ASTM E3038-22a
(Practice)Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems
Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems
SIGNIFICANCE AND USE
5.1 This Practice is intended to provide a means for the AHJ or AA, or both, to verify evidence of a candidate’s experience, knowledge, and qualifications.
5.2 This Practice is not intended to set forth individual credentials for an AHJ or AA, or both.
5.3 This Practice is not intended to establish any performance criteria of firestop systems or fire-resistive joint systems.
Note 4: The performance criteria of a firestop system or fire-resistive joint system is found in many national and international test methods. Some of these methods include, but are not limited to, Test Method E814, UL 1479, ISO 10295-1, Test Method E1966, UL 2079, ISO 10295-2, Test Method E2307, Test Method E2837, etc.
SCOPE
1.1 This practice is intended to assist an authority having jurisdiction (AHJ) or authorizing authority (AA), or both, in establishing minimum qualifications for candidates who desire to conduct inspections in compliance with Practices E2174 and E2393.
Note 1: Authority having jurisdiction (AHJ) is defined in Practices E2174 and E2393.
Note 2: Authorizing authority (AA) is defined in Practices E2174 and E2393. Examples of the AA include, but are not limited to, the responsible architect, engineer, building owner, or their representative.
1.2 This practice makes available a procedure for a candidate to provide evidence to the AHJ or AA, or both, of their specialized knowledge and technical competence related to the firestop industry.
1.3 This practice determines the technical proficiency of a candidate based upon a minimum amount of education, experience, and knowledge possessed, which is needed to ensure candidate competence to conduct inspections in compliance with Practices E2174 and E2393.
1.4 The purpose of this practice is to allow the AHJ or AA, or both, to assess the ability of the candidate to comprehend and use inspection documents to conduct inspections in compliance with Practices E2174 and E2393.
Note 3: Inspection document is defined in Practices E2174 and E2393. The firestop submittal, when approved for use, should have sufficient details, including, but not limited to, the firestop manufacturer’s product data, a design listing of the tested firestop, and when required a judgment (Alternative Means and Methods). The judgment is commonly referred to as an “Engineering Judgment” in the firestop industry. These judgments are not always issued by an engineer or a registered design professional.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
- Status
- Published
- Publication Date
- 31-Oct-2022
- Technical Committee
- E06 - Performance of Buildings
- Drafting Committee
- E06.21 - Serviceability
Relations
- Effective Date
- 01-Jan-2024
- Effective Date
- 01-Dec-2023
- Effective Date
- 01-Nov-2023
- Effective Date
- 15-Apr-2020
- Effective Date
- 01-Apr-2020
- Effective Date
- 01-Jul-2019
- Effective Date
- 01-Jul-2019
- Effective Date
- 01-Mar-2019
- Effective Date
- 15-Dec-2018
- Effective Date
- 01-Apr-2018
- Effective Date
- 01-Mar-2018
- Effective Date
- 01-Aug-2016
- Effective Date
- 01-Oct-2015
- Effective Date
- 01-Oct-2015
- Effective Date
- 01-Sep-2015
Overview
ASTM E3038-22a: Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems provides a standardized method for authorities having jurisdiction (AHJ) or authorizing authorities (AA) to verify the qualifications and technical competence of prospective inspectors in the firestop and fire-resistive joint systems industry. This standard ensures that candidates meet established minimum qualifications and are capable of performing inspections in accordance with related ASTM practices, supporting building safety and code compliance.
ASTM E3038-22a does not address the performance specifications of firestop systems themselves, nor does it set requirements for the credentials of AHJs or AAs. Instead, it offers clear procedures for candidates to demonstrate their professional readiness to inspect these critical building components.
Key Topics
Minimum Qualifications
Outlines the minimum education, experience, and industry knowledge required of candidates, including:- Building construction experience in firestop systems
- Experience in quality control within the firestop industry
- Engagement in the selection or installation of firestop and fire-resistive joint systems
- Credentials as a registered design professional with relevant firestop experience
Qualification Process
Provides a procedure for candidates to document and submit evidence of:- Professional experience and education
- Completion of an applicable firestop industry examination
- Sufficient training and continuing education
Impartiality and Independence
Requires candidates and their employing firms to be fully independent from manufacturers, installers, contractors, and suppliers of firestop materials, ensuring integrity and impartiality in inspections.Documentation and Evidence of Compliance
Specifies the submission process for documentation to AHJ or AA, with periodic re-evaluation as required by project or authority.
Applications
ASTM E3038-22a is highly relevant for:
- Authorities Having Jurisdiction (AHJ): Helps enforce building safety codes by establishing clear criteria for inspector qualifications, directly supporting compliance with Practices E2174 (On-Site Inspection of Installed Firestop Systems) and E2393 (On-Site Inspection of Installed Fire-Resistive Joint Systems and Perimeter Fire Barriers).
- Design Professionals and Building Owners: Provides a baseline for selecting qualified inspectors, ensuring firestop and joint system integrity in new construction and renovations.
- Inspection Agencies & Candidate Inspectors: Offers a transparent framework for documenting qualifications, promoting inspector credibility.
- Code and Safety Compliance: Supports adherence to the International Building Code (IBC) and other regulations requiring third-party inspections of fire-resistive assemblies.
Related Standards
- ASTM E2174 - Practice for On-Site Inspection of Installed Firestop Systems
- ASTM E2393 - Practice for On-Site Inspection of Installed Fire-Resistive Joint Systems and Perimeter Fire Barriers
- ASTM E814 / UL 1479 / ISO 10295-1 - Fire Tests of Penetration Firestop Systems
- ASTM E1966 / UL 2079 / ISO 10295-2 - Fire Tests for Fire-Resistive Joint Systems
- ASTM E2307 - Fire Resistance of Perimeter Fire Barriers
- ASTM E2837 - Fire Resistance of Continuity Head-of-Wall Joint Systems
Additional international references include ISO/IEC 17020 and ISO/IEC 17065 for conformity assessment, and FM 4991 and AC291 for inspector and contractor accreditation.
By following ASTM E3038-22a, authorities and organizations can protect building occupants and property by ensuring that critical life safety systems are inspected by qualified, independent professionals-supporting both regulatory compliance and public safety.
Buy Documents
ASTM E3038-22a - Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems
REDLINE ASTM E3038-22a - Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems
Get Certified
Connect with accredited certification bodies for this standard

NSF International
Global independent organization facilitating standards development and certification.
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
ASTM E3038-22a is a standard published by ASTM International. Its full title is "Standard Practice for Assessing and Qualifying Candidates as Inspectors of Firestop Systems and Fire-Resistive Joint Systems". This standard covers: SIGNIFICANCE AND USE 5.1 This Practice is intended to provide a means for the AHJ or AA, or both, to verify evidence of a candidate’s experience, knowledge, and qualifications. 5.2 This Practice is not intended to set forth individual credentials for an AHJ or AA, or both. 5.3 This Practice is not intended to establish any performance criteria of firestop systems or fire-resistive joint systems. Note 4: The performance criteria of a firestop system or fire-resistive joint system is found in many national and international test methods. Some of these methods include, but are not limited to, Test Method E814, UL 1479, ISO 10295-1, Test Method E1966, UL 2079, ISO 10295-2, Test Method E2307, Test Method E2837, etc. SCOPE 1.1 This practice is intended to assist an authority having jurisdiction (AHJ) or authorizing authority (AA), or both, in establishing minimum qualifications for candidates who desire to conduct inspections in compliance with Practices E2174 and E2393. Note 1: Authority having jurisdiction (AHJ) is defined in Practices E2174 and E2393. Note 2: Authorizing authority (AA) is defined in Practices E2174 and E2393. Examples of the AA include, but are not limited to, the responsible architect, engineer, building owner, or their representative. 1.2 This practice makes available a procedure for a candidate to provide evidence to the AHJ or AA, or both, of their specialized knowledge and technical competence related to the firestop industry. 1.3 This practice determines the technical proficiency of a candidate based upon a minimum amount of education, experience, and knowledge possessed, which is needed to ensure candidate competence to conduct inspections in compliance with Practices E2174 and E2393. 1.4 The purpose of this practice is to allow the AHJ or AA, or both, to assess the ability of the candidate to comprehend and use inspection documents to conduct inspections in compliance with Practices E2174 and E2393. Note 3: Inspection document is defined in Practices E2174 and E2393. The firestop submittal, when approved for use, should have sufficient details, including, but not limited to, the firestop manufacturer’s product data, a design listing of the tested firestop, and when required a judgment (Alternative Means and Methods). The judgment is commonly referred to as an “Engineering Judgment” in the firestop industry. These judgments are not always issued by an engineer or a registered design professional. 1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard. 1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
SIGNIFICANCE AND USE 5.1 This Practice is intended to provide a means for the AHJ or AA, or both, to verify evidence of a candidate’s experience, knowledge, and qualifications. 5.2 This Practice is not intended to set forth individual credentials for an AHJ or AA, or both. 5.3 This Practice is not intended to establish any performance criteria of firestop systems or fire-resistive joint systems. Note 4: The performance criteria of a firestop system or fire-resistive joint system is found in many national and international test methods. Some of these methods include, but are not limited to, Test Method E814, UL 1479, ISO 10295-1, Test Method E1966, UL 2079, ISO 10295-2, Test Method E2307, Test Method E2837, etc. SCOPE 1.1 This practice is intended to assist an authority having jurisdiction (AHJ) or authorizing authority (AA), or both, in establishing minimum qualifications for candidates who desire to conduct inspections in compliance with Practices E2174 and E2393. Note 1: Authority having jurisdiction (AHJ) is defined in Practices E2174 and E2393. Note 2: Authorizing authority (AA) is defined in Practices E2174 and E2393. Examples of the AA include, but are not limited to, the responsible architect, engineer, building owner, or their representative. 1.2 This practice makes available a procedure for a candidate to provide evidence to the AHJ or AA, or both, of their specialized knowledge and technical competence related to the firestop industry. 1.3 This practice determines the technical proficiency of a candidate based upon a minimum amount of education, experience, and knowledge possessed, which is needed to ensure candidate competence to conduct inspections in compliance with Practices E2174 and E2393. 1.4 The purpose of this practice is to allow the AHJ or AA, or both, to assess the ability of the candidate to comprehend and use inspection documents to conduct inspections in compliance with Practices E2174 and E2393. Note 3: Inspection document is defined in Practices E2174 and E2393. The firestop submittal, when approved for use, should have sufficient details, including, but not limited to, the firestop manufacturer’s product data, a design listing of the tested firestop, and when required a judgment (Alternative Means and Methods). The judgment is commonly referred to as an “Engineering Judgment” in the firestop industry. These judgments are not always issued by an engineer or a registered design professional. 1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard. 1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
ASTM E3038-22a is classified under the following ICS (International Classification for Standards) categories: 13.220.01 - Protection against fire in general. The ICS classification helps identify the subject area and facilitates finding related standards.
ASTM E3038-22a has the following relationships with other standards: It is inter standard links to ASTM E176-24, ASTM E2837-23a, ASTM E2307-23b, ASTM E2174-20a, ASTM E2174-20, ASTM E2174-19, ASTM E2307-19, ASTM E1966-15(2019), ASTM E176-18a, ASTM E2174-18, ASTM E176-18, ASTM E699-16, ASTM E2307-15b, ASTM E2307-15be1, ASTM E2393-10a(2015). Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ASTM E3038-22a is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E3038 − 22a
Standard Practice for
Assessing and Qualifying Candidates as Inspectors of
Firestop Systems and Fire-Resistive Joint Systems
This standard is issued under the fixed designation E3038; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope priate safety, health, and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
1.1 This practice is intended to assist an authority having
1.6 The text of this standard references notes and footnotes
jurisdiction (AHJ) or authorizing authority (AA), or both, in
that provide explanatory material. These notes and footnotes
establishing minimum qualifications for candidates who desire
(excluding those in tables and figures) shall not be considered
to conduct inspections in compliance with Practices E2174 and
as requirements of the standard.
E2393.
1.7 This international standard was developed in accor-
NOTE 1—Authority having jurisdiction (AHJ) is defined in Practices
dance with internationally recognized principles on standard-
E2174 and E2393.
ization established in the Decision on Principles for the
NOTE 2—Authorizing authority (AA) is defined in Practices E2174 and
Development of International Standards, Guides and Recom-
E2393.ExamplesoftheAAinclude,butarenotlimitedto,theresponsible
architect, engineer, building owner, or their representative.
mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
1.2 This practice makes available a procedure for a candi-
date to provide evidence to the AHJ or AA, or both, of their
2. Referenced Documents
specialized knowledge and technical competence related to the
firestop industry.
2.1 ASTM Standards:
E176 Terminology of Fire Standards
1.3 This practice determines the technical proficiency of a
E631 Terminology of Building Constructions
candidate based upon a minimum amount of education,
E699 SpecificationforAgenciesInvolvedinTesting,Quality
experience, and knowledge possessed, which is needed to
Assurance, and Evaluating of Manufactured Building
ensure candidate competence to conduct inspections in com-
Components
pliance with Practices E2174 and E2393.
E814 Test Method for Fire Tests of Penetration Firestop
1.4 The purpose of this practice is to allow theAHJ orAA,
Systems
or both, to assess the ability of the candidate to comprehend
E1966 Test Method for Fire-Resistive Joint Systems
and use inspection documents to conduct inspections in com-
E2032 Practice for Extension of Data From Fire Resistance
pliance with Practices E2174 and E2393.
Tests Conducted in Accordance with ASTM E 119
E2174 Practice for On-Site Inspection of Installed Firestop
NOTE 3—Inspection document is defined in Practices E2174 and
E2393. The firestop submittal, when approved for use, should have
Systems
sufficient details, including, but not limited to, the firestop manufacturer’s
E2307 Test Method for Determining Fire Resistance of
product data, a design listing of the tested firestop, and when required a
Perimeter Fire Barriers Using Intermediate-Scale, Multi-
judgment (Alternative Means and Methods). The judgment is commonly
story Test Apparatus
referred to as an “Engineering Judgment” in the firestop industry. These
E2393 Practice for On-Site Inspection of Installed Fire
judgments are not always issued by an engineer or a registered design
professional.
Resistive Joint Systems and Perimeter Fire Barriers
E2750 Guide for Extension of Data from Penetration
1.5 This standard does not purport to address all of the
Firestop System Tests Conducted in Accordance with
safety concerns, if any, associated with its use. It is the
ASTM E814
responsibility of the user of this standard to establish appro-
E2837 Test Method for Determining the Fire Resistance of
Continuity Head-of-Wall Joint Systems Installed Between
This practice is under the jurisdiction of ASTM Committee E06 on Perfor-
mance of Buildings and is the direct responsibility of Subcommittee E06.21 on
Serviceability. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Nov. 1, 2022. Published November 2022. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 2016. Last previous edition approved in 2022 as E3038-22. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/E3038-22A. the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E3038 − 22a
Rated Wall Assemblies and Nonrated Horizontal Assem- 3.2.2 firestop industry, n—the field of work related to
blies firestop systems and fire-resistive joint systems.
2.2 ISO Standards: 3.2.2.1 Discussion—Fire-resistive joint systems are well
ISO/IEC 17020 Conformity assessment—Requirements for known as described in Test Method E1966. However, Test
the operation of various types of bodies performing Methods E2307 and E2837 also address specific types of
inspection fire-resistive joint systems called perimeter joint protections
ISO/IEC 17065 Conformity assessment—Requirements for (also known as perimeter fire barriers), and continuity head-
bodies certifying products, processes and services of-wall joint systems, respectively.
ISO 10295-1 Fire tests for building elements and
3.2.3 firestop industry inspector, n—the individual possess-
components—Fire testing of service installations—Part 1:
ing the credentials set forth in this Practice, and who is
Penetration seals
authorized by theAHJ orAA, or both, to conduct an inspection
ISO 10295-2 Fire tests for building elements and
under Practices E2174 and E2393, or both.
components—Fire testing of service installations—Part 2:
4. Summary of Practice
Linear joint (gap) seals
ISO/DTR 12470-1 Fire-resistance tests—Guidance on the
4.1 This Practice sets forth the minimum qualifications
application and extension of results from tests conducted
required to be eligible as a candidate to conduct inspections
on fire containment assemblies and products—Part 1:
under Practices E2174 and E2393.
Loadbearing elements and vertical and horizontal separat-
4.2 This Practice sets forth the information that needs to be
ing elements
documented by the candidate and a procedure to submit that
2.3 UL Standards:
information directly or indirectly to the AHJ or AA, or both.
UL 1479 Standard for Fire Tests of Penetration Firestops
UL 2079 Standard for Tests for Fire Resistance of Building
5. Significance and Use
Joint Systems
5.1 This Practice is intended to provide a meansfortheAHJ
2.4 Other Documents:
orAA, or both, to verify evidence of a candidate’s experience,
FCIA Firestop Manual of Practice
knowledge, and qualifications.
FM 4991 Approval Standard for Firestop Contractors Class
Number 4991
5.2 This Practice is not intended to set forth individual
AC291 Accreditation Criteria for Special Inspection Agen-
credentials for an AHJ or AA, or both.
cies
5.3 This Practice is not intended to establish any perfor-
8 9
IFC Firestop Inspection Manual
mance criteria of firestop systems or fire-resistive joint sys-
IFC Guidelines for Engineering Judgments
tems.
International Building Code
NOTE 4—The performance criteria of a firestop system or fire-resistive
joint system is found in many national and international test methods.
3. Terminology
Some of these methods include, but are not limited to, Test Method E814,
UL1479, ISO 10295-1, Test Method E1966, UL2079, ISO 10295-2, Test
3.1 Definitions—Terms defined in Terminology E631, Ter-
Method E2307, Test Method E2837, etc.
minology E176, and Specification E699 will prevail for terms
not defined in this Practice.Terminology E631 definitions shall
6. Procedure
apply when there is a conflict between Terminology E176,
6.1 The candidate shall be acceptable to the AHJ or AA, or
Specification E699, and Terminology E631 definitions.
both. The candidate shall meet at least one requirement in 6.2,
3.2 Definitions of Terms Specific to This Standard:
Prerequisites, and all of the requirements contained in 6.3,
3.2.1 candidate, n—the individual seeking the designation
Inspector Qualifications.
and recognition as a firestop industry inspector.
6.2 Prerequisites—The candidate shall meet and provide
documentation for at least one of the following requirements,
Available from International Organization for Standardization (ISO), ISO
which is acceptable to the AHJ or AA, or both:
Central Secretariat, Chemin de Blandonnet 8, CP 401, 1214 Vernier, Geneva,
6.2.1 Have a minimum of two years of experience in
Switzerland, http://www.iso.org.
building construction within the firestop industry conducting
Available from Underwriters Laboratories (UL), UL Solutions Headquarters,
333 Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
inspections under the direction of an inspector; or
Available from Firestop Contractors International Association, 4415 W. Harri-
6.2.2 Have a minimum of two years of experience in the
son Street, Suite 540, Hillside, IL 60162, https://www.fcia.org/FCIA-MANUAL-
firestop industry conducting quality control; or
OF-PRACTICE.
Available from FM Global, 270 Central Ave., Johnston, RI 02919-4949,
NOTE 5—Some methods used to assess quality control entities and
http://www.fmapprovals.com/approval-standards.
systems include, but are not limited to: Specification E699 that provides a
Available from International Accreditation Service, 3060 Saturn Street, Suite
means for evaluating agencies conducting quality control; ISO/IEC 17065
100, Brea, CA, 92821-1732, https://www.iasonline.org/resources/accreditation-
that affords a method to accredit organizations that oversee quality control
criteria-for-special-inspection-agencies-ac291/.
processes; ISO/IEC 17020 used to establish bodies performing inspection,
International Firestop Council, 2660 S. Utica Ave., Tulsa, OK 74114
etc.
Available from http://www.firestop.org/inspection-guidelines.html.
Available from http://www.firestop.org/engineering-judgement-guidelines.
6.2.3 Have a minimum four years of full-time (or at least
International Building Code is a registered trademark of and available from
6160 h) experience in the selection or installation, or both, of
International Code Council (ICC), 500 New Jersey Ave., NW, 6th Floor,
Washington, DC 20001, http://www.iccsafe.org. firestop systems or fire-resistive joint systems, or both; or
E3038 − 22a
NOTE 6—“Full-time” is considered “working the full number of hours
6.3.2.2 Option 2—Attend a 6-h educational program that is
considered normal or standard.” One can reasonably estimate that there
acceptable to the AHJ or AA, or both, and planned with the
are ≈250 working days per year. The number of working days less a
explicit purpose of educating parties specifically interested in
maximum of 30 days for allotted “days off,” which is commonly referred
the firestop industry.
toa
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E3038 − 22 E3038 − 22a
Standard Practice for
Assessing and Qualifying Candidates as Inspectors of
Firestop Systems and Fire-Resistive Joint Systems
This standard is issued under the fixed designation E3038; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice is intended to assist an authority having jurisdiction (AHJ) or authorizing authority (AA), or both, in establishing
minimum qualifications for candidates who desire to conduct inspections in compliance with Practices E2174 and E2393.
NOTE 1—Authority having jurisdiction (AHJ) is defined in Practices E2174 and E2393.
NOTE 2—Authorizing authority (AA) is defined in Practices E2174 and E2393. Examples of the AA include, but are not limited to, the responsible
architect, engineer, building owner, or their representative.
1.2 This practice makes available a procedure for a candidate to provide evidence to the AHJ or AA, or both, of their specialized
knowledge and technical competence related to the firestop industry.
1.3 This practice determines the technical proficiency of a candidate based upon a minimum amount of education, experience, and
knowledge possessed, which is needed to ensure candidate competence to conduct inspections in compliance with Practices E2174
and E2393.
1.4 The purpose of this practice is to allow the AHJ or AA, or both, to assess the ability of the candidate to comprehend and use
inspection documents to conduct inspections in compliance with Practices E2174 and E2393.
NOTE 3—Inspection document is defined in Practices E2174 and E2393. The firestop submittal, when approved for use, should have sufficient details,
including, but not limited to, the firestop manufacturer’s product data, a design listing of the tested firestop, and when required a judgment (Alternative
Means and Methods). The judgment is commonly referred to as an “Engineering Judgment” in the firestop industry. These judgments are not always
issued by an engineer or a registered design professional.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered as requirements of the standard.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
This practice is under the jurisdiction of ASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.21 on Serviceability.
Current edition approved July 1, 2022Nov. 1, 2022. Published July 2022November 2022. Originally approved in 2016. Last previous edition approved in 20202022 as
E3038-20.-22. DOI: 10.1520/E3038-22.10.1520/E3038-22A.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E3038 − 22a
2. Referenced Documents
2.1 ASTM Standards:
E176 Terminology of Fire Standards
E631 Terminology of Building Constructions
E699 Specification for Agencies Involved in Testing, Quality Assurance, and Evaluating of Manufactured Building Components
E814 Test Method for Fire Tests of Penetration Firestop Systems
E1966 Test Method for Fire-Resistive Joint Systems
E2032 Practice for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119
E2174 Practice for On-Site Inspection of Installed Firestop Systems
E2307 Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test
Apparatus
E2393 Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers
E2750 Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM E814
E2837 Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall
Assemblies and Nonrated Horizontal Assemblies
2.2 ISO Standards:
ISO/IEC 17020 Conformity assessment—Requirements for the operation of various types of bodies performing inspection
ISO/IEC 17065 Conformity assessment—Requirements for bodies certifying products, processes and services
ISO 10295-1 Fire tests for building elements and components—Fire testing of service installations—Part 1: Penetration seals
ISO 10295-2 Fire tests for building elements and components—Fire testing of service installations—Part 2: Linear joint (gap)
seals
ISO/DTR 12470-1 Fire-resistance tests—Guidance on the application and extension of results from tests conducted on fire
containment assemblies and products—Part 1: Loadbearing elements and vertical and horizontal separating elements
2.3 UL Standards:
UL 1479 Standard for Fire Tests of Penetration Firestops
UL 2079 Standard for Tests for Fire Resistance of Building Joint Systems
2.4 Other Documents:
FCIA Firestop Manual of Practice
FM 4991 Approval Standard for Firestop Contractors Class Number 4991
AC291 Accreditation Criteria for Special Inspection Agencies
8 9
IFC Firestop Inspection Manual
IFC Guidelines for Engineering Judgments
International Building Code
3. Terminology
3.1 Definitions—Terms defined in Terminology E631, Terminology E176, and Specification E699 will prevail for terms not
defined in this Practice. Terminology E631 definitions shall apply when there is a conflict between Terminology E176,
Specification E699, and Terminology E631 definitions.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 candidate, n—the individual or company seeking the designation and recognition as a firestop industry inspector.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Available from International Organization for Standardization (ISO), ISO Central Secretariat, Chemin de Blandonnet 8, CP 401, 1214 Vernier, Geneva, Switzerland,
http://www.iso.org.
Available from Underwriters Laboratories (UL), UL Solutions Headquarters, 333 Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
Available from Firestop Contractors International Association, 4415 W. Harrison Street, Suite 540, Hillside, IL 60162, https://www.fcia.org/FCIA-MANUAL-OF-
PRACTICE.
Available from FM Global, 270 Central Ave., Johnston, RI 02919-4949, http://www.fmapprovals.com/approval-standards.
Available from International Accreditation Service, 3060 Saturn Street, Suite 100, Brea, CA, 92821-1732, https://www.iasonline.org/resources/accreditation-criteria-
for-special-inspection-agencies-ac291/.
International Firestop Council, 2660 S. Utica Ave., Tulsa, OK 74114
Available from http://www.firestop.org/inspection-guidelines.html.
Available from http://www.firestop.org/engineering-judgement-guidelines.
International Building Code is a registered trademark of and available from International Code Council (ICC), 500 New Jersey Ave., NW, 6th Floor, Washington, DC
20001, http://www.iccsafe.org.
E3038 − 22a
3.2.2 firestop industry, n—the field of work related to firestop systems and fire-resistive joint systems.
3.2.2.1 Discussion—
Fire-resistive joint systems are well known as described in Test Method E1966. However, Test Methods E2307 and E2837 also
address specific types of fire-resistive joint systems called perimeter joint protections (also known as perimeter fire barriers), and
continuity head-of-wall joint systems, respectively.
3.2.3 firestop industry inspector, n—the individual or company possessing the credentials set forth in this Practice, and who is
authorized by the AHJ or AA, or both, to conduct an inspection under Practices E2174 and E2393, or both.
4. Summary of Practice
4.1 This Practice sets forth the minimum qualifications required to be eligible as a candidate to conduct inspections under Practices
E2174 and E2393.
4.2 This Practice sets forth the information that needs to be documented by the candidate and a procedure to submit that
information directly or indirectly to the AHJ or AA, or both.
5. Significance and Use
5.1 This Practice is intended to provide a means for the AHJ or AA, or both, to verify evidence of a candidate’s experience,
knowledge, and qualifications.
5.2 This Practice is not intended to set forth individual credentials for an AHJ or AA, or both.
5.3 This Practice is not intended to establish any performance criteria of firestop systems or fire-resistive joint systems.
NOTE 4—The performance criteria of a firestop system or fire-resistive joint system is found in many national and international test methods. Some of
these methods include, but are not limited to, Test Method E814, UL 1479, ISO 10295-1, Test Method E1966, UL 2079, ISO 10295-2, Test Method E2307,
Test Method E2837, etc.
6. Procedure
6.1 The candidate shall be acceptable to the AHJ or AA, or both. The candidate shall meet at least one requirement in 6.2,
Prerequisites, and all of the requirements contained in 6.3, Inspector Qualifications.
6.2 Prerequisites—The candidate shall meet and provide documentation for at least one of the following requirements, which is
acceptable to the AHJ or AA, or both:
6.2.1 Have a minimum of two years of experience in building construction within the firestop industry conducting inspections
under the direction of an inspector; or
6.2.2 Have a minimum of two years of experience in the firestop industry conducting quality control; or
NOTE 5—Some methods used to assess quality control entities and systems include, but are not limited to: Specification E699 that provides a means for
evaluating agencies conducting quality control; ISO/IEC 17065 that affords a method to accredit organizations that oversee quality control processes;
ISO/IEC 17020 used to establish bodies performing inspection, etc.
6.2.3 Have a minimum four years of full-time (or at least 6160 h) experience in the selection or installation, or both, of firestop
systems or fire-resistive joint systems, or both; or
NOTE 6—“Full-time” is considered “working the full number of hours considered normal or standard.” One can reasonably estimate that there are ≈250
working days per year. The number of working days less a maximum of 30 days for allotted “days off,” which is commonly referred to as vacation
See http://www.merriam-webster.com/dictionary/full-time.
See http://www.workingdays.us/workingdays_holidays_2016.htm.
E3038 − 22a
and sick time, provides 220 working day
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...