Secure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container

This part of the European Standard EN 1047 specifies requirements for data rooms and data containers. It includes a method of test for the determination of the ability of data rooms and data containers to protect temperature and humidity sensitive data media (see 3.5) and hardware systems (see 3.6) from the effects of fire. A test method for measuring the resistance to mechanical stress (impact test) provided by data rooms type B and data containers is also specified.
Requirements are also specified for test specimens, the technical documentation of the test specimens, materials specimens, physical fittings, the correlation of test specimens with the technical documentation and the preparation for type testing, as test procedures as well as the series production.
In addition, a scheme to classify data rooms and data containers from the test results is given (see Table 1).
As well as providing protection against fire, correctly installed data rooms and data containers offer a defined protection against impacts caused by failure during fire of components and objects external to the data room or data container.
Data rooms and data containers having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, lockings, doors, etc.) will only be given the same protection classification as that of the test specimen if the tolerances are within the ranges specified in Clause 7.
NOTE   This European Standard does not regulate the use of data rooms in the meaning of the building laws of the respective countries. In the construction of data rooms, it is advised to consider the respective national requirements.

Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Teil 2: Datensicherungsräume und Datensicherungscontainer

Dieser Teil der Europäischen Norm EN 1047 legt Anforderungen an Datensicherungsräume und Datensicherungscontainer fest. Er umfasst eine Prüfmethode zur Ermittlung der Widerstandsfähigkeit von Datensicherungsräumen und Datensicherungscontainern zum Schutz von temperatur- und feuchtigkeitsempfindlichen Datenträgern (siehe 3.5) und Hardwaresystemen (siehe 3.6) vor Brandeinwirkung. Ferner wird eine Prüfmethode zur Messung des Widerstandes gegen mechanische Beanspruchung (Stoßprüfung) auf Datensicherungsräume Typ B und Datensicherungscontainer festgelegt.
Außerdem sind Anforderungen für die Probekörper, Technische Dokumentation der Probekörper, Materialproben, Einbauten, Übereinstimmung von Probekörpern mit der Technischen Dokumentation und die Vorbereitung der Typprüfung , die Prüfverfahren sowie für die Serienprodukte definiert.
Ferner wird ein Schema zur Klassifizierung von Datensicherungsräumen und Datensicherungscontainern entsprechend ihrem Prüfergebnis gegeben (siehe Tabelle 2).
Neben dem Schutz vor Bränden bieten sachgemäß installierte Datensicherungsräume und Datensicherungscontainer zusätzlich Schutz gegen Stöße aufgrund eines brandbedingten Versagens von Bauteilen und Objekten, die sich außerhalb des Datensicherungsraumes oder Datensicherungscontainers befinden.
Datensicherungsräume und Datensicherungscontainer, die über dieselbe Konstruktion, denselben Schutz und Aufbau (Art und Dicke der Konstruktions- und Schutzmaterialien, Anordnung der Falze, Verschlüsse, Türen usw.) verfügen, können nur dann in die Güteklasse wie der Probekörper eingestuft werden, wenn die Toleranzen nach Abschnitt 7 eingehalten sind.
ANMERKUNG   Diese Europäische Norm regelt nicht die Verwendung des Datensicherungsraumes im Sinne des Baurechts der jeweiligen Länder. Bei der Errichtung von Datensicherungsräumen wird empfohlen die jeweiligen nationalen Anforderungen zu berücksichtigen.

Unités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu - Partie 2: Conteneurs et chambres réfractaires

La présente partie de la Norme européenne EN 1047 spécifie les exigences relatives aux conteneurs et chambres réfractaires. Elle présente une méthode d'essai permettant de déterminer la capacité des chambres et conteneurs réfractaires à protéger les supports d’informations (voir 3.5) ainsi que les systèmes matériels (voir 3.6) sensibles à la température et à l'humidité des effets d'un incendie. Une méthode d’essai est également prescrite pour mesurer la résistance à une force mécanique (essai d’impact) des chambres réfractaires de type B et des conteneurs réfractaires.
De plus, des exigences sont spécifiées pour les éprouvettes, la documentation technique devant accompagner les éprouvettes, les échantillons de matériels, les équipements matériels, la corrélation entre les éprouvettes et la documentation technique, la préparation des essais de type, les procédures d'essai, ainsi que la production en série.
Un plan est également présenté (voir Tableau 1) permettant une classification des chambres et conteneurs réfractaires à partir des résultats des essais.
Les chambres et les conteneurs réfractaires correctement installés assurent non seulement une protection définie contre l’incendie mais aussi contre les conséquences de la défaillance, au cours de l’incendie, de composants et d’objets externes.
Les chambres et conteneurs réfractaires ayant les mêmes caractéristiques de conception, de protection et de construction (types et épaisseurs des matériaux de construction et de protection, géométrie des feuillures, verrouillages, portes, etc.) appartiennent à la même classification de protection que celle de l’éprouvette seulement si les tolérances se trouvent dans les fourchettes spécifiées dans l’Article 7.
NOTE   La présente Norme européenne ne réglemente pas l’utilisation des chambres réfractaires au sens des lois sur la construction, applicables dans les pays respectifs. Il convient que les exigences nationales respectives sur la construction de chambres réfractaires soient prises en considération.

Varnostne shranjevalne enote - Klasifikacija in metode preskušanja požarne odpornosti - 2. del: Prostori in vsebniki za shranjevanje podatkov

Ta del evropskega standarda EN 1047 določa zahteve za prostore in vsebnike za shranjevanje podatkov. Vključuje preskusno metodo, s katero se določi zmožnost prostorov in vsebnikov za shranjevanje podatkov glede zaščite nosilcev podatkov, ki so občutljivi na temperaturo in vlago (glej razdelek 3.5), ter sistemov strojne opreme (glej razdelek 3.6) pred ognjem. Določa tudi preskusno metodo za merjenje odpornosti proti mehanskim vplivom (preskus vpliva), ki jo zagotavljajo prostori za shranjevanje podatkov tipa B in vsebniki za shranjevanje podatkov.
Določa tudi zahteve za preskušance, tehnično dokumentacijo za preskušance vzorce materialov, fizične priključke, razmerje med preskušanci, tehnično dokumentacijo in pripravo na preskušanje tipov, postopke preskusov in tudi serijsko proizvodnjo.
Poleg tega podaja shemo za razvrstitev prostorov in vsebnikov za shranjevanje podatkov na podlagi rezultatov preskusa (glej tabelo 1).
Poleg protipožarne zaščite pravilno vgrajeni prostori in vsebniki za shranjevanje podatkov zagotavljajo tudi opredeljeno zaščito pred izpadom delovanja, do katerega lahko pride zaradi požara, ki prizadene komponente in predmete zunaj prostorov in vsebnikov za shranjevanje podatkov.
Prostori in vsebniki za shranjevanje podatkov z enakimi lastnostmi zasnove, zaščite in gradnje (vrsta in debelina gradbenih in zaščitnih materialov, geometrija utorov, zaklepi, vrata itd.) bodo prejeli isto razvrstitev zaščite kot preskušanec le, če so tolerance v razponu, podanem v 7. točki.
OPOMBA:   Ta evropski standard ne ureja uporabe prostorov za shranjevanje podatkov v pomenu gradbene zakonodaje posameznih držav. Pri gradnji prostorov za shranjevanje podatkov je treba upoštevati posamezne nacionalne zahteve.

General Information

Status
Published
Publication Date
02-Apr-2019
Withdrawal Date
30-Oct-2019
Current Stage
9020 - Submission to 2 Year Review Enquiry - Review Enquiry
Start Date
15-Jul-2024
Completion Date
15-Jul-2024

Relations

Buy Standard

Standard
EN 1047-2:2019
English language
35 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-julij-2019
Nadomešča:
SIST EN 1047-2:2009+A1:2013
Varnostne shranjevalne enote - Klasifikacija in metode preskušanja požarne
odpornosti - 2. del: Prostori in vsebniki za shranjevanje podatkov
Secure storage units - Classification and methods of test for resistance to fire - Part 2:
Data rooms and data container
Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen
Brand - Teil 2: Datensicherungsräume und Datensicherungscontainer
Unités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu -
Partie 2: Conteneurs et chambres réfractaires
Ta slovenski standard je istoveten z: EN 1047-2:2019
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
13.310 Varstvo pred kriminalom Protection against crime
35.220.99 Druge naprave za Other data storage devices
shranjevanje podatkov
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 1047-2
EUROPEAN STANDARD
NORME EUROPÉENNE
April 2019
EUROPÄISCHE NORM
ICS 13.220.40; 13.310; 35.020 Supersedes EN 1047-2:2009+A1:2013
English Version
Secure storage units - Classification and methods of test
for resistance to fire - Part 2: Data rooms and data
container
Unités de stockage en lieu sûr - Classification et Wertbehältnisse - Klassifizierung und Methoden zur
méthodes d'essai de résistance au feu - Partie 2: Prüfung des Widerstandes gegen Brand - Teil 2:
Conteneurs et chambres réfractaires Datensicherungsräume und Datensicherungscontainer
This European Standard was approved by CEN on 11 February 2019.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1047-2:2019 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 Requirements and classification . 9
5 Test specimens, technical documentation, material samples, physical fittings and
correlation . 10
5.1 General requirements for data rooms type A and B and data containers . 10
5.1.1 General requirements for test specimens . 10
5.1.2 Fire retarding seals . 10
5.2 Data room type A test specimens . 12
5.3 Data room type B test specimens . 14
5.4 Data container test specimens . 15
5.5 Test specimen – floor test . 15
5.6 Assessment of construction variants . 16
5.6.1 General . 16
5.6.2 Test specimen – comparison test . 16
5.7 Technical documentation of the test specimens . 17
5.8 Material samples . 17
5.9 Correlation of test specimen and technical documentation . 17
6 Test methods . 17
6.1 General . 17
6.2 Test apparatus. 18
6.3 Preparation of test specimens . 19
6.4 Preparation of furnace . 26
6.5 Conditioning including air conditioning . 27
6.5.1 Data room . 27
6.5.2 Data containers . 27
6.5.3 Wall and floor panels (data rooms, data containers) . 27
6.6 Test procedure . 27
6.6.1 Data room and data container test . 27
6.6.2 Impact test . 28
6.6.3 Floor test . 29
6.6.4 Comparison test . 29
6.6.5 Examinations . 30
6.7 Test report . 30
7 Series production . 31
7.1 General . 31
7.2 Fire-retarding penetration seals and configurations in series production . 32
8 Labelling . 33
Annex A (normative) Design of the reinforced concrete slab for the floor test . 34
Bibliography . 35
European foreword
This document (EN 1047-2:2019) has been prepared by Technical Committee CEN/TC 263 “Secure
storage of cash, valuables and data media”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by October 2019, and conflicting national standards shall
be withdrawn at the latest by October 2019.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1047-2:2009+A1:2013.
This document EN 1047 Secure storage units — Classification and methods of test for resistance to fire is
composed of two parts:
— Part 1: Data cabinets and diskette inserts
— Part 2: Data rooms and data container
In comparison with EN 1047-2:2009+A1:2013, the following changes have been made:
— references have been updated;
— the definitions have been updated to the state of the art;
— the requirements in Table 1 have changed;
— the requirements for doors have been updated (see 4.2);
— for easier and shorter reading the general requirements (for instance equipment of the test
specimen and position of fire-retarding penetration seals) for data rooms type A and data room
type B as well as data containers have moved into one new clause (see 5.1);
— the configuration (including a number and type of cables and pipes reaching into the room) is
defined more precisely and is updated to the state of the art for the type test and the series
products (see3.8, 5.1.2, and 7.2);
— to make sure that customers wishing to have higher data rooms, the test specimen in the furnace is
allowed to be higher than the limit of 2 700 mm which was in the standard before (see 5.2.2 and
5.3.1);
— an additional type test for the floor has been added (see 5.2.4, 5.3.3, 5.4.3, 5.5, 6.2.1d, 6.3.7, 6.6.3
and Annex A);
— the requirements for the comparison test have changed (see Table 1, 5.6, 6.2.1e, 6.3.8, 6.4.5, and
6.6.4);
— the thermocouples have been repositioned for the data room test (see 6.3.4);
— the requirements for series products have been updated and have been moved from the scope to
the new Clause 7 “series products”. Above all the height of a data room may only be increased by
35 % and decreased by 35 % (before both were at 50 %);
— the figures in the standard have been updated;
— editorial changes have been made throughout the standard.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
Introduction
The testing conditions given in this European Standard provide a basis for simulating fires to
determine, in a reproducible way, the fire resistance of data rooms and data containers.
The values for the maximum temperature increase in protection classes R60D and C60D specified in
accordance with Table 1 in this European Standard relate to the relatively short time of high
temperature exposure occurring during a fire test; in general, they are not experienced by data media
and systems hardware stored in data rooms and data containers in the normal and correct way.
EN 1363-1 establishes the general principles for determining the fire resistance of various elements of
construction when subjected to standard fire exposure conditions. Alternative and additional
procedures to meet special requirements are given in EN 1363-2. The development of the temperatures
and the relative humidity in the interior of a data room and data container cannot be measured under
the standard series EN 1363.
The sensitivity of media (see 3.5) and hardware systems (see 3.6) to temperature and humidity
requires additional protection with regard to excessively high temperatures and relative humidity,
proof of which cannot be furnished through type tests in accordance with the European Standards
EN 1363-1 and EN 1363-2. This additional protection requires a series of product solutions, the
performance of which is type tested and certifi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.