ASTM F2873-20
(Practice)Standard Practice for the Installation of Self-Leveling Underlayment and the Preparation of Surface to Receive Resilient Flooring
Standard Practice for the Installation of Self-Leveling Underlayment and the Preparation of Surface to Receive Resilient Flooring
SIGNIFICANCE AND USE
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence.
SCOPE
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...
General Information
- Status
- Published
- Publication Date
- 30-Apr-2020
- Technical Committee
- F06 - Resilient Floor Coverings
- Drafting Committee
- F06.40 - Practices
Relations
- Effective Date
- 01-May-2020
- Effective Date
- 01-Apr-2024
- Effective Date
- 01-Aug-2023
- Effective Date
- 01-Aug-2020
- Effective Date
- 01-Apr-2020
- Effective Date
- 15-Jan-2020
- Effective Date
- 01-Dec-2019
- Effective Date
- 15-Nov-2019
- Effective Date
- 01-Jun-2019
- Effective Date
- 01-Mar-2019
- Effective Date
- 01-Feb-2019
- Effective Date
- 01-Jan-2018
- Effective Date
- 01-Sep-2017
- Effective Date
- 01-Sep-2017
- Effective Date
- 01-Dec-2016
Overview
ASTM F2873-20 is a standard practice developed by ASTM International that outlines the minimum recommendations for the installation of self-leveling underlayments and the preparation of surfaces to receive resilient flooring. This standard addresses the proper preparation of subfloors, the installation of self-leveling underlayment materials, and quality control requirements. It applies to a wide range of subfloor types, including concrete, solid wood, wood structural panels, ceramic and natural stone tiles, terrazzo, epoxy floors, metal subfloors, foils, and certain adhesive residues, as specified by the underlayment manufacturer.
This standard is critical for ensuring that resilient floor coverings-such as vinyl, linoleum, and rubber flooring-are installed over a stable, level, and appropriately prepared substrate, supporting optimal performance and longevity.
Key Topics
- Surface Preparation: Guidelines for cleaning, leveling, and priming various subfloor types (e.g., concrete, wood, metal, tiles) before installing self-leveling underlayments.
- Installation Methods: Recommendations for mixing, pouring, pumping, and drying self-leveling underlayments per manufacturer and project specifications.
- Quality Control: Minimum requirements for compressive strength, density, and testing procedures to ensure consistent product performance.
- Moisture Control: Precautions and requirements regarding moisture vapor emission rates and the use of vapor retarders or barriers where necessary.
- Compatibility and Limitations: Clarification that project specifications, building codes, and manufacturer instructions take precedence where they differ from this standard.
- Environmental, Safety, and Health Considerations: Guidance on managing potential hazards such as asbestos, lead, and silica in existing flooring and adhesives, highlighting the importance of regulatory compliance and appropriate work practices.
- Final Surface Preparation: Ensuring the underlayment surface is clean, smooth, and ready for direct installation of resilient flooring to achieve best results.
Applications
The ASTM F2873-20 standard is widely used in the commercial, residential, and institutional construction sectors for installing resilient flooring systems in environments such as:
- Office buildings
- Healthcare facilities
- Educational institutions
- Retail spaces
- Residential developments
Key benefits and applications include:
- Providing a flat, smooth, and durable substrate for resilient flooring products, essential for high-traffic and demanding environments.
- Enhancing moisture resistance, particularly over on-grade or below-grade concrete slabs with appropriate vapor barriers.
- Supporting quality assurance by establishing consistent installation and preparation practices across project teams and job sites.
- Reducing flooring failures by ensuring compatibility between the substrate, the self-leveling underlayment, and the resilient flooring.
- Ensuring compliance with safety and environmental regulations regarding hazardous materials in existing floors and adhesives.
Related Standards
The proper application of ASTM F2873-20 often involves compliance with or reference to other essential ASTM standards and regulatory documents, including:
- ASTM F710: Practice for Preparing Concrete Floors to Receive Resilient Flooring
- ASTM F1482: Practice for Installation and Preparation of Panel Type Underlayments
- ASTM C1708: Test Methods for Self-Leveling Mortars Containing Hydraulic Cements
- ASTM C109/C109M: Test Method for Compressive Strength of Hydraulic Cement Mortars
- ASTM F1869 / F2170: Test Methods for Measuring Moisture in Concrete Slabs
- OSHA 29 CFR 1926.1153: Respirable Crystalline Silica Standard
By adhering to the guidelines in ASTM F2873-20 and the related standards, contractors and flooring professionals can ensure durable, resilient floor installations that meet both project and regulatory requirements.
Buy Documents
ASTM F2873-20 - Standard Practice for the Installation of Self-Leveling Underlayment and the Preparation of Surface to Receive Resilient Flooring
REDLINE ASTM F2873-20 - Standard Practice for the Installation of Self-Leveling Underlayment and the Preparation of Surface to Receive Resilient Flooring
Get Certified
Connect with accredited certification bodies for this standard

Smithers Quality Assessments
US management systems and product certification.
DIN CERTCO
DIN Group product certification.
Sponsored listings
Frequently Asked Questions
ASTM F2873-20 is a standard published by ASTM International. Its full title is "Standard Practice for the Installation of Self-Leveling Underlayment and the Preparation of Surface to Receive Resilient Flooring". This standard covers: SIGNIFICANCE AND USE 4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings. 4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence. SCOPE 1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring. 1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring. 1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements. 1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations. 1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations. 1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2 1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...
SIGNIFICANCE AND USE 4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling underlayment’s surface prior to the installation of floor coverings. 4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall take precedence. SCOPE 1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood, wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors, ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of resilient flooring. 1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used as a substrate for resilient flooring. 1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by local building codes and may be superseded by the resilient flooring manufacturer's and the self-leveling underlayment manufacturer’s requirements. 1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations. 1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer of the self-leveling underlayment and flooring system for specific recommendations. 1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials. Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on Preventive and Control Measures.”2 1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standar...
ASTM F2873-20 is classified under the following ICS (International Classification for Standards) categories: 83.080.10 - Thermosetting materials. The ICS classification helps identify the subject area and facilitates finding related standards.
ASTM F2873-20 has the following relationships with other standards: It is inter standard links to ASTM F2873-19, ASTM C219-24, ASTM F141-23, ASTM C219-20a, ASTM C219-20, ASTM F141-12(2020), ASTM F2170-19a, ASTM C219-19a, ASTM C219-19, ASTM F2170-19, ASTM F710-19, ASTM F2170-18, ASTM F2170-17, ASTM F710-17, ASTM F2170-16b. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ASTM F2873-20 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: F2873 − 20
Standard Practice for
the Installation of Self-Leveling Underlayment and the
Preparation of Surface to Receive Resilient Flooring
This standard is issued under the fixed designation F2873; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 1.6 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical
1.1 This practice covers the installation of self-leveling
conversions to SI units that are provided for information only
underlayments, which may include a priming system, over
and are not considered standard.
solidwood,woodstructuralpanelsubfloors,overconcrete,and
over certain solidly bonded existing flooring systems such as 1.7 This practice does purport to address the necessity for or
epoxy floors, ceramic and natural stone tiles, terrazzo, metal the safe or correct removal of asbestos containing materials.
subfloors and foils such as steel, copper and lead, solidly Breathing of asbestos dust is hazardous.Asbestos and asbestos
bonded patching and other leveling materials as well as products present demonstrated health risks for users and for
properly prepared non water-soluble adhesive residues as those with whom they come into contact. In addition to other
recommendedbytheunderlaymentmanufacturer.Thispractice precautions, when working with asbestos-cement products,
also covers the preparation of the self-leveling underlayment’s minimize the dust that results. For information on the safe use
surface prior to the installation of resilient flooring. of chrysoltile asbestos, refer to “Safe Use of Chrysotile
Asbestos: A Manual on Preventive and Control Measures.”
1.2 This practice points out the factors that are required to
1.8 This standard does not purport to address all of the
be controlled while installing a self-leveling underlayment to
safety concerns, if any, associated with its use. It is the
be used as a substrate for resilient flooring.
responsibility of the user of this standard to establish appro-
1.3 This practice does not cover the structural adequacy of
priate safety, health, and environmental practices and deter-
the subfloor. The structural integrity of assemblies is governed
mine the applicability of regulatory limitations prior to use.
by local building codes and may be superseded by the resilient
1.9 This international standard was developed in accor-
flooring manufacturer’s and the self-leveling underlayment
dance with internationally recognized principles on standard-
manufacturer’s requirements.
ization established in the Decision on Principles for the
1.4 This practice does not supersede the self-leveling un-
Development of International Standards, Guides and Recom-
derlayment manufacturer’s, adhesive manufacturer’s or resil-
mendations issued by the World Trade Organization Technical
ient flooring manufacturer’s written instructions. Consult the
Barriers to Trade (TBT) Committee.
individual manufacturer for specific recommendations.
2. Referenced Documents
1.5 Some self-leveling underlayments are not suitable for
use on concrete slabs on or below grade due to potential
2.1 ASTM Standards:
moisture problems arising from moisture intrusion. However,
C219 Terminology Relating to Hydraulic and Other Inor-
mostoftheself-levelingunderlaymentsmaybesuitableforuse
ganic Cements
on and below grade if an adequate and effective vapor retarder
C1583 Test Method for Tensile Strength of Concrete Sur-
or vapor barrier is present directly beneath the concrete slab or
faces and the Bond Strength or Tensile Strength of
an effective moisture remediation system has been installed
Concrete Repair and Overlay Materials by Direct Tension
beneath the surface of the self-leveling underlayment. Consult
(Pull-off Method)
the manufacturer of the self-leveling underlayment and floor-
C1708 Test Methods for Self-leveling Mortars Containing
ing system for specific recommendations.
Hydraulic Cements
F141 Terminology Relating to Resilient Floor Coverings
This practice is under the jurisdiction of ASTM Committee F06 on Resilient
Floor Coverings and is the direct responsibility of Subcommittee F06.40 on Available from http://www.chrysotile.com
Practices. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved May 1, 2020. Published June 2020. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 2013. Last previous edition approved in 2019 as F2873-19. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/F2873-20. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2873 − 20
F710 Practice for Preparing Concrete Floors to Receive 4.2 Actual requirements for self-leveling underlayments are
Resilient Flooring generally included as part of project plans or specifications and
F1869 Test Method for Measuring Moisture Vapor Emission may vary from the recommendations set forth in this practice.
Rate of Concrete Subfloor Using Anhydrous Calcium Provisions in the project documents at variance with this
Chloride practice shall take precedence.
F2170 Test Method for Determining Relative Humidity in
5. Product Requirements
Concrete Floor Slabs Using in situ Probes
F1482 Practice for Installation and Preparation of Panel
5.1 For the purpose of this practice, self-leveling underlay-
Type Underlayments to Receive Resilient Flooring
mentshallbehydrauliccementbasedcompounds,asdefinedin
C109/C109M Test Method for Compressive Strength of
3.2.4 in accordance with Terminology C219.
Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube
5.2 Self-levelingunderlaymentsshallbetestedforcompres-
Specimens)
sive strength in accordance with Test Method C109/C109M
2.2 OSHA Standard
modified (air-cured only as detailed in Test Methods C1708).
29 CFR OSHA §1926.1153 Respirable crystalline silica
Specified psi at 28 days shall be a minimum of 3000 psi (20.7
MPa) or as specified by the floor covering manufacturer.
3. Terminology
3.1 Definitions used in this practice shall be in accordance
6. Storage and Handling of Self-Leveling Underlayments
with Terminology F141.
6.1 Self-leveling underlayments included in this practice
3.2 Definitions of Terms Specific to This Standard:
shall be delivered to the jobsites in original, unopened,
3.2.1 fully adhered flooring, n—resilient flooring which has
undamaged bags with identification labels intact. Bags and the
adhesive under the entire product, bonding it to the underlay-
enclosed material should not be damaged and shall be pro-
ment surface.
tected from the elements after delivery to the jobsite.
3.2.2 non-fully adhered flooring, n—resilient flooring that
6.2 All products shall be kept off the ground and protected
may be loose laid, in which no adhesive is utilized, or partially
from moisture and excessive heat or cold in accordance with
bonded to the surface of the underlayment, typically at seams
the manufacturer’s recommendations.
and the surrounding perimeter of the product.
3.2.3 self-leveling underlayment system, n—a non-
7. General Guidelines
structural, hydraulic cement-based, poured mortar composed
7.1 The subfloor shall support design loads as required by
primarily of hydraulic cements, fillers or fine aggregate, and
the prevailing building code but no greater than L/360. Use the
water, which may require the use of a primer to enhance bond
strictest criteria applicable.
strength and inhibit pin hole development, and which is
7.2 Subfloors shall be structurally sound and dimensionally
intended to provide a flat, smooth surface for the finished floor
stable so as to support both the uniform design live and dead
covering.
loads in compliance with the local building code and the
3.2.4 subfloor, n—a structurally sound layer intended to
self-levelingunderlaymentmanufactureraswellastheresilient
provide support for design loads, which may receive resilient
flooring manufacturer’s installation requirements.
floor coverings directly if the surface is suitable to the flooring
7.3 Concrete subfloors shall be as described in Practice
manufacturer.
F710, or meet the requirements of the manufacturer of the
3.2.5 wood structural panel, n—a panel manufactured from
self-leveling underlayment and the manufacturer of the resil-
veneers, or wood strands or wafers, or a combination of veneer
ient floor covering, or both.
and wood strands, or wafers, bonded together with waterproof
7.3.1 Some self-leveling underlayments are recommended
synthetic resins or other suitable, waterproof bonding systems
by their manufacturers for use over concrete that is less than 28
such that they are considered to be Type 1 for exterior
days old and may be part of a moisture remediation system.
exposure. Lauaun plywood is not recommended to receive
7.3.1.1 The suitability of such materials to receive resilient
self-leveling underlayments represented in this practice.
floor coverings remains the sole responsibility of the self-
leveling manufacturer.
4. Significance and Use
7.3.2 Wood subfloors shall be installed and prepared in
4.1 This practice provides minimum recommendations for
accordance with Practice F1482.
the installation of self-leveling underlayments suitable to
7.4 TheHVACsystemshallbeoperationalfortheminimum
receive resilient floor coverings. This practice establishes the
specified time period recommended in the moisture test(s)
properpreparationofthesubfloor,andinstallationmethodsand
being performed prior to test commencement and shall remain
quality control requirements for self-leveling underlayments.
on throughout the test to ensure accurate moisture testing.
This practice addresses any necessary preparation of the
Otherwise, condition a test area to “in service condition”
self-leveling underlayment’s surface prior to the installation of
before testing.
floor coverings.
7.5 Concrete subfloors that exceed the floor covering manu-
facturer’s requirements for moisture in 7.4 shall either be made
Available from Occupational Safety and Health Administration (OSHA), 200
Constitution Ave., NW, Washington, DC 20210, http://www.osha.gov. to dry out until the moisture requirements are within the
F2873 − 20
flooring manufacturer’s limits or shall be remediated using bonding of the self-leveling underlayment to the concrete
products that are suitable to receive underlayments represented subfloor, mechanical profiling may be recommended. Consult
in this practice. the manufacturer of self-leveling underlayment for specific
requirements. All warnings shall be adhered to in accordance
7.6 Forty eight hours before, during and 72 h after installa-
with Practice F710. (Refer to Supplemental Requirements
tionoftheself-levelingunderlaymentiscompleted,thegeneral
Section S1.) Steel troweled concrete, concrete sealed with
contractor shall be responsible for ensuring that the building
curing compounds and any substance that could reduce and
and substrate shall be ventilated and heated to a minimum of
prevent adhesion shall mechanically removed by shot blasting,
50°F (10°C) and a maximum of 90°F (32.2°C) and with a
grinding or using similar mechanical means. The surface
maximumrelativehumidityof60%untilsubfloorandambient
removal must be sufficient to eliminate penetrated contami-
conditions have stabilized. Consult the manufacturer of the
nants. Acid washing or etching and the use of sweeping
self-leveling underlayment for specific recommendations.
compounds and solvent adhesive removers shall not be an
7.7 Installation of the self-leveling underlayment shall not
acceptable surface preparation method.
begin until the building is enclosed, including roof, windows,
8.2.1 Some self-leveling underlayments are suitable for use
doors and other openings, unless the underlayment being
over steel trowled concrete as well as non-dissipating acrylic
installed is totally water resistant, or is otherwise unaffected by
resin curing compounds. Consult the manufacturer of the
casual water. It is recommended that all overhead work be
self-leveling underlayment for specific recommendations.
completed prior to underlayment installation, to minimize
Wax- or petroleum-based curing compounds are bond breakers
surface damage.
and must be mechanically removed. Dissipating curing com-
7.8 Before installation of self-leveling underlayment, the pounds must also be completely mechanically removed.
conditionofthestructuralsubfloorassembliesandanyrequired
8.2.2 Some self-leveling underlayments are suitable for use
elevations shall be inspected and approved by the general
over concrete subfloors treated with silicates or silicas. Consult
contractor or owner, or both, as being suitable to receive the
the manufacturer of the self-leveling underlayment for specific
self-leveling underlayment to meet the flooring manufacturer’s
recommendations.
requirements.
8.3 The surfaces of other substrates shall be clean and free
7.9 Self-leveling underlayment installation shall be per-
of any contaminants that may reduce performance or act as a
formed by an applicator trained to do this type of installation
bond breaker. All ceramic and stone tiles shall be solidly
by the manufacturer of the self-leveling underlayment system,
adhered. Remove all loose tiles. All ceram
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: F2873 − 19 F2873 − 20
Standard Practice for
the Installation of Self-Leveling Underlayment and the
Preparation of Surface to Receive Resilient Flooring
This standard is issued under the fixed designation F2873; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the installation of self-leveling underlayments, which may include a priming system, over solid wood,
wood structural panel subfloors, over concrete, and over certain solidly bonded existing flooring systems such as epoxy floors,
ceramic and natural stone tiles, terrazzo, metal subfloors and foils such as steel, copper and lead, solidly bonded patching and other
leveling materials as well as properly prepared non water-soluble adhesive residues as recommended by the underlayment
manufacturer. This practice also covers the preparation of the self-leveling underlayment’s surface prior to the installation of
resilient flooring.
1.2 This practice points out the factors that are required to be controlled while installing a self-leveling underlayment to be used
as a substrate for resilient flooring.
1.3 This practice does not cover the structural adequacy of the subfloor. The structural integrity of assemblies is governed by
local building codes and may be superseded by the resilient flooring manufacturer’s and the self-leveling underlayment
manufacturer’s requirements.
1.4 This practice does not supersede the self-leveling underlayment manufacturer’s, adhesive manufacturer’s or resilient
flooring manufacturer’s written instructions. Consult the individual manufacturer for specific recommendations.
1.5 Some self-leveling underlayments are not suitable for use on concrete slabs on or below grade due to potential moisture
problems arising from moisture intrusion. However, most of the self-leveling underlayments may be suitable for use on and below
grade if an adequate and effective vapor retarder or vapor barrier is present directly beneath the concrete slab or an effective
moisture remediation system has been installed beneath the surface of the self-leveling underlayment. Consult the manufacturer
of the self-leveling underlayment and flooring system for specific recommendations.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.7 This practice does purport to address the necessity for or the safe or correct removal of asbestos containing materials.
Breathing of asbestos dust is hazardous. Asbestos and asbestos products present demonstrated health risks for users and for those
with whom they come into contact. In addition to other precautions, when working with asbestos-cement products, minimize the
dust that results. For information on the safe use of chrysoltile asbestos, refer to “Safe Use of Chrysotile Asbestos: A Manual on
Preventive and Control Measures.”
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
This practice is under the jurisdiction of ASTM Committee F06 on Resilient Floor Coverings and is the direct responsibility of Subcommittee F06.40 on Practices.
Current edition approved Dec. 1, 2019May 1, 2020. Published March 2019June 2020. Originally approved in 2013. Last previous edition approved in 20182019 as
F2873-18.F2873-19. DOI: 10.1520/F2873-19.10.1520/F2873-20.
Available from http://www.chrysotile.com
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F2873 − 20
2. Referenced Documents
2.1 ASTM Standards:
C219 Terminology Relating to Hydraulic and Other Inorganic Cements
C1583 Test Method for Tensile Strength of Concrete Surfaces and the Bond Strength or Tensile Strength of Concrete Repair and
Overlay Materials by Direct Tension (Pull-off Method)
C1708 Test Methods for Self-leveling Mortars Containing Hydraulic Cements
F141 Terminology Relating to Resilient Floor Coverings
F710 Practice for Preparing Concrete Floors to Receive Resilient Flooring
F1869 Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
F2170 Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
F1482 Practice for Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
C109/C109M Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
2.2 OSHA Standard
29 CFR OSHA §1926.1153 Respirable crystalline silica
3. Terminology
3.1 Definitions used in this practice shall be in accordance with Terminology F141.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 fully adhered flooring, n—resilient flooring which has adhesive under the entire product, bonding it to the underlayment
surface.
3.2.2 non-fully adhered flooring, n—resilient flooring that may be loose laid, in which no adhesive is utilized, or partially
bonded to the surface of the underlayment, typically at seams and the surrounding perimeter of the product.
3.2.3 self-leveling underlayment system, n—a non-structural, hydraulic cement-based, poured mortar composed primarily of
hydraulic cements, fillers or fine aggregate, and water, which may require the use of a primer to enhance bond strength and inhibit
pin hole development, and which is intended to provide a flat, smooth surface for the finished floor covering.
3.2.4 subfloor, n—a structurally sound layer intended to provide support for design loads, which may receive resilient floor
coverings directly if the surface is suitable to the flooring manufacturer.
3.2.5 wood structural panel, n—a panel manufactured from veneers, or wood strands or wafers, or a combination of veneer and
wood strands, or wafers, bonded together with waterproof synthetic resins or other suitable, waterproof bonding systems such that
they are considered to be Type 1 for exterior exposure. Lauaun plywood is not recommended to receive self-leveling
underlayments represented in this practice.
4. Significance and Use
4.1 This practice provides minimum recommendations for the installation of self-leveling underlayments suitable to receive
resilient floor coverings. This practice establishes the proper preparation of the subfloor, and installation methods and quality
control requirements for self-leveling underlayments. This practice addresses any necessary preparation of the self-leveling
underlayment’s surface prior to the installation of floor coverings.
4.2 Actual requirements for self-leveling underlayments are generally included as part of project plans or specifications and may
vary from the recommendations set forth in this practice. Provisions in the project documents at variance with this practice shall
take precedence.
5. Product Requirements
5.1 For the purpose of this practice, self-leveling underlayment shall be hydraulic cement based compounds, as defined in 3.2.4
in accordance with Terminology C219.
5.2 Self-leveling underlayments shall be tested for compressive strength in accordance with Test Method C109/C109M
modified (air-cured only as detailed in Test Methods C1708). Specified psi at 28 days shall be a minimum of 3000 psi (20.7
MPa).MPa) or as specified by the floor covering manufacturer.
6. Storage and Handling of Self-Leveling Underlayments
6.1 Self-leveling underlayments included in this practice shall be delivered to the jobsites in original, unopened, undamaged
bags with identification labels intact. Bags and the enclosed material should not be damaged and shall be protected from the
elements after delivery to the jobsite.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Available from Occupational Safety and Health Administration (OSHA), 200 Constitution Ave., NW, Washington, DC 20210, http://www.osha.gov.
F2873 − 20
6.2 All products shall be kept off the ground and protected from moisture and excessive heat or cold in accordance with the
manufacturer’s recommendations.
7. General Guidelines
7.1 The subfloor shall support design loads as required by the prevailing building code but no greater than L/360. Use the
strictest criteria applicable.
7.2 Subfloors shall be structurally sound and dimensionally stable so as to support both the uniform design live and dead loads
in compliance with the local building code and the self-leveling underlayment manufacturer as well as the resilient flooring
manufacturer’s installation requirements.
7.3 Concrete subfloors shall be as described in Practice F710, or meet the requirements of the manufacturer of the self-leveling
underlayment and the manufacturer of the resilient floor covering, or both.
7.3.1 Some self-leveling underlayments are recommended by their manufacturers for use over concrete that is less than 28 days
old and may be part of a moisture remediation system.
7.3.1.1 The suitability of such materials to receive resilient floor coverings remains the sole responsibility of the self-leveling
manufacturer.
7.3.2 Wood subfloors shall be installed and prepared in accordance with Practice F1482.
7.4 The HVAC system shall be operational for the minimum specified time period recommended in the moisture test(s) being
performed prior to test commencement and shall remain on throughout the test to ensure accurate moisture testing. Otherwise,
condition a test area to “in service condition” before testing.
7.5 Concrete subfloors that exceed the floor covering manufacturer’s requirements for moisture in 7.4 shall either be made to
dry out until the moisture requirements are within the flooring manufacturer’s limits or shall be remediated using products that are
suitable to receive underlayments represented in this practice.
7.6 Forty eight hours before, during and 72 h after installation of the self-leveling underlayment is completed, the general
contractor shall be responsible for ensuring that the building and substrate shall be ventilated and heated to a minimum of 50°F
(10°C) and a maximum of 90°F (32.2°C) and with a maximum relative humidity of 60 % until subfloor and ambient conditions
have stabilized. Consult the manufacturer of the self-leveling underlayment for specific recommendations.
7.7 Installation of the self-leveling underlayment shall not begin until the building is enclosed, including roof, windows, doors
and other openings, unless the underlayment being installed is totally water resistant, or is otherwise unaffected by casual water.
It is recommended that all overhead work be completed prior to underlayment installation, to minimize surface damage.
7.8 Before installation of self-leveling underlayment, the condition of the structural subfloor assemblies and any required
elevations shall be inspected and approved by the general contractor or owner, or both, as being suitable to receive the self-leveling
underlayment to meet the flooring manufacturer’s requirements.
7.9 Self-leveling underlayment installation shall be performed by an applicator trained to do this type of installation by the
manufacturer of the self-leveling underlayment system, or one that can verify experience in performing the work of this practice.
7.10 The general contractor shall protect the self-leveling underlayment, once installed, from drafts, direct sunlight, excessive
heat, and direct exposure construction and trade traffic.
7.10.1 Failure to adequately protect the surface of the self-leveling underlayment from the above conditions will result in a need
for additional surface preparation on the self-leveling underlayment prior to installation of the resilient flooring.
8. Preparation of Subfloor/Underlayment Panels
8.1 The wood subfloor shall be of solid wood or structural wood panel construction installed in accordance with Practice F1482,
clean, permanently dry, and free of any oil, grease, dirt, and other contaminating substances that could affect the performance or
act as a bond breaker. Loose boards shall be mechanically fastened. Badly cupped or warped board subfloors shall be replaced
before installation of underlayment. Any loose sections shall be fastened and any weak or delaminated sections shall be removed
and replaced.
8.2 The surfaces of the concrete structural subfloor shall be dry, clean, and free of construction wastes such as acoustic and wall
texture, dry wall compound, paint, dirt, laitance, solvents, oil, grease, loosely bonded toppings, dust, tar, wax, residual adhesives,
adhesive removers, curing and sealing compounds and other foreign materials as recommended by the manufacturer of the
self-leveling underlayment. To ensure maximum bondi
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...