Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests

SIGNIFICANCE AND USE
4.1 Test Methods E119, E1529, and other standard fire resistance test methods specify that throughout the fire-resistance test, a constant superimposed load shall be applied to a load-bearing test specimen to simulate a maximum allowable load condition. This superimposed load shall be the maximum load allowed by design under nationally recognized structural design criteria for the tested floor configuration (that is, joist selection, spacing, and span).  
4.1.1 For this practice, the nationally recognized structural design criteria to be used to determine the maximum load condition are those for the allowable stress design (ASD) method in the NDS (National Design Specification for Wood Construction).
Note 1: The NDS should be used to ensure calculation of the superimposed load is in compliance with all applicable provisions of that standard. Appendix X1 describes how to calculate the superimposed load in accordance with the NDS.  
4.1.2 Alternatively, the standard fire resistance test methods shall be permitted to be conducted by applying a load less than the maximum allowable load in 4.1.1 for the tested configuration; however, these tests shall be identified in the test report as being conducted under restricted loading conditions.  
4.2 This practice describes procedures for calculating the superimposed load to be applied in standard fire resistance tests of wood floor-ceiling assemblies. Practice D6513 provides a similar methodology for calculating the superimposed load on wood-frame walls.  
4.3 Statements in either the fire resistance test method standard or the nationally recognized structural design standard supersede any procedures described by this practice.
SCOPE
1.1 This practice covers procedures for calculating the superimposed load required to be applied to load-bearing wood-frame floor-ceiling assemblies throughout standard fire-resistance tests.  
1.2 These calculations determine the maximum superimposed load to be applied to the floor-ceiling assembly during the fire resistance test. The maximum superimposed load, calculated in accordance with nationally-recognized structural design criteria, shall be designed to induce the maximum allowable stress in the wood floor-ceiling fire test configuration being tested.  
1.3 This practice is only applicable to those wood-frame floor-ceiling assemblies for which the nationally recognized structural design criteria are contained in the National Design Specification for Wood Construction (NDS).  
1.4 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.  
1.5 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.  
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
30-Jun-2021
Technical Committee
D07 - Wood
Drafting Committee
D07.05 - Wood Assemblies

Relations

Effective Date
01-Jan-2024
Effective Date
01-Oct-2019
Effective Date
15-Dec-2018
Effective Date
01-Nov-2018
Effective Date
01-Nov-2018
Effective Date
01-Sep-2018
Effective Date
01-Jun-2018
Effective Date
01-Mar-2018
Effective Date
01-Mar-2018
Effective Date
01-Nov-2016
Effective Date
01-Jul-2016
Effective Date
01-Apr-2016
Effective Date
01-Aug-2015
Effective Date
01-Aug-2015
Effective Date
01-Jul-2015

Overview

ASTM D7746-21 is the standard practice established by ASTM International for calculating the superimposed load on wood-frame floor-ceiling assemblies during standard fire-resistance tests. This practice is essential for ensuring accurate simulation of real-world structural load conditions in fire testing scenarios. The standard sets out procedures to determine the additional loads that, when applied alongside the assembly’s own weight, induce maximum allowable stress as determined by recognized structural criteria. These calculations are especially relevant for assemblies that must comply with the allowable stress design (ASD) method outlined in the National Design Specification for Wood Construction (NDS).

Key Topics

  • Superimposed Load Calculation: Specifies how to determine the maximum external load to be applied during fire resistance tests, simulating the maximum design load under national structural codes.
  • Allowable Stress Design (ASD) Criteria: Mandates that calculations adhere to ASD methods as defined in the NDS for Wood Construction.
  • Applicability: Limited to wood-frame floor-ceiling assemblies whose structural criteria are set forth in the NDS.
  • Load Application: Details necessary assumptions for load distribution during testing, ensuring that the test conditions mirror in-service arrangements.
  • Reporting Requirements: Outlines the essential data and calculations to be documented in the test report, such as grade and species of wood, joist dimensions, dead and live load estimates, and resulting load effects as percentages of design capacity.
  • Adjustment Factors: Describes required adjustments for design values, including load duration, wet service, temperature, and others per NDS provisions.

Applications

Practical Value

The primary application of ASTM D7746-21 is in the evaluation of fire-resistance performance of wood-frame floor-ceiling assemblies:

  • Building Product Testing: Ensures that floor-ceiling systems meet safety requirements by subjecting them to realistic loading during fire exposure.
  • Compliance Verification: Enables code officials, product manufacturers, and testing laboratories to verify compliance with model building codes and fire safety regulations.
  • Design Validation: Supports architects and structural engineers in validating that their wood floor-ceiling designs will perform as expected under fire conditions while sustaining appropriate loads.
  • Research and Development: Provides a framework for consistent, repeatable testing in the evaluation and improvement of wood-based structural products.

By following this standard, users can ensure that the loads applied during fire testing accurately represent real-world building usage, enhancing the reliability and relevance of fire-resistance ratings.

Related Standards

  • ASTM E119 – Test Methods for Fire Tests of Building Construction and Materials: Governs fire-resistance testing for building elements, referenced for procedural requirements.
  • ASTM E1529 – Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies: Addresses fire exposure in specific risk environments.
  • ASTM D6513 – Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Resistance Tests: Offers a procedure analogous to D7746, but specific to walls.
  • ANSI/AWC NDS – National Design Specification for Wood Construction: Provides the structural design values and criteria used as the basis for load calculation under D7746.
  • ASTM D9 – Terminology Relating to Wood and Wood-Based Products: Definition reference for terms and material properties used throughout D7746.

Keywords

fire-resistance, wood-frame floor-ceiling assembly, superimposed load, standard fire-resistance test, National Design Specification (NDS), allowable stress design, load-bearing, ASTM D7746, structural fire safety, wood construction

Buy Documents

Standard

ASTM D7746-21 - Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests

English language (5 pages)
sale 15% off
sale 15% off
Standard

REDLINE ASTM D7746-21 - Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests

English language (5 pages)
sale 15% off
sale 15% off

Get Certified

Connect with accredited certification bodies for this standard

NSF International

Global independent organization facilitating standards development and certification.

ANAB United States Verified

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Gozdarski inštitut Slovenije

Slovenian Forestry Institute. Forest management certification support, timber testing.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

ASTM D7746-21 is a standard published by ASTM International. Its full title is "Standard Practice for Calculating the Superimposed Load on Wood-frame Floor-Ceiling Assemblies for Standard Fire-Resistance Tests". This standard covers: SIGNIFICANCE AND USE 4.1 Test Methods E119, E1529, and other standard fire resistance test methods specify that throughout the fire-resistance test, a constant superimposed load shall be applied to a load-bearing test specimen to simulate a maximum allowable load condition. This superimposed load shall be the maximum load allowed by design under nationally recognized structural design criteria for the tested floor configuration (that is, joist selection, spacing, and span). 4.1.1 For this practice, the nationally recognized structural design criteria to be used to determine the maximum load condition are those for the allowable stress design (ASD) method in the NDS (National Design Specification for Wood Construction). Note 1: The NDS should be used to ensure calculation of the superimposed load is in compliance with all applicable provisions of that standard. Appendix X1 describes how to calculate the superimposed load in accordance with the NDS. 4.1.2 Alternatively, the standard fire resistance test methods shall be permitted to be conducted by applying a load less than the maximum allowable load in 4.1.1 for the tested configuration; however, these tests shall be identified in the test report as being conducted under restricted loading conditions. 4.2 This practice describes procedures for calculating the superimposed load to be applied in standard fire resistance tests of wood floor-ceiling assemblies. Practice D6513 provides a similar methodology for calculating the superimposed load on wood-frame walls. 4.3 Statements in either the fire resistance test method standard or the nationally recognized structural design standard supersede any procedures described by this practice. SCOPE 1.1 This practice covers procedures for calculating the superimposed load required to be applied to load-bearing wood-frame floor-ceiling assemblies throughout standard fire-resistance tests. 1.2 These calculations determine the maximum superimposed load to be applied to the floor-ceiling assembly during the fire resistance test. The maximum superimposed load, calculated in accordance with nationally-recognized structural design criteria, shall be designed to induce the maximum allowable stress in the wood floor-ceiling fire test configuration being tested. 1.3 This practice is only applicable to those wood-frame floor-ceiling assemblies for which the nationally recognized structural design criteria are contained in the National Design Specification for Wood Construction (NDS). 1.4 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard. 1.5 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard. 1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

SIGNIFICANCE AND USE 4.1 Test Methods E119, E1529, and other standard fire resistance test methods specify that throughout the fire-resistance test, a constant superimposed load shall be applied to a load-bearing test specimen to simulate a maximum allowable load condition. This superimposed load shall be the maximum load allowed by design under nationally recognized structural design criteria for the tested floor configuration (that is, joist selection, spacing, and span). 4.1.1 For this practice, the nationally recognized structural design criteria to be used to determine the maximum load condition are those for the allowable stress design (ASD) method in the NDS (National Design Specification for Wood Construction). Note 1: The NDS should be used to ensure calculation of the superimposed load is in compliance with all applicable provisions of that standard. Appendix X1 describes how to calculate the superimposed load in accordance with the NDS. 4.1.2 Alternatively, the standard fire resistance test methods shall be permitted to be conducted by applying a load less than the maximum allowable load in 4.1.1 for the tested configuration; however, these tests shall be identified in the test report as being conducted under restricted loading conditions. 4.2 This practice describes procedures for calculating the superimposed load to be applied in standard fire resistance tests of wood floor-ceiling assemblies. Practice D6513 provides a similar methodology for calculating the superimposed load on wood-frame walls. 4.3 Statements in either the fire resistance test method standard or the nationally recognized structural design standard supersede any procedures described by this practice. SCOPE 1.1 This practice covers procedures for calculating the superimposed load required to be applied to load-bearing wood-frame floor-ceiling assemblies throughout standard fire-resistance tests. 1.2 These calculations determine the maximum superimposed load to be applied to the floor-ceiling assembly during the fire resistance test. The maximum superimposed load, calculated in accordance with nationally-recognized structural design criteria, shall be designed to induce the maximum allowable stress in the wood floor-ceiling fire test configuration being tested. 1.3 This practice is only applicable to those wood-frame floor-ceiling assemblies for which the nationally recognized structural design criteria are contained in the National Design Specification for Wood Construction (NDS). 1.4 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard. 1.5 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard. 1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

ASTM D7746-21 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 79.080 - Semi-manufactures of timber. The ICS classification helps identify the subject area and facilitates finding related standards.

ASTM D7746-21 has the following relationships with other standards: It is inter standard links to ASTM E176-24, ASTM E119-19, ASTM E176-18a, ASTM E119-18c, ASTM E119-18ce1, ASTM E119-18b, ASTM E119-18a, ASTM E119-18, ASTM E176-18, ASTM E1529-16, ASTM E119-16a, ASTM E119-16, ASTM E176-15a, ASTM E176-15ae1, ASTM E119-15. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

ASTM D7746-21 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: D7746 − 21
Standard Practice for
Calculating the Superimposed Load on Wood-frame Floor-
Ceiling Assemblies for Standard Fire-Resistance Tests
This standard is issued under the fixed designation D7746; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
2.1 ASTM Standards:
1.1 This practice covers procedures for calculating the
D9Terminology Relating to Wood and Wood-Based Prod-
superimposed load required to be applied to load-bearing
ucts
wood-frame floor-ceiling assemblies throughout standard fire-
D6513Practice for Calculating the Superimposed Load on
resistance tests.
Wood-frame Walls for Standard Fire-Resistance Tests
1.2 These calculations determine the maximum superim-
E119Test Methods for Fire Tests of Building Construction
posed load to be applied to the floor-ceiling assembly during
and Materials
the fire resistance test. The maximum superimposed load,
E176Terminology of Fire Standards
calculated in accordance with nationally-recognized structural
E1529Test Methods for Determining Effects of Large Hy-
design criteria, shall be designed to induce the maximum
drocarbon Pool Fires on Structural Members and Assem-
allowablestressinthewoodfloor-ceilingfiretestconfiguration
blies
being tested.
2.2 Other Standards:
1.3 This practice is only applicable to those wood-frame
ANSI/AWCNational Design Specification (NDS) for Wood
floor-ceiling assemblies for which the nationally recognized
Construction
structural design criteria are contained in the National Design
NDS SupplementDesign Values for Wood Construction
Specification for Wood Construction (NDS).
1.4 The text of this standard references notes and footnotes
3. Terminology
whichprovideexplanatorymaterial.Thesenotesandfootnotes
3.1 Definitions—Definitions used in this practice are in
(excluding those in tables and figures) shall not be considered
accordance with Terminology D9 and Terminology E176,
as requirements of the standard.
unless otherwise indicated.
1.5 Thevaluesstatedininch-poundunitsaretoberegarded
3.2 Definitions of Terms Specific to This Standard:
asstandard.Nootherunitsofmeasurementareincludedinthis
3.2.1 gross cross-sectional area, n—section area calcu-
standard.
lated from overall actual dimensions of member.
1.6 This standard does not purport to address all of the 3.2.1.1 Discussion—For sawn lumber and glue laminated
safety concerns, if any, associated with its use. It is the
timber, gross cross-sectional area is based on the standard
responsibility of the user of this standard to establish appro- dressed size of the member as given in the NDS Supplement.
priate safety, health, and environmental practices and deter-
For I-joists and structural composite lumber, the gross cross-
mine the applicability of regulatory limitations prior to use. sectional areas or product dimensions are given in the product
1.7 This international standard was developed in accor- literature or code evaluation report.
dance with internationally recognized principles on standard-
3.2.2 net section area, n—sectionareacalculatedbydeduct-
ization established in the Decision on Principles for the
ingfromthegrosscross-sectionalareatheprojectedareaofall
Development of International Standards, Guides and Recom-
materials removed by boring, grooving, dapping, notching, or
mendations issued by the World Trade Organization Technical
other means.
Barriers to Trade (TBT) Committee.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
This practice is under the jurisdiction ofASTM Committee D07 on Wood and contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
is the direct responsibility of Subcommittee D07.05 on Wood Assemblies. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved July 1, 2021. Published August 2016. Original the ASTM website.
approvedin2011.Lastpreviouseditionapprovedin2016asD7746–11(2016).DOI: AvailablefromAmericanWoodCouncil(AWC),222CatoctinCircleSE,Suite
10.1520/D7746-21. 201, Leesburg, VA20175, http://www.awc.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
D7746 − 21
3.2.2.1 Discussion—For nailed or screwed connections, the systemwouldrequireahigherloadtobeappliedthatconsiders
net section area equals the gross cross-sectional area. the enhanced load-sharing between members provided by the
load frame and the departure from a uniform load condition.
3.2.3 span of member, n—distance from face to face of
supports, plus half of the required bearing length at each end.
NOTE 2—The intent is to simulate uniform loading conditions as
reasonably as possible within typical laboratory constraints. However,
3.2.4 superimposed load, n—additional external load
loads are commonly applied with discrete loading elements, such as dead
needed to be applied to the assembly during the test to achieve
weightpacks,waterbarrels,hydrauliccylinders,pneumaticcylinders,etc.
therequiredstresseswithintheassemblyafteranydeadloadof
An example of a system that conforms to the calculation assumption
the assembly itself is accounted for in the calculations. wouldbeoneinwhichmultiplediscreteloadelementsareprovidedalong
the floor assembly joists to approximate a uniform surface load. Load for
4. Significance and Use each discrete load element is applied to the floor joists by distribution
beams that span across not more than three adjacent floor joists. No more
4.1 Test Methods E119, E1529, and other standard fire
thantwodistributionbeamsshouldbeusedforeachdiscreteloadelement
resistance test methods specify that throughout the fire-
and the distribution beams should be centered below the load element to
ensure equal load distribution. While the barrels or tanks may be evenly
resistancetest,aconstantsuperimposedloadshallbeappliedto
spaced, the distribution beams may not be evenly spaced along the joists,
aload-bearingtestspecimentosimulateamaximumallowable
and loads on adjacent joists may need to be offset slightly along the joist
load condition. This superimposed load shall be the maximum
length to prevent interference between distribution beams. These con-
load allowed by design under nationally recognized structural
straints result in differences between the load effects from a true uniform
design criteria for the tested floor configuration (that is, joist load distribution and the load effects due to a series of point loads.Where
loading consists of a series of point loads applied to each joist, the
selection, spacing, and span).
difference in structural actions between the assumed uniform loading and
4.1.1 For this practice, the nationally recognized structural
the actual load configuration should be considered.
design criteria to be used to determine the maximum load
5.3 Lateral or torsional end support, including but not
condition are those for the allowable stress design (ASD)
limited to bridging, blocking, or bracing, shall be provided at
method in the NDS (National Design Specification for Wood
pointsofbearingtopreventrotation.Whenadditionallateralor
Construction).
torsional support is used away from the ends to enhance
NOTE 1—The NDS should be used to ensure calculation of the
performance of the floor-ceiling assembly, description and
superimposed load is in compliance with all applicable provisions of that
locations of the support shall be reported
standard.Appendix X1 describes how to calculate the superimposed load
in accordance with the NDS.
5.4 Where required to ensure that bearing capacity does not
limit the test load, stiffeners or an increased bearing length
4.1.2 Alternatively,thestandardfireresistancetestmethods
shall be permitted at the bearing locations to increase capacity.
shallbepermittedtobeconductedbyapplyingaloadlessthan
the maximum allowable load in 4.1.1 for the tested configura-
6. Design Load Calculations
tion;however,thesetestsshallbeidentifiedinthetestreportas
6.1 Design Values—-Reference design values: F , F , F ,
b v c'
being conducted under restricted loading conditions.
E and E for rectangular sections are given in the NDS
min
4.2 This practice describes procedures for calculating the
Supplement, product literature, or code evaluation report.
superimposedloadtobeappliedinstandardfireresistancetests
Reference design values: M, V, R , E, EI , and K for I-joists
r I min
of wood floor-ceiling assemblies. Practice D6513 provides a
are given in the product literature, or code evaluation report.
similar methodology for calculating the superimposed load on
6.2 Design Value Adjustments—Reference design values
wood-frame walls.
shall be multiplied by all applicable adjustment factors to
4.3 Statements in either the fire resistance test method
determine the adjusted design values. Additional adjustments,
standardorthenationallyrecognizedstructuraldesignstandard
required to address special design considerations for the
supersede any procedures described by this practice.
specific member type, shall be applied. Not all factors are
applicable to all product types.
5. Test Assumptions
6.2.1 Bending—F for rectangular sections and M for
b
5.1 Floor Assembly Structural Members—For design
I-joists shall be multiplied by all applicable NDS adjustment
considerations, wood-frame floor-ceiling assemblies consist of
factors including: C , C , C, C , C , C , C , C, C , C .
D M t L F V fu i r c
horizontalstructuralmembers(thatis,joists),thefloordecking
6.2.2 Compression parallel to the grain, F , shall be multi-
c
or sheathing, and the perimeter rim boards.
plied by all applicable NDS adjustment factors including: C ,
D
5.2 Loading Conditions—Horizontal framing members sup- C , C, C , C, and C .
M t F i P
port a vertical load that is placed on the floor assembly to 6.2.3 Shear parallel to grain—F for rectangular sections
v
approximate the effects of a uniformly distributed load on the and V for I-joists shall be multiplied by all applicable NDS
joists. Loading shall be applied to joists without relying on adjustment factors including: C , C , C, C.
D M t i
floorsheathingtodistributeload.Loadeffectsonjoistsshallbe 6.2.4 Tension parallel to grain, F, shall be multiplied by all
t
determined based on the actual load distribution. applicable NDS adjustment factors including: C , C , C, C ,
D M t F
5.2.1 The calculation procedure in this standard is not C.
i
appropriate for a test that uses a load application system that 6.2.5 Bearing:
incorporates discrete point load distribution beams or frames 6.2.5.1 Compression perpendicular-to-grain—F for rect-
c'
with spanning capabilities that serve to artificially re-distribute angular sections shall be multiplied by all applicable NDS
load from a failing member to the adjacent framing. Such a adjustment factors including: C , C, C, C .
M t i b
D7746 − 21
6.2.5.2 I-joist Reference Design Reaction—R ,shallbemul- 6.4 Test Load:
r
tipliedbyallapplicableNDSadjustmentfactorsincluding: C ,
6.4.1 Theloadtobeappliedinthetestshallbecalculatedin
D
C , C.
accordance with nationally recognized design criteria. The
M t
6.2.6
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: D7746 − 11 (Reapproved 2016) D7746 − 21
Standard Practice for
Calculating the Superimposed Load on Wood-frame Floor-
Ceiling Assemblies for Standard Fire-Resistance Tests
This standard is issued under the fixed designation D7746; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers procedures for calculating the superimposed load required to be applied to load-bearing wood-frame
floor-ceiling assemblies throughout standard fire-resistance tests.
1.2 These calculations determine the maximum superimposed load to be applied to the floor-ceiling assembly during the fire
resistance test. The maximum superimposed load, calculated in accordance with nationally-recognized structural design criteria,
shall be designed to induce the maximum allowable stress in the wood floor-ceiling fire test configuration being tested.
1.3 This practice is only applicable to those wood-frame floor-ceiling assemblies for which the nationally recognized structural
design criteria are contained in the NDS (National National Design Specification for Wood Construction).Construction (NDS).
1.4 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered as requirements of the standard.
1.5 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this
standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of
the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
This practice is under the jurisdiction of ASTM Committee D07 on Wood and is the direct responsibility of Subcommittee D07.05 on Wood Assemblies.
Current edition approved Aug. 1, 2016July 1, 2021. Published August 2016. Original approved in 2011. Last previous edition approved in 20112016 as
D7746D7746–11(2016).–11. DOI: 10.1520/D7746–11R16.10.1520/D7746-21.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
D7746 − 21
D9 Terminology Relating to Wood and Wood-Based Products
D6513 Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Resistance Tests
E119 Test Methods for Fire Tests of Building Construction and Materials
E176 Terminology of Fire Standards
E1529 Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies
2.2 Other Standards:
NDSANSI/AWC National Design Specification (NDS) for Wood Construction
NDS Supplement Design Values for Wood Construction
3. Terminology
3.1 Definitions—Definitions used in this practice are in accordance with Terminology D9 and Terminology E176, unless otherwise
indicated.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 gross cross-sectional area, n—section area calculated from overall actual dimensions of member.
3.2.1.1 Discussion—
For sawn lumber and glue laminated timber, gross cross-sectional area is based on the standard dressed size of the member as given
in the NDS Supplement. For I-joists and structural composite lumber, the gross cross-sectional areas or product dimensions are
given in the product literature or code evaluation report.
3.2.2 net section area, n—section area calculated by deducting from the gross sectioncross-sectional area the projected area of all
materials removed by boring, grooving, dapping, notching, or other means.
3.2.2.1 Discussion—
For nailed or screwed connections, the net section area equals the gross cross-sectional area.
3.2.3 span of member, n—distance from face to face of supports, plus half of the required bearing length at each end.
3.2.4 superimposed load, n—the additional external load needed to be applied to the assembly to result in the calculatedduring the
test to achieve the required stresses within the assembly whenafter any dead load of the assembly itself is accounted for in the
calculations.
4. Significance and Use
4.1 Test Methods E119, E1529, and other standard fire resistance test methods specify that throughout the fire-resistance test, a
constant superimposed load shall be applied to a load-bearing test specimen to simulate a maximum allowable load condition. This
superimposed load shall be the maximum load allowed by design under nationally recognized structural design criteria for the
tested floor configuration (that is, joist selection, spacing, and span).
4.1.1 For this Practice,practice, the nationally recognized structural design criteria to be used to determine the maximum load
condition are those for the allowable stress design (ASD) method in the NDS (National Design Specification for Wood
Construction).
NOTE 1—The NDS should be used to ensure calculation of the superimposed load is in compliance with all applicable provisions of that standard.
Appendix X1 describes how to calculate the superimposed load in accordance with the NDS.
4.1.2 Alternatively, the standard fire resistance test methods shall be permitted to be conducted by applying a load less than the
maximum allowable load in 4.1.1 for the tested configuration; however, these tests shall be identified in the test report as being
conducted under restricted loading conditions.
4.2 This practice describes procedures for calculating the superimposed load to be applied in standard fire resistance tests of wood
floor-ceiling assemblies. Practice D6513 provides a similar methodology for calculating the superimposed load on wood-frame
walls.
Available from American Wood Council (AWC), 803 Sycolin Road, 222 Catoctin Circle SE, Suite 201, Leesburg, VA 20175, http://www.awc.org.
D7746 − 21
4.3 Statements in either the fire resistance test method standard or the nationally recognized structural design standard supersede
any procedures described by this practice.
4.4 The NDS shall be reviewed to ensure calculations are in compliance with all applicable provisions of that standard.
5. Test Assumptions
5.1 Floor Assembly—Assembly Structural Members—For design considerations, wood-frame floor-ceiling assemblies consist of
horizontal structural members (that is, joists), the floor decking or sheathing, and the perimeter rim boards.
5.2 Loading Conditions—Horizontal framing members support a vertical load that is uniformly distributed placed on the floor
assembly. It is assumed that load application system for the test distributes load between and along framing members in a manner
consistent with a uniform load assumption and provides load distribution to members that is representative of the end-use
application. assembly to approximate the effects of a uniformly distributed load on the joists. Loading shall be applied to joists
without relying on floor sheathing to distribute load. Load effects on joists shall be determined based on the actual load distribution.
5.2.1 The calculation procedure in this standard is not appropriate for a test that uses a load application system that incorporates
discrete point load distribution beams or frames with spanning capabilities that serve to artificially re-distribute load from a failing
member to the adjacent framing. Such a system would require a higher load to be applied that considers the enhanced load-sharing
between members provided by the load frame and the departure from a uniform load condition.
NOTE 2—The calculation procedure in this standard is not appropriate for a test that uses a load application system that incorporates discrete point load
distribution beams or frames with spanning capabilities that serve to artificially re-distribute load from a failing member to the adjacent framing. Such
a system would require a higher load to be applied that considers the enhanced load-sharing between members provided by the load frame and the
departure from a uniform load condition. intent is to simulate uniform loading conditions as reasonably as possible within typical laboratory constraints.
However, loads are commonly applied with discrete loading elements, such as dead weight packs, water barrels, hydraulic cylinders, pneumatic cylinders,
etc. An example of a system that conforms to the calculation assumption would be one in which each discrete load element (that is, dead weight pack,
water barrel, hydraulic cylinder, pneumatic cylinder, etc.) is applied to the floor at not more than two locations along the length of the framing multiple
discrete load elements are provided along the floor assembly joists to approximate a uniform surface load. Load for each discrete load element is applied
to the floor joists by distribution beams that span across not more than three framing members. adjacent floor joists. No more than two distribution beams
should be used for each discrete load element and the distribution beams should be centered below the load element to ensure equal load distribution.
While the barrels or tanks may be evenly spaced, the distribution beams may not be evenly spaced along the joists, and loads on adjacent joists may need
to be offset slightly along the joist length to prevent interference between distribution beams. These constraints result in differences between the load
effects from a true uniform load distribution and the load effects due to a series of point loads. Where loading consists of a series of point loads applied
to each joist, the difference in structural actions between the assumed uniform loading and the actual load configuration should be considered.
5.3 Lateral or torsional end support, including but not limited to bridging, blocking, or bracing, shall be provided at points of
bearing to prevent rotation. When additional lateral or torsional support is used away from the ends to enhance performance of
the floor-ceiling assembly, description and locations of the support shall be reported
5.4 Where required to ensure that bearing capacity does not limit the test load, stiffeners or an increased bearing length shall be
permitted at the bearing locations to increase capacity.
6. Design Load Calculations
6.1 Design Values—-Reference design values: F ,F ,F ,E and E for rectangular sections are given in the NDS Supplement,
b v c' min
product literature, or code evaluation report. Reference design values: M,V,R ,E ,EI , and K for I-joists are given in the product
r I min
literature, or code evaluation report.
6.2 Design Value Adjustments—Reference design values shall be multiplied by all applicable adjustment factors to determine the
adjusted design values. Additional adjustments may be adjustments, required to address special design considerations for the
specific member type. type, shall be applied. Not all factors may be are applicable to all product types.
6.2.1 Bending—F for rectangular sections and M for I-joists shall be multiplied by all applicable NDS adjustment factors
b
including: C ,C ,C ,C ,C ,C ,C ,C ,C ,C .
D M t L F V fu i r c
6.2.2 Compression parallel to the grain, F , shall be multiplied by all applicable NDS adjustment factors including:
c
C ,C ,C ,C ,C , and C .
D M t F i P
D7746 − 21
6.2.3 Shear parallel to grain—F for rectangular sections and V for I-joists shall be multiplied by all applicable NDS adjustment
v
factors including: C ,C ,C ,C .
D M t i
6.2.4 Tension parallel to grain, F , shall be multiplied by all applicable NDS adjustment factors including: C ,C ,C ,C ,C .
t D M t F i
6.2.5 Bearing:
6.2.5.1 Compression perpendicular-to-grain—F for rectangular sections shall be multiplied by all applicable NDS adjustment
c'
factors including: C ,C ,C ,C .
M t i b
6.2.5.2 I-joist Reference Design Reaction—R , shall be multiplied by all applicable NDS adjustment factors including: C ,C ,C .
r D M t
6.2.6 Modulus of elasticity—E or E for rectangular sections and E and EI for I-joists shall be multiplied by all applicable
min I min
NDS adjustment factors including: C ,C ,C ,C .
M t i T
6.3 Adjustment Factors for Design Values—The following adjustment factors are to be assumed by default. If values less than
those listed below are employed, then the appropriate load restriction shall be reported in the test report and used to adjust the
design bending and shear capacity in application:
6.3.1 Load duration factor, C , is 1.0.
D
6.3.2 Wet service factor, C , is 1.0.
M
NOTE 3—The results of testing with load determined based on C =1.0 can be conservatively applied for floors used in wet-service conditions. Where
M
test results are limited to floors used in wet-service conditions, a reduced load consistent with the application of the wet service factor is appropriate. For
both cases, joists are tested in the dry condition, because in-service moisture conditions for wood designed for wet service typically vary significantly
ranging from dry to wet depending on the season and application.
6.3.3 Temperature factor, C , is 1.0.
t
NOTE 4—The results of testing with load determined based on C =1.0 may be conservatively applied for floors used in elevated temperature conditions.
t
6.3.4 Beam stability factor, C , is 1.0 for a single span, sheathed fire test assembly.
L
6.3.5 Size factor, C , is the value taken from tables in the NDS Supplement for the sawn lumber joist material in the test assembly.
F
6.3.6 Volume factor, C , the value pe
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...