Abstract

This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types:
-   hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1);
-   horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2);
-   metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3).
The following construction products are not covered by this standard:
-   unframed glass doors and openable windows;
-   sectional doors (including stacking doors);
-   vertically and horizontally folding doors;
-   horizontally and vertically moving timber sliding doors;
-   horizontally and vertically moving framed sliding doors (metal or timber).
In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned.
This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3.
Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples:
-   Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications;
-   leaf/leaves;
-   wall/ceiling fixed elements;
-   glazed elements, louvres and/or vents;
-   side, transom or overpanels;
-   items of building hardware;
-   decorative finishes;
-   intumescent, smoke, draught or acoustic seals;
-   alternative supporting construction(s).

Status
Not Published
Public Enquiry End Date
30-Jul-2026
Technical Committee
POZ - Požarna varnost
Current Stage
4020 - Public enquire (PE) (Adopted Project)
Start Date
21-May-2026
Due Date
08-Oct-2026
Completion Date
03-Aug-2026

Buy Documents

Draft

SIST EN 15269-20:2020/oprA1:2026

English language (109 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 15269-20:2020/oprA1:2026 is a draft amendment to EN 15269-20:2020 from the European Committee for Standardization (CEN), published through SIST. It sets the rules for extending fire-resistance and smoke-control test results for door, shutter, openable window and operable fabric curtain assemblies, using test evidence from EN 1634-3 and the smoke-control classifications of EN 13501-2. It is written for manufacturers, test laboratories, certification bodies, specifiers and others who need to justify a wider field of application than the exact tested specimen.

What does SIST EN 15269-20:2020/oprA1:2026 specify?

SIST EN 15269-20:2020/oprA1:2026 specifies the methodology for extending the application of test results for smoke control in door, shutter, openable window and operable fabric curtain assemblies. The document is meant to be read with EN 15269-1, and it uses results from tests carried out to EN 1634-3.

The scope covers:

  • hinged and pivoted doors and openable windows, single or double leaf;
  • horizontally and vertically moving steel sliding doors, including telescopic doorsets and versions with pass doors;
  • metal rolling shutters and operable fabric curtains, excluding overlapping systems.

It also states that, unless the context says otherwise, the word “doors” is used for the whole group of doors, shutters, openable windows and operable fabric curtains.

The amendment updates Clause 1 to include the new smoke-control performance characteristics Sa3, Sa4 and S200L. It also updates the document structure through Clause 2, Clause 3, Clause 4, Clause 5, Annex A and Annex C.

AnnexWhat it covers
Annex AConstruction parameter variations and test-scenario rules for hinged/pivoted doorsets and openable windows, sliding doorsets, pass doors, glazing, frames, hardware, side/transom/overpanels, supporting construction and finishes
Annex CCalculation methods for extended application based on leaking gap length and air-flow rate

What are the key requirements of SIST EN 15269-20:2020/oprA1:2026?

SIST EN 15269-20:2020/oprA1:2026 keeps the document centered on one question: when a tested assembly may be extended to other sizes, materials, hardware layouts or supporting constructions without a new full-scale test. The practical message is that the original EN 1634-3 test is only the starting point - the extension must follow the specific rules in Annex A and Annex C.

Test evidence and reporting

Clause 4 and Clause 5 tie the extended application work to the test report and to the EXAP report. If the test report does not clearly state whether the bottom gap was taped over, the EXAP report is prepared on the basis of maintaining an S classification in accordance with EN 13501-2. The note also makes clear that the extra indicator attached to S only shows whether the bottom gap was taped, not the joint length used in the air-flow calculation.

Clause 5 requires the EXAP report to be prepared in line with EN 15725 and with the general requirements of EN 15269-1. In practice, this means the report has to be traceable, technically justified and written in the format expected for extended-application work.

Annex A defines what may be changed

Annex A is the core of the document. It gives tables for three product families and tells the user, for each parameter change, whether the change is possible, whether it needs a new test, and which test scenario applies.

The table logic matters in practice:

  • column 1 identifies the construction parameter;
  • column 3 says whether the variation is allowed and on what conditions;
  • column 4 states the test scenario if another test is needed.

The amendment keeps the rule that extra tests are full-scale EN 1634-3 tests, normally at least the size of the initial test, unless the notified product certification body specifies otherwise or the changed details are limited to the tested size. Where a rule calls for tests from both faces, the document allows one specimen to serve both tests in the named scenarios.

The main Annex A controls

Annex A allows some changes to leaf number, size, edge detail, materials, seals, glazing, hardware and supporting construction, but only when the smoke sealing system is not interfered with or when the rule specifically permits the change. That is the key practical point: the smoke-sealing function has priority over almost every design variation.

The annex also sets general limits that matter to design and certification:

  • size increases must not overload or deform any component so that the assembly cannot close properly;
  • interpolations between the smallest and largest tested sizes are allowed when the tables do not say otherwise;
  • the effect of construction changes on structural behaviour must always be considered by the manufacturer;
  • solid timber parts may be replaced only under the stated density and material conditions;
  • timber doorsets with metal inlays follow the metal-door rules, and test results for doorsets with inlays cannot be transferred to doorsets without them, or vice versa.

Hardware, glazing and supporting construction are controlled separately

Annex A gives separate rules for building hardware, glazed apertures, side and transom panels, frames and supporting constructions. The document requires all building hardware to match the relevant technical specification and the class of use of the doorset. If hardware is removed, any openings or holes must not remain open.

For the reader, this means hardware is not a minor detail. Locks, latches, hinges, closers, cylinders, handles, seals, glazing beads and door viewers all have their own extension rules, and many are only acceptable if they do not interfere with the smoke sealing system.

Annex C gives the calculation basis

Annex C provides the calculation methods for extending the application of smoke-control results. It uses leaking gap length and air-flow rate per unit area of the clear opening. The calculations apply only after successful tests from both faces to EN 1634-3 and only when the tested door leaf area and height meet the annex conditions.

For S and S classifications, Annex C limits the extension by the tested air-flow rate relative to the permitted rate in EN 13501-2. For S doorsets excluding fabric curtains, it gives two ways to calculate the maximum extension - one based on clear opening area and one based on total leaking gap length. For S200L, the same calculation approach can be used up to a higher maximum air flow rate when the tested door leaf area is large enough. In practice, Annex C is the quantitative check that tells you how far the tested result can be stretched.

What terms does SIST EN 15269-20:2020/oprA1:2026 define?

  • Extended application (EXAP) report - the report that records the justified field of extended application for a tested assembly, prepared according to EN 15725 and EN 15269-1.
  • Faces and sides of a door leaf - Clause 3.8 defines the opening face, closing face, hinge side, lock side, top side and bottom side of a door leaf, shown in Figure 3.
  • Worst face - the test face with the higher air-flow rate in the basis tests; it is the side used for additional testing unless another instruction applies.
  • Smoke sealing system - the seal arrangement that controls leakage and must not be interfered with in many permitted variations.
  • Leaking gap length - the total length of the relevant gaps used in Annex C calculations.
  • Clear opening area - the open area used as the basis for the Annex C area calculation.
  • Pass door - the integrated door in a sliding doorset that is treated by special rules in Annex A.

Who uses SIST EN 15269-20:2026/oprA1:2026?

SIST EN 15269-20:2020/oprA1:2026 is used by manufacturers of doors, shutters, windows, operable fabric curtains and their hardware when they want to extend a tested design to other variants. It is also used by fire test laboratories, notified product certification bodies and engineering teams preparing EXAP reports.

Quality managers and buyers use it when they need to check whether a change in size, material, seal, glazing, frame, closer, lock or supporting construction still sits inside the tested field of application. In buildings and industrial products, it is especially relevant to fire safety, doors and windows, smoke control, and building hardware supply chains.

What changed in SIST EN 15269-20:2020/oprA1:2026 from the previous edition?

Compared with EN 15269-20:2020 and its corrigendum AC 2022, the amendment makes these changes:

  • revises the document to match the new smoke-control performance characteristics Sa3, Sa4 and S200L in EN 13501-2;
  • updates Clause 2 with additional normative references;
  • updates Clause 3, including a new term 3.8 for the faces and sides of a door leaf;
  • updates Clause 4, including the rule for cases where the bottom gap tape status is unclear;
  • updates Clause 5 so the EXAP report is aligned with EN 15725;
  • replaces Annex A and revises many of its rules and figures;
  • replaces Annex C with revised calculation methods.

Which standards are used with SIST EN 15269-20:2026/oprA1:2026?

  • EN 15269-1 - provides the general extended-application framework that this part is read with.
  • EN 1634-3 - gives the smoke-control test method whose results are extended.
  • EN 13501-2 - supplies the smoke-control classification terms and the performance basis used in the calculations.
  • EN 15725 - sets the principle for EXAP standards and EXAP reports.
  • EN 12433-1 - supplies terminology for industrial, commercial and garage doors and gates, part 1.
  • EN 12433-2 - supplies terminology for industrial, commercial and garage doors and gates, part 2.
  • EN 12519 - supplies terminology for windows and pedestrian doors.
  • EN 15269-11 - is named in the terms and definitions update as part of the terminology context.

What does the SIST EN 15269-20:2020/oprA1:2026 document contain?

SIST EN 15269-20:2020/oprA1:2026 contains amended clause text for scope, normative references, terms and definitions, field-of-application determination and the EXAP report. It also contains the updated Annex A construction-variation rules and the updated Annex C calculation methods.

Annex A is built around tables and test scenarios, so it functions like a decision map for acceptable changes. Annex C contains calculation procedures that support design extension and certification decisions without reproducing the full test on every variant.

The document also includes figure-based guidance for door leaf faces, louvres, overlap, thermal breaks, glazing beads and other component details. In practice, those figures support the tables by showing exactly which physical feature the rule applies to.

Relations

Effective Date
14-Jun-2023

Buy Documents

Draft

SIST EN 15269-20:2020/oprA1:2026

English language (109 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

SIST EN 15269-20:2020/oprA1:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 20: Smoke control for doors, shutters, operable fabric curtains and openable windows". This standard covers: This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types: - hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1); - horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2); - metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3). The following construction products are not covered by this standard: - unframed glass doors and openable windows; - sectional doors (including stacking doors); - vertically and horizontally folding doors; - horizontally and vertically moving timber sliding doors; - horizontally and vertically moving framed sliding doors (metal or timber). In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3. Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples: - Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications; - leaf/leaves; - wall/ceiling fixed elements; - glazed elements, louvres and/or vents; - side, transom or overpanels; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).

This document, which is intended to be read in conjunction with EN 15269 1, covers doors, shutters, openable windows and fabric curtains of any material and of the following types: - hinged and pivoted (e.g. metal, timber, framed glazed) doors and openable windows of single or double leaf (Table A.1); - horizontally and vertically moving steel sliding doors of single or double leaf with and without pass doors, including telescopic doorsets (Table A.2); - metal rolling shutters and operable fabric curtains (excluding overlapping systems) (Table A.3). The following construction products are not covered by this standard: - unframed glass doors and openable windows; - sectional doors (including stacking doors); - vertically and horizontally folding doors; - horizontally and vertically moving timber sliding doors; - horizontally and vertically moving framed sliding doors (metal or timber). In this document, whenever doors are mentioned, the whole range of doors, shutters, openable windows and operable fabric curtains is included or otherwise mentioned. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634 3. Subject to the completion of the appropriate test or tests, the extended application can cover all or some of the following examples: - Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (S200) classifications; - leaf/leaves; - wall/ceiling fixed elements; - glazed elements, louvres and/or vents; - side, transom or overpanels; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).

SIST EN 15269-20:2020/oprA1:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 91.060.50 - Doors and windows. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 15269-20:2020/oprA1:2026 has the following relationships with other standards: It is inter standard links to SIST EN 15269-20:2020. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN 15269-20:2020/oprA1:2026 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

SIST EN 15269-20:2020/oprA1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • European foreword
  • 1 Modification to Clause 1 "Scope"
  • 2 Modification to Clause 2, "Normative References"
  • 3 Modification to Clause 3, "Terms and definitions"
  • 3.8 faces and sides of a door leaf
  • 4 Modification to Clause 4, "Determination of the field of extended application"
  • 5 Modification to Clause 5, "Extended application report"
  • 6 Modification to Annex A
  • 7 Modification to Annex C
  • Annex C

European foreword

This document (EN 15269:20/prA1:2025) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This document is currently submitted to the CEN Enquiry.

In comparison to EN 15269:2020 and its corrigendum AC 2022, the following amendments have been made to adjust the document to the new performance characteristics "S ", "S ", and "S " according to a3 a4 200L EN 13501-2:

  • complete editorial and technical revision according to the change of the performance characteristics Sa into S and S ; a3 a4
  • Clause 2, "Normative references" updated;
  • Clause 3, "Terms and definitions" updated and add term 3.8.;
  • Clause 4, "Determination of the field of extended application" updated;
  • add information in 4.1.1 for Sa resp. S and S ; a3 a4
  • Annex A (normative) "Construction parameter variations": updated, Since the change of the performance characteristics from S to S and S had to be made in many rules in Annex A, not only the a a3 a4 respective changes shown in this amendment, but the entire Annex A was replaced for better usability of the document.
  • revised introduction in the 4th sentence of the “Construction parameter variations“ of Annex A delete of “Otherwise not possible without additional test” and change of “Not possible without additional test” into “Not possible” in alle rules of Table A.1 to A.3;
  • editorial and technical revision according to the performance characteristics S in the last 200L sentence of the “Construction parameter variations“ of Annex A, in Table A.1 rule A.3.2, in Table A.2 rule A.1.2 to A.1.4 and 1.9, in Table A.3 rule A.1.2 to A.1.4 and 1.9, and in C.3 of Annex C;
  • editorial change in figure A.5;
  • editorial change in figure A.61;
  • editorial change in figure A.96.

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E)

1 Modification to Clause 1 "Scope"

In the nth bullet, replace “(S )” with “(S or S )”, and add “and S )” after “(S )”. a a3 a4 200L 200

2 Modification to Clause 2, "Normative References"

Add the following references:

“EN 12433-1, Industrial, commercial and garage doors and gates - Terminology — Part 1: Types of doors” “EN 12433-2, Industrial, commercial and garage doors and gates - Terminology — Part 2: Parts of doors” “EN 12519, Windows and pedestrian doors – Terminology” “EN 15725, Extended application on the fire performance of construction products and building elements:

Principle of EXAP standards and EXAP reports”

3 Modification to Clause 3, "Terms and definitions"

Add the following references in the first Sentence:

„EN 12433-1, EN 12433-2, EN 12519, EN 15269-11, EN 15725"

Add the following term and definition:

3.8 faces and sides of a door leaf

faces and sides of a door leaf are shown in Figure 3

Key 1 opening face 4 hinge side 2 closing face 5 top side 3 lock side 6 bottom side Figure 3 — Faces and sides of a door leaf

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E)

4 Modification to Clause 4, "Determination of the field of extended application"

In clause 4.1.1 add the following sentence and note below the first sentence:

“If it is not clearly expressed from the test report, whether the bottom gap was taped over or not, the EXAP report is to be prepared on the basis of maintaining an S classification in accordance with a3 EN 13501-2.

NOTE The additional indicator " " or " " for S only indicates whether the bottom gap was taped over in 3 4 a the test or not and has no influence on the joint-length to be considered for the joint length-related air flow rate calculation.”

5 Modification to Clause 5, "Extended application report"

Add in the first sentence …“in line with EN 15725 and”… in front of …” in accordance with the requirements of EN 15269-1” …

6 Modification to Annex A

Replace all of the paragraphs before Table 1 of Annex A with the following:

“The tables are designed to provide rules for the creation of extended application reports by experts in the field of smoke control testing of:

  • Table A.1: hinged and pivoted doorsets.
  • Table A.2: horizontally sliding doorsets (single leaf and double leaf), telescopic doorsets (single leaf and double leaf) and single leaf vertically sliding doorsets.
  • Table A.3: metal rolling shutters and operable fabric curtains (excluding overlapping systems). The Tables A.1, A.2 or A.3 shall only be used to evaluate a field of extended application when at least one positive smoke control test according to EN 1634-3 has resulted in a classification according to EN 13501-2.

The first two columns of Tables A.1, A.2 or A.3 identify possible variations to the construction parameters of the specimen tested.

Column (3) of Tables A.1, A.2 and A.3 indicates the possibility and, if applicable, the condition(s) to be fulfilled to extend the field of application. If a desired parameter variation is not possible or not covered by the allowance(s) in column (3) it shall be tested in accordance with column (4). Where additional tests are deemed to be necessary, column (4) of Tables A.1, A.2 or A.3 defines the test scenario to be used. Where it is possible to use information from tests performed on one configuration for evidence on a different configuration, this allowance has been made in order to reduce the overall number of tests required for extended application evaluation (e.g. single action doorsets to double action doorsets).

The following test scenarios are defined and referred to in column (4) of Tables A.1, A.2 or A.3:

Test shall be performed with a single or double leaf doorset Test scenario A:

Tests shall be performed from both sides with a single leaf doorset Test scenario B:

Tests shall be performed from both sides with a double leaf doorset Test scenario C:

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E) Test shall be performed from the worst side with a double leaf doorset for single Test scenario D:

or double leaf doorsets or with a single leaf doorset for single leaf doorsets Test shall be performed from the worst side with a single leaf doorset for single Test scenario E:

leaf doorsets or a double leaf doorset for double leaf doorsets respectively Tests shall be performed from both sides with a single leaf doorset for single leaf Test scenario F:

doorsets or a double leaf doorset for double leaf doorsets respectively. If the

double leaf doorset test leads to an air flow rate of ≤ 20 m /h, this test is sufficient for single leaf doorsets as well Test scenario G: Tests shall be performed from both sides with a single or double leaf sliding doorset If the building hardware does interfere with the smoke seal system more than Test scenario H:

tested: Tests shall be performed from both sides with a single leaf doorset for single leaf doorsets or a double leaf doorset for double leaf doorsets respectively.

If the double leaf doorset test leads to an air flow rate of ≤ 20 m /h, this test is sufficient for single leaf doorsets as well.

Otherwise: Test shall be performed on the opening face with a double leaf doorset for single or double leaf doorsets or with a single leaf doorset for single leaf doorsets Test scenario I: Test shall be performed from one side with the part(s) changed faced to the test chamber.

Where an additional test is required in column 4, the test shall be a full-scale test according to EN 1634-3 at least with the size of the initial test described in 4.1.1., unless it is otherwise specified by the notified product certification body, or the details changed are limited to the tested size. The test shall be performed with the specimen tested from the side with the higher air flow rate achieved in the basis tests mentioned in 4.1.1 (worst face) unless it is otherwise specified. Where additional tests from both faces are required, it is defined in Annex A explicitly (test scenarios B, C, F, G, and H). In this case one specimen can be used for both tests. If the field of extended application is intended to cover both, products with or without specific retaining element of building hardware, the element of building hardware may be fitted to the test specimen but set disengaged. The rules for increase of the size of Annex C are to be considered to all variations of Tables A.1, A.2 or A.3, if they shall be applied to a larger size than tested. A variation shall not lead to an overload or an improper deformation of any component (which might e.g. prevent to close fully). For rolling shutter assemblies and operable fabric curtains stability and limitation of deformations are crucial for the air flow rate. Calculation principles for stresses and strains are given in Annex D and examples for calculations for relevant parts in Annex E.

Interpolations between minimum and maximum size tested of any measure is possible if not specified otherwise in Tables A.1, A.2 or A.3. The influence of construction parameter variations on the statics of a doorset or operable fabric curtain or shutter assembly shall always be considered by the manufacturer. Parts of solid timber may be replaced by parts of other solid timber of the same or higher density. Glued timber with solid pieces of min. 10 mm thickness may be used instead of solid timber. Composite timber products (e.g. made of Medium Density Fibreboard) may not be replaced with other materials or composites. Timber doorsets with metal inlays shall follow the rules for metal doorsets. Test results achieved with a timber doorset with metal inlays may not be used to evaluate the extended field of application of a timber doorsets without metal inlays and vice versa. If after consideration of a specific construction parameter variation, additional changes are required to be made to the specimen, these may be made providing the implications on other construction parameter

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2025 (E) variations are also taken into account. If two or more construction parameter variations should be tested within the same specimen, those construction parameter variations should not interfere (neither negative nor positive) with each other, unless the construction parameter variations are always used together.

Unless otherwise described in Annex A of this document, the rules for “S ” are also applicable to “S ”.” 200 200L

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Replace Table A.1 with the following Table A.1:

Table A.1 — Construction parameter variations for single or double leaf hinged or pivoted doorsets and openable windows (metal, timber, framed glazed), excluding unframed glass doorsets and openable windows Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A Door leaf In certain cases, the rules given in section A are also appropriate to side and over panels or the door frame; where this is the case it is clearly indicated in column (1). For double leaf doorsets, both leaves shall be of the same basic construction. A.1 General A.1.1 Number of leaves – single Decrease Possible for S and S if the smoke sealing system on the lock Test scenario B a3 a4 leaf from double leaf doorset side was already tested on a double leaf doorset A.1.2 Number of leaves – double Increase Not possible Test scenario C leaf from single leaf doorset A.1.3 Smoke seals (fitted at leaf to Change Not possible Test scenario F frame interface) – location towards the frame rebate – see Figure A.1a A.1.4 Smoke seals (fitted at leaf to Change Not possible Test scenario F frame interface) – location away from the frame rebate – see Figure A.1b A.1.5 Smoke seals (fitted in Change Not possible Test scenario C meeting edges) – location A.1.6 Smoke seals (fitted in leaf or Add/Remove Not possible Test scenario F frame) A.1.7 Intumescent seals (fitted in Add / Remove / Location Possible providing the smoke sealing system is not interfered Test scenario F leaf or frame) which are separate change / Alternative from the smoke seal

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.1.8 Louvres in door leaf or panel Add Not possible Test scenario F A.1.9 Louvres in door leaf or panel Remove Possible - A.1.10 Louvres in door leaf or panel Change Possible - tested with louvre – fitting position vertical A.1.11 Louvres in door leaf or panel Change Possible - tested with louvre – fitting position in horizontal A.1.12 Louvres in door leaf or panel Decrease Possible - tested with louvre – size (total area) - see Figure A.3 A.1.13 Louvres in door leaf or panel Increase Not possible Test scenario F tested with louvre – size (for area or dimensions) A.1.14 Louvre tested in double leaf Change Possible if the area of the louvre is not more than 15 % of Test scenario B doorset – position of louvre from door leaf area or providing that both door leaves are active or one leaf to the opposite leaf the louvre is tested in active leaf A.1.15 Leaf edge rebate (to door Add Possible providing the rebate does not lead to reduced Test scenario F leaf or panel – not at the meeting compression on the seals and any stiffening components in edges; see section A.2 for meeting the door leaf are not reduced edge parameters) – (added rebate shown shaded in drawings) – see Figure A.4

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.1.16 Leaf edge rebate (to door Remove Not possible Test scenario F leaf or panel – not at the meeting edges; see section A.2 for meeting edge parameters) A.1.17 Change in mode of operation Alternative Possible for S and S to provide a double action doorset Test scenario F a3 a4 - single /double action from a single action doorset providing the smoke sealing system, including the area around the hinges/pivots, is unchanged A.1.18 Latched condition for single Change Possible in line with the following relationship Test scenario E, with leaf or double leaf doorsets – the required latching see Figure A.5 condition For Sa3 Tested: Tested: with a Tested: with a without a latch/lock/bo latch/lock/bo latch/lock/bo lt, but lt, latched lt unlatched Extension to: As tested Possible Not possible without a lock/latch/bo lt Extension to: Possible Possible As tested with a lock/latch/bo lt

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) For S and S a4 200 Tested: Tested: with a Tested: with a without a latch/lock/bo latch/lock/bo latch/lock/bo lt, but lt, latched lt unlatched Extension to: As tested Possible Not possible without a lock/latch/bo lt Extension to: Not possible Not possible As tested with a lock/latch/bo lt A.1.19 Additional seals (additional Add Possible providing the smoke sealing system is not interfered Test scenario F to the smoke sealing system) fitted in leaf or frame (e.g. noise reduction) A.2 Meeting edge detail A.2.1 Meeting edge detail – Change Possible for S and S for rebated details shown in Test scenario C a3 a4 see Figure A.6 Figure A.6, interchange between a) and b) only. Change from a) or b) to g) possible but not vice versa providing the smoke sealing system is not interfered.

A.2.2 Astragal – see Figure A.6f) Add Possible - A.2.3 Astragal – see Figure A.6f) Remove Not possible Test scenario C

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3 Size variations A.3.1 Size of door leaf or panel Decrease Possible - (area, width, height)

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3.2 Height/width/area of door Increase Possible for hinged or pivoted latched doorsets in line with Test scenario F leaf the calculations in Annex C and the following limitations:

a) The smoke sealing system is unchanged, b) Size increases by up to 25 % height, 25 % width and 50% in area providing the number of movement restrictors are increased at least in line with the size increase, maintaining positions between movement restrictors and distances from leaf corners as tested, c) Additional for S and S :

a3 a4 Size increase is permitted by up to 25 % height, 25 % width and 25 % in area without additional movement restrictors such as locks, bolts, hinges etc., d) Additional for S for timber doorsets, joinery type

timber framed doorsets, steel doorsets and metal framed doorsets without thermal break (for thermal break see Figure A.30):

Size increase is permitted by up to 250 mm height, 250 mm width and 25 % in area without additional movement restrictors such as locks, bolts, hinges etc., e) Additional for S for metal framed doorsets with

thermal break (for thermal break see Figure A.30), timber doorsets with metal inlay in the facing, joinery type timber framed doorsets with filling with metal inlay in the facing and steel doorsets with stainless steel surface:

Size increase is permitted by up to 150 mm height, 150 mm width and 15 % in area without additional movement restrictors such as locks, bolts, hinges etc.

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.3.3 Thickness of the door leaf or Increase Possible to interpolate between the smallest and largest Test scenario F panel tested thickness.

Possible for Sa3 and Sa4.

Possible for S steel and metal framed doorsets.

For S timber doorsets: possible for doorset leaves without

metal inlay.

A.3.4 Thickness of the door leaf or Decrease Possible to interpolate between the smallest and largest Test scenario F panel tested thickness A.4 Materials and constructions A.4.1 Density of core material of Increase/decrease Possible for S and S doorsets. Test scenario A a3 a4 leaf or panel Possible for S providing the increase/decrease is not

greater than 25 %.

A.4.2 Pattern of core material of Increase Possible also proportionately with a leaf/panel size increase. Test scenario A leaf or panel – number of pieces – For double leaf doorsets, the rule shall be applied to each leaf see Figure A.7 separately.

Possible for S and S a3 a4.

Possible for S200 by up to 50 % providing the test included more than one joint.

SIST EN 15269-20:2020/oprA1:2026 EN 15269-20:2020/prA1:2026 (E) Construction parameter Variation Possibility of extension Additional evidence required (1) (2) (3) (4) A.4.3 Pattern of core material of Decrease Possible also proportionately with a leaf/panel size decrease. Test scenario A leaf or panel – number of pieces – For double leaf doorsets, the rule shall be applied to each leaf see Figure A.7 separately.

Possible for S and S a3 a4.

Possible for S steel based doorsets providing the fixing

technique is unchanged.

Possible for S200 timber based doorsets by up to 50 % providing one joint in the core material remains.

A.4.4 Number of layers of identical Increase Possible for S and S Test scenario A a3 a4.

core material of door leaf or panel – Possible for S steel based doorsets providing the fixing

see Figure A.25 technique to the top-layer/cover-plate (e.g. steel-sheet of the steel-doorset) is unchanged.

Possible for S timber based doorsets providing the test

included more than two joints and the fixing technique to the top layer/cover plate is unchanged.

A.4.5 Number of layers of identical Decrease Possible for S and S Test scenario A a3 a4.

core material of door leaf or panel – providing the fixing technique to the top- Possible for S200 see Figure A.25 layer/cover-plate (e.g. steel-sheet of the steel-doorset) is unchanged.

...