Fire resistance tests for non-loadbearing elements - Part 6: Cavity Barriers

This test method specifies a method for determining the fire resistance of cavity barriers and is to be used in conjunction with EN 1363 1.
This standard is applicable to non-loadbearing vertically or horizontally oriented closed and open cavity barriers, which are used to provide fire separation to uncompartmented or ventilated spaces. Cavity barriers are designed to provide fire separating performance and the test method is therefore based on the standard room fire exposure in EN 1363 1. Open cavity barrier specimens are installed for test in one of two ways to simulate slow or sudden exposure in use.
This standard is not applicable to cavity barriers containing penetration seals, which are to be tested in accordance with EN 1366 3.

Feuerwiderstandsprüfungen für nichttragende Bauteile - Teil 6: Hohlraum-Brandsperren

Dieses Prüfverfahren legt ein Verfahren zur Bestimmung des Feuerwiderstands von Hohlraum-Brandsperren fest und ist in Kombination mit EN 1363-1 anzuwenden.
Diese Norm ist anwendbar auf nichttragende vertikal- oder horizontalausgerichtete geschlossene und offene Hohlraum-Brandsperren, die als Brandsperre in nicht unterteilten oder belüfteten Räumen zum Einsatz kommen. Hohlraum-Brandsperren sind darauf ausgelegt, den Brandübertritt zu verhindern, und das Prüfverfahren basiert daher auf den genormten Beflammungsbedingungen für Räume nach EN 1363-1. Es werden Probekörper von offenen Hohlraum-Brandsperren zur Prüfung in einer von zwei möglichen Konfigurationen installiert, um eine langsame oder plötzliche Einwirkung zu simulieren.
Diese Norm gilt nicht für Hohlraum-Brandsperren mit Abschottungen, die nach EN 1366-3 zu prüfen sind.

Essais de résistance au feu des éléments non porteurs - Partie 6 : Dispositifs de recoupement de lame d'air

La présente méthode d'essai spécifie une méthode permettant de déterminer la résistance au feu des dispositifs de recoupement de lame d’air et doit être utilisée conjointement avec l'EN 1363-1.
La présente norme s'applique aux dispositifs de recoupement de lame d’air non porteurs, fermés et ouverts, orientés verticalement ou horizontalement, qui sont utilisés pour assurer le cloisonnement coupe-feu d'espaces non compartimentés ou ventilés. Les dispositifs de recoupement de lame d’air sont conçus pour offrir des performances de cloisonnement coupe-feu et la méthode d'essai est donc fondée sur l'exposition au feu d'une pièce normalisée selon l'EN 1363-1. Les éléments d'essai de dispositif de recoupement de lame d’air ouvert sont installés en vue de l'essai de manière à simuler une exposition lente ou une exposition soudaine en service.
La présente norme ne s'applique pas aux dispositifs de recoupement de lame d’air contenant des calfeutrements de trémies qui doivent être soumis à essai conformément à l'EN 1366-3.

Preskusi požarne odpornosti nenosilnih elementov - 6. del: Zapore votlih prostorov

General Information

Status
Not Published
Public Enquiry End Date
13-Jul-2016
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
16-Jan-2018
Due Date
21-Jan-2018
Completion Date
16-Jan-2018

Overview

prEN 1364-6 - "Fire resistance tests for non-loadbearing elements - Part 6: Cavity Barriers" (CEN) specifies a laboratory test method to determine the fire resistance of cavity barriers used in concealed building voids. The method is intended to be used in conjunction with EN 1363-1 (standard room fire exposure). It covers both closed and open cavity barriers installed vertically or horizontally in roof voids, under raised access floors, between wall leaves, ventilated façades and similar uncompartmented or ventilated spaces. Results are expressed as the time for which the applicable performance criteria (integrity, insulation where relevant) are met.

Key topics and requirements

  • Scope and applicability: Non-loadbearing cavity barriers (closed and open). Not applicable to cavity barriers containing penetration seals (these fall under EN 1366-3).
  • Reference fire exposure: Tests are based on the standard room fire exposure in EN 1363-1; closed barriers follow the small-room/ISO 834-1 reference scenario described in the standard.
  • Open vs closed barriers: Open cavity barrier specimens are tested to simulate either slow or sudden exposure in-use (two installation/test configurations). Annexes detail specific configurations for walls, underfloor voids and open cavity barriers.
  • Test setup and instrumentation: Requirements for furnace control, thermocouples (furnace and unexposed surface), pressure monitoring, deflection measurement and observations during the test are specified.
  • Performance criteria: Integrity and, where appropriate, insulation are evaluated according to EN 1363-1 criteria. Tests may be terminated or assessed per those criteria.
  • Field of direct application: Guidance on extension of tested dimensions (width/height) and supporting construction limits is provided in the normative annexes.
  • Supporting documents: The method draws on EOTA TR31 and supports ETAG 026-5 for cavity barriers.

Applications and who uses it

  • Manufacturers of cavity barrier products seeking third‑party fire performance data.
  • Independent fire test laboratories performing fire resistance tests on non‑loadbearing elements.
  • Façade engineers, fire safety consultants and specifiers assessing cavity barrier selection for ventilated façades, rainscreens, roof eaves, underfloor voids and timber-framed wall cavities.
  • Building control authorities and certification bodies requiring standardized test evidence for compliance and product approvals.

Related standards

  • EN 1363-1 (fire resistance tests - general requirements / standard fire exposure)
  • EN 1366-3 (fire stopping - penetration seals)
  • EOTA TR31 (reference for closed cavity barrier testing)
  • ETAG 026-5 (service life and guidance for cavity barrier systems)
  • ISO 834-1 (reference small-room fire curve referenced for closed barriers)

Keywords: prEN 1364-6, cavity barriers, fire resistance tests, EN 1363-1, non-loadbearing elements, ventilated façade, underfloor void, raised access floor, fire stopping.

Draft
oSIST prEN 1364-6:2016
English language
30 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Frequently Asked Questions

oSIST prEN 1364-6:2016 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire resistance tests for non-loadbearing elements - Part 6: Cavity Barriers". This standard covers: This test method specifies a method for determining the fire resistance of cavity barriers and is to be used in conjunction with EN 1363 1. This standard is applicable to non-loadbearing vertically or horizontally oriented closed and open cavity barriers, which are used to provide fire separation to uncompartmented or ventilated spaces. Cavity barriers are designed to provide fire separating performance and the test method is therefore based on the standard room fire exposure in EN 1363 1. Open cavity barrier specimens are installed for test in one of two ways to simulate slow or sudden exposure in use. This standard is not applicable to cavity barriers containing penetration seals, which are to be tested in accordance with EN 1366 3.

This test method specifies a method for determining the fire resistance of cavity barriers and is to be used in conjunction with EN 1363 1. This standard is applicable to non-loadbearing vertically or horizontally oriented closed and open cavity barriers, which are used to provide fire separation to uncompartmented or ventilated spaces. Cavity barriers are designed to provide fire separating performance and the test method is therefore based on the standard room fire exposure in EN 1363 1. Open cavity barrier specimens are installed for test in one of two ways to simulate slow or sudden exposure in use. This standard is not applicable to cavity barriers containing penetration seals, which are to be tested in accordance with EN 1366 3.

oSIST prEN 1364-6:2016 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 91.060.99 - Other elements of buildings. The ICS classification helps identify the subject area and facilitates finding related standards.

oSIST prEN 1364-6:2016 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase oSIST prEN 1364-6:2016 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-julij-2016
Preskusi požarne odpornosti nenosilnih elementov - 6. del: Zapore votlih
prostorov
Fire resistance tests for non-loadbearing elements - Part 6: Cavity Barriers
Feuerwiderstandsprüfungen für nichttragende Bauteile - Teil 6: Hohlraum-Brandsperren
Essais de résistance au feu des éléments non porteurs - Partie 6 : Dispositifs de
recoupement de lame d'air
Ta slovenski standard je istoveten z: prEN 1364-6
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.99 Drugi stavbni elementi Other elements of buildings
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

DRAFT
EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2016
ICS 13.220.50; 91.060.99
English Version
Fire resistance tests for non-loadbearing elements - Part 6:
Cavity Barriers
Essais de résistance au feu des éléments non porteurs - Feuerwiderstandsprüfungen für nichttragende
Partie 6 : Dispositifs de recoupement de lame d'air Bauteile - Teil 6: Hohlraum-Brandsperren
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 127.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1364-6:2016 E
worldwide for CEN national Members.

Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 Test equipment — Additional requirements for open cavity barriers . 7
5 Test conditions . 7
5.1 Heating conditions . 7
5.2 Pressure conditions . 7
5.2.1 General . 7
5.2.2 Cavity Barriers mounted within leaves of walls or in roof voids . 7
5.2.3 Cavity barriers mounted underneath raised access floors . 7
5.2.4 Open cavity barriers . 8
6 Test specimen . 8
6.1 General . 8
6.2 Size . 8
6.3 Number . 8
6.4 Design . 9
6.4.1 General . 9
6.4.2 Test configuration . 9
6.4.3 Boundary/restraint conditions . 9
6.4.4 Penetrating services . 9
6.5 Construction . 9
6.6 Verification . 9
7 Installation of test specimen . 10
7.1 General . 10
7.2 Standard supporting construction . 10
7.2.1 General . 10
7.2.2 Vertically oriented test specimens . 10
7.2.3 Horizontal test specimens . 10
7.2.4 Open cavity barrier specimens . 10
7.3 Splice locations for open cavity barriers . 10
7.4 Non-standard supporting construction . 10
8 Conditioning . 10
9 Application of instrumentation . 11
9.1 Thermocouples . 11
9.1.1 Furnace thermocouples (plate thermometers) . 11
9.1.2 Unexposed surface thermocouples . 11
9.2 Pressure . 12
9.3 Deflection . 12
10 Test procedure . 12
10.1 General . 12
10.2 Furnace control . 12
10.3 Evaluation of integrity criteria . 13
10.4 Observations during the test . 13
10.5 Termination of test . 13
11 Performance criteria . 13
11.1 General . 13
11.2 Cavity barriers used as fire stopping . 13
11.3 Open Cavity Barriers . 13
11.3.1 Insulation . 13
11.3.2 Integrity. 13
11.4 Expression of results . 14
12 Test report . 14
12.1 General . 14
12.2 Reports of tests undertaken on Open cavity barriers . 14
13 Field of direct application of the test results . 14
13.1 closed cavity barriers . 14
13.1.1 General . 14
13.1.2 Extension of width . 14
13.1.3 Extension of height . 15
13.1.4 Supporting constructions . 15
13.2 Open cavity barriers . 15
Annex A (normative) Cavity barriers in under floor voids . 17
A.1 Introduction. 17
A.2 Configuration . 17
A.3 Thermocouples for measuring the maximum temperature rise . 18
A.4 Field of direct application . 19
Annex B (normative) Cavity barriers within walls (e.g. masonry leaves) . 20
B.1 Introduction. 20
B.2 Configuration . 20
B.3 Thermocouples for measuring the maximum temperature rise . 22
B.4 Field of direct application . 22
Annex C (normative) Open cavity barriers . 24
C.1 Principle of test/configuration . 24
C.2 Unexposed surface thermocouples . 24
Annex D (normative) Test configuration for immediate heat exposure using
removable shield . 26
D.1 Use of this annex . 26
D.2 Principle of removable test configuration . 26
D.3 Removable shield . 26
D.4 Test procedure amendments for this test configuration . 26
Annex E (informative) Background and testing philosophy of cavity barriers . 28
E.1 Introduction. 28
E.2 Reference scenarios . 28
E.3 Use of tests for classification . 29
Bibliography . 30
European foreword
This document (prEN 1364-6:2016) has been prepared by Technical Committee CEN/TC 127
“Fire safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission
and the European Free Trade Association.
CEN TC 127 is the CEN committee for drafting fire test standards in support of the Construction
Products Regulation. The test method is needed in support of ETAG 026-5 for cavity barriers.
Introduction
Cavity barriers are provided within buildings to restrict the spread of smoke and fire in concealed
spaces. Cavity barriers may be ‘closed’ e.g. in roof voids, under raised floors, between the inner
and outer leaves of walls such as in timber framed construction; or they may be ‘open’, for
example as used in ventilated facade systems, roof eaves, and rain screen cladding systems.
The purpose of this test is to measure the ability of a representative specimen of a cavity barrier
to resist the spread of fire from one side to another. A representative sample of a cavity barrier is
exposed to a specified regime of heating and pressure. The performance of the test specimen is
monitored on the basis of criteria in EN 1363-1. The fire resistance of the tested construction is
expressed as the time for which the appropriate criteria have been satisfied.
The principles embodied in this method follow those embodied in EOTA TR31, the fire resistance
test for closed cavity barriers published in 2008. However, TR31 is not applicable to open cavity
barriers and consequently this method has had to be adapted to include these.
Reference Scenario and limitations
Closed cavity barriers – whose function is to close a gap between fire resistant elements of
building structure – fall within the scope of the small room fire scenario where ISO 834-1 has
been recognized as the reference fire resistance test.
For open cavity barriers, for example those used in ventilated facades, rain screens and roof eaves,
a European reference scenario has not yet been established. Work is on-going to develop a full-
scale façade test and it is expected that this method will be correlated to that full scale test.
Consequently, for the time being, results of tests to this standard cannot be used to imply
performance of an external facade system in which the open cavity barrier is included. The test
results may be used as supplementary evidence of cavity barrier performance in systems already
accepted by current national regulations. Further information is given in Annex E.
Caution — The attention of all persons concerned with managing and carrying out this fire
resistance test, is drawn to the fact that fire testing may be hazardous and that there is a
possibility that toxic and/or harmful smoke and gases may be evolved during the test.
Mechanical and operation hazards may also arise during the construction of the test
elements or structures, their testing and disposal of test residues.
An assessment of all potential hazards and risks to health should be made and safety
precautions should be identified and provided. Written safety instructions should be
issued. Appropriate training should be given to relevant personnel. Laboratory personnel
should ensure that they follow written safety instructions at all times.
1 Scope
This test method specifies a method for determining the fire resistance of cavity barriers and is to
be used in conjunction with EN 1363-1.
This standard is applicable to non-loadbearing vertically or horizontally oriented closed and open
cavity barriers, which are used to provide fire separation to uncompartmented or ventilated
spaces. Cavity barriers are designed to provide fire separating performance and the test method is
therefore based on the standard room fire exposure in EN 1363-1. Open cavity barrier specimens
are installed for test in one of two ways to simulate slow or sudden exposure in use.
This standard is not applicable to cavity barriers containing penetration seals, which are to be
tested in accordance with EN 1366-3.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
EN 1363-1, Fire resistance tests - Part 1: General Requirements
EN 1366-3, Fire resistance tests for service installations - Part 3: Penetration seals
EN ISO 13943:2010, Fire safety - Vocabulary (ISO 13943:2008)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1 and
EN ISO 13943:2010 and the following apply.
3.1
concealed space
space in a building where fire could develop or pass through that is not normally used or
accessible by humans
3.2
closed cavity barrier
non-loadbearing vertically or horizontally oriented element designed to provide fire separation in
a concealed space (cavity)
3.3
splice
connection or junction between or within the length of a linear gap seal where it is being used as a
cavity barrier
3.4
‘open’ cavity barrier
non-loadbearing vertically or horizontally oriented element designed to provide fire separation in
a concealed space (cavity)
Note 1 to entry: These are open to allow ventilation and drainage in the cold state, but which either close
in a fire, or are inherently fire resisting providing fire separation in the cavity.
3.5
façade system
system used to protect the outside vertical envelope of a building from the elements
3.6
air gap
space between the back surface of the external wall panels and the outer face of the inner wall or
insulation layer
4 Test equipment — Additional requirements for open cavity barriers
In addition to the test equipment specified in EN 1363-1, it is required that for open cavity
barriers the internal dimensions of the test furnace shall be such that a distance of at least
200 mm exists between the long edge of the open cavity barrier and the wall of the furnace.
The size of the furnace required will depend on the nominal width of the open cavity barrier and
is given in Table 1 (see also 6.2).
Table 1 — Open cavity barriers
Nominal width of open cavity
Minimum size of furnace required
barrier
< 100 mm 1 m x 1 m x > 0,75 m deep
> 100 mm up to 300 mm 10 times nominal width of cavity barrier x > 0,75 m deep
> 300 mm 3 m x 3 m x > 0,75 m deep
5 Test conditions
5.1 Heating conditions
The heating conditions and the furnace atmosphere shall conform to those given in EN 1363-1.
For open cavity barriers, an option is provided for the use of a removable shield underneath the
cavity barrier which is removed at 5 min into the test immediately exposing the cavity barrier to
the furnace heating conditions at that time. See Annex E.
5.2 Pressure conditions
5.2.1 General
The pressure conditions and the furnace atmosphere shall conform to those given in EN 1363-1
unless modified as follows:
5.2.2 Cavity Barriers mounted within leaves of walls or in roof voids
For cavity barriers mounted between the leaves of walls and above suspended ceilings/in loft
spaces, the pressure conditions and the furnace atmosphere shall conform to those given in
EN 1363-1.
5.2.3 Cavity barriers mounted underneath raised access floors
For cavity barriers mounted underneath raised access floors, the following pressure conditions
shall apply:
For plenum heights not greater than 1 m, the pressure in the furnace 100 mm below the soffit
shall be maintained at + 5 Pa (+ 3 Pa) relative to outside the furnace.
For plenum heights greater than 1 m, the pressure in the furnace 100 mm below the soffit shall
be maintained at +3 Pa of a pressure calculated as follows:
p 0,66 h × 8,5 (1)
where:
P = pressure in Pa
h = height of plenum below the raised floor in m
5.2.4 Open cavity barriers
For open cavity barriers the furnace pressure shall be monitored and controlled so that 5 min
after the commencement of the test, the furnace pressure shall be 20 ± 5 Pa at a position
100 ± 10 mm below the bottom face of the cavity barrier (horizontal orientation) or 100 mm
below the top of the furnace (vertical orientation). Ten minutes after the commencement of the
test, the furnace pressure shall be 20 ± 3 Pa at a position 100 ± 10 mm below the bottom face of
the open-state cavity barrier (horizontal orientation) or 100 mm below the top of the furnace
(vertical orientation).
Laboratories should aim to achieve the specified pressures as soon as possible after
commencement of the test. Furnaces should not be run under, for example negative pressure for
the first few minutes and then the pressure only established just before 5 min.
For open cavity barriers tested using the thermal exposure of the removable shield, the pressure
conditions in 5.2.3 might not be met immediately after the removal of the shield. In such cases,
any pressure drop shall be corrected as quickly as possible and in any case within three minutes.
6 Test specimen
6.1 General
The test specimen shall consist of a cavity barrier mounted in a supporting construction.
6.2 Size
If, in practice, the height or width of the product is 3 m or smaller, then that dimension of the test
specimen shall be tested at full size. If any dimension of the construction is greater than 3 m, then
that dimension shall be tested at not less than 3 m.
A typical minimum length to width ratio for an open cavity barrier is 10:1. In order to maintain
this ratio a test furnace of appropriate dimensions shall be used (see Clause 4).
For open cavity barriers, the distance between the long edge open cavity barrier and the outer
perimeter of the heated part of the separating element shall be not less than 200 mm at any point
in order to avoid boundary effects (see Clause 4).
6.3 Number
The number of test specimens shall be as given in EN 1363-1. However, where information is
required under different boundary/exposure conditions or where an asymmetrical product is to
be evaluated, additional tests shall be undertaken for each situation using separate test
specimens. Where a cavity barrier is intended for use in both horizontal and vertical separating
elements, both orientations shall be tested.
=
6.4 Design
6.4.1 General
The test specimen shall be fully representative of the construction used in practice. More than one
type of cavity barrier system may be included in a single test specimen provided the requirements
on space separation and thermal and pressure conditions are met.
Joints or splices for the purposes of erection, construction or expansion, shall be incorporated in
the test specimen. Different jointing systems or splices may be included in a single test specimen
provided that they are both subjected to furnace pressure conditions equal to or greater than
those specified in 5.2.
The design features which influence fire performance should be included to give the widest
application that can be derived from the field of direct application (see Clause 13).
6.4.2 Test configuration
Four test configurations appropriate to the end uses of cavity barriers are considered in this
document:
1. Above suspended ceilings and in lofts and other roof voids to prevent horizontal fire spread.
2. Below raised access floors between the underside of the raised floor and the upper side of the
structural floor slab. Special considerations for testing these are given in Annex A.
3. Fire stopping between leaves of, for example masonry walls to prevent vertical or horizontal
fire spread between the leaves. Special considerations for testing these are given in Annex B.
4. Open cavity barriers installed as part of external walls, for example facades and roof eaves.
Special considerations for testing these are given in Annex C.
6.4.3 Boundary/restraint conditions
The test specimen shall be installed with boundary and restraint conditions representative of
those found in practice.
Where, in practice the width of the product is larger than the front opening of the furnace, one
vertical edge shall be left unrestrained and there shall be a gap of 25 mm to 50 mm between the
free edge of the test specimen and the test frame. This gap shall be packed with a resilient non-
combustible material (e.g. mineral fibre) to provide a seal without restricting freedom of
movement. The remaining edges shall be restrained as in practice.
6.4.4 Penetrating services
In some cases pipes, cables or other services may pass through a cavity barrier. In this case, the
cavity barrier shall be treated as a penetration sealing system and shall be tested in accordance
with EN 1366-3.
6.5 Construction
The test specimen shall be constructed as described in EN 1363-1.
6.6 Verification
Verification of the test specimen shall be carried out as described in EN 1363-1.
7 Installation of test specimen
7.1 General
The test specimen shall be installed in the test frame and, if used, the supporting construction, as
in practice.
Where voids exist within a cavity barrier (e.g. when it is in the form of a tube), the ends shall be
hermetically sealed in order to prevent airflow through the test specimen.
7.2 Standard supporting construction
7.2.1 General
If the size of the test specimen is smaller than the opening in the test frame then it shall be
installed in the test frame using one of the following approaches:
7.2.2 Vertically oriented test specimens
a) Where the height of the test specimen is smaller than the height of the test frame opening, a
plinth shall be provided to reduce the opening to the required height. The plinth shall possess
sufficient stability for the test specimen and shall be selected from one of the rigid standard
supporting constructions in EN 1363-1.
b) Where the width of the test specimen is smaller, a standard supporting construction shall be
provided on the vertical sides of the opening selected from either the rigid or flexible
standard supporting constructions given in EN 1363-1.
7.2.3 Horizontal test specimens
Where the area of the test specimen is smaller than the area of the test frame opening, then the
furnace opening shall be reduced to the area of the test specimen using a suitable construction. In
the absence of horizontal standard supporting construction in EN 1363-1, gas concrete or dense
concrete slabs shall be used for horizontal specimens.
7.2.4 Open cavity barrier specimens
For open cavity barriers, the supporting construction shall comprise either autoclaved aerated
3 3
concrete, density: (650 ± 200) kg/m or dense concrete, density (2,400 ± 200) kg/m .
7.3 Splice locations for open cavity barriers
Where splices (see 3.3) or consecutive lengths of pre-formed components require to be jointed in
practice, a typical joint shall be included. If two methods of joining consecutive lengths of
component(s) are to be incorporated in the same specimen of open-state cavity barrier, then each
method shall be separated by at least 200 mm. All fixing methods including, for example brackets,
each side
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

oSIST prEN 1364-6:2016 표준은 비하중 지지 요소의 방화 성능 시험 방법을 제시하며, 특히 공동 공간이나 통풍이 있는 공간에 대한 방화 분리를 제공하기 위한 공동 바닥 차단막의 내화 성능을 평가하는 데 초점을 맞추고 있습니다. 이 표준은 EN 1363-1을 참고하여 표준 실내 화재 노출에 기초한 시험 방법을 제공합니다. 이 표준의 주요 강점은 비하중 지지형 수직 및 수평 지향의 폐쇄형 및 개방형 공동 차단막에 적용 가능하다는 점입니다. 이러한 특성은 다양한 설계와 응용 사례에서의 유연성을 증대시키며, 비 compartment 공간에 효과적으로 사용될 수 있습니다. 또한, 공동 차단막 샘플은 사용 중 느리거나 급격한 노출을 시뮬레이션하기 위해 두 가지 방식으로 설치하여 실제 화재 상황에서의 성능을 정확하게 평가할 수 있도록 합니다. oSIST prEN 1364-6:2016 표준은 방화 성능을 검증하기 위한 명확한 지침을 제공하여 공공 안전을 보장하고 건축물의 화재 안전성을 강화하는 데 필수적인 역할을 합니다. 이러한 표준의 존재는 건축 규정 준수와 화재 안전 관리의 일관성을 높여주며, 실제 사례에 기반한 시험 방식을 통해 신뢰성을 확보합니다. 하지만 이 표준은 침투 밀봉을 포함한 공동 차단막에 대해서는 적용되지 않으며, 이 경우에는 EN 1366-3에 따라 별도의 시험이 필요합니다. 이는 특정한 요구 사항에 대한 명확성을 제공하고, 사용자의 혼선을 방지하는 데 기여합니다. 결론적으로, oSIST prEN 1364-6:2016 표준은 비하중 지지 공동 차단막의 방화 성능 평가를 위한 포괄적이고 신뢰할 수 있는 기준을 제시하여, 관련 분야에서의 중요성을 강조합니다. 이러한 표준의 적용은 건축물의 화재 안전성을 높이고, 방화 안전 관리 시스템의 신뢰성을 강화하는 데 기여할 것입니다.

oSIST prEN 1364-6:2016は、非荷重支持要素の火災抵抗試験に関する重要な標準であり、主にキャビティバリアに焦点を当てています。この標準は、火災に対するキャビティバリアの抵抗力を評価するための試験方法を規定しており、EN 1363 1と連携して使用されます。 この標準の適用範囲は、非荷重支持の垂直または水平に配置された閉じた及び開放されたキャビティバリアに及び、これらは非区画または換気された空間に対して火災隔壁を提供するために使用されます。キャビティバリアは火災隔離性能を発揮するように設計されており、試験方法はEN 1363 1における標準的な室内火災曝露に基づいています。このスタンダードでは、開放キャビティバリアの試料を用い、実際の使用状況における緩やかな露出または急激な露出を模擬するために、2つの方法のいずれかで試験用に設置されています。 また、oSIST prEN 1364-6:2016は、EN 1366 3に従って試験されるべき貫通シールを含むキャビティバリアには適用されません。このため、特定の用途に応じた明確な要件を持つ標準となっています。 全体として、この標準はキャビティバリアの火災抵抗性能を確実に評価するための科学的かつ実用的なフレームワークを提供しており、建築物の安全性に対する重要な貢献を果たします。

La norme oSIST prEN 1364-6:2016 constitue un cadre essentiel pour les tests de résistance au feu des éléments non porteurs, spécifiquement pour les barrières de cavité. Son champ d'application est clair et précis, définissant une méthode de test qui permet d'évaluer la résistance au feu des barrières de cavité, s'appliquant à la fois aux éléments verticaux et horizontaux. Une des forces majeures de cette norme réside dans son intégration avec la norme EN 1363-1, qui établit les conditions d'exposition au feu standard dans une salle. La norme détaille les différents types de barrières de cavité, qu'elles soient fermées ou ouvertes, et leur utilisation dans des espaces non compartimentés ou ventilés, garantissant ainsi une séparation efficace en cas d'incendie. Cela souligne la pertinence de la norme dans le contexte de la sécurité incendie moderne, où la protection des occupants et des biens est primordiale. En outre, la méthode de test est conçue pour simuler des expositions lentes ou soudaines, ce qui illustre la flexibilité de la norme face aux différents scénarios d'incendie auxquels les barrières de cavité peuvent être soumises dans la pratique. Il est important de noter que cette norme ne s'applique pas aux barrières de cavité contenant des joints de pénétration, qui doivent être évalués selon EN 1366-3, ce qui renforce la précision et la spécificité des tests. En résumé, la norme oSIST prEN 1364-6:2016 se révèle être un outil incontournable pour les professionnels de la sécurité incendie, offrant un cadre rigoureux et pertinent pour évaluer les performances de résistance au feu des barrières de cavité.

The standard oSIST prEN 1364-6:2016 provides a comprehensive test method for assessing the fire resistance of cavity barriers, making it an essential document for ensuring safety in both residential and commercial buildings. Its scope is well-defined, focusing specifically on non-loadbearing vertically or horizontally oriented closed and open cavity barriers utilized for fire separation in uncompartmented or ventilated spaces. One of the strengths of this standard is its alignment with EN 1363-1, which specifies the standardized room fire exposure conditions under which the tests are conducted. This relationship ensures consistency in testing, providing reliable and comparable results for fire resistance across different materials and designs. Moreover, the provision for testing open cavity barrier specimens under two distinct exposure scenarios-slow or sudden-enhances the applicability of the standard to various real-world conditions, promoting a thorough understanding of fire behavior in different contexts. The relevance of oSIST prEN 1364-6:2016 cannot be overstated, particularly in the current landscape where fire safety regulations are increasingly stringent. By focusing on the fire separating performance of cavity barriers, the standard plays a critical role in fire safety management, enabling designers, builders, and fire protection engineers to implement effective fire safety strategies. Additionally, by clearly stating that this standard does not apply to cavity barriers containing penetration seals-supervised under EN 1366-3-it helps users avoid potential confusion and directs them towards the appropriate testing methods for those elements. This specificity underlines the precision and specialized focus of the standard. In summary, the oSIST prEN 1364-6:2016 offers a robust framework for evaluating fire resistance in cavity barriers, supporting the overall goal of enhancing building safety and compliance with fire safety regulations. Its application in various contexts ensures that it remains relevant in ongoing discussions about fire protection and safety standards.

Die Norm oSIST prEN 1364-6:2016 behandelt die Feuerwiderstandstests für nicht tragende Elemente, insbesondere für Hohlräume und deren Barrieren. Der Anwendungsbereich dieser Norm ist klar definiert, da sie spezifische Prüfmethoden zur Bestimmung des Feuerwiderstands von Hohlraumbarrieren festlegt, die in Verbindung mit der Norm EN 1363-1 verwendet werden sollten. Dies gewährleistet, dass die Tests nach einheitlichen Standards durchgeführt werden, was die Konsistenz und Zuverlässigkeit der Ergebnisse erhöht. Zu den Stärken dieser Norm gehört ihre Anwendung auf sowohl vertikal als auch horizontal ausgerichtete Hohlraumbarrieren, unabhängig davon, ob sie geschlossen oder offen sind. Diese Vielseitigkeit macht die Norm für verschiedene Bauanwendungen relevant, insbesondere in unvernetzten oder belüfteten Räumen, wo Feuertrennung von entscheidender Bedeutung ist. Die klaren Vorgaben für die Installation von offenen Hohlraumbarrierenteststücken ermöglichen es, unterschiedliche Expositionsszenarien zu simulieren, sei es durch langsame oder plötzliche Feuerbelastung, was die praktische Anwendbarkeit der Testergebnisse erhöht. Eine weitere Stärke der Norm liegt in ihrer Fokussierung auf die Feuertrennleistung der Barrieren, was für die Gewährleistung der Sicherheit in Gebäuden unerlässlich ist. Indem sie einen standardisierten Ansatz für die Prüfung von Hohlraumbarrieren bereitstellt, trägt die Norm zur Verbesserung des Brandschutzes und der allgemeinen Sicherheit von Bauwerken bei. Es ist wichtig zu beachten, dass die Norm nicht auf Hohlraumbarrieren anwendbar ist, die Durchdringungsdichtungen enthalten. Diese speziellen Elemente müssen gemäß der Norm EN 1366-3 getestet werden, was die Nische dieser Norm präzise abgrenzt und sicherstellt, dass verschiedene Bauelemente entsprechend ihrer Eigenschaften getestet werden. Insgesamt bietet oSIST prEN 1364-6:2016 eine essentielle Grundlage für die Bewertung der Feuerwiderstandsfähigkeit von Hohlraumbarrieren, die speziell für moderne Baupraktiken von hoher Relevanz ist. Die Norm ist ein wichtiges Werkzeug für Fachleute, die sich mit Brandschutzlösungen befassen und trägt dazu bei, Standards im Bauwesen zu verbessern.