Fume cupboards - Part 6: Variable air volume fume cupboards

This document specifies requirements and type test methods for VAV systems. It also specifies additional requirements to those in EN 14175-2 and additional test methods to those in EN 14175-3 and EN 14175-4 for fume cupboards with VAV systems (VAV fume cupboards).
For terms and definitions, EN 14175-1 applies. For safety and performance requirements of fume cupboards, EN 14175-2 applies. For type testing of fume cupboards with preset air volume flow, EN 14175-3 applies. For on-site test methods of fume cupboards already installed in a laboratory, EN 14175-4 applies.

Abzüge - Teil 6: Abzüge mit variablem Luftstrom

Diese Norm legt Anforderungen und Baumusterprüfverfahren für VAV-Systeme fest. Des Weiteren werden
zusätzliche Anforderungen zu denjenigen in EN 14175-2 und zusätzliche Prüfverfahren für die
Baumusterprüfung und die Vor-Ort-Prüfung von Abzügen mit variablem Luftstrom zu denjenigen in EN 14175-3
und EN 14175-4 festgelegt.
Für Begriffe gilt EN 14175-1. Für Anforderungen an Sicherheit und Leistungsvermögen von Abzügen gilt
EN 14175-2. Für die Baumusterprüfung von Abzügen mit vorgegebenem Luftvolumenstrom gilt EN 14175-3.
Für Vor-Ort-Prüfverfahren von bereits im Labor installierten Abzügen gilt EN 14175-4.

Sorbonnes - Partie 6 : Sorbonnes à débit d'air variable

Le présent document spécifie les exigences et les méthodes d'essai de type des systèmes à débit d'air
variable (VAV). Il spécifie également des exigences supplémentaires à celles de l'EN 14175-2 ainsi que des
méthodes d'essai supplémentaires à celles de l'EN 14175-3 et de l'EN 14175-4 pour les sorbonnes à débit
d'air variable.
Pour les termes et définitions utilisés, l'EN 14175-1 s'applique. Pour les exigences en matière de sécurité et
de performances des sorbonnes, l'EN 14175-2 s'applique. Pour les essais de type des sorbonnes à débit fixe
d'air, l'EN 14175-3 s'applique. Pour les méthodes d'essai sur site des sorbonnes déjà installées en laboratoire,
l'EN 14175-4 s™applique.

Digestoriji - 6. del: Digestoriji s spremenljivim volumnom zraka

General Information

Status
Published
Publication Date
16-May-2006
Withdrawal Date
29-Nov-2006
Current Stage
9060 - Closure of 2 Year Review Enquiry - Review Enquiry
Start Date
04-Mar-2023
Completion Date
04-Mar-2023

Buy Standard

Standard
EN 14175-6:2006
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Fume cupboards - Part 6: Variable air volume fume cupboardsDigestoriji - 6. del: Digestoriji s spremenljivim volumnom zrakaSorbonnes - Partie 6 : Sorbonnes a débit d'air variableAbzüge - Teil 6: Abzüge mit variablem LuftstromTa slovenski standard je istoveten z:EN 14175-6:2006SIST EN 14175-6:2006en71.040.10Kemijski laboratoriji. Laboratorijska opremaChemical laboratories. Laboratory equipmentICS:SLOVENSKI
STANDARDSIST EN 14175-6:200601-oktober-2006

EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 14175-6May 2006ICS 71.040.10 English VersionFume cupboards - Part 6: Variable air volume fume cupboardsSorbonnes - Partie 6 : Sorbonnes à débit d'air variableAbzüge - Teil 6: Abzüge mit variablem LuftstromThis European Standard was approved by CEN on 3 April 2006.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2006 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14175-6:2006: E

Part 5 (Recommendations for installation and maintenance) is in preparation and will be published as a Technical Specification CEN/TS 14175-5. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

modular components enabling the control of the extract volume flow rate of a fume cupboard at various sash openings 3.2 response time time from a change of the set value, e.g. volume flow rate or face velocity, until the actual new set value reaches and maintains a specified percentage 4 Requirements 4.1 General Variable air volume fume cupboards shall meet the requirements specified in EN 14175-2 for general purpose fume cupboards and the following requirements in this document.

The air flow system of the test room should be sized so that the required changes in extract volume flow rate do not cause too large changes of the static pressure in the extract duct. 5.2.2 VAV systems (see 5.3) In the surroundings of 1 m around the test box (see 5.3.2.2), the air conditions as specified in EN 14175-3:2003, 4.2 shall prevail. 5.3 Test of VAV systems 5.3.1 General Type testing of VAV systems not fitted to an individual fume cupboard shall be performed in association with the test box shown in Figure 1. NOTE Basis for this type test is EN 12589.
...