Abstract

This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term "doorset" will be used to cover both doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples:
-   integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classification,
-   glazed elements including vision panels and framed glazed doorsets,
-   air transfer grilles (louvres and/or vents),
-   side, transom or over panels,
-   items of building hardware,
-   decorative and protective finishes,
-   intumescent seals and non-intumescent (smoke, draught or acoustic) seals,
-   alternative supporting construction(s).
This document does not cover horizontal doorsets.
The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

Status
Published
Publication Date
25-Aug-2026
Drafting Committee
CEN/TC 127/WG 3 - Fire Doors
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
26-Aug-2026
Due Date
14-Sep-2025
Completion Date
14-Sep-2025

Buy Documents

Standard

EN 15269-5:2026

English language (214 pages)
Preview
Preview
e-Library read for
×1 day

EN 15269-5:2026 is a CEN European Standard for extending the application of fire resistance test results for hinged and pivoted metal framed glazed doorsets and openable windows. It sets out how test evidence from EN 1634-1 can be used to justify related design variants, hardware changes and supporting constructions. In practice, it helps engineers and certification teams decide which changes stay within the tested family and which changes need more testing.

What does EN 15269-5:2026 specify?

EN 15269-5:2026 specifies a method for extending fire resistance test results for hinged and pivoted steel and aluminium based framed, glazed doorsets or openable windows. Throughout the document, the term doorset is used to cover both doorsets and openable windows unless otherwise stated.

The scope includes examples such as:

  • fire resistance classifications E, EW and EI
  • glazed elements such as vision panels and framed glazed leaves
  • air transfer grilles and vents
  • side, transom and over panels
  • building hardware
  • decorative and protective finishes
  • intumescent and non-intumescent seals
  • alternative supporting constructions

The standard excludes horizontally installed doorsets, such as ceiling applications. It also leaves the extended-application effect on self-closing durability and smoke control outside its rules.

How the document is organized

AnnexWhat it covers
Annex AConstruction parameter variations and the rules for deciding whether a change can be extended or needs additional testing
Annex BArrangements for doorsets with side, transom and/or bottom panels
Annex CGuidance on which part of EN 15269 to use for different doorset types

The main clauses cover scope, normative references, terms and definitions, the extended-application procedure, and the classification report.

What are the key requirements of EN 15269-5:2026?

EN 15269-5:2026 is built around a rule-based assessment of design variations against fire resistance test evidence. The practical question is not only “did the specimen pass?” but also “which nearby designs can be justified from that pass?”

How the extended application is determined

Clause 4 says the starting point is representative specimens tested to EN 1634-1. That matters because the document only extends results from valid fire resistance testing, not from design assumptions.

Clause 4.2 directs users to match each intended variation against Annex A, Table A.1. If the table allows the variation, the change can be recorded in the extended application report; if not, the table identifies the additional test needed. This makes the document usable as a planning tool for test programmes and product families.

Where extra evidence is needed, the additional test is generally a full-scale fire resistance test, and it is normally done on the most onerous side or configuration unless the rule says otherwise. Some items of building hardware can also be supported by EN 1634-2 small-scale evidence. That matters when a manufacturer wants to change hardware without repeating a full doorset test.

The standard also allows a staged approach to building up a family range. Clause 4.3 describes how to choose the most important configurations first, then use the results to cover the remaining variants as far as the rules permit.

What Annex A controls

Annex A is the core decision matrix for construction parameter variations. It covers leaf count, seals, rebates, size changes, infill and core materials, adhesives, finishes, glazing, panel arrangements, hardware, access devices and supporting construction.

A key practical point is the treatment of distortion. Annex A classifies the test specimen as low, medium or high distortion using movement relative to the effective rebate depth measured during the EN 1634-1 test period. That matters because some variation rules only apply at certain distortion levels.

Annex A also makes clear that double leaf doorsets must have both leaves of the same basic construction for these rules to be applied. For many variations, the table says whether the change is directly allowed, allowed only with restrictions, or only possible with an extra test. The table also uses test scenarios A to H to show what kind of extra evidence is needed.

What the test scenarios and size rules mean in practice

Annex A uses different test scenarios to tell users what evidence is needed for a specific change. In practice, this tells a test laboratory whether it needs another full-scale door test, a test on a different leaf arrangement, or hardware evidence from EN 1634-2.

Size changes are treated separately from material or hardware changes. The rules allow some increases or decreases by interpolation between tested sizes when the table permits it. This is useful for product ranges, because it can reduce the number of specimens needed to cover multiple nominal sizes.

What happens after the technical assessment

Clause 5 says the classification report is taken from the extended application report and is presented according to EN 13501-2. In practice, that means the final output is a formal classification report that can be used in product documentation, conformity work and technical files.

What terms does EN 15269-5:2026 define?

  • Full scale test - a test on a full doorset, and EN 1634-1 is the reference method for the products in this standard.
  • Small scale test - a test on items of building hardware used to characterize their influence on fire performance, with EN 1634-2 as the reference method.
  • Effective rebate depth - the overlap dimension used to judge movement between the leaf and the frame, panels or meeting edges during testing.
  • Representative - a doorset design that is fundamentally the same or similar enough to another design for variation assessment.
  • Intumescent seal - an intumescent strip or seal with intumescent characteristics that helps close gaps when exposed to heat.
  • Dog bolt / movement restrictor - an added part on the hinge side that can resist forces such as levering or fire deflection.
  • Load bearing item of building hardware - hardware such as hinges, latches, locks or dog bolts that transfers force or torque between the leaf and the frame.

Who uses EN 15269-5:2026?

Manufacturers of fire doors, glazed doorsets and openable windows use EN 15269-5:2026 to define a product family and justify design variants from test evidence. That includes changes to glazing, seals, profiles, hardware and supporting construction.

Test laboratories and certification bodies use it to plan test programmes and judge whether a proposed change is within the extended field of application. Quality managers and technical file owners use it to document which variants are covered and what extra evidence is needed.

Buyers, specifiers and project engineers use it when they need to compare a tested product with a proposed alternative, especially where hardware substitutions or panel changes are involved.

What changed in EN 15269-5:2026 from the previous edition?

EN 15269-5:2026 supersedes EN 15269-5:2014+A1:2016.

Which standards are used with EN 15269-5:2026?

StandardWhat it contributes
EN 1634-1Base fire resistance test method for doorsets and openable windows
EN 1634-2Fire resistance characterisation test for items of building hardware
EN 13501-2Classification format for the final fire performance report
EN 15269-1General requirements and shared EXAP approach for the EN 15269 series
EN 15269-2Related extended-application method for hinged and pivoted steel doorsets
EN 15254-4:2018Extended application rules for glazed constructions
EN 15725Principles for EXAP standards and EXAP reports
EN 12519Terminology for windows and pedestrian doors
EN ISO 13943Fire safety vocabulary
EN 1363-1 and EN 1364-1General fire resistance testing framework and non-loadbearing wall testing background
EN 179, EN 1125, EN 1155, EN 12365-2, EN 572-9, EN 1748-2-2, EN 13024-2Product standards and test methods for escape hardware, hold-open devices, seals and glass products used in the rules
EN 16035Hardware performance sheet (HPS) format that can support documentation of interchangeable hardware

What does the EN 15269-5:2026 document contain?

EN 15269-5:2026 contains a rule-based procedure for turning one or more fire resistance tests into an extended field of application. It includes a large normative table of construction parameter variations, plus test scenarios and decision outcomes for many common changes.

Annex A also contains tables and figures for distortion levels, panel and profile changes, glazing variations, seal changes, decorative finishes, hardware, access devices and supporting construction. Annex B gives arrangement tables and figures for side, transom and bottom panel configurations. Annex C provides guidance figures that help users choose EN 15269-5 or another EN 15269 part for the product type being assessed.

Relations

Effective Date
19-Jan-2023
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026
Effective Date
25-Nov-2026

Buy Documents

Standard

EN 15269-5:2026

English language (214 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

EN 15269-5:2026 is a standard published by the European Committee for Standardization (CEN). Its full title is "Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows". This standard covers: This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term "doorset" will be used to cover both doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples: - integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classification, - glazed elements including vision panels and framed glazed doorsets, - air transfer grilles (louvres and/or vents), - side, transom or over panels, - items of building hardware, - decorative and protective finishes, - intumescent seals and non-intumescent (smoke, draught or acoustic) seals, - alternative supporting construction(s). This document does not cover horizontal doorsets. The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term "doorset" will be used to cover both doorsets and door assemblies. It prescribes the methodology for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples: - integrity (E), integrity & radiation (EW) or integrity & insulation (EI1 or EI2) classification, - glazed elements including vision panels and framed glazed doorsets, - air transfer grilles (louvres and/or vents), - side, transom or over panels, - items of building hardware, - decorative and protective finishes, - intumescent seals and non-intumescent (smoke, draught or acoustic) seals, - alternative supporting construction(s). This document does not cover horizontal doorsets. The effect on the Classification ‘C’ for the doorsets following an extended application process is not addressed in this document.

EN 15269-5:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 91.060.50 - Doors and windows. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 15269-5:2026 has the following relationships with other standards: It is inter standard links to EN 15269-5:2014+A1:2016, EN 13024-2:2004, EN 12365-2:2003, EN 1364-1:2015, EN 15254-4:2018, EN 1634-2:2008, EN 1155:1997, EN 15725:2023, EN 1363-1:2020, EN ISO 13943:2023, EN 15269-1:2019, EN 572-9:2004, EN 15269-2:2024, EN 179:2008, EN 1125:2008. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 15269-5:2026 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

EN 15269-5:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 full scale test
  • 3.2 small scale test
  • 3.3 effective rebate depth
  • 3.4 opening outwards
  • 3.5 opening inwards
  • 3.6 faces and sides of a hinged door leaf
  • 3.7 representative
  • 3.8 intumescent seal
  • 3.9 dog bolt / movement restrictor
  • 3.10 load bearing item of building hardware
  • 4 Determination of the field of extended application
  • 4.1 General
  • 4.3 Procedure for maximum field of extended application
  • 4.4 Analysis of fire resistance test results
  • 5 Classification report
  • Annex A
  • 1. Connection with vertical side profile of the door-leaf
  • 2. Resulting height of the infill cannot be higher than
  • 1. Connection with horizontal top- or bottom-profile of the
  • 2. Resulting width of the infill cannot be wider than tested
  • Annex B alternative variations in arrangement indicated by numbers ‘1’ or ‘2’ in
  • Annex B
  • Annex B alternative variations in arrangement in the same row assuming the
  • Annex B
  • Annex B
  • 8.10 8.11 - - - x - - - - - - - - - - x x - - - -
  • 9.8 9.9 - - - x - - - - - - - - - x x y - - - -
  • 8.10 8.11 - - - - - - - - -
  • 9.8 9.9 - - - x x - -
  • Annex C
  • 1 Non glass panel 1 Non glass panel 1 Non glass panel
  • 1 Non glass panel 1 Non glass panel 1 Non glass panel
  • 1 Non glass panel 1 Non glass panel 1 Non glass panel
  • Bibliography

1 Scope

This document covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. Throughout this document, the term “doorset” will be used to cover both doorsets and openable windows, unless otherwise stated. It specifies a method for extending the application of test results obtained from fire resistance test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4, the extended application can cover all or some of the following examples:

  • integrity (E), integrity & radiation (EW) or integrity & insulation (EI or EI ), self-closing (C) 1 2 classification,
  • door leaf and window leaf,
  • glazing within the doorset (e.g. for door leaf, side, transom and overpanels),
  • air transfer devices (e.g. ventilation louvers or air transfer grilles),
  • side panels, transom panels, flush over panels,
  • components (e.g. frame and/or suspension system) fixed to the supporting construction (e.g. wall and/or ceiling),
  • items of building hardware,
  • decorative and protective finishes,
  • intumescent strips and intumescent or non-intumescent (e.g. smoke, draught or acoustic) seals,
  • alternative supporting construction(s).

This document does not cover doorsets installed horizontally (e.g. in a ceiling). The effect on the classification durability of self-closing for the doorsets following an extended application process is not addressed in this document. The effect on the Classification smoke control for the doorsets following an extended application process is not addressed in this document. Annex A (normative) provides a thorough list about some of the possible construction parameter variations and the applicability of rules for the extended application of test results. Annex B (normative) shows different arrangements for doorsets incorporating side and/or over panels. Annex C (normative) provides with its Figures (from Figure C.1 to C.6) further clarification concerning the suitability of applying EN 15269-5 (or other parts of EN 15269) depending on the type of doorset for which the extended application of results are intended.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 179, Building hardware - Emergency exit devices operated by a lever handle or push pad, for use on escape routes - Requirements and test methods EN 572-9, Glass in building - Basic soda lime silicate glass products - Part 9: Evaluation of conformity/Product standard EN 1125, Building hardware - Panic exit devices operated by a horizontal bar, for use on escape routes - Requirements and test methods

SIST EN 15269-5:2026 EN 15269-5:2026 (E) EN 1155, Building hardware - Electrically powered hold-open devices for swing doors - Requirements and test methods EN 1363-1, Fire resistance tests - Part 1: General Requirements EN 1364-1, Fire resistance tests for non-loadbearing elements - Part 1: Walls EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and openable windows EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware - Part 2: Fire resistance characterisation test for elements of building hardware EN 1748-2-2, Glass in building - Special basic products - Glass ceramics - Part 2-2: Evaluation of conformity/Product standard EN 12365-2, Building hardware - Gasket and weatherstripping for doors, windows, shutters and curtain walling - Part 2: Linear compression force test methods EN 12519, Windows and pedestrian doors. Terminology EN 13024-2, Glass in building - Thermally toughened borosilicate safety glass - Part 2: Evaluation of conformity/Product standard EN 13501-2, Fire classification of construction products and building elements - Part 2: Classification using data from fire resistance and/or smoke control tests, excluding ventilation services EN 15254-4:2018, Extended application of results from fire resistance tests - Non-loadbearing walls - Part 4: Glazed constructions EN 15269-1, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 1: General requirements EN 15269-2, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 2: Fire resistance of hinged and pivoted steel doorsets EN 15725, Extended application on the fire performance of construction products and building elements:

Principle of EXAP standards and EXAP reports EN ISO 13943, Fire safety - Vocabulary (ISO 13943)

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 1363-1, EN 1634-1, EN 1634-2, EN 12519, EN 15269-1, EN 15725 and EN ISO 13943 and the following apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at http://www.electropedia.org/

SIST EN 15269-5:2026 EN 15269-5:2026 (E)

3.1 full scale test

test of a full scale doorset Note 1 to entry: The method of reference for determining the fire resistance of the products in the scope of this standard shall be EN 1634-1.

3.2 small scale test

test on items of building hardware Note 1 to entry: The method of reference for characterizing the influence on fire performance of items of building hardware for incorporation into the products in the scope of this standard shall be EN 1634-2. EN 1634-2 also defines the decision process that permits its use.

3.3 effective rebate depth

dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door frame, transom or side panel or flush overpanel as well as at door leaf meeting edges (on double leaf doorsets) Note 1 to entry: At the meeting edges and for rebated leaves, this dimension will be the rebate where the intumescent seal is fitted or, if no seal is fitted, the depth of the largest rebate (see Figure 1).

Key x1 example of effective rebate depth in doorset to be tested x2 example of resulting effective rebate depth during testing after movement of 20 mm Figure 1 — Effective rebate depth

3.4 opening outwards

opening the door leaf away from the fireside

3.5 opening inwards

opening the door leaf towards the fireside

SIST EN 15269-5:2026 EN 15269-5:2026 (E)

3.6 faces and sides of a hinged door leaf

all of the surfaces, faces and sides of a door panel that swing open and closed Note 1 to entry: An example is shown in Figure 2.

Key 1 opening face 4 hinge side 2 closing face 5 top side 3 lock side 6 bottom side Figure 2 — Example of faces and sides of a hinged door leaf

SIST EN 15269-5:2026 EN 15269-5:2026 (E)

3.7 representative

doorset design having ‘fundamentally the same’ or ‘similar’ construction as another doorset leaf design for the purpose of evaluating parameter variations, providing the relevant aspects of tested performance are considered Note 1 to entry: See EN 15269-1 for further guidance on evaluation of ‘similar’/’fundamentally the same’.

3.8 intumescent seal

intumescent strips and seals with intumescent characteristics

3.9 dog bolt / movement restrictor

additional part (e.g. a bolt) on the hinge side of the doorset which can bear forces such as those caused by levering for burglary or by deflection in case of fire

3.10 load bearing item of building hardware

item of building hardware which transmits or may transmit forces and/or torques between door leaf and door frame either under normal conditions or under fire conditions EXAMPLES Hinges, latches, locks and dog bolts.

4 Determination of the field of extended application

4.1 General

4.1.1 Before there can be any consideration for extended application, two representative specimens of the doorset, one with the exposure of the opening face and one with the exposure of the closing face, shall have been tested in accordance with EN 1634-1 to achieve a test result which could generate a fire resistance classification in accordance with EN 13501-2 at least equal to the fire resistance classification required from extended application considerations. These tests are referred to in this document as basic tests.

NOTE If a doorset is classified from one side only (e.g. just opening face), the extended application rules cannot lead to a classification of the opposite side or of both sides. 4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular construction parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for any specific construction parameter beyond that achieved during any one fire resistance test unless specifically identified in Table A.1.

4.1.3 If, when following the extended application procedure, any component of the classified product cannot be covered by the extended application rules, a representative specimen incorporating the particular construction parameter variation shall be tested on both sides or on one side, if the required classification is from one side only. Otherwise, that part shall be omitted from the subsequent extended application report and classification report.

4.1.4 A hardware performance sheet (HPS), according to EN 16035 may be part of the documentation

for the assessment and determination of the extended application.

SIST EN 15269-5:2026 EN 15269-5:2026 (E) 4.1.5 If the extension of the design parameter variations of Annex A, Table A.1 does not prevent the doorset from reaching the fully closed position, the rules may be used for a ‘C’ classification, provided that all test evidence used as a basis has resulted in a ‘C’ classification.” 4.2 How to use extended application rules in Annex A, Table A.1 4.2.1 Identify the variations from the original fire resistance test specimen(s) which are required to be covered by an extended application report.

4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Annex A, Table A.1.

4.2.3 Establish from the contents of column (3) of Annex A, Table A.1 whether any extended application is available beyond the direct application rules (DIAP) in EN 1634-1 without the need for further testing 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (3) of Annex A, Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing, the additional test should be made on a representative test specimen, i.e. a doorset of the same or more onerous configuration. Alternatively, column (4) of Annex A, Table A.1 identifies an option for alternative testing and relevant test parameters.

The most onerous configuration shall be the one with the lowest relevant performance in terms of mode of failure and/or highest distortion but shall also be evaluated taking the intended construction parameter variation(s) into account.

For example, if the construction parameter variation involves a change to glazing or side panel and over panel configurations then the previous result where these have been tested would need to be used to make the evaluation of most onerous.

4.2.6 When an additional test according to column (4) of Annex A, Table A.1 is performed and the result of this additional test meets the provisions given in column (3), the possible extensions in column (3) can be applied based on this additional test.

4.3 Procedure for maximum field of extended application

4.3.1 It is possible to provide an extended field of application from a single test. However, where a manufacturer intends to produce a range of doorsets incorporating single leaf doorsets and also double leaf doorsets with or without side, transom or flush over panels, with or without glazing, with or without air transfer devices, e.g. ventilation grilles or louvers, with alternative items of building hardware, etc., it is recommended that careful consideration is given to the complete range of doorset designs and options in order to minimize the testing required before testing commences. 4.3.2 Establish all the construction parameter variations which are required to be part of the product range.

4.3.3 Determine which are the most important design and configuration requirements and incorporate as many as possible into the specimen(s) for the first tests in the series. 4.3.4 Conduct the first fire resistance test or a series of tests and then establish which of the original desired construction parameter variations have not been covered by the fire resistance tests, including direct application possibilities.

4.3.5 Identify these construction parameter variations in Annex A, Table A.1 and establish if any extended application is possible without further testing.

SIST EN 15269-5:2026 EN 15269-5:2026 (E) 4.3.6 Record this for the extended application report together with any restrictions and rules given in column (3) in Annex A, Table A.1.

4.3.7 Evaluate which, if any, of the desired construction parameter variations have not been covered by the field of direct application or the initial field of extended application derived from 4.3.5. 4.3.8 Determine if the product range is to include only single leaf doorsets, only double leaf doorsets or both. Where only single leaf doorsets are to be part of the product range, the outstanding construction parameter variations shall only be incorporated into specimens for the single leaf doorset. Where only double leaf doorsets are to be part of the product range, the outstanding construction parameter variations shall only be incorporated into specimens for double leaf doorsets. Where single leaf and double leaf doorsets are to be included in the product range, the outstanding construction parameter variations for the extended application of single leaf doorsets may be incorporated into either repeated single leaf doorset fire resistance tests or in the most onerous configuration, as defined in column (4) of Annex A, Table A.1, double leaf doorset configurations. See also Annex B.

4.3.9 Select the required outstanding construction parameter variations from column (1) and

column (2) of Annex A, Table A.1 and observe from column (4) of Annex A, Table A.1 which are the most onerous specimen configurations for further testing.

4.3.10 If the complete selection of required construction parameter variations has not been covered by the tests completed in accordance with 4.3.8 and 4.3.9 above, then an appropriate fire resistance test or tests may be repeated with the additional product variations incorporated.

4.4 Analysis of fire resistance test results

4.4.1 In order to maximize the extended field of application, it is important that the test reports shall record details of any premature integrity and/or insulation and/or radiation failure, also record details of any significant distortion to evaluate low, medium and high distortion (see Annex A, Table A.1). 4.4.2 Where a series of fire resistance tests have been conducted, the field of extended application shall be based on the lowest performance achieved from the complete series of fire resistance tests unless premature failure has been attributed to one or more specific construction parameter variation. 4.4.3 Where it has been possible to clearly identify failures that can be unambiguously assigned to a specific construction parameter variation, the extended application for all other construction parameter variations can be based on the performance achieved after isolating the premature failure(s), provided the requirements of 4.1.1 are met. Where the specific construction parameter variation requires category B performance (see EN 1634-1 for the corresponding overrun times) and where failures can be identified as having no relevance to this aspect of the construction, they can be disregarded, and the failure time and associated category revised accordingly. In any case, the failed construction parameters have to be excluded from the classification and EXAP reports.

5 Classification report

The classification report shall be determined from the results of the extended application report and presented in accordance with EN 13501-2.

SIST EN 15269-5:2026 EN 15269-5:2026 (E)

Annex A

(normative)

Construction parameter variations Table A.1 is designed to be used in the field of fire resistance testing of hinged and pivoted metal framed glazed doorsets and openable windows.

The table shall only be used to evaluate a field of extended application when at least one fire resistance test to EN 1634-1 can generate a fire resistance classification according to EN 13501-2. Only results from fire resistance tests in accordance with European Standards can be used as basis for extended application. The first two columns identify possible variations to the construction details of the specimen tested. In the column “Variations”, it could be referenced, in brackets () and in italics, the number of the rule as previously indicated in EN 15269-5:2014+A1:2016. For example, Table A.1 references (C.1.49) in rule C.14.1: this means that that rule C.14.1 was referenced as rule C.1.49 in the old version of the standard. For some construction parameters, it is necessary to evaluate whether the specimen displayed a high, medium or low level of distortion during the fire resistance test. Where this is the case, the following levels shall be used to establish high, medium and low distortion doorsets as measured using the maximum relative movement at any position between the edge of the door leaf and door frame or between the meeting edges of door leaves or the relative movement of the framing members for panelled systems. The measurements shall be taken from the start of the test at any time during the complete required classification period. The deflections shall be measured at the positions given in EN 1634-1:

  • Low: < 40 % of effective rebate depth;
  • Medium: ≥ 40 % and ≤ 85 % of effective rebate depth;
  • High: > 85 % of effective rebate depth.

Evaluations of the influence of a construction parameter variation on performance characteristics (E/EW/EI) lead to the judgement of the possibility of the extension of the field of application, the results of which are given in column (3). In certain cases in column (3), it is a requirement to achieve Category B; the requirements for this are given in EN 1634-1.

...