EN 15269-20:2020/prA1
(Amendment)Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 20: Smoke control for doors, shutters, operable fabric curtains and openable windows
- Abstract
This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types:
- hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1);
- horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2);
- metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3).
The following construction products are not covered by this standard:
- unframed glass doors and openable windows;
- sectional doors (including stacking doors);
- vertically and horizontally folding doors;
- horizontally and vertically moving timber sliding doors;
- horizontally and vertically moving framed sliding doors (metal or timber).
In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
- Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications;
- leaf/leaves;
- wall/ceiling fixed elements;
- glazed elements, louvres and/or vents;
- side, transom or overpanels;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
- Status
- Not Published
- Publication Date
- 10-Aug-2027
- Technical Committee
- CEN/TC 127 - Fire safety in buildings
- Drafting Committee
- CEN/TC 127/WG 3 - Fire Doors
- Current Stage
- 4060 - Closure of enquiry - Enquiry
- Start Date
- 06-Aug-2026
- Due Date
- 23-Oct-2025
- Completion Date
- 23-Oct-2025
EN 15269-20:2020/prA1 is a CEN draft amendment to EN 15269-20:2020 on extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their building hardware. It specifies how test results from EN 1634-3 may be extended for smoke control on doors, shutters, operable fabric curtains and openable windows, for use by manufacturers, test laboratories and certification bodies.
What does EN 15269-20:2020/prA1 specify?
EN 15269-20:2020/prA1 specifies the scope and method for extending smoke-control test results to related product variants. It is intended to be read with EN 15269-1 and it focuses on doors, shutters, openable windows and operable fabric curtains of the product types named in the scope.
The document covers:
- hinged and pivoted doors and openable windows, including framed glazed types
- horizontally and vertically moving steel sliding doors, including telescopic doorsets and pass doors
- metal rolling shutters and operable fabric curtains, excluding overlapping systems
The scope also states the main exclusions, which matters because those product families need other rules or other standards. Unframed glass doors and openable windows, sectional doors, folding doors, and timber or framed sliding doors are outside this part.
Annex structure at a glance
| Annex / table | What it covers |
|---|---|
| Annex A | Construction parameter variations for extended application, with separate rules for hinged/pivoted doors and windows, sliding doors and pass doors, metal framed doorsets, glazed elements, supporting construction and hardware |
| Table A.1 | Hinged or pivoted doorsets and openable windows |
| Table A.2 | Sliding and telescopic doorsets, including pass doors |
| Table A.3 | Metal rolling shutters and operable fabric curtains |
| Annex C | Calculation methods for deriving the extended application from test data |
The amendment also updates the document for revised smoke-control performance characteristics and aligns the reporting and reference framework with related CEN documents.
What are the key requirements of EN 15269-20:2020/prA1?
EN 15269-20:2020/prA1 is mainly about controlled extension of a tested configuration, not free design change. The key rule is that a change is allowed only when the relevant annex table permits it or when the document calls for an additional test.
Test basis and classification
The whole approach depends on a successful smoke-control test according to EN 1634-3 and a classification according to EN 13501-2. Annex A uses the result of that test as the reference point for all later variations. In practice, this means a manufacturer cannot claim extended application unless the base specimen has already been tested and classified.
Clause 4 is also important for reporting the test basis correctly. If the test report does not clearly show whether the bottom gap was taped over, the EXAP report is prepared on the basis of maintaining an S classification according to EN 13501-2. That matters because the report has to stay defensible when the test record is incomplete.
Construction variations in Annex A
Annex A is the core of the document. It sets out which construction changes may be accepted for:
- leaf construction and size
- smoke seals, intumescent seals and gap dimensions
- louvres, glazing and decorative or protective finishes
- door frames, thresholds and supporting construction
- building hardware such as locks, hinges, closers, handles and viewers
The practical value is that it tells a manufacturer when a design change can be carried across from a tested product and when a new test scenario is needed. Many of the rules depend on keeping the smoke-sealing system unchanged, which means the seal arrangement is usually the first thing to check before accepting a variant.
Annex A also introduces test scenarios A to I. These scenarios tell the expert whether one-side testing, both-side testing, worst-face testing, or a different specimen configuration is needed. In practice, this reduces unnecessary repeat tests while still protecting the validity of the result.
Product-specific rules
The annex separates rules by product family so that the extended application stays tied to the actual construction:
- Table A.1 covers hinged or pivoted doorsets and openable windows
- Table A.2 covers sliding and telescopic doorsets and pass doors
- Table A.3 covers metal rolling shutters and operable fabric curtains
That distinction matters because the permitted changes are not the same for a hinged doorset and an operable fabric curtain. For example, pass doors have their own rules and must be tested together with the sliding doorset they belong to. For fabric curtains, the document uses separate rules for the curtain fabric, bottom rail, guides, restraining system and barrel-related parts.
Hardware, glazing and supporting construction
The document treats building hardware as part of the tested system. Clause C says hardware must match the relevant technical specification and be suitable for the class of use of the doorset. If a hardware item is removed, openings must not be left unsealed.
Glazing is also tightly controlled. The rules in Annex A and Annex C distinguish when glazing may be added, removed or modified, and they link those changes to the test basis for the door or panel arrangement. For a reader, the main point is that glazing changes are only acceptable when the glazing system and the smoke-sealing system still fit the tested evidence.
Supporting construction is another major topic. The document allows some changes to the wall or floor interface, fixings and mounting position, but only within the rules in the relevant annex tables. This is important because smoke performance often depends as much on the installation as on the door leaf itself.
Calculation methods in Annex C
Annex C provides the calculation methods used to extend results from a successful test. It uses measured air-flow rate, leaking-gap length and clear-opening area to determine the maximum size or gap configuration that can be claimed.
In practice, Annex C helps the expert turn test data into a permitted field of extended application. The amendment keeps the calculation approach tied to the tested configuration and the applicable smoke-control classification, rather than allowing unrestricted scaling.
What terms does EN 15269-20:2020/prA1 define?
- Extended application report (EXAP report) - the report that records the permitted field of extended application for a tested product.
- Ambient Temperature Smoke Control (Sa) - the smoke-control classification for ambient-temperature performance.
- Medium Temperature Smoke Control (S200) - the smoke-control classification for medium-temperature performance.
- Worst face - the side of the test specimen with the higher air-flow rate in the basis tests.
- Pass door - a smaller pedestrian door integrated into a sliding doorset and tested with the sliding doorset it belongs to.
- Doorset - the complete door assembly, including leaf, frame and related elements, treated as one tested configuration.
- Faces and sides of a door leaf - the opening face, closing face, hinge side, lock side, top side and bottom side shown in the document.
Who uses EN 15269-20:2020/prA1?
EN 15269-20:2020/prA1 is used by manufacturers of smoke-control doors, shutters, windows and operable fabric curtains when they want to justify a product variant from an existing test. It is also used by smoke-control testing laboratories, because the annex tables point to the test scenarios that support or limit extension.
Notified product certification bodies use it when they assess whether a changed product can remain within the tested field of application. Engineers, quality managers and buyers use it to check whether a proposed change affects the validity of existing EN 1634-3 evidence, especially for seals, glazing, hardware, supporting construction and size changes.
What changed in EN 15269-20:2020/prA1 from the previous edition?
EN 15269-20:2020/prA1 modifies EN 15269-20:2020, with reference to its corrigendum AC 2022. The amendment states that it updates the document to reflect revised smoke-control performance characteristics under EN 13501-2.
The amendment makes these changes:
- updates Clause 2 with additional normative references
- updates Clause 3 and adds term 3.8
- updates Clause 4, including the rule for unclear bottom-gap tape-over status
- updates Clause 5 so the report is prepared in line with EN 15725 and EN 15269-1
- replaces Annex A, including the construction-variation tables and test-scenario logic
- replaces Annex C, including the calculation methods
Which standards are used with EN 15269-20:2020/prA1?
- EN 15269-1 - gives the general framework for extended application, which this part uses together with its smoke-control rules.
- EN 1634-3 - provides the test method for smoke-control testing, and the extended application is based on test results from this standard.
- EN 13501-2 - provides the classification system used when the test result is turned into a smoke-control classification.
- EN 15725 - sets the principles for EXAP standards and EXAP reports, which the amendment now cites for reporting.
- EN 12433-1 - adds terminology for industrial, commercial and garage doors and gates.
- EN 12433-2 - adds terminology for parts of doors.
- EN 12519 - adds terminology for windows and pedestrian doors.
What does the EN 15269-20:2020/prA1 document contain?
EN 15269-20:2020/prA1 contains the rules experts use to extend a smoke-control test result to a related product configuration. Most of the technical content is in Annex A, where the document lists permissible variations and shows when a new test scenario is needed.
It also contains the calculation methods in Annex C, which convert tested air-flow behaviour and gap geometry into an extended application claim. Those methods are used for design changes, test planning, certification evidence and technical justification of product variants.
The document also includes figures and tables that identify key details such as leaf faces, rebated edges, glazing arrangements, thermal breaks, overlap geometry and support arrangements. In practice, those illustrations help the reader map a real product to the correct rule in the annex tables without guessing how a particular part is meant.
Relations
- Effective Date
- 14-Jun-2023
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
EN 15269-20:2020/prA1 is a draft published by the European Committee for Standardization (CEN). Its full title is "Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 20: Smoke control for doors, shutters, operable fabric curtains and openable windows". This standard covers: This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types: - hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1); - horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2); - metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3). The following construction products are not covered by this standard: - unframed glass doors and openable windows; - sectional doors (including stacking doors); - vertically and horizontally folding doors; - horizontally and vertically moving timber sliding doors; - horizontally and vertically moving framed sliding doors (metal or timber). In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3. Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples: - Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications; - leaf/leaves; - wall/ceiling fixed elements; - glazed elements, louvres and/or vents; - side, transom or overpanels; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).
This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types: - hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1); - horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2); - metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3). The following construction products are not covered by this standard: - unframed glass doors and openable windows; - sectional doors (including stacking doors); - vertically and horizontally folding doors; - horizontally and vertically moving timber sliding doors; - horizontally and vertically moving framed sliding doors (metal or timber). In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3. Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples: - Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications; - leaf/leaves; - wall/ceiling fixed elements; - glazed elements, louvres and/or vents; - side, transom or overpanels; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).
EN 15269-20:2020/prA1 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 15269-20:2020/prA1 has the following relationships with other standards: It is inter standard links to EN 15269-20:2020. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 15269-20:2020/prA1 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
EN 15269-20:2020/prA1 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- European foreword
- 1 Modification to Clause 1 "Scope"
- 2 Modification to Clause 2, "Normative References"
- 3 Modification to Clause 3, "Terms and definitions"
- 3.8 faces and sides of a door leaf
- 4 Modification to Clause 4, "Determination of the field of extended application"
- 5 Modification to Clause 5, "Extended application report"
- 6 Modification to Annex A
- 7 Modification to Annex C
- Annex C
European foreword
This document (EN 15269:20/prA1:2025) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This document is currently submitted to the CEN Enquiry.
In comparison to EN 15269:2020 and its corrigendum AC 2022, the following amendments have been made to adjust the document to the new performance characteristics "S ", "S ", and "S " according to a3 a4 200L EN 13501-2:
- complete editorial and technical revision according to the change of the performance characteristics Sa into S and S ; a3 a4
- Clause 2, "Normative references" updated;
- Clause 3, "Terms and definitions" updated and add term 3.8.;
- Clause 4, "Determination of the field of extended application" updated;
- add information in 4.1.1 for Sa resp. S and S ; a3 a4
- Annex A (normative) "Construction parameter variations": updated, Since the change of the performance characteristics from S to S and S had to be made in many rules in Annex A, not only the a a3 a4 respective changes shown in this amendment, but the entire Annex A was replaced for better usability of the document.
- revised introduction in the 4th sentence of the “Construction parameter variations“ of Annex A delete of “Otherwise not possible without additional test” and change of “Not possible without additional test” into “Not possible” in alle rules of Table A.1 to A.3;
- editorial and technical revision according to the performance characteristics S in the last 200L sentence of the “Construction parameter variations“ of Annex A, in Table A.1 rule A.3.2, in Table A.2 rule A.1.2 to A.1.4 and 1.9, in Table A.3 rule A.1.2 to A.1.4 and 1.9, and in C.3 of Annex C;
- editorial change in figure A.5;
- editorial change in figure A.61;
- editorial change in figure A.96.
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E)
1 Modification to Clause 1 "Scope"
In the nth bullet, replace “(S )” with “(S or S )”, and add “and S )” after “(S )”. a a3 a4 200L 200
2 Modification to Clause 2, "Normative References"
Add the following references:
“EN 12433-1, Industrial, commercial and garage doors and gates - Terminology — Part 1: Types of doors” “EN 12433-2, Industrial, commercial and garage doors and gates - Terminology — Part 2: Parts of doors” “EN 12519, Windows and pedestrian doors – Terminology” “EN 15725, Extended application on the fire performance of construction products and building elements:
Principle of EXAP standards and EXAP reports”
3 Modification to Clause 3, "Terms and definitions"
Add the following references in the first Sentence:
„EN 12433-1, EN 12433-2, EN 12519, EN 15269-11, EN 15725"
Add the following term and definition:
3.8 faces and sides of a door leaf
faces and sides of a door leaf are shown in Figure 3
Key 1 opening face 4 hinge side 2 closing face 5 top side 3 lock side 6 bottom side Figure 3 — Faces and sides of a door leaf
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E)
4 Modification to Clause 4, "Determination of the field of extended application"
In clause 4.1.1 add the following sentence and note below the first sentence:
“If it is not clearly expressed from the test report, whether the bottom gap was taped over or not, the EXAP report is to be prepared on the basis of maintaining an S classification in accordance with a3 EN 13501-2.
NOTE The additional indicator " " or " " for S only indicates whether the bottom gap was taped over in 3 4 a the test or not and has no influence on the joint-length to be considered for the joint length-related air flow rate calculation.”
5 Modification to Clause 5, "Extended application report"
Add in the first sentence …“in line with EN 15725 and”… in front of …” in accordance with the requirements of EN 15269-1” …
6 Modification to Annex A
Replace all of the paragraphs before Table 1 of Annex A with the following:
“The tables are designed to provide rules for the creation of extended application reports by experts in the field of smoke control testing of:
- Table A.1: hinged and pivoted doorsets.
- Table A.2: horizontally sliding doorsets (single leaf and double leaf), telescopic doorsets (single leaf and double leaf) and single leaf vertically sliding doorsets.
- Table A.3: metal rolling shutters and operable fabric curtains (excluding overlapping systems). The Tables A.1, A.2 or A.3 shall only be used to evaluate a field of extended application when at least one positive smoke control test according to EN 1634-3 has resulted in a classification according to EN 13501-2.
The first two columns of Tables A.1, A.2 or A.3 identify possible variations to the construction parameters of the specimen tested.
Column (3) of Tables A.1, A.2 and A.3 indicates the possibility and, if applicable, the condition(s) to be fulfilled to extend the field of application. If a desired parameter variation is not possible or not covered by the allowance(s) in column (3) it shall be tested in accordance with column (4). Where additional tests are deemed to be necessary, column (4) of Tables A.1, A.2 or A.3 defines the test scenario to be used. Where it is possible to use information from tests performed on one configuration for evidence on a different configuration, this allowance has been made in order to reduce the overall number of tests required for extended application evaluation (e.g. single action doorsets to double action doorsets).
The following test scenarios are defined and referred to in column (4) of Tables A.1, A.2 or A.3:
Test shall be performed with a single or double leaf doorset Test scenario A:
Tests shall be performed from both sides with a single leaf doorset Test scenario B:
Tests shall be performed from both sides with a double leaf doorset Test scenario C:
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E) Test shall be performed from the worst side with a double leaf doorset for single Test scenario D:
or double leaf doorsets or with a single leaf doorset for single leaf doorsets Test shall be performed from the worst side with a single leaf doorset for single Test scenario E:
leaf doorsets or a double leaf doorset for double leaf doorsets respectively Tests shall be performed from both sides with a single leaf doorset for single leaf Test scenario F:
doorsets or a double leaf doorset for double leaf doorsets respectively. If the
double leaf doorset test leads to an air flow rate of ≤ 20 m /h, this test is sufficient for single leaf doorsets as well Test scenario G: Tests shall be performed from both sides with a single or double leaf sliding doorset If the building hardware does interfere with the smoke seal system more than Test scenario H:
tested: Tests shall be performed from both sides with a single leaf doorset for single leaf doorsets or a double leaf doorset for double leaf doorsets respectively.
If the double leaf doorset test leads to an air flow rate of ≤ 20 m /h, this test is sufficient for single leaf doorsets as well.
Otherwise: Test shall be performed on the opening face with a double leaf doorset for single or double leaf doorsets or with a single leaf doorset for single leaf doorsets Test scenario I: Test shall be performed from one side with the part(s) changed faced to the test chamber.
Where an additional test is required in column 4, the test shall be a full-scale test according to EN 1634-3 at least with the size of the initial test described in 4.1.1., unless it is otherwise specified by the notified product certification body, or the details changed are limited to the tested size. The test shall be performed with the specimen tested from the side with the higher air flow rate achieved in the basis tests mentioned in 4.1.1 (worst face) unless it is otherwise specified. Where additional tests from both faces are required, it is defined in Annex A explicitly (test scenarios B, C, F, G, and H). In this case one specimen can be used for both tests. If the field of extended application is intended to cover both, products with or without specific retaining element of building hardware, the element of building hardware may be fitted to the test specimen but set disengaged. The rules for increase of the size of Annex C are to be considered to all variations of Tables A.1, A.2 or A.3, if they shall be applied to a larger size than tested. A variation shall not lead to an overload or an improper deformation of any component (which might e.g. prevent to close fully). For rolling shutter assemblies and operable fabric curtains stability and limitation of deformations are crucial for the air flow rate. Calculation principles for stresses and strains are given in Annex D and examples for calculations for relevant parts in Annex E.
Interpolations between minimum and maximum size tested of any measure is possible if not specified otherwise in Tables A.1, A.2 or A.3. The influence of construction parameter variations on the statics of a doorset or operable fabric curtain or shutter assembly shall always be considered by the manufacturer. Parts of solid timber may be replaced by parts of other solid timber of the same or higher density. Glued timber with solid pieces of min. 10 mm thickness may be used instead of solid timber. Composite timber products (e.g. made of Medium Density Fibreboard) may not be replaced with other materials or composites. Timber doorsets with metal inlays shall follow the rules for metal doorsets. Test results achieved with a timber doorset with metal inlays may not be used to evaluate the extended field of application of a timber doorsets without metal inlays and vice versa. If after consideration of a specific construction parameter variation, additional changes are required to be made to the specimen, these may be made providing the implications on other construction parameter
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E) variations are also taken into account. If two or more construction parameter variations should be tested within the same specimen, those construction parameter variations should not interfere (neither negative nor positive) with each other, unless the construction parameter variations are always used together.
Unless otherwise described in Annex A of this document, the rules for “S ” are also applicable to “S ”.” 200 200L
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Replace Table A.1 with the following Table A.1:
Table A.1 — Construction parameter variations for single or double leaf hinged or pivoted doorsets and openable windows (metal, timber, framed glazed), excluding unframed glass doorsets and openable windows Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A Door leaf In certain cases, the rules given in section A are also appropriate to side and over panels or the door frame; where this is the case it is clearly indicated in column (1). For double leaf doorsets, both leaves shall be of the same basic construction. A.1 General A.1.1 Number of leaves – single Decrease Possible for S and S if the smoke sealing system on the lock Test scenario B a3 a4 leaf from double leaf doorset side was already tested on a double leaf doorset A.1.2 Number of leaves – double Increase Not possible Test scenario C leaf from single leaf doorset A.1.3 Smoke seals (fitted at leaf to Change Not possible Test scenario F frame interface) – location towards the frame rebate – see Figure A.1a A.1.4 Smoke seals (fitted at leaf to Change Not possible Test scenario F frame interface) – location away from the frame rebate – see Figure A.1b A.1.5 Smoke seals (fitted in Change Not possible Test scenario C meeting edges) – location A.1.6 Smoke seals (fitted in leaf or Add/Remove Not possible Test scenario F frame) A.1.7 Intumescent seals (fitted in Add / Remove / Location Possible providing the smoke sealing system is not interfered Test scenario F leaf or frame) which are separate change / Alternative from the smoke seal
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.1.8 Louvres in door leaf or panel Add Not possible Test scenario F A.1.9 Louvres in door leaf or panel Remove Possible - A.1.10 Louvres in door leaf or panel Change Possible - tested with louvre – fitting position vertical A.1.11 Louvres in door leaf or panel Change Possible - tested with louvre – fitting position in horizontal A.1.12 Louvres in door leaf or panel Decrease Possible - tested with louvre – size (total area) - see Figure A.3 A.1.13 Louvres in door leaf or panel Increase Not possible Test scenario F tested with louvre – size (for area or dimensions) A.1.14 Louvre tested in double leaf Change Possible if the area of the louvre is not more than 15 % of Test scenario B doorset – position of louvre from door leaf area or providing that both door leaves are active or one leaf to the opposite leaf the louvre is tested in active leaf A.1.15 Leaf edge rebate (to door Add Possible providing the rebate does not lead to reduced Test scenario F leaf or panel – not at the meeting compression on the seals and any stiffening components in edges; see section A.2 for meeting the door leaf are not reduced edge parameters) – (added rebate shown shaded in drawings) – see Figure A.4
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.1.16 Leaf edge rebate (to door Remove Not possible Test scenario F leaf or panel – not at the meeting edges; see section A.2 for meeting edge parameters) A.1.17 Change in mode of operation Alternative Possible for S and S to provide a double action doorset Test scenario F a3 a4 - single /double action from a single action doorset providing the smoke sealing system, including the area around the hinges/pivots, is unchanged A.1.18 Latched condition for single Change Possible in line with the following relationship Test scenario E, with leaf or double leaf doorsets – the required latching see Figure A.5 condition For Sa3 Tested: Tested: with a Tested: with a without a latch/lock/bo latch/lock/bo latch/lock/bo lt, but lt, latched lt unlatched Extension to: As tested Possible Not possible without a lock/latch/bo lt Extension to: Possible Possible As tested with a lock/latch/bo lt
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) For S and S a4 200 Tested: Tested: with a Tested: with a without a latch/lock/bo latch/lock/bo latch/lock/bo lt, but lt, latched lt unlatched Extension to: As tested Possible Not possible without a lock/latch/bo lt Extension to: Not possible Not possible As tested with a lock/latch/bo lt A.1.19 Additional seals (additional Add Possible providing the smoke sealing system is not interfered Test scenario F to the smoke sealing system) fitted in leaf or frame (e.g. noise reduction) A.2 Meeting edge detail A.2.1 Meeting edge detail – Change Possible for S and S for rebated details shown in Test scenario C a3 a4 see Figure A.6 Figure A.6, interchange between a) and b) only. Change from a) or b) to g) possible but not vice versa providing the smoke sealing system is not interfered.
A.2.2 Astragal – see Figure A.6f) Add Possible - A.2.3 Astragal – see Figure A.6f) Remove Not possible Test scenario C
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3 Size variations A.3.1 Size of door leaf or panel Decrease Possible - (area, width, height)
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3.2 Height/width/area of door Increase Possible for hinged or pivoted latched doorsets in line with Test scenario F leaf the calculations in Annex C and the following limitations:
a) The smoke sealing system is unchanged, b) Size increases by up to 25 % height, 25 % width and 50% in area providing the number of movement restrictors are increased at least in line with the size increase, maintaining positions between movement restrictors and distances from leaf corners as tested, c) Additional for S and S :
a3 a4 Size increase is permitted by up to 25 % height, 25 % width and 25 % in area without additional movement restrictors such as locks, bolts, hinges etc., d) Additional for S for timber doorsets, joinery type
timber framed doorsets, steel doorsets and metal framed doorsets without thermal break (for thermal break see Figure A.30):
Size increase is permitted by up to 250 mm height, 250 mm width and 25 % in area without additional movement restrictors such as locks, bolts, hinges etc., e) Additional for S for metal framed doorsets with
thermal break (for thermal break see Figure A.30), timber doorsets with metal inlay in the facing, joinery type timber framed doorsets with filling with metal inlay in the facing and steel doorsets with stainless steel surface:
Size increase is permitted by up to 150 mm height, 150 mm width and 15 % in area without additional movement restrictors such as locks, bolts, hinges etc.
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3.3 Thickness of the door leaf or Increase Possible to interpolate between the smallest and largest Test scenario F panel tested thickness.
Possible for Sa3 and Sa4.
Possible for S steel and metal framed doorsets.
For S timber doorsets: possible for doorset leaves without
metal inlay.
A.3.4 Thickness of the door leaf or Decrease Possible to interpolate between the smallest and largest Test scenario F panel tested thickness A.4 Materials and constructions A.4.1 Density of core material of Increase/decrease Possible for S and S doorsets. Test scenario A a3 a4 leaf or panel Possible for S providing the increase/decrease is not
greater than 25 %.
A.4.2 Pattern of core material of Increase Possible also proportionately with a leaf/panel size increase. Test scenario A leaf or panel – number of pieces – For double leaf doorsets, the rule shall be applied to each leaf see Figure A.7 separately.
Possible for S and S a3 a4.
Possible for S200 by up to 50 % providing the test included more than one joint.
SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.4.3 Pattern of core material of Decrease Possible also proportionately with a leaf/panel size decrease. Test scenario A leaf or panel – number of pieces – For double leaf doorsets, the rule shall be applied to each leaf see Figure A.7 separately.
Possible for S and S a3 a4.
Possible for S steel based doorsets providing the fixing
technique is unchanged.
Possible for S200 timber based doorsets by up to 50 % providing one joint in the core material remains.
A.4.4 Number of layers of identical Increase Possible for S and S Test scenario A a3 a4.
core material of door leaf or panel – Possible for S steel based doorsets providing the fixing
see Figure A.25 technique to the top-layer/cover-plate (e.g. steel-sheet of the steel-doorset) is unchanged.
Possible for S timber based doorsets providing the test
included more than two joints and the fixing technique to the top layer/cover plate is unchanged.
A.4.5 Number of layers of identical Decrease Possible for S and S Test scenario A a3 a4.
core material of door leaf or panel – providing the fixing technique to the top- Possible for S200 see Figure A.25 layer/cover-plate (e.g. steel-sheet of the steel-doorset) is unchanged.
...