EN 62423:2012
(Main)Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
The scope of IEC 61008-1 and IEC 61009-1 applies with the following additions. IEC 62423:2009 specifies requirements and tests for Type F and Type B RCDs (Residual Current Devices). Requirements and tests given in this standard are in addition to the requirements of Type A residual current devices. This standard can only be used together with IEC 61008-1 and IEC 61009-1. Type F RCCBs (Residual Current Circuit Breaker) and Type F RCBOs (Residual current Circuit Breaker with Overcurrent protection) with rated frequency 50 Hz or 60 Hz are intended for installations when frequency inverters are supplied between phase and neutral or phase and earthed middle conductor and are able to provide protection in case of alternating residual sinusoidal at the rated frequency, pulsating direct residual currents and composite residual currents that may occur. Type B RCCBs and Type B RCBOs are able to provide protection in case of alternating residual sinusoidal currents up to 1 000 Hz, pulsating direct residual currents and smooth direct residual currents. This second edition cancels and replaces the first edition published in 2007 and constitutes a technical revision. The main changes from the first edition are as follows: - requirements and tests for Type F RCD have been introduced; - requirements and test for two-pole Type B RCD have been introduced; - new additional requirements and tests for Type B RCDs have been introduced to cover requirements for Type F too.
Fehlerstrom-/Differenzstrom-Schutzschalter Typ F und Typ B mit und ohne eingebautem Überstromschutz für Hausinstallationen und für ähnliche Anwendungen
Interrupteurs automatiques à courant différentiel résiduel de type B et de type F avec et sans protection contre les surintensités incorporée pour usages domestiques et analogues
Les domaines d'application de la CEI 61008-1 et de la CEI 61009-1 s'appliquent avec les additions suivantes. La CEI 62423:2009 spécifie les exigences et les essais pour les DDR (dispositif de protection à courant différentiel résiduel) de Type B et de Type F. Les exigences et les essais donnés dans la présente norme complètent les exigences des dispositifs à courant différentiel résiduel de Type A. La présente norme ne peut être utilisée que conjointement à la CEI 61008-1 et à la CEI 61009-1. Les ID (interrupteur différentiel sans protection contre les surintensités incorporée) de Type F et les DD (interrupteur différentiel avec protection contre les surintensités incorporée) de Type F de fréquence assignée 50 Hz ou 60 Hz sont destinés à des installations dans lesquelles les convertisseurs de fréquence sont alimentés entre phase et neutre ou entre phase et conducteur milieu mis à la terre et sont aptes à assurer la protection en cas d'apparition de courant différentiel alternatif sinusoïdal à la fréquence assignée, de courant différentiel continu pulsé et de courant différentiel composé. Les ID de Type B et les DD de Type B sont aptes à assurer la protection en cas de courants différentiels résiduels alternatifs sinusoïdaux jusqu'à 1 000 Hz, de courants différentiels résiduels continus pulsés et de courants différentiels résiduels continus lissés. Cette deuxième édition annule et remplace la première édition publiée en 2007 dont elle constitue une révision technique. Les changements par rapport à la première édition sont les suivants: - des exigences et essais ont été introduits pour le DDR de Type F; - des exigences et essais ont été introduits pour le DDR à deux pôles de Type B; - de nouvelles exigences et de nouveaux essais supplémentaires pour les DDR de Type B ont été introduits pour couvrir aussi les exigences et essais pour le Type F.
Odklopniki na preostali tok tipov F in B z vgrajeno nadtokovno zaščito ali brez nje za gospodinjsko in podobno rabo (IEC 62423:2009, spremenjen + popravek dec. 2011)
Na področje uporabe standardov IEC 61008-1 in IEC 61009-1 spadajo tudi naslednji dodatki. Ta standard navaja zahteve in preskuse za zaščitne naprave na preostali (residualni) tok (RCD) tipa F in B. Zahteve in preskusi, ki so podani v tem standardu, so dodatek k zahtevam za zaščitne naprave na preostali (residualni) tok tipa A. Ta standard se lahko uporablja samo skupaj s standardoma IEC 61008-1 in IEC 61009-1. Odklopniki RCCB (odklopniki na preostali (residualni) tok) tipa F in odklopniki RCBO (odklopniki na preostali (residualni) tok z vgrajeno nadtokovno zaščito) z naznačeno frekvenco 50 ali 60 Hz so namenjeni za naprave, kjer so frekvenčni razsmerniki napajani med faznim in nevtralnim ali med faznim in ozemljenim srednjim vodnikom in lahko omogočajo zaščito v primeru, da pride do izmeničnih sinusoidnih residualnih tokov na naznačeni frekvenci, enosmernih utripajočih residualnih tokov in sestavljenih residualnih tokov. Odklopniki RCCB tipa B in odklopniki RCBO tipa B omogočajo zaščito v primeru izmeničnih sinusoidnih residualnih tokov do 1 000 Hz, enosmernih utripajočih residualnih tokov in mehkih enosmernih residualnih tokov. Zaščitne naprave na preostali (residualni) tok v skladu s tem standardom niso namenjene uporabi v enosmerno napajanih sistemih. Nadaljnje zahteve in preskusi za izdelke, ki se uporabljajo v primerih, ko residualni tok ni namenjen obravnavi v standardih IEC 61008-1 in IEC 61009-1, so v obravnavi. Za potrebe izjave proizvajalca ali preverjanja skladnosti bi morali biti tipski preskusi izvedeni v zaporedjih, ki so v skladu z dodatki A, B, C ali D k temu standardu. Popolno zaporedje preskusov za tipski preskus odklopnikov RCCB tipa F in odklopnikov RCBO tipa F je podano v preglednicah A.1 in B.1. Popolno zaporedje preskusov za tipski preskus odklopnikov RCCB tipa B in odklopnikov RCBO tipa B je podano v preglednicah C.1 in D.1.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-februar-2013
1DGRPHãþD
SIST EN 62423:2009
2GNORSQLNLQDSUHRVWDOLWRNWLSRY)LQ%]YJUDMHQRQDGWRNRYQR]DãþLWRDOLEUH]QMH
]DJRVSRGLQMVNRLQSRGREQRUDER,(&VSUHPHQMHQSRSUDYHNGHF
Type F and type B residual current operated circuit-breakers with and without integral
overcurrent protection for household and similar uses (IEC 62423:2009, modified +
corrigendum Dec. 2011)
Fehlerstrom-/Differenzstrom-Schutzschalter Typ F und Typ B mit und ohne eingebautem
Überstromschutz für Hausinstallationen und für ähnliche Anwendungen (IEC
62423:2009, modified + corrigendum Dec. 2011) (IEC 62423:2009, modifiziert)
Interrupteurs automatiques à courant différentiel résiduel de type B et de type F avec et
sans protection contre les surintensités incorporée pour usages domestiques et
analogues ( (IEC 62423:2009, modified + corrigendum Dec. 2011)CEI 62423:2009,
modifiée)
Ta slovenski standard je istoveten z: EN 62423:2012
ICS:
29.120.50 9DURYDONHLQGUXJD Fuses and other overcurrent
PHGWRNRYQD]DãþLWD protection devices
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 62423
NORME EUROPÉENNE
December 2012
EUROPÄISCHE NORM
ICS 29.120; 29.120.50 Supersedes EN 62423:2009
English version
Type F and type B residual current operated circuit-breakers with and
without integral overcurrent protection for household and similar uses
(IEC 62423:2009, modified + corrigendum Dec. 2011)
Interrupteurs automatiques à courant Fehlerstrom-/Differenzstrom-
différentiel résiduel de type B et de type F Schutzschalter Typ F und Typ B mit und
avec et sans protection contre les ohne eingebautem Überstromschutz für
surintensités incorporée pour usages Hausinstallationen und für ähnliche
domestiques et analogues Anwendungen
(CEI 62423:2009, modifiée + corrigendum (IEC 62423:2009, modifiziert +
déc. 2011) corrigendum Dez. 2011)
This European Standard was approved by CENELEC on 2012-06-19. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the CEN-CENELEC Management Centre has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany,
Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62423:2012 E
Foreword
This document (EN 62423:2012) consists of the text of IEC 62423:2009 + corrigendum 2011 prepared
by IEC/TC 23E "Circuit-breakers and similar equipment for household use", together with the common
modifications prepared by CLC/TC 23E "Circuit breakers and similar devices for household and similar
applications".
The following dates are fixed:
(dop) 2013-06-19
• latest date by which this document has to be implemented
at national level by publication of an identical
national standard or by endorsement
(dow) 2017-06-19
• latest date by which the national standards conflicting
with this document have to be withdrawn
This document supersedes EN 62423:2009.
– requirements and tests for Type F RCD have been introduced;
– requirements and tests for two-pole Type B RCD have been introduced;
– new additional requirements and tests for Type B RCDs have been introduced to cover
requirements and tests for Type F too.
This European Standard is to be read in conjunction with the following standards:
EN 61008-1:2012, Residual current operated circuit-breakers without integral overcurrent protection
for household and similar uses (RCCBs) – Part 1: General rules
EN 61009-1:2012, Residual current operated circuit-breakers with integral overcurrent protection for
household and similar uses (RCBOs) – Part 1: General rules
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such
patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association, and supports essential requirements of EU Directive(s).
For the relationship with EU Directive(s) see informative Annex ZZ, which is an integral part of this
document.
Endorsement notice
The text of the International Standard IEC 62423:2009 + corrigendum 2011 was approved by
CENELEC as a European Standard with agreed common modifications.
- 3 - EN 62423:2012
COMMON MODIFICATIONS
Clause Common modification
Introduction Delete “with rated frequency 50 Hz or 60 Hz”.
1 Scope Replace the first two paragraphs by :
The scope of EN 61008-1 and EN 61008-2-1 or EN 61009-1 and EN 61009-2-
1 applies with the following additions.
"This standard specifies requirements and tests for Type F and Type B RCDs
(Residual current devices). Requirements and tests given in this standard are
in addition to the requirements of Type A residual current devices according
to EN 61008-2-1 or EN 61009-2-1. This standard can only be used together
with EN 61008-1 and EN 61009-1."
1 In third paragraph, delete “with rated frequency 50 Hz or 60 Hz”.
1 In sixth paragraph, replace “IEC” with “EN”.
1 Add a new paragraph after fourth paragraph:
"Type F and type B RCDs have high resistance against unwanted tripping
even if the surge voltage causes a flashover and a follow-on current occurs
and in case of inrush residual currents with a maximum duration of 10 ms
which can occur in case of switching ON electronic equipment or EMC-
filters."
1 Delete the seventh paragraph.
1 Modify note 2 by:
“Note 2 : deleted”
2 Replace the contents of Clause 2 with: “Normative references to
international publications are listed in Annex ZA.”
5.2.3 Delete the value "60 Hz" three times: in the title of 5.2.3, in the title of
Table 2 and in note 4 of Table 2.
9.2.1.1 Delete the third paragraph in 9.2.1.1.
9.2.1.2 b) Replace last paragraph by:
The maximum break time shall not exceed 0,3 s for general type RCDs and
for S-type RCDs the maximum break time shall not exceed 0,5 s.
9.2.1.7.1 Add a note after the first paragraph in 9.2.1.7.1 :
Note: The open circuit voltage of the DC source should be high enough to guarantee
stable smooth d.c. current (e.g. more than 24 V).
9.2.2 Delete the paragraph before the note.
Figure 2 Delete “or 60 Hz”.
Annexes A, B, See modified Annexes A to D at the end of the document (modifications in
C and D red).
Annex ZA See new Annex ZA at the end of this document.
Annex A
(normative)
Number of samples to be submitted and test sequences
to be applied for verification of conformity for type F RCCBs
Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table A.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61008-1:2012 .
Table A.1 – Test sequences for Type F RCCBs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61008-1 and according to this
EN 61008-2-1 standard
6 6 Marking
8.1.1 No General
No
8.1.2 Mechanism
No
9.3 Indelibility of marking
No
8.1.3 Clearance and creepage distances (external parts only)
No
9.15 Trip-free mechanism
No
Reliability of screws, current-carrying parts and
9.4
connections
A
No
9.5 Reliability of terminals for external conductors
No
9.6 Protection against electric shock
No
9.13.1
No
Resistance to heat
9.13.2
9.13.3
No
8.1.3 Clearances and creepage distances (internal parts)
No
9.14 Resistance to abnormal heat and to fire
No
9.7 Test of dielectric properties
No
9.8 Temperature rise
No
B 9.20 Resistance of insulation against impulse voltages
No
9.22.2 Reliability at 40 °C
No
9.23 Ageing of electronic components
No
C 9.10 Mechanical and electrical endurance
9.9 Residual operating characteristics
Verification of the correct operation in case of a steady
9.1.2
D increase of composite residual current
Verification of the correct operation in case of sudden
9.1.3
D
appearance of composite residual current
9.17 No Behaviour in the case of failure of the line voltage
D 9.1.5
Unwanted tripping
9.19
Behaviour in the case of surge currents
- 5 - EN 62423:2012
9.1.6
…… Behaviour in the case of inrush residual currents
9.1.4
Correct operation for RCD powered on two poles only
9.1.7
9.21.4 Type A residual current devices
No
9.11.2.3 a) and b) Performance at I
∆m
No
9.16 Test device
No
9.12 Resistance to mechanical shock and impact
9.18 No Non-operating current under overcurrent conditions
No
D 9.11.2.3 c) Verification of the suitability in IT system
No
9.11.2.4 a) Coordination at I
nc
E
No
9.11.2.2 Performance at I
m
No
9.11.2.4 b) Coordination at I
m
F
No
9.11.2.4 c) Coordination at I
∆c
No
9.22.1 Reliability (climatic tests)
G
Verification of correct operation at low ambient air temperature
G 9.Z1 No
of RCCBs for use in the range of .-25 °C to +40 °C
No
EN 61543:1995, Table 4 Harmonics, interharmonics
-T1.1
Signalling voltage
EN 61543:1995, Table 4
a
Conducted unidirectional transients of the ms and µs time
H
-T1.2
scale
EN 61543:1995, Table
5 -T2.3
No Conducted oscillatory voltages or currents
EN 61543:1995, Table 5
Radiated high-frequency phenomena
-T2.1
Conducted unidirectional transients of the ns time scale
EN 61543:1995, Table 5
I (burst)
-T2.5
EN 61543:1995, Table
5 -T2.2
No
EN 61543:1995, Table
Conducted common mode disturbances in the frequency range
5 -T2.6
lower than 150 kHz
J
EN 61543:1995, Table
Electrostatic discharges
6 -T3.1
a
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples prior to the
tests of this sequence.
Annex B
(normative)
Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type F RCBOs
Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table B.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61009-1:2012.
Table B.1 – Test sequences for Type F RCBOs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61009-1 and according to this
EN 61009-2-1 standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
8.1.6 No Non-interchangeability
9.11 No Trip-free mechanism
Reliability of screws, current-carrying parts and
A
9.4 No
connections
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
9.14.1 No
Resistance to heat
9.14.2
No
9.14.3
8.1.3 No Clearances and creepage distances (internal parts)
9.15 No Resistance to abnormal heat and to fire
9.7 No Dielectric properties
9.8 No Temperature rise
B
9.20 No Resistance of insulation against impulse voltages
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
9.10 No Mechanical and electrical endurance
C
1 9.12.11.2.1
Performance at reduced short-circuit currents
No
(and 9.12.12) (Verification of the RCBO after the short-circuit tests)
C
No
Short-circuit test for verifying the suitability of RCBOs for
9.12.11.2.2
use in IT systems
C
(and 9.12.12)
(Verification of the RCBO after the short-circuit tests)
Operating characteristics under residual current
D D 9.9.1
conditions
- 7 - EN 62423:2012
Verification of the correct operation in case of a steady
9.1.2
increase of composite residual current
Verification of the correct operation in case of sudden
9.1.3
appearance of composite residual current
9.17 No Behaviour in the case of failure of the line voltage
9.1.5
Unwanted tripping
9.19
Behaviour in the case of surge currents.
9.1.6
… Behaviour in the case of inrush residual currents
D
9.1.4
Correct operation for RCD powered on two poles only
9.1.7
9.21.1 Type A residual current devices
No
9.12.13 Performance at I
∆m
No
9.16 Test device
No
9.9.2 Overcurrent operating characteristics
E No
Limiting value of overcurrent in case of a single-phase load
9.18
through a 3-pole or 4-pole RCBO
E
No
9.13 Resistance to mechanical shock and impact
E
No
9.12.11.3 (and 9.12.12) Short-circuit performance at 1 500 A
No
F 9.12.11.4 b) (and 9.12.12) Performance at service short-circuit capacity
No
F 9.12.11.4 c) (and 9.12.12.2) Performance at rated short-circuit capacity
F 1
No
9.12.11.4 d)
Performance at I
∆m
F
(and 9.12.12.2) (Verification of RCBO after short-circuit test)
No
9.22.1 Reliability (climatic tests)
G
G
Verification of correct operation at low ambient air temperature of
G1 9.Z1 No
RCBOs for use in the range of .-25 °C to +40 °C
No
IEC 61543:1995, Table 4 - Harmonics, interharmonics
T1.1
Signalling voltage
IEC 61543:1995, Table 4 -
Conducted unidirectional transients of the ms and µs time scale
a
H
T1.2
IEC 61543:1995, Table 5 -
T2.3
No
IEC 61543:1995, Table 5 - Conducted sine-wave voltages or currents
T2.1
Radiated high-frequency phenomena
IEC 61543:1995, Table 5 -
Fast Conducted unidirectional transients of the ns time
I
T2.5
scale (burst)
IEC 61543:1995, Table 5 -
T2.2
No
IEC 61543:1995, Table 5 - Conducted common mode disturbances in the frequency
T2.6 range lower than 150 kHz
J
Electrostatic discharges
IEC 61543:1995, Table 6 -
T3.1
a) For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.
Annex C
(normative)
Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type B RCCBs
Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table C.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 and A.3 of EN 61008-1:2012.
Table C.1 – Test sequences for Type B RCCBs
Test Tests according to Additional tests Test (or inspection)
sequence EN 61008-1 and according to
EN 61008-2-1 this standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
9.15 No Trip-free mechanism
9.4 No Reliability of screws, current-carrying parts and connections
A
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
Verification of the RCD after
9.13.1 9.2.4
test sequence
Resistance to heat
9.13.2
No
9.13.3
8.1.3 No Clearances and creepage distances (internal parts)
9.14 No Resistance to abnormal heat and to fire
9.7 No Test of dielectric properties
9.8 No Temperature rise
9.20 No Resistance of insulation against impulse voltages
B
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
-- 9.2.4 Verification of the RCD after test sequence
9.10 No Mechanical and electrical endurance
C
-- 9.2.4 Verification of the RCD after test sequence
9.9 No Residual operating characteristics
Verification of the correct operation in case of a steady
9.1.2
D D0 increase of composite residual current
Verification of the correct operation in case of sudden
9.1.3
appearance of composite residual current
- 9 - EN 62423:2012
Verification of the correct operation in case of residual
smooth direct current without load for ratings of I not tested
9.2.1.7.1 ∆n
in D
9.17 No Behaviour in the case of failure of the line voltage
9.19 9.1.5 Unwanted tripping
Behaviour in the case of surge currents
9.1.6 Behaviour in the case of inrush residual currents
9.1.4 Correct operation for RCD powered on two poles only
9.2.3 Correct operation for RCD powered on two poles only
a
9.21.1 9.1.7 Type A residual current devices
D
9.2.1 Type B residual current devices
9.2.2 Tests at temperature limits
No Performance at I
9.11.2.3 a) and b)
∆m
9.16 No Test device
9.12 No Resistance to mechanical shock and impact
9.18 No Non-operating current under overcurrent conditions
-- 9.2.4 Verification of the RCD after test sequence
9.11.2.3 c) No Verification of the suitability in IT system
D2
-- 9.2.4 Verification of the RCD after test sequence
No Coordination at I
9.11.2.4 a)
nc
E No Performance at I
9.11.2.2
m
-- 9.2.4 Verification of the RCD after test sequence
No Coordination at I
9.11.2.4 b)
m
F No Coordination at I
9.11.2.4 c)
∆c
-- 9.2.4 Verification of the RCD after test sequence
9.22.1 No Reliability (climatic tests)
G
-- 9.2.4 Verification of the RCD after test sequence
Verification of correct operation at low ambient air temperature of
9.Z1 No
RCCBs for use in the range of .-25 °C to +40 °C
G
9.2.4 Verification of the RCD after test sequence
No
EN 61543:1995, Harmonics, interharmonics
Table 4 -T1.1
Signalling voltage
EN 61543:1995,
b
Conducted unidirectional transients of the ms and µs time
H
Table 4 -T1.2
scale
EN 61543:1995,
Table 5 -T2.3
EN 61543:1995, No Conducted oscillatory voltages or currents
Table 5 -T2.1
Radiated high-frequency phenomena
EN 61543:1995,Table
Conducted unidirectional transients of the ns time scale
I
5 -T2.5
(burst)
EN 61543:1995,
Table 5 -T2.2
EN 61543:1995, No
Conducted common mode disturbances in the frequency range
Table 5 -T2.6
lower than 150 kHz
J
EN 61543:1995,
Electrostatic discharges
Table 6 –T3.1
a
For devices having different residual current detection systems, for which the test according to 9.21.1 was made
without supply voltage, an additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 U to verify
n
that there is no interference between the different systems. Only the lower limits of the tripping currents are verified.
b
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.
Annex D
(normative)
Number of samples to be submitted and test sequences
to be applied for verification of conformity for Type B RCBOs
Verification of conformity may be made
– by the manufacturer for the purpose of suppliers declaration (13.5.1 of ISO/IEC Guide 2);
– by an independent body for certification (13.5.2 of ISO/IEC Guide 2).
According to the terminology of ISO/IEC Guide 2 the term "certification" can be used for the
second case only.
The tests are made according to Table D.1 below, where the tests in each sequence are
carried out in the order indicated.
The sampling procedure is given in A.2 to A.5 of EN 61009-1:2012.
Table D.1 – Test sequences for Type B RCBOs
Test Tests according to Additional tests Test (or Inspection)
sequence EN 61009-1 and according to
EN 61009-2-1 this standard
6 6 Marking
8.1.1 No General
8.1.2 No Mechanism
9.3 No Indelibility of marking
8.1.3 No Clearance and creepage distances (external parts only)
8.1.6 No Non-interchangeability
9.11 No Trip-free mechanism
9.4 No Reliability of screws, current-carrying parts and connections
A
9.5 No Reliability of terminals for external conductors
9.6 No Protection against electric shock
Verification of the RCD
9.14.1 9.2.4
after test sequence
Resistance to heat
9.14.2
No
9.14.3
8.1.3 No Clearances and creepage distances (internal parts)
9.15 No Resistance to abnormal heat and to fire
9.7 No Dielectric properties
9.8 No Temperature rise
9.20 No Resistance of insulation against impulse voltages
B
9.22.2 No Reliability at 40 °C
9.23 No Ageing of electronic components
-- 9.2.4 Verification of the RCD after test sequence
9.10 No Mechanical and electrical endurance
-- 9.2.4 Verification of the RCD after test sequence
C C
9.12.11.2.1 Performance at reduced short-circuit currents
No
(and 9.12.12) (Verification of the RCBO after the short-circuit tests)
- 11 - EN 62423:2012
Short-circuit test for verifying the suitability of RCBOs for use
9.12.11.2.2
in IT systems
C No
(and 9.12.12)
(Verification of the RCBO after the short-circuit tests)
9.9.1 No Operating characteristics under residual current conditions
Verification of the correct operation in case of a steady
9.1.2
increase of composite residual current
Verification of the correct operation in case of sudden
D 9.1.3
appearance of composite residual current
Verification of the correct operation in case of residual
smooth direct current without load for ratings of I not tested
9.2.1.7.1 ∆n
in D
9.17 No Behaviour in the case of failure of the line voltage
9.19 9.1.5 Behaviour in the case of surge currents
D
9.1.6 Behaviour in the case of inrush residual currents
9.1.4 Correct operation for RCD powered on two poles only
9.2.3 Correct operation for RCD powered on two poles only
a
9.21.1 9.1.7 Type A residual current devices
D
9.2.1 Type B residual current devices
9.2.2 Tests at temperature limits
No Performance at I
9.12.13
∆m
9.16 No Test device
-- 9.2.4 Verification of the RCD after test sequence
9.9.2 No Overcurrent operating characteristics
E
No Limiting value of overcurrent in case of a single-phase load
9.18
through a 3-pole or 4-pole RCBO
9.13 No Resistance to mechanical shock and impact
E
9.12.11.3 (and 9.12.12) No Short-circuit performance at 1 500 A
9.12.11.4 b)
No
F Performance at service short-circuit capacity
(and 9.12.12)
9.12.11.4 c)
No
F Performance at rated short-circuit capacity
(and 9.12.12.2)
No
9.12.11.4 d) Performance at I
∆m
F
(and 9.12.12.2) (Verification of RCBO after short-circuit test)
9.22.1 No Reliability (climatic tests)
G
-- 9.2.4 Verification of the RCD after test sequence
Verification of correct operation at low ambient air temperature of
9.Z1 No
RCBOs for use in the range of .-25 °C to +40 °C
G
9.2.4 Verification of the RCD after test sequence
EN 61543:1995, Table 4 No
-T1.1
Harmonics, interharmonics
Signalling voltage
b EN 61543:1995, Table 4
H
-T1.2
Conducted unidirectional transients of the ms and µs time
scale
EN 61543:1995 Table
5 -T2.3
No
EN 61543:1995, Table 5 Conducted oscillatory voltages or currents
-T2.1 Radiated high-frequency phenomena
EN 61543:1995, Table 5 Conducted unidirectional transients of the ns time scale
I
(burst)
-T2.5
EN 61543:1995, Table
5 -T2.2
EN 61543:1995, Table No Conducted common mode disturbances in the frequency range
5 -T2.6 lower than 150 kHz
J
EN 61543:1995, Table
Electrostatic discharges
6 –T3.1
a
For devices having different residual current detection systems, for which the test according to 9.21.1 was made
without supply voltage, an additional test according to 9.21.1.1 shall be made with a supply voltage of 1,1 U to verify
n
that there is no interference between the different systems. Only the lower limits of the tripping currents are verified.
b
For devices containing a continuously operating oscillator, the test of CISPR 14-1 shall be carried out on the samples
prior to the tests of this sequence.
- 13 - EN 62423:2012
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year
CISPR 14-1 2005 Electromagnetic compatibility - EN 55014-1 2006
+ corr. January 2009 Requirements for household appliances,
electric tools and similar apparatus -
Part 1: Emission
IEC/TS 60479-1 - Effects of current on human beings and - -
livestock -
Part 1: General aspects
IEC/TS 60479-2 - Effects of current on human beings and - -
livestock -
Part 2: Special aspects
IEC 61008 Series Residual current operated circuit-breakers EN 61008 Series
without integral overcurrent protection for
household and similar uses (RCCB's)
IEC 61009 Series Residual current operated circuit-breakers EN 61009 Series
with integral overcurrent protection for
household and similar uses (RCBO's)
IEC 61543 1995 Residual current-operated protective devices EN 61543 1995
(RCDs) for household and similar use - + corr. December 1997
Electromagnetic compatibility + A12 2005
Annex ZB
(normative)
Special national conditions
Special national condition: National characteristic or practice that cannot be changed even over a
long period, e.g. climatic conditions, electrical earthing conditions.
NOTE If it affects harmonization, it forms part of the European Standard / Harmonization Document.
For the countries in which the relevant special national conditions apply these provisions are
normative, for other countries they are informative.
Clause Special national condition
The Netherlands
Scope Add the following:
This standard together with these requirements apply for 2 pole type B RCD for use in TN
and TT distribution systems for protection of line and neutral circuits (L-N).
Modify note 2 reading: additional requirements for 1 pole devices for use in TN-S or TN-
C-S systems and 2 pole devices (L-L) for use between phases are under consideration
3.2
Modify as follows
3.2 residual current devices for which tripping is ensured as for type A according to
EN 61008-1 or EN 61009-1, as applicable, and in addition for the following residual
currents:
3.2.1 Type B residual current devices with 3 or 4 poles
Existing text
3.2.2 Type B residual current devices with 2 poles
Residual current devices for which tripping is ensured as for RCD type A according
EN 61008-1 or EN 61009-1, as applicable , and in addition:
- for residual sinusoidal alternating currents up to 1 000 Hz,
- for residual pulsating direct currents,
- for residual alternating currents superimposed on a smooth direct current,
- for residual pulsating rectified d.c which results from 2 phases,
- for residual d.c currents that may result from inverter circuits.
NOTE The above 5th dash refers to fault conditions in micro generators, such as fuel cells or PV systems, being
connected through an inverter to the electrical installation connected in turn to another supply source (in general
the public supply system).
- 15 - EN 62423:2012
5.1 Add to the last dash:
- for 3 and 4 pole residual current devices only.
Add a following new dash:
- for residual direct currents originating from invertors connected to the supply
system.
5.4 Add the following new subclause
5.4 Standard values of break time and non-actuating time for general type 2 pole B
type RCDs in case of residual pulsating direct currents which may result from an
inverter circuit connected to the supply system.
Table 3 – Standard values of non-operating current and break times for general
type 2-pole B type RCDs in case of residual pulsating direct currents which may
result from an inverter circuit connected to the supply system
Standard values of break time (s) at a residual current
composed by a smooth dc current and a half wave rectified
sinusoidal current having opposite polarity
I I I I
Δ 1 Δ 2 Δ 3 Δ 4
Smooth residual current + 1,5 I + 3 I + 6 I + 15 I
Δn Δn Δn Δn
Half wave sinusoidal - 1,125 I - 2,25 I - 4,5 I - 11,25 I
Δn Δn Δn Δn
residual current (peak
value) 1
Break time Non-tripping 0,3 0,15 0,04
8.1.4
Add to this clause the following text (Not applicable for 2 pole devices L-N).
8.1.5 Add to this clause the following text (Not applicable for 2 pole devices).
8.1.6
Add to this clause the following text (Not applicable for 2 pole devices).
8.1.7 Add the following new subclause
8.1.7 Residual pulsating direct currents originating from a single phase inverter
circuit connected to the supply system
2 pole type B RCDs shall operate in response to a steady increase of residual pulsating
direct currents resulting from an inverter connected to the supply system within the limits
of the composed residual current according to table 3 between the values I and I
Δ 1 Δ 2.
2 pole type B RCDs shall operate in response to a sudden appearance of residual
pulsating direct currents resulting from an inverter connected to the supply system within
the time limits specified in table 3 for the currents I , I and ≥ I
Δ 2 Δ 3 Δ 4.
Compliance is checked by the test of 9.1.7.1 and 9.1.7.2.
9.1.6 Modify the heading reading
9.1.6 Verification of the correct operation of 3 and 4 pole type B RCDs in case of
residual smooth direct current
9.1.7 Add a following new clause
9.1.7 Verification of the correct operation of 2 pole type B RCDs in case of residual
direct currents when protecting a single phase inverter circuit connected to the
supply
The RCD is connected as shown in Figure 1 and supplied with rated voltage.
9.1.7.1 Slowly rising residual pulsating current
The test circuit being connected to line and neutral terminal or if applicable to the line
terminals, the RCD and test switch S being closed
The test currents I and I are set to 0,2 x the values as given for the tripping current I .
1 2 Δ 2
Current I is increased to the value 0,3 x the value of the smooth residual current
applicable for I followed by increasing the half wave pulsating residual current I to 0,3
Δ 2 2
times the value as given for I
Δ 2
Subsequently the currents are further increased in steps to 0,4 times, 0,5 times, 0,6 times
etc of the residual operating current I .
Δ 2
The RCD shall not trip before the current reaches the value I and shall trip before this
Δ1
current exceeds the value I
Δ 2.
9.1.7.2 Suddenly appearing residual pulsating current
The RCD is initially closed but bypassed by calibration links B With switches S and S
L. 1
closed the currents I and I are set in turn to the values as applicable for I , I and I ,
1 2 Δ2 Δ3 Δ 4
respectively, as given in Table 3.
Switches S and S are then opened and the calibration links are removed.
Switch S is first closed, then S is closed and the residual currents start to flow.
The break time is measured for each value and shall not exceed the specified break times
given in Table 3. This test is repeated 3 times for each of the residual current values.
9.3 Modify this clause as follows:
2 pole B type RCD shall trip within 0,3 s with the composite residual test current I as
Δ2
specified in Table 2.
3 and 4 pole type B RCD shall trip with a test current of 2,5 I with smooth direct current.
Δn
- 17 - EN 62423:2012
Key
A ammeters
S and S all-pole switch
R and R adjustable resistors
1 2
D diode
B d.c supply
RCD 2-pole RCD under test
B bridging links for the RCD for calibration of the test currents of 9.1.7.2 and
L
9.3
Figure 1 – Test circuit for the verification of correct operation of 2 pole type B RCD
for protection of single phase inverter circuit connected to a supply L-N.
Annex A Modify or add the following items in Table A1:
Test Additional
Test according to test Test (or inspection)
sequence EN 61008-1 according to
this standard
D D
9.1.6.1 Verification of correct operation of 3
and 4 pole type B RCCB in case of
residual smooth direct current
without load for ratings of I not
Δn
tested in D
9.1.7 Verification of correct operation of 2
pole type B RCCB in case of
residual currents when protecting a
single phase inverter circuit
connected to the supply
Annex B Modify or add the following items in Table B1:
Test Additional
Test according to test Test (or inspection)
sequence EN 61009-1 according
this standard
D D 9.1.6.1 Verification of correct operation of 3
and 4 pole type B RCBO in case of
residual smooth direct current
without load for ratings of I not
Δn
tested in D
9.1.7 Verification of correct operation of 2
pole type B RCBO in case of
residual currents when protecting a
single phase inverter circuit
connected to the supply
Annex C
Modify and add the following items in Annex C
rd
Add to the beginning of the 3 paragraph the wording: “In case of 3 or 4 pole RCD”.
th
paragraph:
Introduce the following new 4
In case of 2 pole RCD a d.c residual current composed by a smooth d.c. current having
the value I and a half wave pulsating residual current with power frequency and having
the peak value of – 0,75 I is passed through one pole. The type B RCCB or type B RCBO,
as applicable, shall not trip at a current less than or equal to the value specified for I
Δn1
and shall trip at the current I within the time specified in Table 3.
Δn2
__________
- 19 - EN 62423:2012
Annex ZZ
(informative)
Coverage of Essential Requirements of EU Directives
This European Standard has been prepared under a mandate given to CENELEC by the
European Commission and the European Free Trade Association and within its scope the
standard covers all relevant essential requirements as given in Article 1 of Annex I of the EU
Directive 2004/108/EC.
Compliance with this standard provides one means of conformity with the specified essential
requirements of the Directive(s) concerned.
WARNING: Other requirements and other EU Directives may be applicable to the products
falling within the scope of this standard.
IEC 62423 ®
Edition 2.0 2009-11
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Type F and type B residual current operated circuit-breakers with and without
integral overcurrent protection for household and similar uses
Interrupteurs automatiques à courant différentiel résiduel de type B et de type F
avec et sans protection contre les surintensités incorporée pour usages
domestiques et analogues
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
W
CODE PRIX
ICS 29.120; 29.120.50 ISBN 978-2-88910-700-1
– 2 – 62423 © IEC:2009
CONTENTS
FOREWORD.5
INTRODUCTION.7
1 Scope.8
2 Normative references .8
3 Terms and definitions .9
4 Classification.9
4.1 According to behaviour in presence of d.c. components .9
5 Characteristics .10
5.1 Type F residual current device .10
5.2 Type B residual current device .10
5.2.1 General .10
5.2.2 Standard values of break time and non-actuating time for residual
direct currents which result from rectifying circuits and for residual
smooth direct current.10
5.2.3 Values of tripping current according to frequencies which differ from
the rated frequency 50/60 Hz.11
6 Marking and other product information.11
6.1 Marking for Type F RCDs .11
6.2 Marking for Type B RCDs.11
7 Standard conditions for operation in service and for installation.11
8 Conditions for construction and operation.12
8.1 Conditions for Type F and Type B RCDs − Requirements for operation in
case of sinusoidal residual currents comprising of multi-frequency
components resulting from control equipment supplied from single phase .12
8.2 Conditions for Type B RCDs.12
8.2.1 Operation in response to the type of residual current.12
8.3 Behaviour of Type F and Type B RCDs .13
8.3.1 Behaviour of RCDs in the case of surge residual currents .13
8.3.2 Behaviour of RCDs in the case of inrush residual currents.14
8.3.3 Behaviour in case of residual pulsating direct currents in presence of
a standing smooth direct current of 0,01 A.14
9 Tests .14
9.1 Tests for Type F and Type B RCDs .14
9.1.1 General .14
9.1.2 Verification of the correct operation in case of a steady increase of
composite residual current.14
9.1.3 Verification of the correct operation in case of sudden appearance of
composite residual current.15
9.1.4 Verification of the correct operation for four-pole Type F RCD
powered on two poles only .15
9.1.5 Verification of behaviour at surge currents up to 3 000 A (8/20 μs
surge current test) .15
9.1.6 Verification of behaviour in the case of inrush residual currents.16
9.1.7 Verification of the correct operation in case of residual pulsating
direct currents in presence of a standing smooth direct current of
0,01 A .16
9.2 Tests for Type B RCDs.16
62423 © IEC:2009 – 3 –
9.2.1 Verification of the operating characteristic at the reference
temperature (20 ± 5) °C.16
9.2.2 Tests at the temperature limits .19
9.2.3 Verification of the correct operation for three- and four-pole Type B
RCDs powered on two poles only .19
9.2.4 Verification of the RCD after test sequences.19
Annex A (normative) Number of samples to be submitted and test sequences to be
applied for verification of conformity for type F RCCBs .28
Annex B (normative) Number of samples to be submitted and test sequences to be
applied for verification of conformity for Type F RCBOs .30
Annex C (normative) Number of samples to be submitted and test sequences to be
applied for verification of conformity for Type B RCCBs .32
Annex D (normative) Number of samples to be submitted and test sequences to be
applied for verification of conformity for Type B RCBOs .34
Annex E (normative) Routine tests for Type F and Type B RC
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...