Thermal energy meters - Part 6: Installation, commissioning, operational monitoring and maintenance

This document specifies commissioning, operational monitoring and maintenance and applies to thermal energy meters. Thermal energy meters are instruments intended for measuring the energy which in a heat-exchange circuit is absorbed (cooling) or given up (heating) by a liquid called the heat-conveying liquid. The thermal energy meter indicates the quantity of thermal energy in legal units.
This document covers meters for closed systems only, where the differential pressure over the thermal load is limited.
This document is not applicable to:
-   electrical safety requirements;
-   pressure safety requirements; and
-   surface mounted temperature sensors.

Thermische Energiemessgeräte - Teil 6: Einbau, Inbetriebnahme, Überwachung und Wartung

Dieses Dokument legt die Inbetriebnahme, Betriebsüberwachung und Wartung fest und gilt für thermische Energiemessgeräte. Thermische Energiemessgeräte sind Messgeräte, die dazu bestimmt sind, die Energie zu messen, die in einem Wärmetauschkreislauf von einer als Wärmeträgerflüssigkeit bezeichneten Flüssigkeit aufgenommen (Kühlung) oder abgegeben (Heizung) wird. Das thermische Energiemessgerät zeigt die Menge der thermischen Energie in gesetzlichen Einheiten an.
Dieses Dokument behandelt nur Messgeräte für geschlossene Systeme, bei denen der Differenzdruck über die thermische Last begrenzt ist.
Dieses Dokument ist nicht anwendbar für:
—   Anforderungen an die elektrische Sicherheit;
—   Anforderungen an die Drucksicherheit;
—   oberflächenmontierte Temperaturfühler.

Compteurs d'énergie thermique - Partie 6 : Installation, mise en service, surveillance et maintenance

Le présent document spécifie l’installation, la mise en service, la surveillance de fonctionnement et la maintenance et s’applique aux compteurs d’énergie thermique. Les compteurs d’énergie thermique sont des instruments destinés à mesurer l’énergie thermique qui, dans un circuit d’échange thermique, est absorbée (refroidissement) ou cédée (chauffage) par un liquide appelé « liquide caloporteur ». Le compteur d’énergie thermique fournit la quantité d’énergie thermique en unités de mesure légales.
Le présent document couvre les compteurs pour les systèmes fermés uniquement, où la pression différentielle dans la charge thermique est limitée.
Le présent document ne s’applique pas :
-   aux prescriptions de sécurité électrique ;
-   aux prescriptions de sécurité relatives à la pression ; ni
-   aux sondes de température montées en surface.

Merilniki toplote - 6. del: Vgradnja, zagon, nadzor in vzdrževanje

Ta dokument določa zagon, nadzor delovanja in vzdrževanje ter se uporablja za merilnike toplote. Merilniki toplote so instrumenti, namenjeni merjenju energije, ki jo v krogotoku toplotne izmenjave absorbira (hlajenje) ali oddaja (ogrevanje) tekočina, imenovana tekočina za prenos toplote. Merilnik toplote podaja količino toplote v predpisanih enotah.
Ta dokument ne zajema zahtev za električno varnost.
Ta dokument ne zajema tlačnih varnostnih zahtev.
Ta dokument ne zajema površinsko nameščenih senzorjev temperature.
Ta dokument zajema samo števce za zaprte sisteme, pri katerih je diferencialni tlak nad toplotno obremenitvijo omejen.

General Information

Status
Published
Publication Date
06-Sep-2022
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
07-Sep-2022
Due Date
22-Nov-2021
Completion Date
07-Sep-2022

Relations

Standard
EN 1434-6:2022
English language
28 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2022
Nadomešča:
SIST EN 1434-6:2016+A1:2019
Merilniki toplote - 6. del: Vgradnja, zagon, nadzor in vzdrževanje
Thermal energy meters - Part 6: Installation, commissioning, operational monitoring and
maintenance
Thermische Energiemessgeräte - Teil 6: Einbau, Inbetriebnahme, Überwachung und
Wartung
Compteurs d'énergie thermique - Partie 6 : Installation, mise en service, surveillance et
maintenance
Ta slovenski standard je istoveten z: EN 1434-6:2022
ICS:
17.200.20 Instrumenti za merjenje Temperature-measuring
temperature instruments
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 1434-6
EUROPEAN STANDARD
NORME EUROPÉENNE
September 2022
EUROPÄISCHE NORM
ICS 17.200.20 Supersedes EN 1434-6:2015+A1:2019
English Version
Thermal energy meters - Part 6: Installation,
commissioning, operational monitoring and maintenance
Compteurs d'énergie thermique - Partie 6 : Installation, Thermische Energiemessgeräte - Teil 6: Einbau,
mise en service, surveillance et maintenance Inbetriebnahme, Überwachung und Wartung
This European Standard was approved by CEN on 17 July 2022.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1434-6:2022 E
worldwide for CEN national Members.

Contents Page
European foreword . 3
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 5
4 Requirements . 6
4.1 Design requirements . 6
4.2 Installation requirements. 8
4.3 Thermal energy meter commissioning . 8
4.3.1 General . 8
4.3.2 Certification check . 9
4.3.3 Installation check . 9
4.3.4 Thermal energy meter security . 9
4.4 Operating requirements with heat-conveying liquids other than water . 10
Annex A (informative) Thermal energy meter installation . 11
A.1 General . 11
A.2 Criteria for the selection of a thermal energy meter . 11
A.3 Quality of the heat conveying liquid . 12
A.3.1 General . 12
A.3.2 Primary water quality . 12
A.3.3 Secondary water quality. 12
A.3.4 Monitoring heat conveying liquids other than water . 12
A.4 Thermal energy meter flow circuit design . 14
A.5 Additional recommendations for cooling application . 15
A.6 Examples for the installation of thermal energy meters . 15
A.7 Additional recommendations for large pipes > DN 250 . 21
Annex B (informative) Thermal energy meter operational monitoring and maintenance . 23
B.1 Introduction . 23
B.2 Thermal energy meter service life . 23
B.3 Thermal energy meter monitoring procedures . 23
B.4 Maintenance check list . 24
B.5 Replacement of failed thermal energy meters . 24
Annex C (informative) Suggested gauge for checking the dimensions of installed
temperature sensor pockets . 26
Annex ZA (informative) Relationship between this European Standard and the essential
requirements of Directive 2014/32/EU aimed to be covered . 27
Bibliography. 28
European foreword
This document (EN 1434-6:2022) has been prepared by Technical Committee CEN/TC 176 “Thermal
energy meters”, the secretariat of which is held by SIS.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2023, and conflicting national standards shall
be withdrawn at the latest by March 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1434-6:2015+A1:2019.
EN 1434, Thermal energy meters, consists of the following parts:
— Part 1: General requirements;
— Part 2: Constructional requirements;
— Part 3: Data exchange and interfaces ;
— Part 4: Pattern approval tests;
— Part 5: Initial verification tests;
— Part 6: Installation, commissioning, operational monitoring and maintenance.
In comparison with EN 1434-6:2015+A1:2019, the following changes have been made:
— the title of this standard has been changed into “Thermal energy meters”;
— Annex ZA has been adjusted to the new Directive 2014/32/EU (MID);
— wording “heat meter” has been partly and where applicable changed into “thermal energy meter”
within the whole document;
— new clauses have been inserted: 4.1.4, 4.1.5, 4.4, A.3.4, 3.7.
This document has been prepared under a Standardization Request given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Directive(s) / Regulation(s).
For relationship with EU Directive(s) / Regulation(s), see informative Annex ZA, which is an integral
part of this document.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,

EN 1434-3 is maintained by CEN/TC 294.
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the
United Kingdom.
1 Scope
This document specifies commissioning, operational monitoring and maintenance and applies to
thermal energy meters. Thermal energy meters are instruments intended for measuring the energy
which in a heat-exchange circuit is absorbed (cooling) or given up (heating) by a liquid called the heat-
conveying liquid. The thermal energy meter indicates the quantity of thermal energy in legal units.
This document covers meters for closed systems only, where the differential pressure over the thermal
load is limited.
This document is not applicable to:
— electrical safety requirements;
— pressure safety requirements; and
— surface mounted temperature sensors.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 1434-1:2022, Thermal energy meters — Part 1: General requirements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1434-1:2022 and the following
apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp
3.1
thermal energy system
heating or cooling installations of the dwelling or premises, including the exchange circuit, the thermal
energy meter, the associated fittings and the electrical equipment
Note 1 to entry: The heating or cooling systems typically commences and finishes at the two connections to the
heat or cooling mains.
3.2
thermal energy mains
heat or cooling supplier’s distribution pipes to which the consumer's installation is connected
3.3
inlet and outlet limbs
pipes connecting the heating or cooling system to the thermal energy mains
3.4
primary circuit
circuit hydraulically connected to the thermal energy mains
3.5
secondary circuit
circuit hydraulically separated from the primary circuit
3.6
competent authority
persons or organizations charged with the responsibility for the thermal energy meter and/or its
installation
3.7
cooling system
cooling installation of an apartment or building, including cooling exchanger circuit, cooling meter,
accessories and electrical equipment
Note 1 to entry: The cooling system usually starts and ends at the two connections to the cooling distribution
network.
4 Requirements
4.1 Design requirements
4.1.1 When designing the heating and cooling system, the thermal energy meter's manufacturer
specification and installation instructions shall be followed. The design shall make monitoring and
maintenance possible. An example is given in Annex B.
For q 6 m /h and less, it is recommended to use direct short sensors. To achieve good temperature
p
sensitivity, direct sensors should be installed without temperature pockets. Temperature pockets
should only be used when required for safety reasons.
These installation points shall be insulated in accordance with the applicable legal regulations or other
technical measures shall be taken to reduce dissipation errors.
4.1.2 To avoid systematic measurement errors, the temperature sensors in the supply and return
pipes shall be used at almost identical pressure conditions.
For typical systematic negative error as a function of differential pressure and temperature difference,
see Table 1. Table 1 is only applicable to the medium water.
Table 1 — Typical systematic negative error as a function of differential pressure and
temperature difference
Diff pressure Temperature difference in K
in bar
3 5 10 20 30 40 50 60
0,5 0,2 0,2 0,1 0,1 0,1 0 0 0
1 0,5 0,4 0,3 0,2 0,1 0,1 0,1 0,1
2 0,9 0,7 0,5 0,3 0,2 0,2 0,1 0,1
3 1,4 1,1 0,8 0,5 0,3 0,2 0,2 0,2
4 1,8 1,5 1,0 0,6 0,4 0,3 0,3 0,2
5 2,3 1,9 1,3 0,8 0,5 0,4 0,3 0,3
6 2,7 2,2 1,5 0,9 0,6 0,5 0,4 0,3
7 3,2 2,6 1,9 1,1 0,7 0,6 0,5 0,4
8 3,6 3,0 2,0 1,2 0,9 0,7 0,5 0,4
9 4,1 3,3 2,3 1,4 1,0 0,7 0,6 0,5
10 4,5 4,0 2,5 1,5 1,1 0,8 0,7 0,5
The values are shown as fraction of the maximum permissible error for the calculator. The values below
the marked line are higher than 1/3rd of the maximum permissible error for the thermal energy
calculator. If the resulting error is higher than 1/3rd of the maximum permissible error, it is
recommended to change the installation to have smaller differential pressure.
NOTE In cases where flows from two different loads with different temperatures (e.g. for space heating and
domestic warm water) are merged together just before the temperature sensor, the optimum position for the
sensor is after the flow sensor.
4.1.3 For bifunctional meters for change-over systems between heating and cooling additional
requirements are necessary to ensure the correct switching over function between the heating and
cooling register. These requirements are:
— the lowest operating temperature in the inlet pipe at heating conditions shall be at least 3 °C higher
than any specified optional switching over temperature θ ;
hc
— the highest operating temperature in the inlet pipe at cooling conditions shall be at least 3 °C lower
than any specified optional switching over temperature θ ;
hc
— the minimum temperature difference in heating and cooling application shall be more than 3 K.
NOTE The above-mentioned temperature range of at least 3 °C covers the maximum accepted uncertainty in
measured temperature and the cable resistance.
A temperature sensor with smaller tolerances than 2 °C for measuring of the measured temperature is
recommended.
4.1.4 In the heating or cooling system there shall be at least one tapping point for the check according
to 4.4 “Operating requirements”.
4.1.5 Temperature sensors for fast response meters shall be direct mounted probes, type DS or type
DL. Pocket mounted probes are not suitable for fast response meters.
4.2 Installation requirements
The thermal energy meter shall be installed in accordance with the manufacturer's instructions.
Before installation, the circuit into which the flow sensor is to be installed shall be thoroughly flushed to
remove debris. The strainer, where fitted, shall be cleaned.
The thermal energy meter shall be protected from the risk of damage by shock and vibration induced by
the surroundings at the place of installation.
The thermal energy meter shall not be subjected to undue stresses caused by pipes and fittings.
The pipelines of the heating system up and downstream of the thermal energy meter shall be
adequately anchored.
Thermal energy meters designed to operate from an AC mains supply shall be wired in accordance with
wiring regulations applicable.
The AC mains power supply shall be secured against accidental interruption. However, circuit
protection shall be incorporated according to the state of the art, to safely disconnect the device when
electrical problems occur.
Measurement signal leads shall not be laid directly alongside other leads such as mains supply cables,
low voltage supply cables and data communication cables and shall be independently supported. The
separation between those groups shall not be less than 50 mm. Unless the calculator under installation
was type tested according to the latest version of EN 1434-4:2022, it is recommended to install cables
and calculators with a distance of at least 60 cm to strong electromagnetic fields, e.g. frequency
controlled pumps and similar high energy mains cables.
Mains and external signal cables longer than 10 m shall in areas where lightning is frequent be
protected with an external lightning surge protection at the cable entrance to the building.
Each signal lead between temperature sensors and calculator shall be one continuous length without
joints except 4-wire connection solutions which are approved.
Signal circuits between parts of a thermal energy meter shall be so installed as to deter unauthorized
interference and disconnection.
Precautions shall be taken to prevent damage to the thermal energy meter by unfavourable hydraulic
conditions (cavitation, surging, water hammer).
When the installation of the thermal energy meters is complete, it shall be inspected and approved by
representatives of the competent authority in accordance with established procedures and the
inspection shall be documented.
Installation should be done according to national legislation on legal metrology.
4.3 Thermal energy meter commissioning
4.3.1 General
The responsibility for the carrying out of each of the inspection phases is not necessarily restricted to
one person or one authority depending on the national legislation on legal metrology, but however
arranged, the following points shall be addressed and responsibilities defined.
4.3.2 Certification check
Before commissioning commences it shall be ascertained firstly that the correct thermal energy meter
has been installed by comparing the thermal energy meter manufacturer's type and size designation
against the system specification. Secondly, it shall be checked that the thermal energy meter, if a
complete instrument, bears the correct pattern approval mark and, if a combined instrument, that each
of the meters sub-assemblies bear the pattern approval marks stipulated in the pattern approval
document for the thermal energy meter installed.
4.3.3 Installation check
At least the following points shall be checked:
— Is the flow sensor mounted in the correct position and with the correct flow direction?
— Does the temperature sensor fit correctly into the pocket (pockets shall be marked “EN 1434” or
dimensions checked)? Instructions on how to check this can be found in Annex C.
— Are the temperature sensors correctly installed?
— Is the thermal energy meter installed at a safe distance from sources of electromagnetic
interference (switchgear, electric motors, fluorescent lights)?
— If applicable, has the thermal energy meter been correctly earthed?
— The specified protection class (IP) has to be ensured: Is every cable diameter within the minimum
and maximum diameter as specified by the manufacturer?
— Are the gaskets dedicated to the application (e.g. temperature range, pressure, durability,
medium)?
— Are the accessories correctly installed according to the installation instructions of the manufacturer
and operator?
— Is the thermal energy meter seen to be functioning when the heating or cooling system starts
operating?
4.3.4 Thermal energy meter security
At the completion of commissioning, the thermal energy meter's protective devices shall be sealed by
representatives of the competent authority. For any further adjustment of the meter or for replacement
of sub-assemblies, batteries, etc., it will thus be necessary to break one or more seals.
If a seal has to be broken, then the renewal should be conducted in conformity with the national
legislation of legal metrology.
4.4 Operating requirements with heat-conveying liquids other than water
Damage to the liquid due to overheating and oxygen influence shall be prevented by suitable design and
operational management of the system. If the liquid has been damaged, the liquid in the system shall be
exchanged.
The concentration of the heat conveying liquid other than water shall be monitored. Tapping should be
performed through the filling/draining point. Any dead volumes of stagnant liquid shall be drained
before sampling. The concentration shall be determined and documented based on a density
measurement or the refractive index (see A.3.4) when the system is initiated. If it can be demonstrated
that the same accuracy can be achieved by another method, this method may also be used. In addition,
the determined concentration of the filled mixture shall be compared with the initial concentration of
the liquid. If the concentration deviates by more than ± 1,0 % compared to the initial concentration, it
shall be brought to the initial concentration of the system filling (e.g. initiated by dilution or
segregation). When refilling, the concentration of the initial fluid shall be maintained. Another option is
that the meter has the functionality to self-adapt to the new physical properties of the liquid.
It shall then be checked at least every 12 months. The results of the test shall be officially documented
includ
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...