IEC 61918:2018/AMD2:2024
(Amendment)Amendment 2 - Industrial communication networks - Installation of communication networks in industrial premises
Amendment 2 - Industrial communication networks - Installation of communication networks in industrial premises
Amendement 2 - Réseaux de communication industriels - Installation de réseaux de communication dans des locaux industriels
General Information
Relations
Standards Content (Sample)
IEC 61918 ®
Edition 4.0 2024-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Industrial communication networks – Installation of communication networks in
industrial premises
Réseaux de communication industriels – Installation de réseaux de
communication dans des locaux industriels
I IEC 6918 :2018-09/AMD2:2024-03(en)
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews, graphical symbols and the glossary.
committee, …). It also gives information on projects, replaced With a subscription you will always have access to up to date
and withdrawn publications. content tailored to your needs.
IEC Just Published - webstore.iec.ch/justpublished
Electropedia - www.electropedia.org
Stay up to date on all new IEC publications. Just Published
The world's leading online dictionary on electrotechnology,
details all new publications released. Available online and once
containing more than 22 500 terminological entries in English
a month by email.
and French, with equivalent terms in 25 additional languages.
Also known as the International Electrotechnical Vocabulary
IEC Customer Service Centre - webstore.iec.ch/csc
(IEV) online.
If you wish to give us your feedback on this publication or need
further assistance, please contact the Customer Service
Centre: sales@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Recherche de publications IEC - IEC Products & Services Portal - products.iec.ch
webstore.iec.ch/advsearchform Découvrez notre puissant moteur de recherche et consultez
La recherche avancée permet de trouver des publications IEC gratuitement tous les aperçus des publications, symboles
en utilisant différents critères (numéro de référence, texte, graphiques et le glossaire. Avec un abonnement, vous aurez
comité d’études, …). Elle donne aussi des informations sur les toujours accès à un contenu à jour adapté à vos besoins.
projets et les publications remplacées ou retirées.
Electropedia - www.electropedia.org
IEC Just Published - webstore.iec.ch/justpublished
Le premier dictionnaire d'électrotechnologie en ligne au monde,
Restez informé sur les nouvelles publications IEC. Just
avec plus de 22 500 articles terminologiques en anglais et en
Published détaille les nouvelles publications parues.
français, ainsi que les termes équivalents dans 25 langues
Disponible en ligne et une fois par mois par email.
additionnelles. Egalement appelé Vocabulaire
Electrotechnique International (IEV) en ligne.
Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
IEC 61918 ®
Edition 4.0 2024-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Industrial communication networks – Installation of communication networks in
industrial premises
Réseaux de communication industriels – Installation de réseaux de
communication dans des locaux industriels
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 25.040.40, 33.020, 35.240.50 ISBN 978-2-8322-8280-9
– 2 – IEC 61918:2018/AMD2:2024
© IEC 2024
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
INDUSTRIAL COMMUNICATION NETWORKS – INSTALLATION
OF COMMUNICATION NETWORKS IN INDUSTRIAL PREMISES
AMENDMENT 2
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
Amendment 2 to IEC 61918:2018 and to IEC 61918:2018/AMD1:2022 has been prepared by
subcommittee 65C: Industrial networks, of IEC technical committee 65: Industrial-process
measurement, control and automation.
The text of this Amendment is based on the following documents:
Draft Report on voting
65C/1282/FDIS 65C/1290/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this Amendment is English.
© IEC 2024
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications/.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
IMPORTANT – The "colour inside" logo on the cover page of this document indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this document using a colour printer.
___________
INTRODUCTION to Amendment 2
This Amendment 2 describes the result of the maintenance activity of IEC 61918:2018 that
takes into account the evolution of the technology, which is being considered during the
Installation Profiles revision cycle.
The following technical changes were made in IEC 61918:2018/AMD1:2022 and
a) Subclauses 4.1.2, 4.1.3, 4.2.1.2, 4.2.2, 4.2.3.2, 4.3.2.1, 4.3.2.3, 4.4.1.2.1, 4.4.2.2, 4.4.2.5.
4.4.3.1, 4.4.3.2.1, 4.4.3.4.1, 4.4.7.1.4, 4.4.7.3.1, 5.1.1, 5.7, 6.1, 6.2.8.3, 6.3.2.1.2 and 8.3.3
have been updated;
b) Annex O has been modified by replacing the references to ISO/IEC TR 11801-9902 with
references to ISO/IEC 11801-3:2017/AMD1:2021;
c) Table B.3 has been updated;
d) Clause B.6 has been added;
e) Annexes D, I, J, K and M have been updated;
f) Annex Q has been added.
– 4 – IEC 61918:2018/AMD2:2024
© IEC 2024
1 Scope
Delete the existing fifth paragraph of the Scope.
2 Normative references
Delete the following reference:
IEC 60603 (all parts), Connectors for electronic equipment
Add the following new references:
IEC 61076-2-104, Connectors for electronic equipment – Product requirements – Part 2-104:
Circular connectors – Detail specification for circular connectors with M8 screw-locking or snap-
locking
IEC 61076-2-114, Connectors for electrical and electronic equipment – Product requirements –
Part 2-114: Circular connectors – Detail specification for connectors with M8 screw- locking
with power contacts and signal contacts for data transmission up to 100 MHz
IEC 61076-3-122, Connectors for electrical and electronic equipment – Product requirements –
Part 3-122: Detail specification for 8-way, shielded, free and fixed connectors for I/O and data
transmission with frequencies up to 500 MHz and current-carrying capacity in industrial
environments
IEC 61076-3-124, Connectors for electrical and electronic equipment – Product requirements –
Part 3-124: Rectangular connectors – Detail specification for 10-way, shielded, free and fixed
connectors for I/O and data transmission with frequencies up to 500 MHz
IEC 61156-13:2023, Multicore and symmetrical pair/quad cables for digital communications –
Part 13: Symmetrical single pair cables with transmission characteristics up to 20 MHz –
Horizontal floor wiring – Sectional specification
Replace the existing reference to IEC 61158-2:2014 with the following new reference:
IEC 61158-2:2023, Industrial communication networks – Fieldbus specifications – Part 2:
Physical layer specification and service definition
Replace the existing reference to IEC 61784-1:— with the following new reference:
IEC 61784-1-x, Industrial networks – Profiles – Part 1-x: Fieldbus profiles
Replace the existing reference to IEC 61784-2:— with the following new reference:
IEC 61784-2-x, Industrial networks – Profiles – Part 2-x: Additional real-time fieldbus profiles
based on ISO/IEC/IEEE 8802-3
Add the following new references:
IEC 63171-2:2021, Connectors for electrical and electronic equipment – Part 2: Detail
specification for 2-way, shielded or unshielded, free and fixed connectors: mechanical mating
information, pin assignment and additional requirements for type 2
IEC 63171-5:2022, Connectors for electrical and electronic equipment – Part 5: Detail
specification for 2-way M8 and M12 circular connectors, shielded or unshielded, free and fixed
– Mechanical mating information, pin assignment and additional requirements for Type 5
© IEC 2024
Delete the following reference:
ISO/IEC TR 11801-9902:2017, Information technology – Generic cabling for customer premises
– Part 9902: Specifications for End-to-end link configurations
Replace the existing references to ISO/IEC 14763-2:2012 and
ISO/IEC 14763-2:2012/AMD1:2015 with the following new reference:
ISO/IEC 14763-2:2019, Information technology – Implementation and operation of customer
premises cabling – Part 2: Planning and installation
Replace the existing reference to ISO/IEC 14763-3:2014 with the following new references:
ISO/IEC 14763-3:2014, Information technology –-Implementation and operation of customer
premises cabling – Part 3: Testing of optical fibre cabling
ISO/IEC 14763-3:2014/AMD1:2018
Replace the existing reference to ISO/IEC 14763-4:2018 with the following new reference:
ISO/IEC 14763-4:2021, Information technology – Implementation and operation of customer
premises cabling – Part 4: Measurement of end-to-end (E2E) links, modular plug terminated
links (MPTL) and direct attach cabling
Add the following new references:
ISO/IEC TS 29125:2017/AMD1:2020, Information technology – Telecommunications cabling
requirements for remote powering of terminal equipment
Replace the existing reference to IEEE Std 802.3-2015 and the reference to IEEE Std 802.3cg
added by IEC 61918:2018/AMD1:2022 with the following new reference and notes:
IEEE Std 802.3-2022, Standard for Ethernet, available at http://www.ieee.org
NOTE 1 The contents of IEEE Std 802.3cg have been integrated in IEEE Std 802.3-2022, Clause 146.
NOTE 2 Physical Layer specifications for 100BASE-T1 and 1000BASE-T1 are provided in IEEE Std 802.3-2022,
Clause 96 and Clause 97 respectively.
4 Installation planning
4.1.2 Cabling in industrial premises
Replace, in the first item of the first bulleted list, after "(all parts)", the comma added by IEC
61918:2018/AMD1:2022 with a semicolon.
Replace, in the second item of the second bulleted list, "ISO/IEC/IEEE 8802-3:2021 and
IEEE Std 802.3cg" as amended by IEC 61918:2018/AMD1:2022 with "ISO/IEC/IEEE 8802-3".
– 6 – IEC 61918:2018/AMD2:2024
© IEC 2024
Figure 3 – Automation island cabling attached to elements of generic cabling
Replace existing Figure 3 with the following new figure:
4.2.2 Security
Replace, at the end of the first paragraph of 4.2.2, "requirements for security." with the following
new text:
technical and organizational measures aimed at mitigating the specific security risk for the
communication subset identified during the security design of the whole automation system.
Delete the EXAMPLE.
Replace the existing third paragraph of 4.2.2 with the following new text:
IEC 62443 breaks down the design of security within a system to security levels based on risk
level. For each level there are different measures. For this purpose, cabling, planning and
installation play a role in implementing countermeasures and are central to achieving physical
and environmental security countermeasures, in accordance with Clause 4 and Clause 5, in
general, and requirements described in 4.4.9.1 (Routing of cables), 4.4.9.6.(Installing
redundant communication cables), 4.4.11 (Mechanical protection of cabling components),
5.2.1.2 (Protecting communication cables against potential mechanical damage), in particular.
Moreover, the first security level defined in IEC 62443 requires that a protection against
unintentional failures be implemented. An important contribution to this protection comes from
the application of the rules for installation verification and installation acceptance tests,
installation administration and installation maintenance and troubleshooting, described in
Clause 6, Clause 7 and Clause 8, which reduce the risk of intermittent system malfunction due
to incorrect cabling (e.g. insufficient implemented protection from electromagnetic interferences,
instable connections, etc.).
4.2.3.2 Use of the described environment to produce a bill of material
Add, after Figure 7, the following new text:
Passive optical components in the harsh industrial environment should be protected with
suitable mitigation techniques or tested according to IEC 61753-1.
© IEC 2024
4.3.1.4 Combination of basic topologies
Add, after Figure 10, the following new text and new Figure 53:
A mesh configuration is composed of linear configurations where the active nodes are partially
(as in Figure 53, with one linear configuration in green and a second one in blue) or totally
directly interconnected.
Figure 53 – Example of mesh topology
4.4.1.4 Optical fibre cables
Replace, at the end of the fourth paragraph of 4.4.1.4, "IEC 60793-2-10: type A1a.3" with "IEC
60793-2-10, type A1a.3 (A1-OM4)".
4.4.2.3 Connecting hardware for copper cabling CPs not based on Ethernet
Replace, in the NOTE to Table 8, "may" with "can".
4.4.3.2.1 Common description
d) Balanced 1-pair cabling
Replace the existing bullet d) of 4.4.3.2.1 added by IEC 61918:2018/AMD1:2022 with the
following new bullet d):
d) Balanced 1-pair reference implementation and cabling
For 1-pair reference implementation and cabling, the requirements specified in Annex Q apply.
Figure 43 – Pin and pair grouping assignments for two eight position IEC 60603-7
subparts and four position IEC 60603 series to IEC 61076-2-101 connectors
Replace the existing title of Figure 43 with the following new title:
Figure 43 – Pin and pair grouping assignments for two eight position IEC 60603-7
subparts and four position IEC 60603-7 series to IEC 61076-2-101 connectors
Annex D Connector tables
Replace, in the third paragraph of Annex D, "to Table D.13" with "to Table D.15".
Replace, in the fourth paragraph of Annex D, at the end of bullet a), " – " with " - ".
Add, in the bullet list of CPF, at the end of the CPF 8 bullet, the following new text:
and CP 8/6 (CC-Link IE TSN)
– 8 – IEC 61918:2018/AMD2:2024
© IEC 2024
Add, in the bullet list of CPF, at the end of the CPF 19 bullet, the following new text:
, CP 19/3 (Σ-LINK II) and CP 19/4 (MECHATROLINK-4)
Add, at the end of the bullet list of CPF, the following new bullet:
• CPF 22 (AUTBUS): CP 22/1 (AUTBUS).
Table D.3 – 8-way modular connector
Replace existing Table D.3 with the following new table:
Pin
CP
1 2 3 4 5 6 7 8 Housing
CP 1/1 - - - - - - - - -
CP 1/2 T568A or T568B Drain
CP 2/1 - - - - - - - - -
CP 2/2 T568A or T568B Drain
CP 2/3 - - - - - - - - -
CP 3/1 - - - - - - - - -
CP 3/2 - - - - - - - - -
a
CP 3/3
a
CP 3/4
YE OG WH - - BU - - Drain
a
CP 3/5
a
CP 3/6
CP 4/1 - - - - - - - - -
CP 4/3 T568A or T568B Drain
CP 6/1
- - - - - - - - -
CP 6/3
CP 6/2 T568B Drain
CP 8/1
- -
CP 8/2
CP 8/3 - -
CP 8/4
CP 8/5 T568B Drain
CP 8/6
CP 10/1 T568B Drain
CP 11/1
T568B Drain
CP 11/2
CP 11/3 - - - - - - - - -
b
CP 12/1
YE OG WH - - BU - - Drain
b
CP 12/2
CP 13/1 T568B Drain
CP 14/1
T568B Drain
CP 14/2
CP 14/3 - - - - - - - - -
CP 15/1
T568A or T568B Drain
CP 15/2
CP 16/1 - -
CP 16/2 - -
CP 16/3 YE OG WH - - BU - - Drain
CP 17/1 T568B Drain
CP 18/1
YE OG WH - - BU - - Drain
CP 18/2
CP 19/1 - - - - - - - - -
c
BU WH OG - - YE - - Drain
CP 19/2
CP 19/3 - - - - - - - - -
CP 19/4 BU WH OG - - YE - - Drain
© IEC 2024
Pin
CP
1 2 3 4 5 6 7 8 Housing
CP 20/1
T568A or T568B Drain
CP 20/2
CP 21/1 T568A or T568B Drain
CP 22/1 -
a
With four pair cabling, use T568A or T568B
b
With four pair cabling, use T568B
c
With crossover pairing pins: 1-3, 2-6, 3-1, 6-2.
Table D.5 – M12-4 D-coding connector
Replace existing Table D.5 with the following new table:
Pin
CP
1 2 3 4 Housing
CP 1/1 - - - - -
CP 1/2 - - - - -
CP 2/1 - - - - -
CP 2/2 WH/OG OG WH/GN GN Drain
CP 2/3 - - - - -
CP 3/1 - - - - -
CP 3/2 - - - - -
CP 3/3
CP 3/4
YE WH OG BU Drain
CP 3/5
CP 3/6
CP 4/1 - - - - -
CP 4/3 - - - - -
CP 6/1
- - - - -
CP 6/3
CP 6/2 WH/OG OG WH/GN GN Drain
CP 8/1
- - - - -
CP 8/2
CP 8/3 - - - - -
CP 8/4 - - - - -
CP 8/5 - - - - -
CP 8/6 WH/OG WH/GN OG GN Drain
CP 10/1 - - - - -
CP 11/1
CP 11/2 - - - - -
CP 11/3
CP 12/1
YE WH OG BU Drain
CP 12/2
CP 13/1 YE WH OG BU Drain
CP 14/1
WH/OG OG WH/GN GN Drain
CP 14/2
CP 14/3 - - - - -
CP 15/1
WH/OG OG WH/GN GN Drain
CP 15/2
CP 16/1 - - - - -
CP 16/2 - - - - -
CP 16/3 YE WH OG BU Drain
CP 17/1 - - - - -
CP 18/1
YE WH OG BU Drain
CP 18/2
CP 19/1 - - - - -
– 10 – IEC 61918:2018/AMD2:2024
© IEC 2024
Pin
CP
1 2 3 4 Housing
a
CP 19/2 BU OG WH YE Drain
CP 19/3 - - - - -
CP 19/4 BU OG WH YE Drain
CP 20/1 - - - - -
CP 20/2 - - - - -
CP 21/1 - - - - -
CP 22/1 - - - - -
a
With crossover pairing pins: 1-2, 2-1, 3-4, 4-3.
Table D.8 – SubD connector
Replace, in Table D.8, the two rows for CP 14/1 and CP 14/2 with the following new row:
CP
14/1
WH/OG OG WH/GN BU WH/BU WH/BN GN BN - Drain
CP
14/2
Table D.10 – Open style connector
Replace existing Table D.10 with the following new table:
Pin
CP
Device
1 2 3 4 5 6 7 8
housing
CP 1/1 - - - - - - - - -
CP 1/2 - - - - - - - - -
CP 2/1 - - - - - - - - -
CP 2/2 - - - - - - - - -
CP 2/3 BK BU Drain WH RD - - - -
CP 3/1 - - - - - - - - -
CP 3/2 - - - - - - - - -
CP 3/3
CP 3/4
- - - - - - - - -
CP 3/5
CP 3/6
CP 4/1 - - - - - - - - -
CP 4/3 - - - - - - - - -
CP 6/1
- - - - - - - - -
CP 6/3
CP 6/2 - - - - - - - - -
CP 8/1
BU WH YE - Drain - - - -
CP 8/2
CP 8/3 - - - - - - - - -
CP 8/4 - - - - - - - - -
CP 8/5 - - - - - - - - -
CP 8/6 - - - - - - - - -
CP 10/1 - - - - - - - - -
CP 11/1
CP 11/2 - - - - - - - - -
CP 11/3
CP 12/1 - - - - - - - - -
CP 12/2 - - - - - - - - -
CP 13/1 - - - - - - - - -
© IEC 2024
Pin
CP
Device
1 2 3 4 5 6 7 8
housing
a
CP 14/1
WH/OG OG WH/GN GN - - - - Drain
a
CP 14/2
b
CP 14/1
WH/OG OG WH/GN GN BU BN - - Drain
b
CP 14/2
c
CP 14/1
WH/OG OG WH/GN BU WH/BU GN WH/BN BN Drain
c
CP 14/2
CP 14/3 - - - - - - - - -
CP 15/1 - - - - - - - - -
CP 15/2 - - - - - - - - -
CP 16/1 - - - - - - - - -
CP 16/2 - - - - - - - - -
CP 16/3 - - - - - - - - -
CP 17/1 - - - - - - - - -
CP 18/1 - - - - - - - - -
CP 18/2 - - - - - - - - -
CP 19/1 - - - - - - - - -
CP 19/2 - - - - - - - - -
b
CP 19/3 OG BK BN GY RD BU - - Drain
c
OG BK BN GY RD BU YE WH Drain
CP 19/3
CP 19/4 - - - - - - - - -
CP 20/1 - - - - - - - - -
CP 20/2 - - - - - - - - -
CP 21/1 - - - - - - - - -
CP 22/1 WH - RD - - - - - -
a
Using open style 4 pins.
b
Using open style 6 pins.
c
Using open style 8 pins.
– 12 – IEC 61918:2018/AMD2:2024
© IEC 2024
Table D.11 – M12-8 X-coding and A-coding connector
Replace existing Table D.11 with the following new table:
Pin
CP
1 2 3 4 5 6 7 8 Housing
CP 1/1 - - - - - - - - -
CP 1/2 - - - - - - - - -
CP 2/1 - - - - - - - - -
CP 2/2 WH/GN GN WH/OG OG WH/BN BN WH/BU BU Drain
CP 2/3 - - - - - - - - -
CP 3/1 - - - - - - - - -
CP 3/2 - - - - - - - - -
CP 3/3 WH/GN GN WH/OG OG WH/BN BN WH/BU BU Drain
CP 3/4
or
CP 3/5
WH/OG OG WH/GN GN WH/BN BN WH/BU BU Drain
CP 3/6
CP 4/1 - - - - - - - - -
CP 4/3 - - - - - - - - -
CP 6/1
- - - - - - - - -
CP 6/3
CP 6/2 WH/GN GN WH/OG OG WH/BN BN WH/BU BU Drain
CP 8/1
- - - - - - - - -
CP 8/2
CP 8/3 - - - - - - - - -
CP 8/4
CP 8/5 WH/GN GN WH/OG OG WH/BN BN WH/BU BU Drain
CP 8/6
CP 10/1 - - - - - - - - -
CP 11/1
CP 11/2
- - - - - - - - -
CP 11/3
CP 12/1
WH/OG OG WH/GN GN WH/BN BN WH/BU BU Drain
CP 12/2
CP 13/1 - - - - - - - - -
CP 14/1 - - - - - - - - -
CP 14/2 - - - - - - - - -
CP 14/3 - - - - - - - - -
CP 15/1 - - - - - - - - -
CP 15/2 - - - - - - - - -
CP 16/1 - - - - - - - - -
CP 16/2 - - - - - - - - -
CP 16/3 - - - - - - - - -
CP 17/1 - - - - - - - - -
CP 18/1 - - - - - - - - -
CP 18/2 WH/GN GN WH/OG OG WH/BN BN WH/BU BU Drain
CP 19/1 - - - - - - - - -
CP 19/2 - - - - - - - - -
a
OG BK BN GY RD BU YE WH Drain
CP 19/3
CP 19/4 OR/WH OG GR/WH GR BU BU/WH BR/WH BR Drain
CP 20/1 - - - - - - - - -
CP 20/2 - - - - - - - - -
CP 21/1 - - - - - - - - -
CP 22/1 - - - - - - - - -
a
This connector is A-coding. All the others are X-coding
© IEC 2024
Table D.12 – BNC connector
Replace existing Table D.12 with the following new table:
Connections
CP
Centre Outer part
CP 1/1 - -
CP 1/2 - -
CP 2/1 wire shield
CP 2/2 - -
CP 2/3 - -
CP 3/1 - -
CP 3/2 - -
CP 3/3
CP 3/4
- -
CP 3/5
CP 3/6
CP 4/1 - -
CP 4/3 - -
CP 6/1
- -
CP 6/3
CP 6/2 - -
CP 8/1
- -
CP 8/2
CP 8/3 - -
CP 8/4 - -
CP 8/5 - -
CP 8/6 - -
CP 10/1 - -
CP 11/1
CP 11/2
- -
CP 11/3
CP 12/1 - -
CP 12/2 - -
CP 13/1 - -
CP 14/1 - -
CP 14/2 - -
CP 14/3 - -
CP 15/1 - -
CP 15/2 - -
CP 16/1 - -
CP 16/2 - -
CP 16/3 - -
CP 17/1 - -
CP 18/1 - -
CP 18/2 - -
CP 19/1 - -
CP 19/2 - -
CP 19/3 - -
CP 19/4 - -
CP 20/1 - -
CP 20/2 - -
CP 21/1 - -
CP 22/1 wire shield
Insert, in Tables D.4, D.6, D.7, D.8, D.9 and D.13, new rows for CP 8/6, CP 19/3, CP 19/4 and
CP 22/1 and insert " - " as the content of all other cells of these new rows.
Add, at the end of Annex D, the following new Tables D.14 and D.15:
– 14 – IEC 61918:2018/AMD2:2024
© IEC 2024
Table D.14 – Rectangular 8-way/10-way modular connectors
Pin
CP
Device
1 2 3 4 5 6 7 8
housing
CP 1/1 - - - - - - - - -
CP 1/2 - - - - - - - - -
CP 2/1 - - - - - - - - -
CP 2/2 - - - - - - - - -
CP 2/3 - - - - - - - - -
CP 3/1 - - - - - - - - -
b
BU WH OG YE - - - - Drain
CP 3/2
c
BU WH OG YE - - - - Drain
CP 3/2
CP 3/3
CP 3/4
- - - - - - - - -
CP 3/5
CP 3/6
CP 4/1 - - - - - - - - -
CP 4/3 - - - - - - - - -
CP 6/1
- - - - - - - - -
CP 6/3
CP 6/2 - - - - - - - - -
CP 8/1
- - - - - - - - -
CP 8/2
CP 8/3 - - - - - - - - -
CP 8/4 - - - - - - - - -
CP 8/5 - - - - - - - - -
CP 8/6 - - - - - - - - -
CP 10/1 - - - - - - - - -
CP 11/1
CP 11/2 - - - - - - - - -
CP 11/3
CP 12/1 - - - - - - - - -
CP 12/2 - - - - - - - - -
CP 13/1 - - - - - - - - -
CP 14/1 - - - - - - - - -
CP 14/2 - - - - - - - - -
CP 14/1 - - - - - - - - -
CP 14/2 - - - - - - - - -
CP 14/1 - - - - - - - - -
CP 14/2 - - - - - - - - -
CP 14/3 - - - - - - - - -
CP 15/1 - - - - - - - - -
CP 15/2 - - - - - - - - -
CP 16/1 - - - - - - - - -
CP 16/2 - - - - - - - - -
CP 16/3 - - - - - - - - -
CP 17/1 - - - - - - - - -
CP 18/1 - - - - - - - - -
CP 18/2 - - - - - - - - -
CP 19/1 - - - - - - - - -
a,b
CP 19/2 BU WH OG - - YE - - Drain
CP 19/3 - - - - - - - - -
b
CP 19/4 BU WH OG - - YE - - Drain
CP 20/1 - - - - - - - - -
CP 20/2 - - - - - - - - -
CP 21/1 - - - - - - - - -
CP 22/1 - - - - - - - - -
NOTE Rectangular connectors are specified in IEC 61076-3-122 (8-way) and IEC 61076-3-124 (10-way).
a
With crossover pairing: pins: 1-OG, 2-YE, 3-BU, 6-WH
b
8-way
c
10-way
© IEC 2024
Table D.15 – M8-4 A-coding, D-coding, P-coding, X-coding connectors
Pin
CP
1 2 3 4 Housing
CP 1/1 - - - - -
CP 1/2 - - - - -
CP 2/1 - - - - -
CP 2/2 - - - - -
CP 2/3 - - - - -
CP 3/1 - - - - -
CP 3/2 - - - - -
CP 3/3
CP 3/4
YE WH OG BU Drain
CP 3/5
CP 3/6
CP 4/1 - - - - -
CP 4/3 - - - - -
CP 6/1
- - - - -
CP 6/3
d
- - - - Drain
CP 6/2
CP 8/1
- - - - -
CP 8/2
CP 8/3 - - - - -
CP 8/4 - - - - -
CP 8/5 - - - - -
CP 10/1 - - - - -
CP 11/1
CP 11/2 - - - - -
CP 11/3
a p
CP 12/1
YE WH BU OG Drain
a p
CP 12/2
CP 13/1 - - - - -
CP 14/1
- - - - -
CP 14/2
CP 14/3 - - - - -
CP 15/1
- - - - -
CP 15/2
CP 16/1 - - - - -
CP 16/2 - - - - -
CP 16/3 - - - - -
CP 17/1 - - - - -
CP 18/1
- - - - -
CP 18/2
CP 19/1 - - - - -
CP 19/2 - - - - -
CP 20/1 - - - - -
CP 20/2 - - - - -
CP 21/1 - - - - -
x
WH - RD - Drain
CP 22/1
a
A-coding specified in IEC 61076-2-104
d
D-coding specified in IEC 61076-2-114
p
P-coding specified in IEC 61076-2-114
x
X-coding specified in IEC 61076-2-101, IEC 63171-2 and IEC 63171-5
– 16 – IEC 61918:2018/AMD2:2024
© IEC 2024
Annex M Trade names of communication profiles
Table M.1 – Trade names of CPFs and CPs
Add, at the end of Table M.1, a new row with "CP 22/1" in column "Family CPF numbers" and ®
"AUTBUS " in column "Technology name".
Add the following footnote next to "AUTBUS":
27 ®
AUTBUS is the registered trade name of the Kyland Technology Co., Ltd. This information is given for the
convenience of users of this part of this document and does not constitute an endorsement by IEC of the
trademark holder or any of its products. Compliance does not require use of the trade name. Use of the trade
name requires permission of Kyland Technology Co., Ltd.
Annex O End-to-end link
Replace all six occurrences of "ISO/IEC TR 11801-9902" in Annex O not already replaced by
IEC 61918:2018/AMD1:2022 with "ISO/IEC 11801-3/AMD1".
O.3 E2E link normative description
Replace the existing first two paragraphs of Clause O.3 with the following new text:
Figure O.3, Figure O.4, Figure O.5, Figure O.6, Figure O.7, Figure O.8 and Figure O.9
describe several common E2E links. The difference amongst the E2E links is the number of
connections in the link.
Replace the existing first sentence of the fourth paragraph of Clause O.3 with the following new
text:
ISO/IEC 11801-3/AMD1 provides limit line equations for the worst case six connections E2E
link and proposes to use these equations to validate any E2E link to simplify the procedure.
Annex Q Additional requirements for the installation of Ethernet-based
balanced 1-pair networks in industrial premises
The following modifications apply to the Annex Q added by IEC 61918:2018/AMD1:2022.
Q.1 Overview
Replace the existing second paragraph of Clause Q.1 with the following new text:
These Ethernet based balanced 1-pair networks use the industrial versions of 1 000 Mbit/s,
100 Mbit/s and 10 Mbit/s specifications given in ISO/IEC/IEEE 8802-3:2022.
Q.2.2 Basic balanced 1-pair network characteristics
Delete the existing second paragraph of Q.2.2.
Table Q.1 – Basic balanced 1-pair network characteristics
Add, in the last row, column "type A" of Table Q.1, "UTP" after "26 to 22".
Delete, in the last row, column "type B" of Table Q.1, "UTP" after "26 to 22".
© IEC 2024
Q.2.3 Balanced 1-pair cables
Replace, in the first paragraph of Q.2.3, "IEC 61156-11 and IEC 61156-12 apply." with
"IEC 61156-11, IEC 61156-12 and IEC 61156-13 apply."
Q.2.4 Balanced 1-pair connecting hardware
Replace, at the end of the fifth paragraph of Q.2.4, "connectors and the pin numbering" with the
following new text:
connectors, the pin numbering and the section of the shield embedded in the connector seen
just around the two pins, which allows the cable shield connection
Q.2.5.1 Balanced 1-pair cabling channels specification
Add, after Figure Q.5, the following new note:
NOTE Reference implementation formulas of balanced 1-pair cabling are for future study.
Bibliography
Add, at the end of Bibliography, the following new reference:
[40] ISO/IEC TR 11801-9902:2017, Information technology – Generic cabling for customer
premises – Part 9902: End-to-end link configurations
___________
– 18 – IEC 61918:2018/AMD2:2024
© IEC 2024
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
RÉSEAUX DE COMMUNICATION INDUSTRIELS – INSTALLATION
DE RÉSEAUX DE COMMUNICATION DANS DES LOCAUX INDUSTRIELS
AMENDEMENT 2
AVANT-PROPOS
1) La Commission Électrotechnique Internationale (IEC) est une organisation mondiale de normalisation composée
de l’ensemble des comités électrotechniques nationaux (Comités nationaux de l’IEC). L’IEC a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l’électricité et de l’électronique. À cet effet, l'IEC – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de l'IEC"). Leur élaboration est confiée à des comités d'études, aux
travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec l’IEC, participent également aux
travaux. L’IEC collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de l’IEC concernant les questions techniques représentent, dans la mesure du
possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de
l’IEC intéressés sont représentés dans chaque comité d’études.
3) Les Publications de l’IEC se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de l’IEC. Tous les efforts raisonnables sont entrepris afin que l’IEC
s’assure de l’exactitude du contenu technique de ses publications; l’IEC ne peut pas être tenue responsable de
l’éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d’encourager l’uniformité internationale, les Comités nationaux de l’IEC s’engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de l’IEC dans leurs publications nationales
et régionales. Toutes divergences entre toutes Publications de l’IEC et toutes publications nationales ou
régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) L’IEC elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de l’IEC. L’IEC n'est responsable d'aucun des services effectués par les organismes de certification
indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à l’IEC, à ses administrateurs, employés, auxiliaires ou mandataires,
y compris ses experts particuliers et les membres de ses comités d’études et des Comités nationaux de l’IEC,
pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre dommage de quelque
nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais de justice) et les dépenses
découlant de la publication ou de l’utilisation de cette Publication de l’IEC ou de toute autre Publication de l’IEC,
ou au crédit qui lui est accordé.
8) L’attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L'IEC attire l'attention sur le fait que la mise en application du présent document peut entraîner l'utilisation d'un
ou de plusieurs brevets. L'IEC ne prend pas position quant à la preuve, à la validité et à l'applicabilité de tout
droit de brevet revendiqué à cet égard. À la date de publication du présent document, l'IEC n'a pas reçu
notification qu'un ou plusieurs brevets pouvaient être nécessaires à sa mise en application. Toutefois, il y a lieu
d'avertir les responsables de la mise en application du présent document que des informations plus récentes
sont susceptibles de figurer dans la base de données de brevets, disponible à l'adresse https://patents.iec.ch.
L'IEC ne saurait être tenue pour responsable de l'identification de ces droits de propriété en tout ou partie.
L'amendement 2 de l'IEC 61918:2018 et de l'IEC 61918:2018/AMD1:2022 a été établi par le
sous-comité 65C: Réseaux industriels, du comité d'études 65 de l'IEC: Mesure, commande et
automation dans les processus industriels.
© IEC 2024
Le texte de cet Amendement est issu des documents suivants:
Projet Rapport de vote
65C/1282/FDIS 65C/1290/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à son approbation.
La langue employée pour l’élaboration de cet Amendement est l’anglais.
Ce document a été rédigé selon les Directives ISO/IEC, Partie 2, il a été développé selon les
Directives ISO/IEC, Partie 1 et les Directives ISO/IEC, Supplément IEC, disponibles sous
www.iec.ch/members_experts/refdocs. Les principaux types de documents développés par
l'IEC sont décrits plus en détail sous www.iec.ch/publications/.
Le comité a décidé que le contenu de ce document ne sera pas modifié avant la date de stabilité
indiquée sur le site web de l’IEC sous webstore.iec.ch dans les données relatives au document
recherché. À cette date, le document sera
• reconduit,
• supprimé, ou
• révisé.
IMPORTANT – Le logo "colour inside" qui se trouve sur la page de couverture de ce
document indique qu’il contient des couleurs qui sont considérées comme utiles à une
bonne compréhension de son contenu. Les utilisateurs devraient, par conséquent,
imprimer ce document en utilisant une imprimante couleur.
___________
INTRODUCTION de l’Amendement 2
Cet Amendement 2 décrit le résultat des travaux de maintenance réalisés sur l'IEC 61918:2018
qui prennent en compte l'évolution de la technologie, qui a été examinée dans le cadre du cycle
de révision des profils d'installation.
Les modifications techniques suivantes ont été apportées à l'IEC 61918:2018/AMD1:2022 et à
l'IEC 61918:2018/AMD2:—:
a) Les paragraphes 4.1.2, 4.1.3, 4.2.1.2, 4.2.2, 4.2.3.2, 4.3.2.1, 4.3.2.3, 4.4.1.2.1, 4.4.2.2,
4.4.2.5. 4.4.3.1, 4.4.3.2.1, 4.4.3.4.1, 4.4.7.1.4, 4.4.7.3.1, 5.1.1, 5.7, 6.1, 6.2.8.3, 6.3.2.1.2
et 8.3.3 ont été mis à jour.
b) L'Annexe O a été modifiée en remplaçant les références à l'ISO/IEC TR 11801-9902 par
des références à l'ISO/IEC 11801-3:2017/AMD1:2021.
c) Le Tableau B.3 été mis à jour.
d) L'Article B.6 a été ajouté.
e) Les Annexes D, I, J, K et M ont été mises à jour.
f) L'Annexe Q a été ajoutée.
– 20 – IEC 61918:2018/AMD2:2024
© IEC 2024
1 Domaine d’application
Supprimer le cinquième alinéa existant du Domaine d'application.
2 Références normatives
Supprimer la référence suivante:
IEC 60603 (toutes les parties), Connecteurs pour équipements électroniques
Ajouter les nouvelles références suivantes:
IEC 61076-2-104, Connecteurs pour équipements électroniques – Exigences de produit –
Partie 2-104: Connecteurs circulaires – Spécification particulière pour les connecteurs
circulaires M8 à vis ou à encliquetage
IEC 61076-2-114, Connecteurs pour équipements électroniques – Exigences de produit –
Partie 2-114: Connecteurs circulaires – Spécification particulière pour les connecteurs avec
verrouillage à vis M8 avec contacts de puissance et contact de signaux pour transmission de
données jusqu'à 100 MHz
IEC 61076-3-122, Connecteurs pour équipements électroniques – Exigences de produit –
Partie 3-122: Spécification particulière pour les fiches et les embases écrantées à 8 voies pour
les entrées/sorties et la transmission des données à des fréquences jusqu’à 500 Mhz avec
courant limite admissible dans des environnements industriels
IEC 61076-3-124, Connecteurs pour équipements électroniques – Exigences de produit –
Partie 3-124: Connecteurs rectangulaires – Spécification particulière pour les fiches et les
embases écrantées à 10 voies pour les entrées/sorties et la transmission de données à des
fréquences jusqu'à 500 MHz
IEC 61156-13:2023, Multicore and symmetrical pair/quad cables for digital communications –
Part 13: Symmetrical single pair cables with transmission characteristics up to 20 MHz –
Horizontal floor wiring – Sectional specification (disponible en anglais seulement)
Remplacer la référence existante à l'IEC 61158-2:2014 par la nouvelle référence suivante:
IEC 61158-2:2023, Réseaux de communication industriels – Spécifications des bus de terrain
– Partie 2: Spécification et définition des services de la couche physique
Remplacer la référence existante à l'IEC 61784-1:— par la nouvelle référence suivante:
IEC 61784-1-x, Réseaux industriels – Profils – Partie 1-x: Profils de bus de terrain
Remplacer la référence existante à l'IEC 61784-2:— par la nouvelle référence suivante:
IEC 61784-2-x, Réseaux industriels – Profils – Partie 2-x: Profils de bus de terrain
supplémentaires pour les réseaux en temps réel fondés sur l'ISO/IEC/IEEE 8802-3
Ajouter les nouvelles références suivantes:
IEC 63171-2:2021, Connectors for electrical and electronic equipment – Part 2: Detail
specification for 2-way, shielded or unshielded, free and fixed connectors: mechanical mating
information, pin assignment and additional require
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.