Secure storage units - Classification and methods of test for resistance to fire - Light fire storage units

This European Standard specifies requirements for light fire storage units providing protection against fire.
The method of test is specified to determine the ability of light fire storage units to protect paper media from the effects of fire. Two levels of fire exposure periods (LFS 30 P and LFS 60 P) are specified using the maximum temperature increase permitted within the storage space of the light fire storage unit.
Requirements are also specified for the test specimen, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the light fire storage units from the test results is also given (see Table 1).

Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Leichte Brandschutzschränke

Diese Europäische Norm legt Anforderungen an leichte Brandschutzschränke zum Schutz gegen Brände fest.
Das Prüfverfahren dient der Ermittlung der Widerstandsfähigkeit von leichten Brandschutzschränken, um Papierdokumente vor Brandeinwirkung zu schützen. Zwei Stufen der Beflammungsdauer (LFS 30 P und LFS 60 P) sind vorgesehen, die unter Berücksichtigung der im Innenraum des Brandschutzschrankes maximal zulässigen Temperaturerhöhung definiert werden.
Außerdem sind Anforderungen für den Probekörper, die technische Dokumentation des Probekörpers, die Übereinstimmung von Probekörper mit der technischen Dokumentation, die Vorbereitung der Typprüfung sowie das Prüfverfahren definiert.
Ferner wird ein Schema zur Klassifizierung von leichten Brandschutzschränken nach ihrem Prüfergebnis gegeben (siehe Tabelle 1).

Unités de stockage en lieu sûr - Classification et méthodes d'essais de résistance au feu - Meubles ignifuges premier niveau

La présente Norme européenne spécifie les exigences relatives aux meubles ignifuges premier niveau
procurant une protection contre l’incendie.
Cette méthode d’essai vise à déterminer la capacité des meubles ignifuges premier niveau à protéger le
média papier contre les effets du feu. Deux niveaux de durée d’exposition au feu (MIPN 30 P et MIPN 60 P)
sont spécifiées, compte tenu de l’augmentation maximale de température admise dans l’espace de stockage
du meuble ignifuge premier niveau.
Les exigences s’appliquent également à l’éprouvette, à la documentation technique concernant l’éprouvette, à
la corrélation entre l’éprouvette et la documentation technique, à la préparation de l’essai de type et aux
modes opératoires d’essai.
Une classification des meubles ignifuges premier niveau en fonction des résultats d’essai est également
fournie (voir Tableau 1).

Varnostne shranjevalne enote - Klasifikacija in metode preskušanja odpornosti proti ognju - Shranjevalne enote za zaščito papirja do 170 °C

General Information

Status
Withdrawn
Publication Date
28-Apr-2009
Withdrawal Date
06-Aug-2019
Current Stage
9960 - Withdrawal effective - Withdrawal
Completion Date
07-Aug-2019

Relations

Buy Standard

Standard
EN 15659:2009
English language
13 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Leichte BrandschutzschränkeUnités de stockage en lieu sur - Classification et méthodes d'essaisde résistance au feu - Meubles ignifuges premier niveauSecure storage units - Classification and methods of test for resistance to fire - Light fire storage units35.220.99Druge naprave za shranjevanje podatkovOther data storage devices13.310Varstvo pred kriminalomProtection against crime13.220.40Sposobnost vžiga in obnašanje materialov in proizvodov pri gorenjuIgnitability and burning behaviour of materials and productsICS:Ta slovenski standard je istoveten z:EN 15659:2009SIST EN 15659:2009en,fr01-oktober-2009SIST EN 15659:2009SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 15659April 2009ICS 13.220.40; 91.060.01 English VersionSecure storage units - Classification and methods of test forresistance to fire - Light fire storage unitsUnités de stockage en lieu sûr - Classification et méthodesd'essaisde résistance au feu - Meubles ignifuges premierniveauWertbehältnisse - Klassifizierung und Methoden zurPrüfung des Widerstandes gegen Brand - LeichteBrandschutzschränkeThis European Standard was approved by CEN on 19 March 2009.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre:
Avenue Marnix 17,
B-1000 Brussels© 2009 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15659:2009: ESIST EN 15659:2009

Figures Figure 1 — Measurement points . 9 Figure 2 — Cable entry hole and sealing . 10 Figure 3 — Protection of instrument cables . 11
Tables Table 1 — Protection level requirements . 6
The method of test is specified to determine the ability of light fire storage units to protect paper media from the effects of fire. Two levels of fire exposure periods (LFS 30 P and LFS 60 P) are specified using the maximum temperature increase permitted within the storage space of the light fire storage unit. Requirements are also specified for the test specimen, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures. A scheme to classify the light fire storage units from the test results is also given (see Table 1). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:1999, Fire resistance tests — Part 1: General requirements EN 60584-1, Thermocouples — Part 1: Reference tables (IEC 60584-1:1995). 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 light fire storage unit storage unit designed to protect paper media, except for paper grades where data loss occurs at temperatures below 172°C, as well as valuables against the effects of temperatures up to 172°C NOTE A light fire storage unit can have doors, drawers, lids, connections and fittings. 3.2 compartment part of a light fire storage unit which can be closed with a separate door, lid or cover NOTE A compartment formed by inserting a shelf board is not a compartment within the meaning of this standard. 3.3 lock device which verifies an entered code and performs a blocking function on the boltwork or the door 4 Requirements, classification and locks 4.1 Light fire storage units shall provide protection against the effects of fire (see Clause 6) and be classified as specified in Table 1. SIST EN 15659:2009

Where LFS is the symbol applied for light fire storage units. NOTE 2
The numerical values in the protection level are the duration of fire exposure during the type test in minutes.
NOTE 3
P represents protection of data on paper, excluding those paper grades which lose data below 172ºC.
4.2 Light fire storage units shall be fitted with a lock. 5 Test specimen, technical documentation and correlation 5.1 Test specimen Of several models of a series (with one door, two doors, drawers, etc.) having the same design, protection and construction features (type and thickness of construction and protective materials, rabbet geometry, etc.) as well as the same base (with a tolerance of ± 15 % each applicable to the internal dimensions of width and depth), the models with the smallest and largest internal height resp. the lowest and highest number of drawers shall be tested.
Light fire storage units with double doors shall be regarded as a separate model range. Where a variety of locking options is available, the test specimen used in the type test shall be coordinated with the testing laboratory. Two identical light fire storage units shall be available: one for the fire endurance test, the other for verifying correlation of the filling material with the technical documentation. The testing laboratory shall decide which test specimen will be used for the type test. The test specimen shall be modified at its base for installing the measuring instrumentation (see 6.3.1 and Figure 2) and may have, but need not have a plinth. 5.2 Technical documentation of the test specimen Detailed technical documentation about the range and test specimen (drawings, specifications of materials, installation and processing advice) shall be submitted to the testing laboratory before the type test. The drawings shall give specifications as to height, width and depth of the test specimens, materials and their thicknesses, dimensions of rabbet edges, locking system, welds including the method of their execution, seals, etc. The mass of the plinth shall be given. Samples and detailed specifications of all heat protection materials and seals used in the test specimens shall accompany the test specimens. The date(s) on which the test specimens were filled with fire protection materials shall be given. NOTE 1 With reference to all heat protection materials, the technical documentation should include: a) quality control parameters, and b) details of the performance characteristics, or c) details of the constituent materials and processing methods.
The test specimens and the supplied technical documentation must correlate. As to mass, the two test specimens shall not differ by more than 10 %. In series production, the wall, ceiling and door thicknesses must not be below the specified minimum limit of the type-tested thickness by more than 3 %.
6 Test methods 6.1 Principle The fire endurance of the test specimen is assessed by heating in a furnace. During the type test the temperature in the interior of the test specimen is measured. 6.2 Test equipment 6.2.1 The furnace which must be capable of providing the uniform heating conditions specified in this standard, and constructed so that the four vertical walls of the test specimen can each be exposed to the same heating conditions with no direct flame impingement onto the test specimen. The distance between the interior walls of the furnace and the surface of the test specimen shall be ≥ 750 mm. The furnace conditions shall conform to EN 1363-1. To meet these conditions, the setting of the neutral pressure level shall be made in accordance with 6.2.2 and the measurement of the temperature in the interior of the furnace shall be made with instrumentation in accordance with 6.2.3. 6.2.2 The furnace shall be operated such that the neutral pressure level is reached after 5 min of firing, measured at ± 5 Pa 1,000 mm above the furnace base. Test specimens with an external height of > 1,000 mm shall be placed on the furnace base during the type test. Test specimens with an external height of ≤ 1,000 mm shall be positioned on a plinth of brick with a height of 500 mm. For pressure measurements, pressure measuring heads in accordance with 4.5.2 of EN 1363-1:1999 shall be used. NOTE In order to ensure consistent heating conditions, the width of the plinth area around the projected cross-sectional area of the test specimen should not exceed 200 mm. 6.2.3 Thermocouples of type K (NiCr-N
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.