Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases)

SIGNIFICANCE AND USE
The LFL and UFL of gases and vapors define the range of flammable concentrations in air.
5.2 This method measures the LFL and UFL for upward (and partially outward) flame propagation. The limits for downward flame propagation are narrower.
Limits of flammability may be used to determine guidelines for the safe handling of volatile chemicals. They are used particularly in assessing ventilation requirements for the handling of gases and vapors. NFPA 69 provides guidance for the practical use of flammability limit data, including the appropriate safety margins to use.
5.4 As discussed in Brandes and Ural , there is a fundamental difference between the ASTM and European methods for flammability determination. The ASTM methods aim to produce the best representation of flammability parameters, and rely upon the safety margins imposed by the application standards, such as NFPA 69. On the other hand, European test methods aim to result in a conservative representation of flammability parameters. For example, in this standard, LFL is the calculated average of the lowest go and highest no-go concentrations while the European test methods report the LFL as the minimum of the 5 highest no-go concentrations.
Note 2—For hydrocarbons, the break point between nonflammability and flammability occurs over a narrow concentration range at the lower flammability limit, but the break point is less distinct at the upper limit. For materials found to be non-reproducible per 13.1.1 that are likely to have large quenching distances and may be difficult to ignite, such as ammonia and certain halogenated hydrocarbon, the lower and upper limits of these materials may both be less distinct. That is, a wider range exists between flammable and nonflammable concentrations (see Annex A1).
SCOPE
1.1 This test method covers the determination of the lower and upper concentration limits of flammability of chemicals having sufficient vapor pressure to form flammable mixtures in air at atmospheric pressure at the test temperature. This test method may be used to determine these limits in the presence of inert dilution gases. No oxidant stronger than air should be used.  
Note 1—The lower flammability limit (LFL) and upper flammability limit (UFL) are sometimes referred to as the lower explosive limit (LEL) and the upper explosive limit (UEL), respectively. However, since the terms LEL and UEL are also used to denote concentrations other than the limits defined in this test method, one must examine the definitions closely when LEL and UEL values are reported or used.  
1.2 This test method is based on electrical ignition and visual observations of flame propagation. Users may experience problems if the flames are difficult to observe (for example, irregular propagation or insufficient luminescence in the visible spectrum), if the test material requires large ignition energy, or if the material has large quenching distances.
1.3 Annex A1 provides a modified test method for materials (such as certain amines, halogenated materials, and the like) with large quenching distances which may be difficult to ignite.
1.4 In other situations where strong ignition sources (such as direct flame ignition) is considered credible, the use of a test method employing higher energy ignition source in a sufficiently large pressure chamber (analogous, for example, to the methods in Test Method E2079 for measuring limiting oxygen concentration) may be more appropriate. In this case, expert advice may be necessary.
1.5 The flammability limits depend on the test temperature and pressure. This test method is limited to an initial pressure of the local ambient or less, with a practical lower pressure limit of approximately 13 kPa (100 mm Hg). The maximum practical operating temperature of this equipment is approximately 150°C.
1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are included in t...

General Information

Status
Historical
Publication Date
30-Sep-2009
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E681-09 - Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases)
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E681-09 - Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases)
English language
12 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E681 − 09
StandardTest Method for
Concentration Limits of Flammability of Chemicals (Vapors
1
and Gases)
This standard is issued under the fixed designation E681; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.6 The values stated in SI units are to be regarded as
standard. No other units of measurement are included in this
1.1 This test method covers the determination of the lower
standard.
and upper concentration limits of flammability of chemicals
having sufficient vapor pressure to form flammable mixtures in
1.7 Thistestmethodshouldbeusedtomeasureanddescribe
air at atmospheric pressure at the test temperature. This test
the properties of materials, products, or assemblies in response
method may be used to determine these limits in the presence
to heat and flame under controlled laboratory conditions and
of inert dilution gases. No oxidant stronger than air should be
shouldnotbeusedtodescribeorappraisethefirehazardorfire
used.
risk of materials, products, or assemblies under actual fire
conditions.However,resultsofthistestmethodmaybeusedas
NOTE 1—The lower flammability limit (LFL) and upper flammability
elements of a fire risk assessment that takes into account all of
limit (UFL) are sometimes referred to as the lower explosive limit (LEL)
and the upper explosive limit (UEL), respectively. However, since the
the factors pertinent to an assessment of the fire hazard of a
terms LEL and UEL are also used to denote concentrations other than the
particular end use.
limitsdefinedinthistestmethod,onemustexaminethedefinitionsclosely
when LEL and UEL values are reported or used. 1.8 This standard may involve hazardous materials,
operations, and equipment. This standard does not purport to
1.2 This test method is based on electrical ignition and
address all of the safety concerns, if any, associated with its
visual observations of flame propagation. Users may experi-
use. It is the responsibility of the user of this standard to
ence problems if the flames are difficult to observe (for
establish appropriate safety and health practices and deter-
example, irregular propagation or insufficient luminescence in
mine the applicability of regulatory limitations prior to use.
the visible spectrum), if the test material requires large ignition
Specific precautionary statements are given in Section 8
energy, or if the material has large quenching distances.
1.3 AnnexA1 provides a modified test method for materials
2. Referenced Documents
(such as certain amines, halogenated materials, and the like)
2
2.1 ASTM Standards:
withlargequenchingdistanceswhichmaybedifficulttoignite.
E171 Practice for Conditioning and Testing Flexible Barrier
1.4 In other situations where strong ignition sources (such
Packaging
as direct flame ignition) is considered credible, the use of a test
E582 Test Method for Minimum Ignition Energy and
method employing higher energy ignition source in a suffi-
Quenching Distance in Gaseous Mixtures
ciently large pressure chamber (analogous, for example, to the
E1445 Terminology Relating to Hazard Potential of Chemi-
methods in Test Method E2079 for measuring limiting oxygen
cals
concentration) may be more appropriate. In this case, expert
E1515 Test Method for Minimum Explosible Concentration
advice may be necessary.
of Combustible Dusts
1.5 The flammability limits depend on the test temperature
E2079 Test Methods for Limiting Oxygen (Oxidant) Con-
and pressure. This test method is limited to an initial pressure
centration in Gases and Vapors
of the local ambient or less, with a practical lower pressure
3
2.2 NFPA Standard:
limit of approximately 13 kPa (100 mm Hg). The maximum
NFPA 69 Standard on Explosion Prevention Systems
practical operating temperature of this equipment is approxi-
mately 150°C.
1 2
This test method is under the jurisdiction ofASTM Committee E27 on Hazard For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Potential of Chemicals and is the direct responsibility of Subcommittee E27.04 on contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Flammability and Ignitability of Chemicals. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved Oct. 1, 2009. Published January 2010. Originally the ASTM website.
3
approved in 1979. Last previous edition approved in 2004 as E681 – 04. DOI: Available from National Fire Protection Association (NFPA), 1 Batterymarch
10.1520/E0681-09. Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:E681–04 Designation: E681 – 09
Standard Test Method for
Concentration Limits of Flammability of Chemicals (Vapors
1
and Gases)
This standard is issued under the fixed designation E681; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method covers the determination of the lower and upper concentration limits of flammability of chemicals having
sufficient vapor pressure to form flammable mixtures in air at atmospheric pressure at the test temperature. This test method may
be used to determine these limits in the presence of inert dilution gases. No oxidant stronger than air should be used.
NOTE 1—The lower flammability limit (LFL) and upper flammability limit (UFL) are sometimes referred to as the lower explosive limit (LEL) and
the upper explosive limit (UEL), respectively. However, since the terms LELand UELare also used to denote concentrations other than the limits defined
in this test method, one must examine the definitions closely when LEL and UEL values are reported or used.
1.2 This test method is based on electrical ignition and visual observations of flame propagation. Users may experience
problems if the flames are difficult to observe (for example, irregular propagation or insufficient luminescence in the visible
spectrum), if the test material requires large ignition energy, or if the material has large quenching distances.
1.3 AnnexA1 provides a modified test method for materials (such as certain amines, halogenated materials, and the like) with
large quenching distances which may be difficult to ignite.
1.4 In other situations where strong ignition sources (such as direct flame ignition) is considered credible, the use of a test
method employing higher energy ignition source in a sufficiently large pressure chamber (analogous, for example, to the methods
in Test Method E2079 for measuring limiting oxygen concentration) may be more appropriate. In this case, expert advice may be
necessary.
1.5 The flammability limits depend on the test temperature and pressure.This test method is limited to an initial pressure of the
local ambient or less, with a practical lower pressure limit of approximately 13 kPa (100 mm Hg). The maximum practical
operating temperature of this equipment is approximately 150°C (302°F). 150°C.
1.6 The values stated in SI units are to be regarded as the standard. The values given in parenthesesNo other units of
measurement are provided for information only. included in this standard.
1.7 This test method should be used to measure and describe the properties of materials, products, or assemblies in response
to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk
of materials, products, or assemblies under actual fire conditions. However, results of this test method may be used as elements
of a fire risk assessment that takes into account all of the factors pertinent to an assessment of the fire hazard of a particular end
use.
1.8 This standard may involve hazardous materials, operations, and equipment. This standard does not purport to address all
of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate
safety and health practices and determine the applicability of regulatory limitations prior to use.Specificprecautionarystatements
are given in Section 8
2. Referenced Documents
2
2.1 ASTM Standards:
E171 Specification for Atmospheres for Conditioning and Testing Flexible Barrier Materials
E582
E582 Test Method for Minimum Ignition Energy and Quenching Distance in Gaseous Mixtures
E1445
E1445 Terminology Relating to Hazard Potential of Chemicals
1
This test method is under the jurisdiction of ASTM Committee E27 on Hazard Potential of Chemicals and is the direct responsibility of Subcommittee E27.04 on
Flammability and Ignitability of Chemicals.
Current edition approved JuneOct. 1, 2004.2009. Published July 2004.January 2010. Originally approved in 1979. Last previous edition approved in 20012004 as E681
– 01.04. DOI: 10.1520/E0681-049.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.