements in technology and manufacturing processes, the minimum efficiency
levels can be reviewed and increased in time.
This document differs from others in this series in that the fan is not evaluated at its peak efficiency value.
Rather, the fan is evaluated at every duty point within its stated performance range. In doing so, this
document addresses both the design and selection of fans for reduced power consumption.
The fan energy index provides a consistent basis to compare fan energy performance across fan types
and sizes at a given fan duty point. This document can be used by fan specifiers to communicate fan
efficiency design intent and by those selecting fans to compare the energy use of various fan options. With
improvements in technology and manufacturing processes, the minimum allowable fan energy index can be
reviewed and increased in time.

v
International Standard ISO 12759-6:2024(en)
Fans — Efficiency classification for fans —
Part 6:
Calculation of the fan energy index
1  Scope
This document defines the calculation method for determining the fan energy index (FEI), which is an energy
efficiency metric for fan duty points. This metric provides a standardized and consistent basis to compare
fan energy performance across fan types and sizes at a given fan duty point.
This document is applicable to fans driven by electric motors and fans without drives. It is not applicable to
circulating fans or air curtains.
The fan energy index can only be calculated for fan duty points above a minimum air power of 125 W (where
air power is the product of volume flow rate and fan static pressure) or above a minimum volume flow rate
of 2,0 m /s.
2  Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
ISO 5801:2017, Fans — Performance testing using standardized airways
ISO 12759-1, Fans — Efficiency classification for fans — General information for fans
ISO 12759-2:2019, Fans — Efficiency classification for fans — Part 2: Standard losses for drive components
ISO 13348, Industrial fans — Tolerances, methods of conversion and technical data presentation
ISO 13349-1, Fans — Vocabulary and definitions of categories — Part 1: Vocabulary
ISO 13350, Fans — Performance testing of jet fans
IEC 60034-30-1:2014, Rotating electrical machines—Part 30-1: Efficiency classes of line operated AC motors
(IE code)
IEC 60034-2-1, Rotating electrical machines—Part 2-1: Standard methods for determining losses and efficiency
from tests (excluding machines for traction vehicles)
IEC 60034-2-3, Rotating electrical machines—Part 2-3: Specific test methods for determining losses and
efficiency of converter-fed AC motors
ANSI/AMCA Standard 230, Laboratory Methods of Testing Air Circulating Fans for Rating and Certification
ANSI/AMCA Standard 260, Laboratory Methods of Testing Induced Flow Fans for Rating
3  Terms, definitions and symbols
For the purposes of this document, the terms and definitions given in ISO 13349-1 and ISO 12759-1 and the
following apply.
ISO 12759-6:2024(en)
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1  Terms and definitions
3.1.1  General terms
3.1.1.1
fan
rotary-bladed machine that receives mechanical energy and utilizes it by means of one or more impellers
(3.1.1.2) fitted with blades to maintain a continuous flow of air or other gas passing through it and whose
work per unit mass does not normally exceed 25 kJ/kg
Note 1 to entry: See ISO 13349-1:2022, 3.1.1 for a more complete definition.
3.1.1.2
impeller
rotating part of the fan (3.1.1.1) that imparts energy to the air stream
[SOURCE: ISO 13349-1:2022, 3.7.3, modified – changing gas flow to air stream]
3.1.1.3
housing
stationary part of the fan (3.1.1.1) that interacts with the air stream passing through the impeller (3.1.1.2)
Note 1 to entry: A housing can be an element around the impeller (3.1.1.2) which guides the air stream towards,
through and from the impeller.
Note 2 to entry: A housing can have additional parts included within or attached to it that affect the performance of
the fan (3.1.1.1), such as an inlet bell (also known as venturi), inlet cone, inlet radius, inlet ring, inlet guide vane, outlet
guide vane or outlet diffuser.
3.1.1.4
fan without drives
non-driven fan
bare shaft fan
fan (3.1.1.1) without motor, transmission (3.1.1.8), or motor controller (3.1.1.14)
Note 1 to entry: In this definition, the term drive refers to motors, transmissions, and motor controllers.
3.1.1.5
driven fan
fan (3.1.1.1) driven by an electrical motor, with or without a transmission (3.1.1.8) or motor controller
(3.1.1.14)
Note 1 to entry: In this document, the term motor always refers to an electric motor.
[SOURCE: ISO 13349-1:2022, 3.1.3, modified – Note 1 included in the body of the term]
3.1.1.6
direct driven fan
driven fan (3.1.1.5) configuration in which the impeller (3.1.1.2) is connected directly to the motor
3.1.1.7
belt driven fan
driven fan (3.1.1.5) configuration in which the impeller (3.1.1.2) is connected to the motor through a set of
belts and pulleys mounted on the motor shaft and fan shaft
Note 1 to entry: This includes fans with V-belt transmissions (3.1.1.10) or synchronous belt transmissions (3.1.1.11).

ISO 12759-6:2024(en)
3.1.1.8
transmission
component that transfers energy from a motor to an impeller
EXAMPLE Pulleys, belts, gears, couplings.
3.1.1.9
V-belt transmission
form of transmission (3.1.1.8) utilizing drive belts having a substantially trapezoidal cross-section that use
pulleys having smooth contact surfaces
Note 1 to entry: Conventional V-belts have a constant cross-section along their length, while notched V-belts (also
known as cogged V-belts) have slots running perpendicular to their length. The slots reduce bending resistance and
offer improved efficiency over conventional V-belts.
3.1.1.10
synchronous belt transmission
form of transmission (3.1.1.8) utilizing drive belts having a substantially rectangular cross-section containing
teeth that engage corresponding teeth on the pulleys, resulting in no-slip power transmission
Note 1 to entry: These belts are sometimes called timing or toothed belts.
3.1.1.11
standalone fan
fan (3.1.1.1) in at least a minimum testable configuration
Note 1 to entry: This includes any motor, transmission or motor controller if included in the rated fan. It also includes
any appurtenances included in the rated fan, and it excludes the impact of any surrounding equipment whose purpose
exceeds or is different than that of the fan. See 4.1.
Note 2 to entry: Standalone fans do not include provisions for air conditioning, air filtration, air mixing, air treatment
or heating.
EXAMPLE Power roof ventilators, side-wall exhaust fans, inline fans, jet fans and induced-flow laboratory
exhaust fans.
[SOURCE: ISO 13349-1:2022, 3.1.4, modified – addition of an example and of more detail to the notes]
3.1.1.12
embedded fan
integrated fan
fan (3.1.1.1) that is set or fixed firmly inside or attached to a surrounding piece of equipment whose purpose
exceeds that of a fan (3.1.1.1) or is different than that of a standalone fan (3.1.1.11)
Note 1 to entry: The surrounding equipment can have safety or energy efficiency requirements of its own.
Note 2 to entry: Embedded fans are also known as integrated fans.
EXAMPLE Supply fans in air handling units, condenser fans in heat rejection equipment, tangential blowers in air
curtain units and induced or forced draft combustion blowers in boilers or furnaces.
3.1.1.13
motor controller
device that is used to control the speed of the motor and subsequently the fan (3.1.1.1)
3.1.1.14
regulated motor
motor whose efficiency or power usage is subject to regional or national regulation

ISO 12759-6:2024(en)
EXAMPLES Europe: Commission Regulation (EU) 2019/1781
China: GB 18613
United States: Code of Federal Regulations 10CFR Part 431
3.1.1.15
default motor efficiency
default efficiency assigned to the motor at a given motor output power when either the specific motor is not
identified or the efficiency of the motor used is unknown
Note 1 to entry: The use of a default efficiency is designed to represent typically available motors. Since motor
efficiency regulations are controlled regionally, the default motor efficiency shall reflect these regulations. See 5.3.5
for examples.
3.1.1.16
duty point
single volume flow rate (q ) and pressure (p or p ) point within the published operating range of the fan
V f fs
(3.1.1.1)
3.1.1.17
reference electrical power
reference power used to relate the performance of all fans to a common baseline
Note 1 to entry: The reference electrical power defines a single value of fan electrical input power for a given volume
flow rate and fan pressure.
3.1.2  Impeller types
NOTE See ISO 13349-1 for a more complete description of the variations between impeller types. The definitions
below include only the differentiation needed for this standard.
3.1.2.1
axial impeller
propeller
impeller (3.1.1.2) with a number of blades extending radially from a central hub in which airflow through the
impeller is axial in direction; that is, airflow enters and exits the impeller parallel to the shaft axis (i.e. with
a fan flow angle (3.1.2.5) ≤ 20°)
Note 1 to entry: Blades can either be single thickness or aerofoil shaped.
3.1.2.2
centrifugal impeller
impeller (3.1.1.2) with a number of blades extending between a back plate and shroud in which airflow enters
axially through one or two inlets and exits radially at the impeller periphery, either into open space or into a
housing, with a fan flow angle (3.1.2.5) ≥ 70°
Note 1 to entry: Impellers (3.1.1.2) can be classified as single inlet or double inlet.
Note 2 to entry: Blades can be tilted backward or forward with respect to the direction of impeller rotation. Impellers
with backward tilted blades can be aerofoil shaped (AF), backward curved single thickness (BC), backward inclined
single thickness flat (BI) or radial tipped (RT). Impellers with forward tilted blades are known as forward curved (FC).
3.1.2.3
radial impeller
form of centrifugal impeller (3.1.2.2) with a number of blades extending radially from a central hub in which
airflow enters axially through a single inlet and exits radially at the impeller periphery into a housing
with impeller blades positioned such that the outward direction of the blade at the impeller periphery is
perpendicular within 25°to the axis of rotation
Note 1 to entry: Radial impellers can optionally have a back plate and/or shroud.

ISO 12759-6:2024(en)
3.1.2.4
mixed flow impeller
impeller (3.1.1.2) with construction characteristics between those of an axial impeller (3.1.2.1) and centrifugal
impeller (3.1.2.2) with a fan flow angle (3.1.2.5) between 20° and 70°
Note 1 to entry: Airflow enters axially through a single inlet and exits with combined axial and radial directions at a
mean diameter greater than the inlet.
Note 2 to entry: Mixed flow impellers are sometimes known as diagonal impellers.
Note 3 to entry: Mixed flow impellers are abbreviated as MF in Table A.1.
3.1.2.5
fan flow angle
angle of the centreline of the air-conducting surface of a fan blade measured at the midpoint of its trailing
edge with the centreline of the rotation axis, in a plane through the rotation axis and the midpoint of the
trailing edge
3.1.3  Fan types
NOTE See ISO 13349-1 for a more complete description of the variations between fan types. The definitions
below include only those fan types that are tested differently, function differently, or have a unique advantage, other
than efficiency, over other fan types (e.g., sound levels, compact size) such that they can be expected to operate at a
different FEI range than other fan types. Additional information on typical duct connections is also provided.
3.1.3.1
centrifugal housed fan
radial-flow fan
fan with a centrifugal or radial impeller in which airflow exits into a housing that is generally scroll shaped
to direct the air through a single fan outlet
Note 1 to entry: Inlets and outlets can optionally be ducted.
3.1.3.2
centrifugal inline fan
fan with a centrifugal or mixed flow impeller in which airflow enters axially at the fan inlet and the housing
redirects radial airflow from the impeller to exit the fan in an axial direction
Note 1 to entry: Inlets and outlets can optionally be ducted.
3.1.3.3
centrifugal unhoused fan
plenum fan
fan with a centrifugal impeller in which airflow enters through a panel and discharges into free space
Note 1 to entry: Outlets are not ducted.
Note 2 to entry: This fan type also includes fans designed for use in fan arrays that have partition walls separating the
fan from other fans in the array.
3.1.3.4
power roof ventilator
PRV
fan with an internal motor and a housing to prevent precipitation from entering the building
Note 1 to entry: It has a base designed to fit over a roof or wall opening, usually by means of a roof curb.
3.1.3.5
centrifugal PRV exhaust
PRV with a centrifugal impeller that exhausts air from a building
Note 1 to entry: Inlets are typically ducted, but outlets are not ducted.

ISO 12759-6:2024(en)
3.1.3.6
centrifugal PRV supply
PRV with a centrifugal impeller that supplies air to a building
Note 1 to entry: Inlets are not ducted, and outlets are typically ducted.
3.1.3.7
axial PRV
PRV with an axial impeller that either supplies or exhausts air to a building
Note 1 to entry: Inlets and outlets are typically not ducted.
3.1.3.8
axial inline fan
fan with an axial impeller and a cylindrical housing with or without turning vanes
Note 1 to entry: Inlets and outlets can optionally be ducted.
3.1.3.9
axial panel fan
fan with an axial impeller mounted in a short housing consisting of a panel, ring or orifice plate
Note 1 to entry: The housing is typically mounted to a wall separating two spaces and the fans are used to increase the
pressure across this wall. Inlets and outlets are not ducted.
Note 2 to entry: These fans are sometimes known as propeller fans or plate-mounted axial fans.
3.1.3.10
laboratory exhaust fan
fan designed specifically for exhausting contaminated air vertically away from a building, with fan outlets
typically constricted to achieve a high outlet velocity
Note 1 to entry: Laboratory exhaust fans can be designed with or without induced flow. Induced flow lab exhaust fans
use their high velocity discharge to entrain additional air to mix with contaminated building exhaust air.
Note 2 to entry: Inlets can optionally be ducted, and outlets are not ducted.
3.1.3.11
jet fan
fan used for producing a high velocity flow of air in a space
Note 1 to entry: Typical function is to add momentum to the air within a tunnel. Inlets and outlets are not ducted.
3.1.3.12
circulating fan
fan used for the general circulation of air within a space that has no provision for connection to ducting or
separation of the fan inlet from its outlet
3.1.3.13
crossflow fan
fan with a housing that creates an airflow path through the impeller in a direction at right angles to its axis
of rotation and with airflow both entering and exiting the impeller at its periphery
Note 1 to entry: Inlets and outlets can optionally be ducted.
3.1.3.14
fan array
common application of fans using multiple fans in parallel between two plenum sections for a factory-
packaged or field-erected air handling unit

ISO 12759-6:2024(en)
3.2  Symbols
Symbol Represented quantity Unit
A Fan outlet or discharge area m
A, B, C, D, E Constants dimensionless
I Fan energy index (FEI) dimensionless
P Reference electrical input power kW
ed,ref
P Actual fan electrical input power kW
ed,act
P Reference fan shaft power kW
a,ref
P Actual fan shaft power kW
a,act
P Reference motor output power kW
o,ref
P Actual motor output power kW
o,act
P Default motor output power kW
o,def
p Pressure constant Pa
p Fan static pressure at duty point Pa
fs
p Fan total pressure at duty point Pa
f
q Fan volume flow rate at duty point m /s
V
q Volume flow rate constant m /s
T Force due to fan thrust N
m
η Fan efficiency constant dimensionless
η Reference transmission efficiency dimensionless
T,ref
η Actual transmission efficiency dimensionless
T,act
η Reference motor efficiency dimensionless
mot,ref
η Actual motor efficiency dimensionless
mot,act
η Actual motor and controller efficiency dimensionless
mc,act
η Reference motor controller efficiency dimensionless
c,ref
η Default motor efficiency dimensionless
mot,def
Ρ Fan air density kg/m
ρ Standard air density kg/m
ref
4  General
4.1  Minimum testable configuration
The FEI calculation is based on fan performance derived from tests in accordance with recognized fan test
standards. See Annex A to determine the appropriate test standard for each fan type. These test standards
each require some minimum configuration in order to run the tests. This document is also based on tests of
fans in at least a minimum testable configuration, including the following:
— impeller;
— motor or separate shaft with bearings to support the impeller;
— structure, housing or stator, unless the fan does not require these (e.g. an unshrouded circulating fan).
Each rated fan model shall be rated according to the applicable fan type listed in Table A.1, in accordance
with how that fan is distributed in commerce. For example, if a fan meets the definition of a jet fan, it shall be
tested and rated as a jet fan according to Table A.1.

ISO 12759-6:2024(en)
4.2  FEI pressure basis
The FEI shall be calculated using the fan total pressure or the fan static pressure, based on the fan type. See
Annex A for a complete explanation of the pressure basis and to learn which pressure to use.
4.3  Appurtenances
Certain accessories or appurtenances can be used to improve fan performance, including but not limited to
inlet bells, diffusers, stators and guide vanes. If an appurtenance improves the performance of the fan and
is always supplied with the fan when distributed in commerce, it shall be tested with the fan. Test ducts
included during testing are not required to be supplied with the fan.
Appurtenances that reduce the performance of a fan are not included in their minimum testable configuration
used to determine FEI. These include but are not limited to guards, dampers, filters and weather hoods. The
effect of these appurtenances on fan performance can be tested and published to aid in fan selection, but the
appurtenances are not included in the fan test used to determine FEI.
As illustrated in Figure 1, the reduced performance of a fan with appurtenances (Figure 1, key reference [2])
can be published and matched against system pressures in order to make proper fan selections. The process
of fan selection includes determining the fan speed or blade pitch needed to achieve the required system
pressure (p ) at the required volume flow rate (q ) (Figure 1, key reference [4]). Once the required fan
f,req V,req
speed or blade pitch are determined, the FEI is determined from the standalone fan performance (Figure 1,
key reference [1]) at the same volume flow rate, fan speed and blade pitch (Figure 1, key reference [5]),
combined with the fan electrical power at this standalone fan duty point.
Key
X volume flow rate, expressed in m /s
Y total or static pressure, expressed in Pa
1 pressure curve of fan alone
2 pressure curve of fan with appurtenances
3 system resistance curve external to fan and appurtenances
4 fan duty point with appurtenances
5 fan alone duty point used for FEI calculation
6 pressure reduction due to fan appurtenances

ISO 12759-6:2024(en)
q volume flow rate of fan alone
v
p pressure capacity of fan alone
f
q required volume flow rate of fan
V,req
p pressure required to overcome system resistance
f,req
Figure 1 — Fan performance curves at constant fan speed and blade pitch with and without
appurtenances
4.4  Fans embedded in other equipment
This document does not apply to fan performance when the fan is tested embedded inside of other
equipment. However, this document may be used to calculate FEI for a fan that, while tested in a standalone
configuration, will be embedded into other equipment. The FEI for the embedded fan is assigned to be equal
to the standalone fan performance at the same volume flow rate, fan speed and blade pitch.
Under no circumstances shall a test of an embedded fan inside the equipment be used to predict the FEI of
the standalone fan. See Annex D for additional information on issues related to embedded fan performance.
5  Fan energy index
5.1  General
The fan energy index (FEI) is defined as a ratio of the reference electrical input power to the electrical input
power of the actual fan for which the FEI is calculated, both calculated at the same duty point, which is
characterized by a value of fan volume flow rate (q ) and pressure (p or p ). FEI values (I) can be calculated
V f fs
for each point on a fan curve according to Formula (1).
P
ed,ref
I= (1)
P
ed,act
where
P is the reference electrical input power in kW;
ed,ref
P is the actual fan electrical input power in kW.
ed,act
Use the total pressure or the static pressure consistently throughout Clause 5, and it is important to state
how the FEI has been determined, whether using total or static pressure (see 5.2.2.1 and Annex B).
5.2  Reference electrical input power
5.2.1  General
The reference concept is used to normalize the FEI calculation to a consistent power level independent of
fan type, fan drive components or any regulatory requirements. The reference electrical input power is
ultimately a function of only fan volume flow rate and fan pressure, but requires an iterative calculation
beginning with Formula (2). Details of the basis for the reference electrical input power, including the
constants q , p , and η , are contained in Annex F.
0 0 0
     
11 1
PP=× × × (2)
     
ed,,refra ef
ηη η
Tc,,refmot refr, ef
     
ISO 12759-6:2024(en)
where
P is the reference fan shaft power in kW;
a,ref
η is the reference transmission efficiency;
T,ref
η is the reference motor efficiency;
mot,ref
η is the reference motor controller efficiency.
c,ref
5.2.2  Reference shaft power
5.2.2.1  General
The fan performance at the duty point shall be obtained by testing in accordance with the standards listed
in Table A.1 or calculated in accordance with the fan laws and conversion rules specified in ISO 13348. If
needed, the interpolation methods in Annex E may also be used.
The reference shaft power, P , shall be calculated either on a fan total pressure basis or a fan static
a,ref
pressure basis, depending on the fan type. See Annex A for a complete description and a list of fan types and
the FEI pressure basis.
Throughout Clause 5, it is required to use total or static pressure consistently. Both P (5.2) and P (5.3)
a,ref a,act
are a function of fan pressure and shall use the same pressure basis. For example, if the required pressure
basis from Annex A is fan total pressure, the powers P and P are calculated at the same fan total
a,ref a,act
pressure, even if the fan performance is ultimately published in terms of fan static pressure.
5.2.2.2  Total pressure basis
For fan types identified in Annex A as using a total pressure basis, the reference shaft power (P ) at a
a,ref
given duty point is a function of fan volume flow rate (q ) and fan total pressure (p ) at that duty point,
V f
calculated according to Formula (3):
 ρ 
qq+ ×+pp ×
()
Vf00 
ρ
 
ref
P = (3)
ar, ef
1000×η
where
q is fan volume flow rate in m /s;
V
p is fan total pressure in Pa;
f
ρ is air density in kg/m ;
ρ is standard air density, 1,2 kg/m ;
ref
q = 0,118 m /s;
p = 100 Pa;
η = 66 %.
ISO 12759-6:2024(en)
5.2.2.3  Static pressure basis
For fan types identified in Annex A as using a static pressure basis, the reference shaft power (P ) at a
a,ref
given duty point is a function of fan volume flow rate (q ) and fan static pressure (p ) at that duty point,
V fs
calculated according to Formula (4):
 
ρ
qq+ ×+pp ×
()
 
Vf00s
ρ
 
ref
P = (4)
ar, ef
1000×η
where
q is fan volume flow rate in m /s;
V
p is fan static pressure in Pa;
fs
ρ is air density in kg/m ;
ρ is standard air density, 1,2 kg/m ;
ref
q = 0,118 m /s;
p = 100 Pa;
η = 60 %.
5.2.3  Reference transmission efficiency
The reference transmission efficiency (η ) shall be calculated using Formula (5):
T,ref
00, 5
P
 
ar, ef
η =×09, 6 (5)
 
Tr, ef
P +16, 4
 ar, ef 
where P is reference shaft power in kW.
a,ref
NOTE This formula is from ISO 12759-2:2019, 4.2.2.
5.2.4  Reference motor efficiency
The reference motor output power (P ) shall be calculated using Formula (6):
o,ref
P
ar, ef
P = (6)
or, ef
η
Tr, ef
where
P is reference shaft power in kW;
a,ref
η is reference transmission efficiency.
T,ref
The reference motor efficiency shall be calculated according to Formula (7) using the coefficients A–E found
in Table 1.
43 21
AP×lg  +×BPlg  +×CPlg  +×DPlg  +E
() () () ()
 or,,ef   oref   or, ef   or, ef 
η = (7)
motr, ef
ISO 12759-6:2024(en)
where
P is reference motor output power in kW;
o,ref
A, B, C, D, E are coefficients found in Table 1.
Table 1 — Reference motor efficiency coefficients
P < 185 kW P ≥ 185 kW
o,ref o,ref
A −0,381 2 0
B 2,583 4 0
C −7,257 7 0
D 12,555 9 0
E 85,027 4 96,2
5.2.5  Reference motor controller efficiency
The reference motor controller efficiency (η ) is as assigned a value of 100 % since there is no motor
c,ref
controller in the reference model.
5.3  Actual fan electrical input power
5.3.1  General
P is the fan electrical input power associated with a given fan duty point in terms of volume flow rate
ed,act
and pressure.
Actual fan electrical input power shall be determined by one of the methods found in 5.3.2 to 5.3.5. The
methods to determine fan electrical input power are defined as a function of the fan configuration being
rated and are summarized in Table 2.

ISO 12759-6:2024(en)
Table 2 — Methods to determine fan electrical input power
Fan configura- P  determina-
ed,act
tion Motor type Subclause tion Example applications
— Fans sold without motors
Fan for which
Default motor effi-
— Catalogues used for fan
the motor is not N/A 5.3.5
ciency calculation
selection prior to motor
yet selected
selection
— Electrical power
measurement and density
Electrical power
corrections of fans rated
measurement, calcu-
Any 5.3.2
with motors
lations according to
Annex E
— Motors for which no test
standards apply
Polyphase induction
motors, both regulated
— Three-phase regulated
and non-regulated, with
motors ≥ 0,75 kW
nameplate power and ISO 12759-2 calcula-
Fan with motor 5.3.3
— Three-phase non-regulated
poles that fall within tion
motors ≥ 0,75 kW (e.g. AO, XP,
the range covered in ISO
two-speed)
12759-2:2019, Annex B,
C, and D
— Single-phase regulated
Motor for which 5.3.3
motors
does not apply and the
Motor test according
performance can be — Single-phase non-regulated
5.3.4 to recognized stand-
measured in accord- motors
ard
ance with a known test
— Three-phase motors below
standard
0,75 kW
— Electrical power
measurement and density
and/or speed corrections of
Electrical power
fans rated with a motor and
measurement, calcu-
Any 5.3.2
controller
lations according to
Annex E
— Motors with controllers for
which no test standards
apply
Motor and controller
for which 5.3.3 does not — Electronically commutated
Fan with motor Motor and controller
apply and the perfor- (EC), permanent magnet
and motor con- 5.3.4 test according to rec-
mance can be measured (PM) motors with integral or
troller ognized standard
in accordance with a separate motor controllers
known test standard
Polyphase induction
motors, both regulated
— Three-phase regulated
and non-regulated, with
motors ≥ 0,75 kW
nameplate power and ISO 12759-2 calcula-
5.3.3
— Three-phase non-regulated
poles that fall within tion
motors ≥ 0,75 kW (e.g. AO, XP,
the range covered in ISO
two-speed)
12759-2:2019, Annex B,
C, and D.
5.3.2  Measurement of fan electrical input power
This subclause covers direct measurement of fan electrical input power in accordance with ISO 5801,
ISO 13350, ANSI/AMCA Standard 230 or ANSI/AMCA Standard 260. Interpolation of fan electrical input
power from these measurements may also be done in accordance with Annex E. This method may be used

ISO 12759-6:2024(en)
for all fans except fans without drives. It covers direct measurement of fan electrical input power at the
tested duty points and conversion of measured values to other duty points.
The fan electrical input power (P ) is the motor input power (P ) for fans without motor controllers and
ed,act e
is the motor controller input power (P ) for fans with motor controllers included.
ed
5.3.3  Fan electrical input power calculation using ISO 12759-2
This subclause covers measurement of fan shaft input power in accordance with ISO 5801, ISO 13350 or
ANSI/AMCA Standard 260, or rating of fan shaft input power in accordance with ISO 13348, combined with
power drive component efficiency calculations of ISO 12759-2. This method is applicable to (i) fans with
motors that fall directly within the scope of ISO 12759-2 or (ii) other three-phase induction motors with
nameplate power and number of poles that otherwise fall within the scope of ISO 12759-2, either with or
without motor controllers. Fan electrical input power is calculated based on the tested fan performance, the
known full load motor efficiency, and calculated part load losses.
For fans with motors that fall within the scope of ISO 12759-2, fan electrical input power (P ) shall
ed,act
be calculated according to ISO 12759-2, except that the nominal regulated motor efficiency (η ) in
mreg
ISO 12759-2:2019, 4.2.3 shall be either the nominal efficiency as listed in ISO 12759-2:2019,Annex B, C, or D,
or the certified full-load efficiency of the motor as required to meet relevant regional regulations.
For fans with three-phase induction motors outside the scope of ISO 12759-2 but with nameplate power
and number of poles that otherwise fall within the scope of ISO 12759-2, fan electrical input power shall be
calculated according to ISO 12759-2, with the following exceptions:
a) If the motor nameplate power is listed in the tables in ISO 12759-2:2019, Annex B, C, or D, then the
nominal regulated motor efficiency (η ) in ISO 12759-2:2019, 4.2.3 shall be the minimum of that
mreg
shown on the motor nameplate and that of ISO 12759-2:2019, Annex B, C, or D. The motor nameplate
power and efficiency shall be the full-load motor output power and efficiency determined based on
testing in accordance with IEC 60034-2-1 or NEMA MG-1 (Section IV, Part 34, for air over motors), as
applicable.
b) If the motor nameplate power falls betwe
...


Norme
internationale
ISO 12759-6
Première édition
Ventilateurs — Classification du
2024-05
rendement des ventilateurs —
Partie 6:
Calcul de l'indice énergétique des
ventilateurs
Fans — Efficiency classification for fans —
Part 6: Calculation of the fan energy index
Numéro de référence
DOCUMENT PROTÉGÉ PAR COPYRIGHT
© ISO 2024
Tous droits réservés. Sauf prescription différente ou nécessité dans le contexte de sa mise en œuvre, aucune partie de cette
publication ne peut être reproduite ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique,
y compris la photocopie, ou la diffusion sur l’internet ou sur un intranet, sans autorisation écrite préalable. Une autorisation peut
être demandée à l’ISO à l’adresse ci-après ou au comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Case postale 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Genève
Tél.: +41 22 749 01 11
E-mail: copyright@iso.org
Web: www.iso.org
Publié en Suisse
ii
Sommaire  Page
Avant-propos .iv
Introduction .v
1  Domaine d'application . 1
2  Références normatives . 1
3  Termes, définitions et symboles . 2
3.1 Termes et définitions .2
3.1.1 Termes généraux .2
3.1.2 Types de roue .4
3.1.3 Types de ventilateurs .5
3.2 Symboles .7
4  Généralités . 8
4.1 Configuration testable minimale .8
4.2 Pression du FEI .8
4.3 Accessoires .8
4.4 Ventilateurs incorporés dans un autre équipement .9
5  Indice énergétique du ventilateur . 10
5.1 Généralités .10
5.2 Puissance électrique à l'entrée de référence .10
5.2.1 Généralités .10
5.2.2 Puissance à l’arbre de référence .10
5.2.3 Rendement de la transmission de référence . 12
5.2.4 Rendement du moteur de référence . 12
5.2.5 Rendement de la commande moteur de référence . 13
5.3 Puissance électrique à l'entrée du ventilateur effective . 13
5.3.1 Généralités . 13
5.3.2 Mesurage de la puissance électrique à l'entrée du ventilateur . 15
5.3.3 Calcul de la puissance électrique à l'entrée du ventilateur en utilisant
l’ISO 12759-2 . 15
5.3.4 Puissance à l’arbre du moteur combinée avec un moteur ou un moteur et une
commande soumis à l’essai .16
5.3.5 Calcul de la puissance électrique à l'entrée du ventilateur pour des ventilateurs
avec des moteurs de rendement inconnu .17
6  Utilisation du FEI . 19
6.1 Exigences pour l’utilisation du FEI .19
6.2 Valeurs de FEI publiées .19
Annexe A (normative)  Types de ventilateurs, configurations d’essai et pression du FEI .20
Annexe B (informative)  Usage du FEI .25
Annexe C (informative)  Groupes de ventilateurs.31
Annexe D (informative)  Questions pratiques avec des ventilateurs incorporés .33
Annexe E (informative)  Mesurage de la puissance électrique — Calcul pour d’autres vitesses et
masses volumiques .34
Annexe F (informative)  Base de calcul de la puissance électrique à l’entrée de référence . 41
Bibliographie .45

iii
Avant-propos
L'ISO (Organisation internationale de normalisation) est une fédération mondiale d'organismes nationaux
de normalisation (comités membres de l'ISO). L'élaboration des Normes internationales est en général
confiée aux comités techniques de l'ISO. Chaque comité membre intéressé par une étude a le droit de faire
partie du comité technique créé à cet effet. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec l'ISO participent également aux travaux. L'ISO collabore étroitement avec
la Commission électrotechnique internationale (IEC) en ce qui concerne la normalisation électrotechnique.
Les procédures utilisées pour élaborer le présent document et celles destinées à sa mise à jour sont
décrites dans les Directives ISO/IEC, Partie 1. Il convient, en particulier, de prendre note des différents
critères d'approbation requis pour les différents types de documents ISO. Le présent document a
été rédigé conformément aux règles de rédaction données dans les Directives ISO/IEC, Partie 2 (voir
www.iso.org/directives).
L’ISO attire l’attention sur le fait que la mise en application du présent document peut entraîner l’utilisation
d’un ou de plusieurs brevets. L’ISO ne prend pas position quant à la preuve, à la validité et à l’applicabilité de
tout droit de propriété revendiqué à cet égard. À la date de publication du présent document, l’ISO [avait/
n'avait pas] reçu notification qu’un ou plusieurs brevets pouvaient être nécessaires à sa mise en application.
Toutefois, il y a lieu d’avertir les responsables de la mise en application du présent document que des
informations plus récentes sont susceptibles de figurer dans la base de données de brevets, disponible à
l'adresse www.iso.org/brevets. L’ISO ne saurait être tenue pour responsable de ne pas avoir identifié tout ou
partie de tels droits de propriété.
Les appellations commerciales éventuellement mentionnées dans le présent document sont données pour
information, par souci de commodité, à l’intention des utilisateurs et ne sauraient constituer un engagement.
Pour une explication de la nature volontaire des normes, la signification des termes et expressions
spécifiques de l'ISO liés à l'évaluation de la conformité, ou pour toute information au sujet de l'adhésion de
l'ISO aux principes de l’Organisation mondiale du commerce (OMC) concernant les obstacles techniques au
commerce (OTC), voir www.iso.org/avant-propos.
Le présent document a été élaboré par le comité technique ISO/TC 117, Ventilateurs.
Une liste de toutes les parties de la série ISO 12759 se trouve sur le site Web de l’ISO.
Il convient que l’utilisateur adresse tout retour d’information ou toute question concernant le présent
document à l’organisme national de normalisation de son pays. Une liste exhaustive desdits organismes se
trouve à l’adresse www.iso.org/fr/members.html.

iv
Introduction
L’industrie des ventilateurs est mondiale, avec un pourcentage important d’exportations et de concessions de
licences. Afin de garantir que les caractéristiques de performance des ventilateurs définies sont les mêmes
dans le monde entier, une série de normes a été élaborée. Ce secteur industriel pense qu’il est désormais
nécessaire de reconnaître le besoin d’élaborer des normes de rendement minimal.
Afin d’encourager leur mise en œuvre, un système de classification, constitué d’une série de plages de
rendement, est proposé. En fonction des améliorations des technologies et des procédés de fabrication, les
classes de rendement minimal pourront être révisées et augmentées par la suite.
Le présent document diffère des autres partie de la présente série en ce que le ventilateur n’est pas évalué à
sa valeur de rendement maximale. Au lieu de cela, le ventilateur est évalué à chaque point de fonctionnement
proposé pour la vente. Ce faisant, le présent document traite à la fois de la conception de ventilateurs
efficaces et de la sélection de ventilateurs pour une consommation électrique réduite.
l'indice énergétique des ventilateurs fournit une base cohérente pour comparer les performances
énergétiques de ventilateurs de différents types et tailles à un point de fonctionnement de ventilateur donné.
Le présent document peut être utilisé par les spécificateurs de ventilateurs pour communiquer l’intention de
conception de rendement d’un ventilateur par les personnes sélectionnant des ventilateurs pour comparer
la consommation d’énergie de différentes options de ventilateur. Avec l'amélioration de la technologie et
des procédés de fabrication, l'indice énergétique minimum autorisé pour les ventilateurs peut être revu et
augmenté au fil du temps.
v
Norme internationale ISO 12759-6:2024(fr)
Ventilateurs — Classification du rendement des
ventilateurs —
Partie 6:
Calcul de l'indice énergétique des ventilateurs
1  Domaine d'application
Le présent document définit la méthode de calcul pour l’indice énergétique des ventilateurs (FEI), qui est
un paramètre d’efficacité énergétique pour les points de fonctionnement des ventilateurs. Cette mesure
fournit une base standardisée et cohérente pour comparer les performances énergétiques de ventilateurs de
différents types et tailles à un point de fonctionnement de ventilateur donné.
Le présent document s'applique aux ventilateurs entraînés par des moteurs électriques et aux ventilateurs
sans entraînement. Il ne s'applique pas aux ventilateurs brasseurs d’air ou aux rideaux d'air.
L'indice énergétique des ventilateurs ne peut être calculé que pour des points de fonctionnement des
ventilateurs supérieurs à une puissance d'air minimale de 125 W où la puissance d'air est le produit du débit-
volume et de la pression statique du ventilateur ou supérieurs à un débit-volume minimal de 2,0 m /s.
2  Références normatives
Les documents suivants sont cités dans le texte de sorte qu'ils constituent, pour tout ou partie de leur
contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s’applique. Pour
les références non datées, la dernière édition du document de référence s’applique (y compris les éventuels
amendements).
ISO 5801:2017, Ventilateurs — Essais aérauliques sur circuits normalisés
ISO 12759-1, Ventilateurs — Classification du rendement des ventilateurs — Partie 1: Exigences générales
ISO 12759-2, Ventilateurs — Classification du rendement des ventilateurs — Partie 2: Détermination à charge
partielle
ISO 13348, Ventilateurs industriels — Tolérances, méthodes de conversion et présentation des données
techniques
ISO 13349-1, Ventilateurs — Vocabulaire et définitions des catégories — Partie 1: Vocabulaire
ISO 13350, Ventilateurs — Essai de performance des ventilateurs accélérateurs
IEC 60034-30-1:2014, Machines électriques tournantes — Partie 30-1: Classes de rendement pour les moteurs à
courant alternatif alimentés par le réseau (code IE)
IEC 60034-2-1, Machines électriques tournantes — Partie 2-1: Méthodes normalisées pour la détermination des
pertes et du rendement à partir d'essais (à l'exclusion des machines pour véhicules de traction)
IEC 60034-2-3, Machines électriques tournantes — Partie 2-3: Méthodes d’essai spécifiques pour la détermination
des pertes et du rendement des moteurs à courant alternatif alimentés par convertisseur
ANSI/AMCA Standard 260, Laboratory Methods of Testing Induced Flow Fans for Rating

3  Termes, définitions et symboles
Pour les besoins du présent document, les termes et définitions donnés dans les ISO 13349-1 et ISO 12759-1
ainsi que les suivants, s’appliquent.
L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation,
consultables aux adresses suivantes:
— ISO Online browsing platform: disponible à l'adresse https:// www .iso .org/ obp
— IEC Electropedia: disponible à l'adresse https:// www .electropedia .org/
3.1  Termes et définitions
3.1.1  Termes généraux
3.1.1.1
ventilateur
turbomachine qui reçoit de l'énergie mécanique et l'utilise à l'aide d'une ou plusieurs roues (3.1.1.2) à aubes
de manière à entretenir un écoulement continu d'air ou d'un autre gaz qui le traverse et dont le travail
massique ne dépasse pas normalement 25 kJ/kg
Note 1 à l'article: Voir l’ISO 13349-1:2022, 3.1.1 pour une information plus complète.
3.1.1.2
roue
partie rotative du ventilateur (3.1.1.1) qui transmet de l’énergie dans le flux d’air
[SOURCE: ISO 13349-1:2022, 3.7.3, modifié – remplacement de débit de gaz par flux d’air]
3.1.1.3
enveloppe
composant du ventilateur (3.1.1.1) qui interagit avec le flux d’air qui passe à travers la roue (3.1.1.2)
Note 1 à l'article: Une enveloppe peut être un élément autour de la roue (3.1.1.2) qui guide le flux d’air vers, à travers et
à partir de la roue.
Note 2 à l'article: Un carter peut être doté de pièces supplémentaires incluses ou rattachées qui affectent les
performances du ventilateur (3.1.1.1), telles qu'un pavillon d’aspiration (également appelé venturi), un cône d'entrée, un
rayon d'entrée, un anneau d'entrée, une aube directrice d'entrée, une aube directrice de sortie ou un diffuseur de sortie.
3.1.1.4
ventilateur sans entraînement
ventilateur non entraîné
ventilateur seul
ventilateur (3.1.1.1) sans moteur, transmission (3.1.1.8) ou commande de moteur (3.1.1.14)
Note 1 à l'article: Dans la présente définition, le terme entraînement désigne les moteurs, transmissions et les
commandes de moteur.
3.1.1.5
motoventilateur
ventilateur (3.1.1.1) entraîné par un moteur électrique, avec ou sans transmission (3.1.1.8) ou commande de
moteur (3.1.1.14)
Note 1 à l'article: Dans le présent document, le terme moteur désigne toujours un moteur électrique.
[SOURCE: ISO 13349-1:2022, 3.1.3, modifié – Note 1 incluse dans le corps du terme]
3.1.1.6
ventilateur à entraînement direct
configuration de motoventilateur (3.1.1.5) dans laquelle la roue (3.1.1.2) est reliée directement au moteur

3.1.1.7
ventilateur à entraînement par courroies
configuration de motoventilateur (3.1.1.5) dans laquelle la roue (3.1.1.2) est reliée au moteur par
l’intermédiaire d’un ensemble de courroies et de poulies montées sur l’arbre du moteur et l’arbre du
ventilateur
Note 1 à l'article: Ceci comprend les ventilateurs ayant des transmissions par courroies trapézoïdales (3.1.1.10) ou par
courroies synchrones (3.1.1.11).
3.1.1.8
transmission
composant qui transfère de l’énergie d’un moteur à une roue
EXEMPLE Poulies, courroies, engrenages, accouplements.
3.1.1.9
transmission par courroies trapézoïdales
forme de transmission (3.1.1.8) utilisant des courroies d’entraînement ayant une section transversale
sensiblement trapézoïdale qui utilise des poulies ayant une surface de contact lisse
Note 1 à l'article: Les courroies trapézoïdales conventionnelles ont une section transversale constante sur toute la
longueur, tandis que les courroies trapézoïdales crantées (aussi appelées courroies trapézoïdales dentées) ont des
fentes perpendiculaires à leur longueur. Les fentes réduisent la résistance à la flexion et offrent un meilleur rendement
que les courroies trapézoïdales classiques.
3.1.1.10
transmission par courroies synchrones
forme de transmission (3.1.1.8) utilisant des courroies d’entraînement ayant une section transversale
sensiblement rectangulaire contenant des dents qui engagent les dents correspondantes sur les poulies afin
de permettre une transmission de puissance sans glissement
Note 1 à l'article: Ces courroies sont parfois appelées courroies de distribution ou courroies dentées.
3.1.1.11
ventilateur autonome
ventilateur (3.1.1.1) dans au moins une configuration testable minimale
Note 1 à l'article: Cela comprend tout moteur, transmission ou commande de moteur si le ventilateur évalué en inclut
une. Cela comprend également tout accessoire inclus dans le ventilateur évalué, et exclut l’impact de tout équipement
environnant dont l’objectif dépasse ou est différent de celui du ventilateur. Voir 4.1.
Note 2 à l'article: Les ventilateurs autonomes ne comprennent pas de dispositifs pour le conditionnement de l’air, la
filtration de l’air, le brassage de l’air, le traitement de l’air ou le chauffage.
EXEMPLE Ventilateurs de toit motorisés, ventilateurs d’extraction sur paroi latérale, ventilateurs en ligne,
ventilateurs accélérateurs et ventilateurs d’extraction en laboratoire à flux induit.
[SOURCE: ISO 13349-1:2022, 3.1.4, modifié – ajout d’un exemple et de détails aux notes]
3.1.1.12
ventilateur incorporé
ventilateur intégré
ventilateur (3.1.1.1) qui est placé ou fixé fermement à l’intérieur de ou attaché à une pièce environnante d’un
équipement dont l’objectif dépasse celui d’un ventilateur (3.1.1.1) ou est différent de celui d’un ventilateur
autonome (3.1.1.11)
Note 1 à l'article: L'équipement environnant peut avoir ses propres exigences en matière de sécurité ou d'efficacité
énergétique.
Note 2 à l'article: Les ventilateurs incorporés sont également appelés ventilateurs intégrés.
EXEMPLE Ventilateurs de soufflage dans les caissons de traitement d’air, ventilateurs de condenseur dans les
équipements de rejet de chaleur, les turbines tangentielles dans les unités de rideau d’air, et ventilateurs d’air de
combustion à tirage induit ou tirage forcé dans les chaudières ou les fours.

3.1.1.13
commande de moteur
dispositif qui peut être utilisé pour commander la vitesse du moteur et par conséquent du ventilateur (3.1.1.1)
3.1.1.14
moteur régulé
moteur dont le rendement ou la consommation électrique est soumis(e) à des réglementations régionale ou
nationale
EXEMPLES Europe: Règlement de la commission (UE) 2019/1781
Chine: GB 18613
États-Unis: Code des règlements fédéraux 10CFR Part 431
3.1.1.15
rendement de moteur par défaut
rendement par défaut attribué au moteur à une puissance de sortie du moteur donnée lorsque le moteur
spécifique n’est pas identifié ou que le rendement du moteur utilisé est inconnu
Note 1 à l'article: L’utilisation d’un rendement par défaut est destinée à représenter les moteurs généralement
disponibles. Puisque les réglementations de rendement de moteur sont contrôlées régionalement, le rendement du
moteur par défaut doit refléter ces réglementations. Voir 5.3.5 pour des exemples.
3.1.1.16
point de fonctionnement
point de débit-volume (q ) et de pression (pf ou p ) unique au sein de la plage de fonctionnement publiée du
v fs
ventilateur (3.1.1.1)
3.1.1.17
puissance électrique de référence
puissance de référence utilisée pour comparer les performances de tous les ventilateurs à une base commune
Note 1 à l'article: La puissance électrique de référence définit une valeur unique de puissance électrique à l'entrée du
ventilateur pour un débit-volume et une pression de ventilateur donnés.
3.1.2  Types de roue
NOTE Voir l’ISO 13349-1 pour une description complète des variations entre les types de roues. Les définitions
ci-dessous incluent uniquement la différenciation nécessaire à la présente norme.
3.1.2.1
roue axiale
hélice
roue (3.1.1.2) avec un certain nombre de pales s’étendant radialement à partir d’un moyeu central, dans
lequel le flux d’air traversant la roue est axial; c’est-à-dire que le flux d’air entre dans la roue et en sort
parallèlement à l’axe de l’arbre (c’est-à-dire, avec un angle d’écoulement (3.1.2.5) ≤ 20 )
Note 1 à l'article: Les pales peuvent être d'épaisseur constante ou profilées.
3.1.2.2
roue centrifuge
roue (3.1.1.2) avec un certain nombre de pales s’étendant entre un disque arrière et un disque avant, dans
laquelle le flux d’air entre axialement par une ou deux aspirations et sort radialement à la périphérie de la
roue, soit dans l'espace libre, soit dans une volute avec un angle d’écoulement du ventilateur (3.1.2.5) ≤ 70°
Note 1 à l'article: Les roues (3.1.1.2) peuvent être classées comme simple ouïe d'aspiration ou double ouïes d'aspiration.
Note 2 à l'article: Les pales peuvent être penchées vers l’arrière ou vers l’avant par rapport à la direction de rotation
de la roue. Les roues avec pales penchées vers l’arrière peuvent être profilées (AF), d'épaisseur constante et courbées
vers l’arrière (BC), d'épaisseur constante, plates et courbées vers l’arrière (BI), ou radiales en périphérie (RT). Les
roues avec pales penchées vers l’avant sont dites courbées vers l’avant (FC).

3.1.2.3
roue radiale
forme de roue  centrifuge (3.1.2.2) avec un certain nombre de pales s’étendant radialement à partir d’un
moyeu central, dans laquelle le flux d’air entre axialement par une seule ouïe d'aspiration et sort radialement
à la périphérie de la roue dans une volute, les pales de la roue étant positionnées de sorte que la tangente à la
pale à la périphérie de la roue soit perpendiculaire avec une tolérance de 25° à l’axe de rotation
Note 1 à l'article: Les roues radiales peuvent facultativement avoir un disque arrière et/ou disque avant.
3.1.2.4
roue hélico-centrifuge
roue (3.1.1.2) avec des caractéristiques de construction intermédiaires entre celles d’une roue axiale (3.1.2.1)
et d’une roue centrifuge (3.1.2.2) avec un angle d’écoulement du ventilateur (3.1.2.5) entre à 20° et à 70°
Note 1 à l'article: Le flux d’air entre axialement par une seule ouïe d'aspiration et sort avec des directions axiale et
radiale combinées à un diamètre moyen supérieur à l’ouïe d'aspiration.
Note 2 à l'article: Les roues hélico-centrifuges sont parfois connues sous le nom de roues diagonales.
Note 3 à l'article: Les roues hélico-centrifuges portent l’abréviation MF dans le Tableau A.1.
3.1.2.5
angle d’écoulement du ventilateur
angle de la ligne médiane de la surface d’écoulement de l’air d’une pale de ventilateur mesuré au milieu de
son bord de fuite avec la ligne médiane de l’axe de rotation, dans un plan passant par l’axe de rotation et le
milieu du bord de fuite
3.1.3  Types de ventilateurs
NOTE Voir l’ISO 13349-1 pour une description plus complète des variations entre les types de ventilateurs. Les
définitions ci-dessous n'incluent que les types de ventilateurs qui sont testés différemment, fonctionnent différemment
ou présentent un avantage unique, autre que l'efficacité, par rapport aux autres types de ventilateurs (par exemple,
niveaux sonores, taille compacte), de sorte que l'on peut s'attendre à ce qu'ils fonctionnent dans une plage de FEI
différente de celle des autres types de ventilateurs. Des informations supplémentaires sur les raccordements typiques
des conduits sont également fournies.
3.1.3.1
ventilateur centrifuge dans une enveloppe
ventilateur à écoulement radial
ventilateur avec une roue centrifuge ou radiale dans laquelle le flux d’air sort dans une enveloppe qui est
généralement en forme de volute pour diriger l’air par une seule ouïe de refoulement du ventilateur
Note 1 à l'article: Les ouïes d'aspiration et de refoulement peuvent facultativement être raccordées.
3.1.3.2
ventilateur centrifuge en ligne
ventilateur avec une roue centrifuge dans laquelle le flux d’air entre axialement par l'ouïe d’aspiration du
ventilateur et l' enveloppe redirige le flux d’air radial provenant de la roue pour qu’il sorte du ventilateur
dans une direction axiale
Note 1 à l'article: Les ouïes d'aspiration et de refoulement peuvent facultativement être raccordées.
3.1.3.3
ventilateur centrifuge à roue libre
ventilateur centrifuge de plénum
ventilateur avec une roue centrifuge dans laquelle le flux d’air entre par un panneau et est refoulé dans un
espace libre
Note 1 à l'article: Les ouïes de refoulement ne sont pas raccordées.
Note 2 à l'article: Ce type de ventilateurs comprend les ventilateurs destinés à être utilisés sur des groupes de
ventilateurs montés en parallèle, chaque ventilateur étant cloisonné par rapport aux autres ventilateurs du groupe.

3.1.3.4
ventilateur de toiture
PRV
ventilateur avec un moteur interne et un chapeau permettant d’éviter que les précipitations n’entrent dans
le bâtiment
Note 1 à l'article: Il comprend un socle destiné à s’adapter sur une ouverture de toit ou de mur, généralement au moyen
d’un rebord de toit.
3.1.3.5
extracteur PRV centrifuge
PRV avec une roue centrifuge qui extrait de l’air d’un bâtiment
Note 1 à l'article: L'aspiration est généralement raccordée, mais le refoulement n'est pas raccordé.
3.1.3.6
PRV centrifuge d’alimentation
PRV avec une roue centrifuge qui fournit de l’air à un bâtiment
Note 1 à l'article: L'aspiration n'est pas raccordée, mais le refoulement l'est généralement.
3.1.3.7
PRV axial
PRV avec une roue axiale qui fournit de l’air à un bâtiment ou en évacue d’un bâtiment
Note 1 à l'article: L'aspiration et le refoulement ne sont généralement pas raccordés.
3.1.3.8
ventilateur en ligne
ventilateur avec une roue axiale et une enveloppe cylindrique avec ou sans aubes directrices
Note 1 à l'article: L’aspiration et le refoulement peuvent être facultativement raccordés.
3.1.3.9
ventilateur axial en paroi
ventilateur avec une roue axiale montée dans une virole courte qui peut être un panneau, un anneau ou un
diaphragme
Note 1 à l'article: La virole est généralement montée sur un mur séparant deux espaces et les ventilateurs sont utilisés
pour augmenter la pression de part et d’autre de ce mur. L'aspiration et le refoulement ne sont généralement pas
raccordés.
Note 2 à l'article: Ces ventilateurs sont parfois connus sous le nom de ventilateurs hélices.
3.1.3.10
ventilateur extracteur d'air de laboratoire
ventilateur conçu spécialement pour évacuer l’air contaminé verticalement d’un bâtiment. Le refoulement
du ventilateur est généralement étroit pour atteindre une vitesse de refoulement élevée
Note 1 à l'article: Les ventilateurs d’extraction de laboratoire peuvent être conçus avec ou sans flux induit. Les
ventilateurs extracteurs d'air de laboratoire utilisent leur refoulement à vitesse élevée pour entraîner de l’air
supplémentaire afin qu’il se mélange avec l’air d’extraction contaminé du bâtiment.
Note 2 à l'article: L'aspiration peut facultativement être raccordée, le refoulement n'est pas raccordé.
3.1.3.11
ventilateur accélérateur
ventilateur utilisé pour produire un flux d’air à vitesse élevée dans un espace
Note 1 à l'article: Une fonction habituelle est d’ajouter du mouvement à l’air à l’intérieur d’un tunnel. L'aspiration et le
refoulement ne sont pas raccordés.

3.1.3.12
ventilateur brasseur d’air
ventilateur utilisé pour faire circuler l'air à l’intérieur d’un espace qui n’a pas de dispositif de raccordement à
un conduit ou de séparation entre l’aspiration et le refoulement du ventilateur
3.1.3.13
ventilateur tangentiel
ventilateur avec une enveloppe qui crée un flux d’air à travers la roue dans une direction à angle droit par
rapport à son axe de rotation et où un flux d’air à la fois entre et sort de la roue à sa périphérie
Note 1 à l'article: Les ouïe d'aspiration et de refoulement peuvent facultativement être raccordés.
3.1.3.14
groupe de ventilateurs
application courante de ventilateurs utilisant de multiples ventilateurs en parallèle entre deux sections de
plénum pour un caisson de traitement d’air incorporé en usine ou monté sur place
3.2  Symboles
Symbole Quantité représentée Unité
A Aire de l'ouïe de refoulement du ventilateur m
A, B, C, D, E Constantes sans dimension
I Indice énergétique du ventilateur (FEI) sans dimension
P Puissance électrique de référence à l’entrée du ventilateur kW
ed,ref
P Puissance électrique effective à l'entrée à l'entrée du ventilateur kW
ed,act
P Puissance de référence à l’arbre du ventilateur kW
a,ref
P Puissance effective à l’arbre du ventilateur kW
a,act
P Puissance de référence en sortie moteur kW
o,ref
P Puissance effective en sortie moteur kW
o,act
P Puissance par défaut en sortie moteur kW
o,def
p Constante de pression Pa
p Pression statique du ventilateur au point de fonctionnement Pa
fs
p Pression totale du ventilateur au point de fonctionnement Pa
f
q Débit-volume du ventilateur au point de fonctionnement m /s
V
q Constante de débit-volume m /s
T Force due à la poussée du ventilateur N
m
η Constante de rendement du ventilateur sans dimension
η Rendement de référence de la transmission sans dimension
T,ref
η Rendement effectif de la transmission sans dimension
T,act
η Rendement de référence du moteur sans dimension
mot,ref
η Rendement effectif du moteur sans dimension
mot,act
η Rendement effectif du moteur et de la commande sans dimension
mc,act
η Rendement de référence de la commande du moteur sans dimension
c,ref
η Rendement par défaut du moteur sans dimension
mot,def
P Masse volumique de l’air du ventilateur kg/m
ρ Masse volumique de l’air standard kg/m
ref
4  Généralités
4.1  Configuration testable minimale
Le calcul du FEI est basé sur les performances des ventilateurs calculées à partir d’essais conformes à des
normes d’essai de ventilateur reconnues. Voir l’Annexe A pour déterminer la norme d’essai appropriée pour
chaque type de ventilateurs. Ces normes d’essai requièrent chacune une configuration minimale afin de
pouvoir réaliser les essais. Le présent document est également basé sur des essais de ventilateurs dans au
moins une configuration testable minimale comprenant:
— roue;
— moteur et arbre distinct avec paliers pour soutenir la roue;
— structure ou enveloppe ou stator, sauf si le ventilateur ne les requiert pas (par exemple, un ventilateur
brasseur d’air non caréné).
Chaque modèle de ventilateur évalué doit être classé selon le type de ventilateur applicable figurant dans
le Tableau A.1, en fonction du mode de distribution de ce ventilateur dans le commerce. Par exemple, si un
ventilateur répond à la définition d’un ventilateur accélérateur, il doit être soumis à l’essai et classé comme
ventilateur accélérateur selon le Tableau A.1.
4.2  Pression du FEI
Le FEI doit être calculé en utilisant la pression totale du ventilateur ou la pression statique du ventilateur, en
fonction du type de ventilateur. Voir l’Annexe A pour une explication complète de la pression et pour savoir
quelle pression utiliser.
4.3  Accessoires
Certains accessoires peuvent être utilisés pour améliorer les performances des ventilateurs, y compris, mais
sans s’y limiter, les pavillons d’aspiration, les diffuseurs, les stators ou les aubes directrices. Si un accessoire
améliore les performances du ventilateur et s'il est toujours fourni avec le ventilateur lorsqu’il est distribué
dans le commerce, il doit être soumis à l’essai avec le ventilateur. Il n’est pas exigé que les conduits d’essai
utilisés pendant les essais soient fournis avec le ventilateur.
Les accessoires qui réduisent les performances d’un ventilateur ne sont pas inclus dans la configuration
testable minimale utilisée pour déterminer le FEI. Ceux-ci comprennent, sans toutefois s’y limiter, les
protecteurs, les amortisseurs, les filtres ou les capots de protection contre les intempéries. L’effet de ces
accessoires sur les performances des ventilateurs peut être soumis à l’essai et publié pour faciliter la
sélection des ventilateurs, mais les accessoires ne sont pas compris dans l’essai de ventilateur utilisé pour
déterminer le FEI.
Comme illustré à la Figure 1, les performances réduites d’un ventilateur avec accessoires (Figure 1, courbe
étiquetée [2]) peuvent être publiées et comparées aux pressions du système afin de faire une sélection
correcte du ventilateur. Le processus de sélection des ventilateurs comprend la détermination de la vitesse
de rotation du ventilateur et/ou du pas des pales nécessaire(s) pour atteindre la pression du système requise
(p ) au débit-volume requis (q ) (Figure 1, courbe étiquetée [4]). Une fois la vitesse du ventilateur
f,req v,req
et/ou le pas des pales déterminé(e), le FEI est calculé à partir des performances du ventilateur autonome
(Figure 1, courbe étiquetée [1]) aux mêmes débit-volume, vitesse de rotation et pas des pales (Figure 1,
courbe étiquetée [5]) combinés avec la puissance électrique du ventilateur en un point de fonctionnement de
ce ventilateur autonome.
Légende
X débit-volume, exprimé en m /s
Y pression statique totale, exprimée en Pa
1 courbe de pressions du ventilateur seul
2 courbe de pressions du ventilateur avec accessoires
3 courbe de résistance du système externe au ventilateur et ses accessoires
4 point de fonctionnement du ventilateur avec accessoires
5 point de fonctionnement du ventilateur seul utilisé pour le calcul du FEI
6 réduction des pressions due aux accessoires du ventilateur
q débit-volume du ventilateur seul
v
p capacité de pression du ventilateur seul
f
q débit-volume requis du ventilateur
V,req
p pression nécessaire pour surmonter la résistance du système
f,req
Figure 1 — Courbes du ventilateur à une vitesse de ventilateur et un pas de pales constants avec et
sans accessoires
4.4  Ventilateurs incorporés dans un autre équipement
Le présent document ne s’applique pas aux performances des ventilateurs lorsque le ventilateur soumis à
l’essai est incorporé à l’intérieur d’un autre équipement. Cependant, le présent document peut être utilisée
pour calculer le FEI pour un ventilateur qui, lorsqu’il est soumis à l’essai dans une configuration autonome,
sera incorporé dans un autre équipement. Le FEI du ventilateur incorporé est déterminé à partir des
performances du ventilateur autonome aux mêmes débit-volume, vitesse de ventilateur et pas des pales.
En aucun cas, un essai d’un ventilateur incorporé dans l’équipement ne doit être utilisé pour prévoir le FEI
du ventilateur autonome. Voir l’Annexe D pour des informations supplémentaires sur les questions liées aux
performances d’un ventilateur incorporé.

5  Indice énergétique du ventilateur
5.1  Généralités
L’indice énergétique du ventilateur (FEI) est défini comme le rapport de la puissance électrique à l’entrée
du ventilateur de référence à la puissance électrique d’entrée du ventilateur effectif pour lequel le FEI est
calculé, au même point de fonctionnement, qui est caractérisé par une valeur de débit-volume (q ) et de
V
pression (p ou p ) du ventilateur. Les valeurs du FEI (I) peuvent être calculées pour chaque point sur une
f fs
courbe de ventilateur conformément à la Formule (1).
P
ed,ref
I= (1)
P
ed,act

P est la puissance électrique à l’entrée de référence en kW
ed,ref
P est la puissance électrique à l’entrée effective en kW
ed,act
Utiliser la pression totale ou la pression statique de manière cohérente dans l'ensemble de l'Article 5, et il
est important d’indiquer comment le FEI a été déterminé, que ce soit en utilisant la pression totale ou la
pression statique (voir 5.2.2.1 et l'Annexe B).
5.2  Puissance électrique à l'entrée de référence
5.2.1  Généralités
Le concept de référence est utilisé pour normaliser le calcul du FEI à un niveau de puissance cohérent
indépendant du type de ventilateur, des composants d’entraînement du ventilateur ou de toutes exigences
réglementaires. La puissance électrique à l'entrée de référence est finalement une fonction du débit-volume
et de la pression du ventilateur, mais requiert un calcul itératif commençant par la Formule (2). Les détails
de la base de la puissance électrique à l’entrée de référence, y compris les constantes q , p et η , figurent à
0 0 0
l'Annexe F.
     
11 1
PP=×  × × (2)
     
ed,,refra ef
ηη η
 Tc,,refm  ot refr  , ef 

P est la puissance à l’arbre de référence en kW;
a,ref
η est le rendement de la transmission de référence;
T,ref
η est le rendement du moteur de référence;
mot,ref
η est le rendement de la commande moteur de référence.
c,ref
5.2.2  Puissance à l’arbre de référence
5.2.2.1  Généralités
Les performances du ventilateur au point de fonctionnement doivent être obtenues par des essais conformes
aux normes énumérées dans le Tableau A.1 ou calculées conformément aux lois et aux règles de conversion
spécifiées dans l’ISO 13348. Si nécessaire, les méthodes d’interpolation de l'Annexe E peuvent également
être utilisées.
La puissance à l'arbre de référence, P , doit être calculée soit à partir de la pression totale du ventilateur,
a,ref
soit à partir de la pression statique du ventilateur, en fonction du type de ventilateur. Voir l'Annexe A pour
une description complète et une liste des types de ventilateurs et de la pression FEI.
Tout au long de l'Article 5, il est nécessaire d'utiliser systématiquement la pression totale ou statique. P
a,ref
(5.2) et P (5.3) sont fonction de la pression du ventilateur et doivent utiliser la même base de pression.
a,act
Par exemple, si la base de pression requise de l'Annexe A est la pression totale du ventilateur, les puissances,
P , et P sont calculées à la même pression totale du ventilateur, même si la performance du ventilateur
a,ref a,act
est finalement publiée en termes de pression statique du ventilateur.
5.2.2.2  Pression totale
Pour les ventilateurs identifiés dans l’Annexe A comme utilisant la pression totale, la puissance à l’arbre
du ventilateur de référence (P ) à un point de fonctionnement donné est fonction du débit-volume du
a,ref
ventilateur (q ) et de la pression totale du ventilateur (p ) à ce point de fonctionnement. Elle est calculée
V f
selon la Formule (3):
 
ρ
qq+ ×+pp ×
()
 
Vf00
ρ
 
ref
P = (3)
ar, ef
1 000× η

q est le débit-volume du ventilateur en m /s;
V
p est la pression totale du ventilateur en Pa;
f
3;
ρ est la masse volumique de l’air en kg/m
3;
ρ est la masse volumique de l’air standard, 1,2 kg/m
ref
q = 0,118 m /s;
p = 100 Pa;
η = 66 %.
5.2.2.3  Pression statique
Pour les ventilateurs identifiés dans l’Annexe A comme utilisant la base de pression statique, la puissance
à l’arbre du ventilateur de référence (P ) à un point de fonctionnement donné est une fonction du débit-
a,ref
-volume du ventilateur (q ) et de la pression statique du ventilateur (p ) à ce point de fonctionnement,
V fs
calculée selon la Formule (4):
 ρ 
qq+ ×+pp ×
()
Vf00 s 
ρ
 
ref
P = (4)
ar, ef
1 000×η

q est le débit volume du ventilateur en m /s;
V
p est la pression statique du ventilateur en Pa;
fs
3;
ρ est la masse volumique de l’air en kg/m
3;
ρ est la masse volumique de l’air standard, 1,2 kg/m
ref
q = 0,118 m /s;
p = 100 Pa;
η = 60 %.
5.2.3  Rendement de la transmission de référence
Le rendement de la transmission de référence (η ) doit être calculé en utilisant
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

ISO 12759-6:2024 is a standard published by the International Organization for Standardization (ISO). Its full title is "Fans - Efficiency classification for fans - Part 6: Calculation of the fan energy index". This standard covers: This document defines the calculation method for determining the fan energy index (FEI), which is an energy efficiency metric for fan duty points. This metric provides a standardized and consistent basis to compare fan energy performance across fan types and sizes at a given fan duty point. This document is applicable to fans driven by electric motors and fans without drives. It is not applicable to circulating fans or air curtains. The fan energy index can only be calculated for fan duty points above a minimum air power of 125 W (where air power is the product of volume flow rate and fan static pressure) or above a minimum volume flow rate of 2,0 m3/s.

This document defines the calculation method for determining the fan energy index (FEI), which is an energy efficiency metric for fan duty points. This metric provides a standardized and consistent basis to compare fan energy performance across fan types and sizes at a given fan duty point. This document is applicable to fans driven by electric motors and fans without drives. It is not applicable to circulating fans or air curtains. The fan energy index can only be calculated for fan duty points above a minimum air power of 125 W (where air power is the product of volume flow rate and fan static pressure) or above a minimum volume flow rate of 2,0 m3/s.

ISO 12759-6:2024 is classified under the following ICS (International Classification for Standards) categories: 23.120 - Ventilators. Fans. Air-conditioners. The ICS classification helps identify the subject area and facilitates finding related standards.

You can purchase ISO 12759-6:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.