Electromagnetic compatibility (EMC) - Part 2-14: Environment - Overvoltages on public electricity distribution networks

IEC TR 61000-2-14:2006 Describes the electromagnetic environment with respect to the voltages in excess of normal that are found on electricity supply networks operating at low and medium nominal voltages and that can be impressed on equipment connected to those networks, without considering further effects (e.g. amplification or attenuation) within an installation. Since these overvoltages have the potential to hinder the functioning of electrical and electronic equipment, they fall within the definition of electromagnetic disturbance in the field of EMC. Various categories of overvoltage are described, based on relative magnitude, duration and energy content. This Technical Report describes the phenomena of overvoltages, it does not specify compatibility levels and does not directly specify emission and immunity levels. The report describes the various phenomena and processes that cause overvoltages, including the transfer into the networks concerned of overvoltages that originate in or traverse other networks and installations, including higher voltage networks and the installations of electricity users. The effects of overvoltages on equipment are outlined. Some case studies of overvoltage events are presented. Recommendations are made regarding the general technical approach to mitigating the risk of equipment being hindered from operating as intended by the effects of overvoltages. (It is not the function of IEC publications to assign responsibility for mitigating measures to any of the parties involved.) The purpose of this report is to ensure that this important category of electromagnetic disturbance is included in the description of the environment in Part 2 of IEC 61000. For that purpose, only a brief description is provided of the various overvoltages and their causes and effects. A much more detailed treatment can be found in IEC 62066. A UIE publication - Guide to quality of electrical supply for industrial installations, Part VI: Transient and temporary overvoltages and currents - has a similar content. Measurement methods are specified in IEC 61000-4-30.

Compatibilité électromagnétique (CEM) - Partie 2-14: Environnement - Surtensions sur les réseaux de distribution publics

IEC/TR 61000-2-14:2006 décrit l'environnement électromagnétique en ce qui concerne les tensions supérieures aux valeurs normales qui apparaissent dans les réseaux d'alimentation électrique fonctionnant aux tensions nominales basses et moyennes, et dont peuvent faire l'objet les matériels connectés à ces réseaux, sans tenir compte de leurs effets (amplification ou atténuation, par exemple) à l'intérieur d'une installation. Ces surtensions risquant d'empêcher le fonctionnement du matériel électrique et électronique, elles entrent dans le cadre de la définition des perturbations électromagnétiques dans le domaine de la CEM. Différentes catégories de surtensions sont décrites, en fonction de l'amplitude relative, de la durée et du contenu énergétique. Le présent Rapport technique décrit les phénomènes de surtension. Il ne précise pas les niveaux de compatibilité ni ne spécifie directement les niveaux d'émission et d'immunité. Le rapport décrit les différents phénomènes et processus à l'origine de surtensions, y compris le transfert dans les réseaux concernés de surtensions qui prennent leur source ou traversent d'autres réseaux et installations, y compris les réseaux à haute tension et les installations des usagers. Les effets des surtensions sur le matériel sont présentés. Certaines études de cas relatives à des événements de surtension sont présentées.
Des recommandations sont formulées en ce qui concerne l'approche technique générale permettant de limiter le risque de difficultés de fonctionnement lié aux effets des surtensions (il ne revient pas aux publications de l'IEC d'attribuer la responsabilité des mesures d'atténuation à l'une des parties impliquées.) Le présent rapport a pour objet de vérifier que cette catégorie importante de perturbations électromagnétiques est incluse dans la description de l'environnement dans la Partie 2 de l'IEC 61000. À cet effet, seule une brève description des différentes surtensions et de leurs causes et effets est fournie. Un traitement beaucoup plus détaillé peut être consulté dans l'IEC 62066. Une publication UIE (Guide to quality of electrical supply for industrial installations, Part VI: Transient and temporary overvoltages and currents – disponible en anglais seulement) présente un contenu similaire. Les méthodes de mesure sont spécifiées dans l'IEC 61000-4-30. NOTE Le présent Rapport technique ne contient pas de résultats de mesure détaillés relatifs aux surtensions. Par conséquent, la probabilité d'occurrence ne peut pas être évaluée.
Mots clés: surtensions

General Information

Status
Published
Publication Date
12-Dec-2006
Current Stage
PPUB - Publication issued
Start Date
31-Dec-2006
Completion Date
13-Dec-2006
Ref Project

Buy Standard

Technical report
IEC TR 61000-2-14:2006 - Electromagnetic compatibility (EMC) - Part 2-14: Environment - Overvoltages on public electricity distribution networks Released:12/13/2006 Isbn:2831889405
English language
43 pages
sale 15% off
Preview
sale 15% off
Preview
Technical report
IEC TR 61000-2-14:2006 - Electromagnetic compatibility (EMC) - Part 2-14: Environment - Overvoltages on public electricity distribution networks
English and French language
88 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


TECHNICAL IEC
REPORT TR 61000-2-14
First edition
2006-12
Electromagnetic compatibility (EMC) –
Part 2-14:
Environment – Overvoltages on public electricity
distribution networks
Reference number
IEC/TR 61000-2-14:2006(E)
Publication numbering
As from 1 January 1997 all IEC publications are issued with a designation in the
60000 series. For example, IEC 34-1 is now referred to as IEC 60034-1.
Consolidated editions
The IEC is now publishing consolidated versions of its publications. For example,
edition numbers 1.0, 1.1 and 1.2 refer, respectively, to the base publication, the
base publication incorporating amendment 1 and the base publication incorporating
amendments 1 and 2.
Further information on IEC publications
The technical content of IEC publications is kept under constant review by the IEC,
thus ensuring that the content reflects current technology. Information relating to
this publication, including its validity, is available in the IEC Catalogue of
publications (see below) in addition to new editions, amendments and corrigenda.
Information on the subjects under consideration and work in progress undertaken
by the technical committee which has prepared this publication, as well as the list
of publications issued, is also available from the following:
• IEC Web Site (www.iec.ch)
• Catalogue of IEC publications
The on-line catalogue on the IEC web site (www.iec.ch/searchpub) enables you to
search by a variety of criteria including text searches, technical committees
and date of publication. On-line information is also available on recently issued
publications, withdrawn and replaced publications, as well as corrigenda.
• IEC Just Published
This summary of recently issued publications (www.iec.ch/online_news/ justpub)
is also available by email. Please contact the Customer Service Centre (see
below) for further information.
• Customer Service Centre
If you have any questions regarding this publication or need further assistance,
please contact the Customer Service Centre:

Email: custserv@iec.ch
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
TECHNICAL IEC
REPORT TR 61000-2-14
First edition
2006-12
Electromagnetic compatibility (EMC) –
Part 2-14:
Environment – Overvoltages on public electricity
distribution networks
© IEC 2006 ⎯ Copyright - all rights reserved
No part of this publication may be reproduced or utilized in any form or by any means, electronic or
mechanical, including photocopying and microfilm, without permission in writing from the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
PRICE CODE
Commission Electrotechnique Internationale X

International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
For price, see current catalogue

– 2 – TR 61000-2-14 © IEC:2006(E)
CONTENTS
FOREWORD.4
INTRODUCTION.6

1 Scope.7
2 Normative references .7
3 Terms and definitions .7
4 Description of overvoltages .10
4.1 General .10
4.2 External overvoltages.11
4.3 Internal overvoltages.11
4.4 Overvoltage waveshape .11
5 Long duration overvoltages .12
5.1 Sustained earth faults.12
5.2 Broken neutral on LV network.12
5.3 Maloperation of voltage regulating equipment.13
5.4 Overvoltages due to voltage unbalances .13
5.5 Dispersed generation .14
6 Short duration overvoltages.15
6.1 Earth faults.15
6.2 Load rejection (sudden load loss) .16
6.3 Self-excitation .16
6.4 Resonance and ferroresonance.16
7 Very short duration overvoltages (transients).18
7.1 General description .18
7.2 Lightning .19
7.3 Switching .20
7.4 Summary of surge duration and cause.26
8 Effects of overvoltages on equipment .27
8.1 General considerations.27
8.2 Reduction in life of filament lamps .28
8.3 Effect of overvoltages on IT equipment.28
9 Case studies .29
9.1 General .29
9.2 Switching of LV power factor correction capacitor.29
9.3 Metal fusion furnace .30
9.4 Switching of MV power factor correction capacitor.31
9.5 DC traction system .32
9.6 Load switching .34
10 Protection against the effects of overvoltages.36
10.1 General considerations.36
10.2 Point on wave switching .36
10.3 Arcing horns and spark gaps .37
10.4 Overvoltage protection relays .38
10.5 Snubbers (high frequency RC filter).38
10.6 Uninterruptible power supply (UPS) systems .39

TR 61000-2-14 © IEC:2006(E) – 3 –
10.7 Surge protection device (SPD) .39
11 Conclusions.41
12 Recommendations.42

Bibliography.43

Figure 1 – Lightning impulse test voltage characteristic .11
Figure 2 – Broken neutral on LV network .13
Figure 3 – The effect of distributed generation on network voltage.14
Figure 4 – Line – Neutral temporary overvoltage on healthy phase for single phase line
– earth fault .15
Figure 5 – Typical transient overvoltage when energizing a capacitor bank.22
Figure 6 – Notching caused by power electronics switching .24
Figure 7 – ITI (CBEMA) curve for equipment connected to 120 V 60 Hz systems .29
Figure 8 – Voltage waveform distorted by the energization of a PFC capacitor .30
Figure 9 – Phase to ground overvoltage in case of a single (a) or multiple (b) faults .30
Figure 10 – Equivalent circuit.31
Figure 11 – Extruder connection – single line diagram .32
Figure 12 – Current waveforms (phases A and C) taken at the main LV circuit breaker.32
Figure 13 – Single line diagram of public transportation system .33
Figure 14 – Voltage waveforms associated with overvoltages on public transportation
system .34
Figure 15 – 20 kV line-to-earth voltages during breaking transformer current.35
Figure 16 – Spark gap .37
Figure 17 – Two-stage surge protection scheme .40

Table 1 – Surges on the low voltage network .26
Table 2 – Surges on the medium voltage network .27
Table 3 – Reduction of filament lamp life .28
Table 4 – Protective levels for typical MV surge arresters (effectively earthed neutral
systems) .41

– 4 – TR 61000-2-14 © IEC:2006(E)
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 2-14: Environment – Overvoltages on public electricity
distribution networks
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of thi
...


IEC TR 61000-2-14 ®
Edition 1.0 2006-12
TECHNICAL
REPORT
RAPPORT
TECHNIQUE
colour
inside
Electromagnetic compatibility (EMC) –
Part 2-14: Environment – Overvoltages on public electricity distribution
networks
Compatibilité électromagnétique (CEM) –
Partie 2-14: Environnement – Surtensions sur les réseaux de distribution
publics
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.

IEC publications search - webstore.iec.ch/advsearchform Electropedia - www.electropedia.org
The advanced search enables to find IEC publications by a The world's leading online dictionary on electrotechnology,
variety of criteria (reference number, text, technical containing more than 22 000 terminological entries in English
committee,…). It also gives information on projects, replaced and French, with equivalent terms in 16 additional languages.
and withdrawn publications. Also known as the International Electrotechnical Vocabulary

(IEV) online.
IEC Just Published - webstore.iec.ch/justpublished
Stay up to date on all new IEC publications. Just Published IEC Glossary - std.iec.ch/glossary
details all new publications released. Available online and once 67 000 electrotechnical terminology entries in English and
a month by email. French extracted from the Terms and Definitions clause of IEC
publications issued since 2002. Some entries have been
IEC Customer Service Centre - webstore.iec.ch/csc collected from earlier publications of IEC TC 37, 77, 86 and
If you wish to give us your feedback on this publication or need CISPR.

further assistance, please contact the Customer Service

Centre: sales@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.

Recherche de publications IEC - Le premier dictionnaire d'électrotechnologie en ligne au monde,
webstore.iec.ch/advsearchform avec plus de 22 000 articles terminologiques en anglais et en
La recherche avancée permet de trouver des publications IEC français, ainsi que les termes équivalents dans 16 langues
en utilisant différents critères (numéro de référence, texte, additionnelles. Egalement appelé Vocabulaire
comité d’études,…). Elle donne aussi des informations sur les Electrotechnique International (IEV) en ligne.

projets et les publications remplacées ou retirées.
Glossaire IEC - std.iec.ch/glossary
IEC Just Published - webstore.iec.ch/justpublished 67 000 entrées terminologiques électrotechniques, en anglais
Restez informé sur les nouvelles publications IEC. Just et en français, extraites des articles Termes et Définitions des
Published détaille les nouvelles publications parues. publications IEC parues depuis 2002. Plus certaines entrées
Disponible en ligne et une fois par mois par email. antérieures extraites des publications des CE 37, 77, 86 et
CISPR de l'IEC.
Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
Electropedia - www.electropedia.org

IEC TR 61000-2-14 ®
Edition 1.0 2006-12
TECHNICAL
REPORT
RAPPORT
TECHNIQUE
colour
inside
Electromagnetic compatibility (EMC) –

Part 2-14: Environment – Overvoltages on public electricity distribution

networks
Compatibilité électromagnétique (CEM) –

Partie 2-14: Environnement – Surtensions sur les réseaux de distribution

publics
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.240.01; 33.100.01 ISBN 978-2-8322-6681-6

– 2 – IEC TR 61000-2-14:2006  IEC 2006
CONTENTS
FOREWORD . 4
INTRODUCTION . 6

1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 Description of overvoltages . 10
4.1 General . 10
4.2 External overvoltages . 11
4.3 Internal overvoltages . 11
4.4 Overvoltage waveshape . 11
5 Long duration overvoltages . 12
5.1 Sustained earth faults. 12
5.2 Broken neutral on LV network. 12
5.3 Maloperation of voltage regulating equipment. 13
5.4 Overvoltages due to voltage unbalances . 13
5.5 Dispersed generation . 14
6 Short duration overvoltages . 15
6.1 Earth faults . 15
6.2 Load rejection (sudden load loss) . 16
6.3 Self-excitation . 16
6.4 Resonance and ferroresonance . 16
7 Very short duration overvoltages (transients) . 18
7.1 General description . 18
7.2 Lightning . 19
7.3 Switching . 20
7.4 Summary of surge duration and cause. 26
8 Effects of overvoltages on equipment . 27
8.1 General considerations . 27
8.2 Reduction in life of filament lamps . 28
8.3 Effect of overvoltages on IT equipment . 28
9 Case studies . 29
9.1 General . 29
9.2 Switching of LV power factor correction capacitor . 29
9.3 Metal fusion furnace . 30
9.4 Switching of MV power factor correction capacitor . 31
9.5 DC traction system . 32
9.6 Load switching . 34
10 Protection against the effects of overvoltages . 36
10.1 General considerations . 36
10.2 Point on wave switching . 36
10.3 Arcing horns and spark gaps . 37
10.4 Overvoltage protection relays . 38
10.5 Snubbers (high frequency RC filter) . 39
10.6 Uninterruptible power supply (UPS) systems . 39
10.7 Surge protection device (SPD) . 39

11 Conclusions . 41
12 Recommendations . 42
Bibliography . 43

Figure 1 – Lightning impulse test voltage characteristic . 11
Figure 2 – Broken neutral on LV network . 13
Figure 3 – The effect of distributed generation on network voltage . 14
Figure 4 – Line – Neutral temporary overvoltage on healthy phase for single phase line
– earth fault . 15
Figure 5 – Typical transient overvoltage when energizing a capacitor bank . 22
Figure 6 – Notching caused by power electronics switching . 24
Figure 7 – ITI (CBEMA) curve for equipment connected to 120 V 60 Hz systems . 29
Figure 8 – Voltage waveform distorted by the energization of a PFC capacitor . 30
Figure 9 – Phase to ground overvoltage in case of a single (a) or multiple (b) faults . 30
Figure 10 – Equivalent circuit . 31
Figure 11 – Extruder connection – single line diagram . 32
Figure 12 – Current waveforms (phases A and C) taken at the main LV circuit breaker . 32
Figure 13 – Single line diagram of public transportation system . 33
Figure 14 – Voltage waveforms associated with overvoltages on public transportation
system . 34
Figure 15 – 20 kV line-to-earth voltages during breaking transformer current . 35
Figure 16 – Spark gap . 37
Figure 17 – Two-stage surge protection scheme . 40

Table 1 – Surges on the low voltage network . 26
Table 2 – Surges on the medium voltage network . 27
Table 3 – Reduction of filament lamp life . 28
Table 4 – Protective levels for typical MV surge arresters (effectively earthed neutral
systems) .
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.