Emergency safety showers - Part 2: Plumbed-in eyewash units

This document is a product specification, giving performance requirements for emergency safety eyewash units connected to the water supply. It is applicable to plumbed-in eyewash units only.
Requirements are given in respect of the performance, installation, adjustment and marking of the eyewash units, as well as installation, operation and maintenance instructions to be given by the manufacturer.
NOTE   Attention is drawn to national regulations which can apply in respect of the installation and use of eyewash units.

Sicherheitsnotduschen - Teil 2: Augenduschen mit Wasseranschluss

Dieses Dokument ist eine Produktnorm, die Leistungsanforderungen an Sicherheitsaugenduschen festlegt, die an die Wasserversorgung angeschlossen sind. Sie ist nur für Sicherheitsaugenduschen mit Wasseranschluss anwendbar.
Es sind Anforderungen hinsichtlich der Leistung, Installation, Justierung und Kennzeichnung der Augenduschen festgelegt sowie Anforderungen an die vom Hersteller zur Verfügung zu stellenden Installations-, Bedienungs- und Wartungsanleitungen.
ANMERKUNG   Es wird auf nationale Regelwerke hingewiesen, die hinsichtlich Installation und Anwendung von Augenduschen gelten können.

Douches de sécurité - Partie 2 : Unités de lavage d'yeux raccordées au réseau d'eau

Le présent document est une spécification de produit, définissant les exigences de performances des unités de lavage d’yeux de sécurité utilisant de l’eau. Il est applicable seulement aux unités de lavage d’yeux raccordées au réseau d’eau.
Des exigences sont données concernant les performances, l’installation, les réglages et le marquage des unités de lavage d’yeux ainsi que les instructions d’installation, de fonctionnement et de maintenance à fournir par le fabricant.
NOTE   L’attention est attirée sur les réglementations nationales qui peuvent concerner l’installation et l’utilisation des unités de lavage d’yeux.

Varnostne prhe za prvo pomoč - 2. del: Pripomočki za spiranje oči s stalnim priključkom na vodovod

General Information

Status
Published
Publication Date
23-Dec-2025
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
24-Dec-2025
Due Date
18-Jun-2026
Completion Date
24-Dec-2025

Relations

Effective Date
13-Mar-2024

Overview

EN 15154-2:2025 - Emergency safety showers: Part 2 - Plumbed-in eyewash units is a CEN product specification for eyewash units permanently connected to a water supply. The standard sets mandatory performance, installation, adjustment and marking requirements and defines the minimum content of manufacturer installation, operation and maintenance instructions. It applies to plumbed-in eyewash units only and is intended for use where immediate eye irrigation is required (for example chemical laboratories and industrial sites).

Key topics and technical requirements

  • Scope: Performance specification for permanently plumbed eyewash units; attention to applicable national regulations.
  • Wash-off time: Continuous delivery for at least 15 minutes at manufacturer‑specified pressure.
  • Flow rate: Minimum 6 L/min per nozzle at the installation pressure; unit must be non‑injurious and nozzles protected from airborne contaminants (protection removable without extra user motion).
  • Jet height: Spray height between 100 mm and 300 mm from nozzle centre before collapse.
  • Water quality & temperature: Use potable water or equivalent; materials must not contaminate water. Tepid temperatures are recommended (Annex A).
  • Installation clearances & heights: Nozzles installed at 1 000 ± 200 mm above standing surface and ≥ 150 mm from walls or obstructions; clear approach area ≥ 800 mm wide and 2 000 mm high.
  • Activation system: Single unassisted person must achieve full flow; valves open within 1 s. Manual actuators: max 90° or 200 mm stroke, max 100 N force or 7 Nm torque. Valve must remain open until manually closed.
  • Automatic release: If occupant-weight activated, triggering load 20–35 kg, basin must support up to 200 kg; optical or other sensors must open within 1 s.
  • Outlet nozzles: Allow eyelid opening and simultaneous washing of both eyes; directional adjustments removable only with a tool; removable nozzles require a tool.
  • Marking & documentation: Permanent ID with manufacturer name/address, model and minimum flow rate; safety sign per ISO 3864‑1; comprehensive instruction handbook with installation, microbiological risk controls, testing, flushing and maintenance guidance.

Applications and users

  • Intended for laboratory managers, EHS/safety officers, facility engineers, installers, equipment manufacturers and procurement teams specifying emergency eye-wash stations.
  • Applicable in chemical laboratories, industrial process areas, educational labs, and any workplace where ocular exposure to hazardous substances is possible.
  • Helps ensure compliance, proper siting, reliable operation, and effective first aid response.

Related standards

  • EN 15154 series (Parts 1–6) - other body‑shower and eyewash types
  • EN ISO 21420 (protective gloves) and ISO 3864‑1 (safety signs) - normative references cited by EN 15154‑2

Keywords: EN 15154-2:2025, emergency safety showers, plumbed-in eyewash units, eyewash installation, flow rate, wash-off time, laboratory safety, CEN standard, eyewash maintenance.

Frequently Asked Questions

EN 15154-2:2025 is a standard published by the European Committee for Standardization (CEN). Its full title is "Emergency safety showers - Part 2: Plumbed-in eyewash units". This standard covers: This document is a product specification, giving performance requirements for emergency safety eyewash units connected to the water supply. It is applicable to plumbed-in eyewash units only. Requirements are given in respect of the performance, installation, adjustment and marking of the eyewash units, as well as installation, operation and maintenance instructions to be given by the manufacturer. NOTE Attention is drawn to national regulations which can apply in respect of the installation and use of eyewash units.

This document is a product specification, giving performance requirements for emergency safety eyewash units connected to the water supply. It is applicable to plumbed-in eyewash units only. Requirements are given in respect of the performance, installation, adjustment and marking of the eyewash units, as well as installation, operation and maintenance instructions to be given by the manufacturer. NOTE Attention is drawn to national regulations which can apply in respect of the installation and use of eyewash units.

EN 15154-2:2025 is classified under the following ICS (International Classification for Standards) categories: 71.040.10 - Chemical laboratories. Laboratory equipment. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 15154-2:2025 has the following relationships with other standards: It is inter standard links to EN 15154-2:2006. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 15154-2:2025 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2026
Varnostne prhe za prvo pomoč - 2. del: Pripomočki za spiranje oči s stalnim
priključkom na vodovod
Emergency safety showers - Part 2: Plumbed-in eye-wash units
Sicherheitsnotduschen - Teil 2: Augenduschen mit Wasseranschluss
Douches de sécurité - Partie 2 : Unités de lavage d'yeux raccordées au réseau d'eau
Ta slovenski standard je istoveten z: EN 15154-2:2025
ICS:
11.160 Prva pomoč First aid
71.040.10 Kemijski laboratoriji. Chemical laboratories.
Laboratorijska oprema Laboratory equipment
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 15154-2
EUROPEAN STANDARD
NORME EUROPÉENNE
December 2025
EUROPÄISCHE NORM
ICS 71.040.10 Supersedes EN 15154-2:2006
English Version
Emergency safety showers - Part 2: Plumbed-in eyewash
units
Douches de sécurité - Partie 2 : Unités de lavage d'yeux Sicherheitsnotduschen - Teil 2: Augenduschen mit
raccordées au réseau d'eau Wasseranschluss
This European Standard was approved by CEN on 24 November 2025.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15154-2:2025 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 Performance . 5
4.1 Wash-off time . 5
4.2 Flow rate of water . 6
4.3 Jet height . 6
4.4 Water quality and water temperature . 6
5 Design requirements for installation . 6
5.1 General. 6
5.2 Clearance . 6
5.3 Materials and geometry . 6
6 Activation system . 7
6.1 General. 7
6.2 Valves . 7
6.3 Automatic activation. 7
6.3.1 General. 7
6.3.2 Full body weight activation . 7
6.3.3 Other automatic activation mechanisms . 7
7 Outlet Nozzle(s) . 7
8 Information for marking, installation, service use and maintenance . 8
8.1 Marking and labelling . 8
8.2 Instruction handbook. 8
Annex A (informative) General guidance . 9
A.1 Water temperature . 9
A.2 Guidelines to recommended installation . 9
A.3 Cleaning . 9
A.4 Testing . 10
Annex B (informative) Recommendation regarding environmental impact . 11
Bibliography . 12

European foreword
This document (EN 15154-2:2025) has been prepared by Technical Committee CEN/TC 332 “Laboratory
equipment”, the secretariat of which is held by DIN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by June 2026 and conflicting national standards shall be
withdrawn at the latest by June 2026.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 15154-2:2006.
— harmonization with EN 15154-5;
— addition of informative Annex B “Recommendations regarding environmental impact”.
This document, EN 15154-2, is part of a series of standards on emergency safety showers (see Table 1).
Table 1 — Subject areas covered under the EN 15154 series of standards
Part of Sites other than
Type Laboratories Non plumbed-in Plumbed-in
EN 15154 laboratories
c
1 Body shower X - - X
2 Eyewash unit X X - X
a a a
3 Body shower X X X -
4 Eyewash unit X X X -
c b
5 Body shower - X X X
6 Body shower - X - X
a
Non plumbed-in body showers affected by EN 15154-3 are fixed, transportable or portable.
b
Non plumbed-in body showers affected by EN 15154-5 are tank showers or trailer-mounted.
c
In possible combination with eyewash units.
NOTE Attention is drawn to national regulations in some European countries, e.g. Germany, which can request
to connect emergency safety eyewash units to a water supply.
A list of all parts in a series can be found on the CEN website: www.cencenelec.eu.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
Plumbed-in eyewash units are designed and intended to be installed in close range of persons working
in a potentially hazardous area exposed to the risks of burning/burns and/or hazardous chemical
substances getting splashed onto the eyes, despite other risk mitigation measures.
The main purpose of these devices is to immediately deliver flushing fluid in sufficient volume to flush
the eyes following exposure to injurious substances or heat.
Once this is accomplished, the injured person can proceed to the care of an ophthalmologist.
Emergency safety eyewash units are primarily emergency facilities and not intended for use for personal
cleaning or personal hygiene.
Annex A provides recommendations on general settings for emergency safety eyewash units installations
and Annex B provides recommendations regarding environmental impact.
1 Scope
This document is a product specification, giving performance requirements for emergency safety
eyewash units connected to the water supply. It is applicable to plumbed-in eyewash units only.
Requirements are given in respect of the performance, installation, adjustment and marking of the
eyewash units, as well as installation, operation and maintenance instructions to be given by the
manufacturer.
NOTE Attention is drawn to national regulations which can apply in respect of the installation and use of
eyewash units.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN ISO 21420, Protective gloves — General requirements and test methods (ISO 21420)
ISO 3864-1, Graphical symbols — Safety colours and safety signs — Part 1: Design principles for safety signs
and safety markings
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp/
— IEC Electropedia: available at https://www.electropedia.org
3.1
emergency safety eyewash unit
device specially designed and intended to deliver a flushing fluid to irrigate and flush the eyes and to
sufficiently wash away contaminants or to dilute them, rendering them harmless
[SOURCE: EN 15154-1:2025, 3.5]
3.2
plumbed-in emergency safety eyewash unit
emergency safety eyewash unit that is permanently connected to a continuous water supply
4 Performance
4.1 Wash-off time
The plumbed in eyewash unit shall be able to deliver water at a constant manufacturer-specified
pressure, and continued for at least 15 min.
NOTE Attention is drawn to national regulations.
...

Questions, Comments and Discussion