Empty enclosures for low-voltage switchgear and controlgear assemblies - General requirements (IEC 62208:2023)

IEC 62208:2023 applies to empty enclosures, as provided by the enclosure manufacturer, prior to the incorporation of switchgear and controlgear components by the assembly manufacturer. This document specifies general definitions, classifications, characteristics and test requirements of enclosures to be used as part of switchgear and controlgear assemblies (e.g. in accordance with the product standard in the IEC 61439 series), the rated voltage of which does not exceed 1 000 V AC or 1 500 V DC, and suitable for general use for either indoor or outdoor applications. This third edition cancels and replaces the second edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) consideration of the modifications introduced in IEC 61439-1:2020;
b) alignment of test procedures with the newest relevant standards.

Leergehäuse für Niederspannungs-Schaltgerätekombinationen - Allgemeine Anforderungen (IEC 62208:2023)

Enveloppes vides destinées aux ensembles d'appareillages à basse tension - Exigences générales (IEC 62208:2023)

L'IEC 62208:2023 s'applique aux enveloppes vides, dans l'état dans lequel elles sont fournies par le fabricant d'enveloppes, avant incorporation des composants d'appareillage par le fabricant de l'ensemble. Le présent document spécifie les définitions, les classifications, les caractéristiques et les exigences d'essai générales des enveloppes à utiliser en tant que partie d'ensembles d'appareillage (selon par exemple la norme de produit de la série IEC 61439), dont la tension assignée ne dépasse pas 1 000 V en courant alternatif ou 1 500 V en courant continu pour usage général extérieur ou intérieur. Cette troisième édition annule et remplace la deuxième édition parue en 2011. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) prise en compte des modifications introduites dans l'IEC 61439-1:2020;
b) alignement des procédures d'essai sur les toutes nouvelles normes applicables.

Prazna ohišja za sestave nizkonapetostnih stikalnih in krmilnih naprav - Splošne zahteve (IEC 62208:2023)

Standard IEC 62208:2023 se uporablja za prazna ohišja, ki jih je dobavil proizvajalec ohišij, preden proizvajalec sestava doda stikalne in krmilne dele. Ta dokument določa splošne definicije, klasifikacije, značilnosti in preskusne zahteve za ohišja, ki so namenjena za uporabo kot del sestavov stikalnih in krmilnih naprav (npr. v skladu s standardom za izdelek iz skupine standardov IEC 61439), katerih nazivna napetost ne presega 1000 V AC ali 1500 V DC in ki so primerna za splošno uporabo v zaprtih prostorih ali na prostem. Tretja izdaja razveljavlja in nadomešča drugo izdajo, objavljeno leta 2011. Ta izdaja je tehnično popravljena izdaja. Ta izdaja v primerjavi s prejšnjo vključuje naslednje pomembne tehnične spremembe:
a) upoštevanje sprememb, uvedenih v standardu IEC 61439-1:2020;
b) uskladitev preskusnih postopkov z najnovejšimi ustreznimi standardi.

General Information

Status
Published
Public Enquiry End Date
22-Sep-2022
Publication Date
17-Oct-2023
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
03-Oct-2023
Due Date
08-Dec-2023
Completion Date
18-Oct-2023

Relations

Overview

EN IEC 62208:2023 specifies general requirements for empty enclosures supplied by the enclosure manufacturer for use in low‑voltage switchgear and controlgear assemblies. It applies to enclosures intended for assembly manufacturers to incorporate switchgear/controlgear components rated up to 1 000 V AC or 1 500 V DC, suitable for indoor or outdoor use. The 2023 edition supersedes EN 62208:2011 and includes technical updates aligned with IEC 61439‑1:2020 and updated test procedures.

Key topics and technical requirements

  • Scope and classification: definitions and classifications of empty enclosures for switchgear and controlgear assemblies.
  • Design and construction: static loads, access to the interior, lifting/transport supports, mounting arrangements and permissible loads.
  • Protection ratings: requirements and verifications for IP (ingress protection) per IEC 60529 and IK (mechanical impact) per IEC 62262.
  • Electrical safety: rules for protection against electric shock, earth continuity for Class I enclosures and requirements for Class II enclosures.
  • Material and fire performance: tests for insulating materials, thermal stability, glow‑wire, needle‑flame and ball pressure tests to assess resistance to heat and fire.
  • Dielectric strength: type tests and preconditioning for enclosures with/without metal elements inside the protected space.
  • Environmental resistance: corrosion testing, salt‑mist, UV resistance, and damp heat cycling per referenced environmental standards.
  • Thermal power dissipation: methods for determining ability to dissipate heat by test or calculation.
  • Marking and documentation: required information including dimensional data, mounting, lifting points, protective measures and EMC considerations.

Practical applications and users

EN IEC 62208:2023 is essential for:

  • Enclosure manufacturers designing and certifying empty housings for LV assemblies.
  • Assembly manufacturers (panel builders) selecting compliant enclosures for assemblies per the IEC 61439 series.
  • Test laboratories and certification bodies conducting type tests (IP, IK, dielectric, corrosion, thermal).
  • Design engineers, procurement and compliance teams ensuring product selection meets regulatory and safety requirements for indoor/outdoor LV switchgear installations.

Related standards

  • IEC 61439 series (switchgear and controlgear assemblies) - referenced for assembly requirements.
  • IEC 60529 (IP Code), IEC 62262 (IK Code), IEC 60695 series (fire tests), IEC 60068 series (environmental testing) - normative references cited for specific tests and criteria.

EN IEC 62208:2023 ensures empty enclosures meet consistent mechanical, thermal, electrical and environmental performance expectations, helping manufacturers and specifiers achieve safe, reliable LV switchgear assemblies.

Standard
SIST EN IEC 62208:2023
English language
34 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Frequently Asked Questions

SIST EN IEC 62208:2023 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Empty enclosures for low-voltage switchgear and controlgear assemblies - General requirements (IEC 62208:2023)". This standard covers: IEC 62208:2023 applies to empty enclosures, as provided by the enclosure manufacturer, prior to the incorporation of switchgear and controlgear components by the assembly manufacturer. This document specifies general definitions, classifications, characteristics and test requirements of enclosures to be used as part of switchgear and controlgear assemblies (e.g. in accordance with the product standard in the IEC 61439 series), the rated voltage of which does not exceed 1 000 V AC or 1 500 V DC, and suitable for general use for either indoor or outdoor applications. This third edition cancels and replaces the second edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) consideration of the modifications introduced in IEC 61439-1:2020; b) alignment of test procedures with the newest relevant standards.

IEC 62208:2023 applies to empty enclosures, as provided by the enclosure manufacturer, prior to the incorporation of switchgear and controlgear components by the assembly manufacturer. This document specifies general definitions, classifications, characteristics and test requirements of enclosures to be used as part of switchgear and controlgear assemblies (e.g. in accordance with the product standard in the IEC 61439 series), the rated voltage of which does not exceed 1 000 V AC or 1 500 V DC, and suitable for general use for either indoor or outdoor applications. This third edition cancels and replaces the second edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) consideration of the modifications introduced in IEC 61439-1:2020; b) alignment of test procedures with the newest relevant standards.

SIST EN IEC 62208:2023 is classified under the following ICS (International Classification for Standards) categories: 29.130.20 - Low voltage switchgear and controlgear. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN IEC 62208:2023 has the following relationships with other standards: It is inter standard links to SIST EN 62208:2012. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN IEC 62208:2023 is associated with the following European legislation: EU Directives/Regulations: 2014/35/EU; Standardization Mandates: M/511. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase SIST EN IEC 62208:2023 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2023
Prazna ohišja za sestave nizkonapetostnih stikalnih in krmilnih naprav - Splošne
zahteve (IEC 62208:2023)
Empty enclosures for low-voltage switchgear and controlgear assemblies - General
requirements (IEC 62208:2023)
Leergehäuse für Niederspannungs-Schaltgerätekombinationen - Allgemeine
Anforderungen (IEC 62208:2023)
Enveloppes vides destinées aux ensembles d'appareillages à basse tension - Exigences
générales (IEC 62208:2023)
Ta slovenski standard je istoveten z: EN IEC 62208:2023
ICS:
29.130.20 Nizkonapetostne stikalne in Low voltage switchgear and
krmilne naprave controlgear
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 62208

NORME EUROPÉENNE
EUROPÄISCHE NORM September 2023
ICS 29.130.20 Supersedes EN 62208:2011
English Version
Empty enclosures for low-voltage switchgear and controlgear
assemblies - General requirements
(IEC 62208:2023)
Enveloppes vides destinées aux ensembles d'appareillages Leergehäuse für Niederspannungs-
à basse tension - Exigences générales Schaltgerätekombinationen - Allgemeine Anforderungen
(IEC 62208:2023) (IEC 62208:2023)
This European Standard was approved by CENELEC on 2023-09-06. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2023 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 62208:2023 E
European foreword
The text of document 121B/180/FDIS, future edition 3 of IEC 62208, prepared by SC 121B "Low-
voltage switchgear and controlgear assemblies" of IEC/TC 121 "Switchgear and controlgear and their
assemblies for low voltage" was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN IEC 62208:2023.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2024-06-06
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2026-09-06
document have to be withdrawn
This document supersedes EN 62208:2011 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a Standardization Request addressed to CENELEC by the
European Commission.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 62208:2023 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standard indicated:
IEC 60216 (series) NOTE Approved as EN 60216 (series)
IEC 60670 (series) NOTE Approved as EN 60670 (series)
IEC 60670-24 NOTE Approved as EN 60670-24
IEC 60715 NOTE Approved as EN 60715
IEC 60721-3-3:2019 NOTE Approved as EN IEC 60721-3-3:2019 (not modified)
IEC 61000-5-7:2001 NOTE Approved as EN 61000-5-7:2001 (not modified)
IEC 61140:2016 NOTE Approved as EN 61140:2016 (not modified)
IEC 61439 (series) NOTE Approved as EN IEC 61439 (series)
IEC 61439-1:2020 NOTE Approved as EN IEC 61439-1:2021 (not modified)
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cencenelec.eu.
Publication Year Title EN/HD Year
IEC 60068-2-2 2007 Environmental testing - Part 2-2: Tests - EN 60068-2-2 2007
Test B: Dry heat
IEC 60068-2-11 2021 Environmental testing - Part 2-11: Tests - EN IEC 60068-2-11 2021
Test Ka: Salt mist
IEC 60068-2-30 2005 Environmental testing - Part 2-30: Tests - EN 60068-2-30 2005
Test Db: Damp heat, cyclic (12 h + 12 h
cycle)
IEC 60085 2007 Electrical insulation - Thermal evaluation EN 60085 2008
and designation
IEC 60364 series Low-voltage electrical installations HD 60364 series
IEC 60529 1989 Degrees of protection provided by EN 60529 1991
enclosures (IP Code)
- -  + corrigendum May 1993
+ A1 1999  + A1 2000
+ A2 2013  + A2 2013
IEC 60695-2-10 2021 Fire hazard testing - Part 2-10: EN IEC 60695-2-10 2021
Glowing/hot-wire based test methods -
Glow-wire apparatus and common test
procedure
IEC 60695-2-11 2021 Fire hazard testing - Part 2-11: EN IEC 60695-2-11 2021
Glowing/hot-wire based test methods -
Glow-wire flammability test method for end
products (GWEPT)
IEC 60695-10-2 2014 Fire hazard testing - Part 10-2: Abnormal EN 60695-10-2 2014
heat - Ball pressure test method
IEC 60695-11-5 2016 Fire hazard testing - Part 11-5: Test flames EN 60695-11-5 2017
- Needle-flame test method - Apparatus,
confirmatory test arrangement and
guidance
IEC TR 60890 2014 A method of temperature-rise verfification - -
of low-voltage switchgear and controlgear
assemblies by calculation
IEC 62262 2002 Degrees of protection provided by EN 62262 2002
enclosures for electrical equipment against
external mechanical impacts (IK code)
+ AMD 2021  + A1 2021
ISO 178 2019 Plastics - Determination of flexural EN ISO 178 2019
properties
ISO 179-1 2010 Plastics - Determination of Charpy impact EN ISO 179-1 2010
properties - Part 1: Non-instrumented
impact test
ISO 179-2 2020 Plastics - Determination of Charpy impact EN ISO 179-2 2020
properties - Part 2: Instrumented impact
test
ISO 2409 2020 Paints and varnishes - Cross-cut test EN ISO 2409 2020
ISO 4628-3 2016 Paints and varnishes - Evaluation of EN ISO 4628-3 2016
degradation of coatings - Designation of
quantity and size of defects, and of
intensity of uniform changes in appearance
- Part 3: Assessment of degree of rusting
ISO 4892-2 2013 Plastics - Methods of exposure to EN ISO 4892-2 2013
laboratory light sources - Part 2: Xenon-arc
lamps
ISO 11469 2016 Plastics - Generic identification and EN ISO 11469 2016
marking of plastics products
IEC 62208 ®
Edition 3.0 2023-06
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Empty enclosures for low-voltage switchgear and controlgear assemblies –

General requirements
Enveloppes vides destinées aux ensembles d'appareillage à basse tension –

Exigences générales
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.130.20 ISBN 978-2-8322-7071-4

– 2 – IEC 62208:2023 © IEC 2023
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
4 Classification . 10
5 Electromagnetic compatibility (EMC) . 11
6 Information to be given regarding the enclosure . 11
6.1 General . 11
6.2 Marking . 11
6.3 Documentation . 11
6.3.1 General . 11
6.3.2 Dimensions . 12
6.3.3 Mounting arrangements . 12
6.3.4 Permissible loads . 12
6.3.5 Lifting and transport support . 12
6.3.6 Protective measures . 12
6.3.7 Thermal power dissipation capability . 13
7 Service conditions . 13
7.1 General . 13
7.2 Normal service conditions . 13
7.3 Special service conditions . 13
7.4 Conditions during transport and storage . 14
8 Design and construction . 14
8.1 General . 14
8.2 Static loads . 14
8.3 Lifting and transport support . 14
8.4 Access to the interior of the enclosure . 15
8.5 Protection against electric shock . 15
8.5.1 General . 15
8.5.2 Requirements for earth continuity within the class I enclosure . 15
8.5.3 Requirements for class II enclosure . 15
8.6 Protection against mechanical impact (IK code) . 16
8.7 Protection against contact with live parts, ingress of solid foreign bodies and
water (IP code) . 16
8.8 Protection against corrosion . 16
8.9 Enclosures constructed of or covered by insulating material . 16
9 Type tests . 16
9.1 General . 16
9.2 General conditions of tests. 16
9.3 Marking . 17
9.4 Static loads . 17
9.5 Lifting . 18
9.6 Mechanical operation . 18
9.7 Axial loads of metal inserts . 18
9.8 Degree of protection against external mechanical impacts (IK code) . 19

IEC 62208:2023 © IEC 2023 – 3 –
9.9 Degree of protection (IP code) . 20
9.9.1 Degree of protection against access to hazardous parts and against the
ingress of solid foreign objects indicated by first characteristic numeral . 20
9.9.2 Degree of protection against ingress of water as indicated by second
characteristic numeral . 20
9.9.3 Degree of protection against hazardous parts as indicated by additional
letter . 21
9.10 Properties of insulating materials . 21
9.10.1 Thermal stability . 21
9.10.2 Resistance to normal heat . 21
9.10.3 Resistance to abnormal heat and fire due to internal electric effects . 22
9.11 Dielectric strength . 23
9.11.1 General . 23
9.11.2 Preconditioning . 23
9.11.3 Enclosures without metal elements inside the protected space . 23
9.11.4 Enclosures having metal elements inside the protected space . 24
9.11.5 Results to be obtained . 24
9.12 Effective earth continuity between the exposed-conductive-parts of the class
I enclosure and the protective circuit . 24
9.13 Resistance to ultra-violet (UV) radiation . 24
9.13.1 Verification by test . 24
9.13.2 Verification by comparison to a reference design . 25
9.14 Resistance to corrosion . 26
9.14.1 General . 26
9.14.2 Test procedure . 26
9.14.3 Results to be obtained . 27
9.15 Thermal power dissipation capability . 27
9.15.1 General . 27
9.15.2 Determination of the power dissipation capability by test . 27
9.15.3 Determination of the power dissipation capability by calculation and
comparison . 28
9.15.4 Determination of the power dissipation capability by calculation method . 28
Annex A (informative) List of notes concerning certain countries . 29
Bibliography . 30

Table 1 – Climatic conditions . 13
Table 2 – Number of samples to be tested and order of test per sample . 17
Table 3 – Axial loads of metal inserts . 19
Table 4 – Dielectric test voltage . 24

– 4 – IEC 62208:2023 © IEC 2023
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EMPTY ENCLOSURES FOR LOW-VOLTAGE
SWITCHGEAR AND CONTROLGEAR ASSEMBLIES –
GENERAL REQUIREMENTS
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
IEC 62208 has been prepared by subcommittee 121B: Low-voltage switchgear and controlgear
assemblies, of IEC technical committee 121: Switchgear and controlgear and their assemblies
for low voltage. It is an International Standard.
This third edition cancels and replaces the second edition published in 2011. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) consideration of the modifications introduced in IEC 61439-1:2020;
b) alignment of test procedures with the newest relevant standards.

IEC 62208:2023 © IEC 2023 – 5 –
The text of this International Standard is based on the following documents:
Draft Report on voting
121B/180/FDIS 121B/180/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
The reader's attention is drawn to the fact that Annex A lists all of the "in-some-country" clauses
on differing practices of a less permanent nature relating to the subject of this document.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – IEC 62208:2023 © IEC 2023
INTRODUCTION
The purpose of this document is to harmonize as far as practicable all rules and requirements
of a general nature applicable to empty enclosures for low-voltage switchgear and controlgear
assemblies, in order to obtain uniformity of requirements and verification for empty enclosures
and to avoid the need for verification in other standards.

IEC 62208:2023 © IEC 2023 – 7 –
EMPTY ENCLOSURES FOR LOW-VOLTAGE
SWITCHGEAR AND CONTROLGEAR ASSEMBLIES –
GENERAL REQUIREMENTS
1 Scope
This document applies to empty enclosures, as provided by the enclosure manufacturer, prior
to the incorporation of switchgear and controlgear components by the assembly manufacturer.
This document specifies general definitions, classifications, characteristics and test
requirements of enclosures to be used as part of switchgear and controlgear assemblies (e.g.
in accordance with the product standard in the IEC 61439 series), the rated voltage of which
does not exceed 1 000 V AC or 1 500 V DC, and suitable for general use for either indoor or
outdoor applications.
NOTE 1 Additional requirements could apply for specific applications.
NOTE 2 Empty enclosures according to this document are suitable for mounting of electrical components.
This document does not apply to enclosures which are covered by other specific products
standards (e.g. IEC 60670-24).
Compliance with the safety requirements of the applicable product standard for the final product
produced using an empty enclosure is the responsibility of the assembly manufacturer.
NOTE 3 This document could serve as a basis for other technical committees.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60068-2-2:2007, Environmental testing – Part 2-2: Tests – Test B: Dry heat
IEC 60068-2-11:2021, Environmental testing – Part 2-11: Tests – Test Ka: Salt mist
IEC 60068-2-30:2005, Environmental testing – Part 2-30: Tests – Test Db: Damp heat, cyclic
(12 h + 12 h cycle)
IEC 60085:2007, Electrical insulation – Thermal evaluation and designation
IEC 60364 (all parts), Low-voltage electrical installations
IEC 60529:1989, Degrees of protection provided by enclosures (IP Code)
IEC 60529:1989/AMD1:1999
IEC 60529:1989/AMD2:2013
IEC 60695-2-10:2021, Fire hazard testing – Part 2-10: Glowing/hot-wire based test methods –
Glow-wire apparatus and common test procedure
IEC 60695-2-11:2021, Fire hazard testing – Part 2-11: Glowing/hot-wire based test methods –
Glow-wire flammability test methods for end-products (GWEPT)

– 8 – IEC 62208:2023 © IEC 2023
IEC 60695-10-2:2014, Fire hazard testing − Part 10-2: Abnormal heat − Ball pressure test
method
IEC 60695-11-5:2016; Fire hazard testing – Part 11-5: Test flames – Needle-flame test method
– Apparatus, confirmatory test arrangement and guidance
IEC TR 60890:2014, A method of temperature-rise verification of low-voltage switchgear and
controlgear assemblies by calculation
IEC 62262:2002, Degrees of protection provided by enclosures for electrical equipment against
external mechanical impacts (IK code)
IEC 62262:2002/AMD1:2021
ISO 178:2019, Plastics – Determination of flexural properties
ISO 179-1:2010, Plastics – Determination of Charpy impact properties – Part 1:
Non-instrumented impact test
ISO 179-2:2020, Plastics – Determination of Charpy impact properties – Part 2: Instrumented
impact test
ISO 2409:2020, Paints and varnishes – Cross-cut test
ISO 4628-3:2016, Paints and varnishes – Evaluation of degradation of coatings – Designation
of quantity and size of defects, and of intensity of uniform changes in appearance – Part 3:
Assessment of degree of rusting
ISO 4892-2:2013, Plastics – Methods of exposure to laboratory light sources – Part 2:
Xenon-arc lamps
ISO 11469:2016, Plastics – Generic identification and marking of plastic products
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
• IEC Electropedia: available at https://www.electropedia.org/
• ISO Online browsing platform: available at https://www.iso.org/obp
3.1
empty enclosure
enclosure intended for support and installation of electrical equipment, whose internal space
provides suitable protection against external influences as well as a specified degree of
protection against approach to or contact with live parts and against contact with moving parts
Note 1 to entry: Throughout this document, the word enclosure is used for empty enclosure.
Note 2 to entry: For the purposes of this document, the terms boxes, cubicles, desks or cabinets are alternative
terms for enclosures.
IEC 62208:2023 © IEC 2023 – 9 –
3.2
protected space
internal space or portion of an enclosure as specified by the enclosure manufacturer intended
to enclose electrical components, and which provides defined protection against external
influences and contact with live parts
3.3
cover
external part of the enclosure
3.4
door
hinged or sliding cover
3.5
mounting plate
separate internal accessory of the enclosure intended for the mounting of electrical components
3.6
cable gland plate
removable accessory of the enclosure, intended for securing and sealing of cables, conductors
and conduits at their point of entry
3.7
removable cover
cover which is designed for closing an opening in the external enclosure and which can be
removed for carrying out certain operations and maintenance work
Note 1 to entry: A lid is considered as a removable cover.
3.8
inspection
action comprising careful scrutiny, including visual scrutiny where conditions are obvious, of an
item carried out either without dismantling, or with the addition of partial dismantling as required,
supplemented by means such as measurement, in order to arrive at a reliable conclusion as to
the condition of an item
[SOURCE: IEC 60050-426:2020, 426-14-02, modified – "including visual scrutiny where
conditions are obvious" has been added.]
3.9
rated insulation voltage
U
i
value of the RMS withstand voltage assigned by the enclosure manufacturer to the enclosure
or to a part of it, characterizing the specified (long-term) withstand capability of its insulation
[SOURCE: IEC 60050-312:2014, 312-06-02, modified – Symbol U has been added, in the
i
definition "rated value" has been replaced by "value", "enclosure" has been added to
manufacturer, "equipment" has been replaced by "enclosure" and the Note has been deleted.]

– 10 – IEC 62208:2023 © IEC 2023
3.10
class I enclosure
enclosure with at least one provision for a basic protection and a connection to a protective
conductor as provision for fault protection
Note 1 to entry: See IEC 61140:2016, 7.3 for further details.
[SOURCE: IEC 61439-1:2020, 3.7.24, modified – "assembly" has been replaced by "enclosure"
and Note 2 to entry has been deleted.]
3.11
class II enclosure
enclosure which is provided with the following;
• basic insulation as provision for basic protection, and
• supplementary insulation as provision for fault protection,
or in which
• basic protection and fault protection are provided by reinforced insulation
Note 1 to entry: See IEC 61140:2016, 7.4 for further details.
[SOURCE: IEC 61439-1:2020, 3.7.25, modified – "assembly" has been replaced by
"enclosure".]
3.12
empty enclosure for indoor installation
empty enclosure that is designed for use in locations where the normal service conditions for
indoor use as specified in Clause 7 apply
3.13
empty enclosure for outdoor installation
empty enclosure that is designed for use in locations where the normal service conditions for
outdoor use as specified in Clause 7 apply
4 Classification
Enclosures are classified according to:
a) the type of material:
• insulating;
• metallic;
• combination of insulating and metallic.
b) method of mounting:
• floor standing;
• wall mounting;
• flush mounting;
• pole mounting.
c) the intended location:
• outdoor;
• indoor.
IEC 62208:2023 © IEC 2023 – 11 –
d) the degree of protection:
• IP code, according to IEC 60529:1989 and IEC 60529:1989/AMD1:1999 and
AMD2:2013;
• IK code, according to IEC 62262:2002 and IEC 62262:2002/AMD1:2021.
5 Electromagnetic compatibility (EMC)
EMC requirements are not applicable for enclosures according to this document.
NOTE EMC is not a basic requirement for empty enclosures to this document. However, when enclosure
manufacturers want to assign a degree of protection against electromagnetic disturbances (EM code) it is referred
to IEC 61000-5-7:2001.
6 Information to be given regarding the enclosure
6.1 General
The following information shall be given by the enclosure manufacturer.
6.2 Marking
The enclosure shall be identifiable, making it possible for the assembly manufacturer to obtain
relevant information from the enclosure manufacturer. Such identification shall comprise:
• either the name, trade mark or identification mark of the enclosure manufacturer;
• type designation or identification number of the enclosure.
The marking shall be durable and easily legible and can be inside the enclosure.
Compliance is checked according to the test of 9.3 and by inspection.
Marking for the recycling of plastic parts shall be as stated in ISO 11469.
Marking of enclosures used for class II assemblies with the symbol IEC 60417-5172

(2003-02) is the responsibility of the assembly manufacturer.
6.3 Documentation
6.3.1 General
The enclosure manufacturer’s documentation shall include:
– the enclosure classification (see Clause 4);
– any instruction necessary for the correct handling, assembling, mounting and service
conditions of the enclosure;
– a reference to this document, and
– the following characteristics:
• dimensions (see 6.3.2);
• mounting arrangements (6.3.3);
• permissible loads (see 6.3.4);
• lifting and transport devices, if necessary (see 6.3.5);
• protective measures (see 6.3.6);
• thermal power dissipation capability (see 6.3.7);
• applicable service conditions (see Clause 7);

– 12 – IEC 62208:2023 © IEC 2023
• location and size of protected space (see 3.2);
• rated insulation voltage U of enclosures constructed of an insulating material and Class
i
II enclosures (see 9.11.3, Table 4);
• degree of protection against mechanical impact (IK code, see 8.6);
• degree of protection against contact with hazardous live parts, ingress of solid foreign
bodies and water (IP code, see 8.7);
• maximum permissible temperatures inside for which enclosures constructed of insulating
material is suitable (see 9.10.2).
6.3.2 Dimensions
The dimensions shall be given in millimetres.
The external dimensions (height, width and depth) are nominal values and shall be indicated in
the catalogue of the enclosure manufacturer.
The projection of cable gland plates, removable covers and handles shall not be included in the
external nominal dimensions, the dimensions of such shall be included in the enclosure
manufacturer’s documentation.
6.3.3 Mounting arrangements
The means and location of the enclosure mounting arrangements shall be defined in the
enclosure manufacturer’s documentation.
6.3.4 Permissible loads
The permissible loads that the enclosure, mounting plates, switchgear and controlgear supports
and doors are able to carry shall be defined in the enclosure manufacturer’s documentation.
The load shall be given in Newtons.
If the enclosure includes or can include a mounting plate or switchgear and controlgear
supports, the permissible load that the accessory can carry, according to the fixing means
provided inside the enclosure, shall be defined in the enclosure manufacturer’s documentation.
(see also 8.2).
6.3.5 Lifting and transport support
Where required, the correct location and installation of lifting and transport support and the
thread size of lifting devices shall be given in the enclosure manufacturer’s documentation or
in the instructions on how the enclosure has to be handled (see also 8.3).
6.3.6 Protective measures
The enclosure manufacturer shall indicate in the technical documentation if the enclosure is
suitable for a class I or class II assembly.
In the case of a class I enclosure, the enclosure manufacturer shall indicate if the enclosure
ensures electrical continuity throughout by the conductive structural parts of the enclosure or if
and how separate protective conductors to the protective circuits of the installation shall be
carried out (see also 8.5).
IEC 62208:2023 © IEC 2023 – 13 –
6.3.7 Thermal power dissipation capability
The data for the thermal power dissipation capability are a function of the admissible
temperature inside the enclosure. They shall be provided for the intended mounting methods
(e.g. flush mounting, surface mounting) of the enclosure and of the design of the enclosure, i.e.
with or without ventilation openings and number of horizontal partitions. They shall include at
least temperature rise inside the enclosure at the top, for a given power loss inside the
enclosure. This will provide the assembly manufacturer with the correct data for the selection
of the enclosure according to electrical equipment to be installed. The data for the thermal
power dissipation capability shall be defined in the enclosure manufacturer’s documentation
(see also 9.15).
7 Service conditions
7.1 General
Enclosures conforming to this document are intended for use under the following service
conditions.
The enclosure manufacturer shall specify the locations for which the enclosure is intended.
7.2 Normal service conditions
Enclosures conforming to this document are intended for use under the normal service
conditions detailed in Table 1.
Table 1 – Climatic conditions
Indoor installations Outdoor installations
Environmental parameter
Lower limit Upper limit Lower limit Upper limit
+40 °C +40 °C
average over a period of average over a period of
Ambient air temperature −5 °C −25 °C
24 h does not exceed 24 h does not exceed
+35 °C +35 °C
−5…+30 °C: 95 % −25…+27 °C: 100 %
a
Humidity conditions 5 % +35 °C: 70 % 15 % +35 °C: 60 %
+40 °C: 57 % +40 °C: 46 %
a
Relationship between air temperature and humidity is given in IEC 60721-3-3:2019, Figure A.1. Moderate
condensation should be borne in mind which can occasionally occur due to variations in temperature.

7.3 Special service conditions
Special service conditions can be induced by particular conditions required in product standards
or by user requirement. The user shall inform the enclosure manufacturer if such special service
conditions exist.
NOTE If any special condition requires a specific test or verification, and there is no standardized test method, the
test method to be carried out will be by an agreement between the manufacturer and the user.
Examples of such conditions can include the following:
• values of ambient air temperature and/or humidity differing from those defined in Subclause
7.2, Table 1;
• applications where variations in climatic conditions are likely to result in exceptional
condensation inside the enclosure;

– 14 – IEC 62208:2023 © IEC 2023
• heavy pollution of the air due to presence of dust (coal, cement, etc.), smoke, corrosive or
radioactive substances, vapours or salt;
• exposure to abnormal mechanical stresses (heavy vibrations, shocks, seismic occurrences,
etc.);
• presence of fauna, flora, mould, fungus or small creatures;
• ionizing influences;
• electromagnetic interferences;
• exposure to any type of radiation (for example, solar radiation, X-rays, microwave, ultraviolet
other than solar, lasers, etc.).
7.4 Conditions during transport and storage
A special agreement shall be made between the enclosure manufacturer and the user if the
conditions during transport, storage and installation, for example temperature and humidity
conditions, differ from those defined in 7.2.
8 Design and construction
8.1 General
The enclosure shall be constructed only of materials capable of withstanding the mechanical,
electrical and thermal stresses, as specified in Clause 9, as well as the effects of humidity which
are likely to be encountered in normal use.
The enclosure manufacturer shall state in its documentation if mounting accessories or methods
of mounting affects the technical characteristics of the enclosure.
8.2 Static loads
The enclosure manufacturer shall specify the maximum permissible static load that the
enclosure and its doors are able to carry.
If the enclosure includes or can include a mounting plate or switchgear and controlgear
supports, the enclosure manufacturer shall also specify the maximum permissible load of that
accessory according to the fixing means provided, except when the mounting plate and any
convenient support are designed, manufactured and tested for a specific equipment (e.g. for a
specific brand or manufacturer).
If the enclosure manufacturer offers plinths, wheels, levelling feet or other similar accessories
intended to be used for the enclosure, then the enclosure manufacturer shall declare the
maximum static load with these accessories.
Compliance is checked according to the test of 9.4.
8.3 Lifting and transport support
If the enclosure is equipped or delivered together with lifting and transport supports, the
enclosure manufacturer shall indicate in the technical documentation the correct location and
installation of these supports, the thread size of lifting devices (if applicable), how the enclosure
has to be handled, and the maximum weight for handling without lifting.
Compliance is checked according to the test of 9.5.

IEC 62208:2023 © IEC 2023 – 15 –
8.4 Access to the interior of the enclosure
Adequate access to the protected space shall be provided by means of (a) door(s) or removable
cover(s). Access may be restricted by the use of a key or tool to provide a degree of protection
to prevent contact with live parts with an enclosure used in an electric system, in accordance
with 8.5.
Cable gland plates and covers which are removable from the outside shall require the use of a
tool.
8.5 Protection against electric shock
8.5.1 General
The following requirements are intended to ensure that the required protective measures are
obtained when an enclosure is used in an electric system conforming to the IEC 60364 series.
8.5.2 Requirements for earth continuity within the class I enclosure
The enclosure manufacturer shall provide means for the connection of an external earthing or
protective conductor.
All exposed-conductive-parts of the enclosure shall be interconnected together and to the
means for the connection of an external earthing or protective conductor.
Certain exposed-conductive-parts (e.g., screws, rivets, nameplates) that do not constitute a
danger need not be connected to the earthing a
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

The SIST EN IEC 62208:2023 standard provides a comprehensive framework for empty enclosures designed for low-voltage switchgear and controlgear assemblies. Its scope clearly delineates the applicability to empty enclosures provided by manufacturers before any integration of switchgear or controlgear components, which is crucial for ensuring safety and functionality in electrical installations. One of the primary strengths of this standard is its detailed definitions and classifications that offer clarity to manufacturers, allowing for a uniform understanding of enclosure requirements in the context of switchgear assemblies. By specifying general characteristics and test requirements, it enhances the reliability and safety of the enclosures utilized in low-voltage applications, where the rated voltage does not exceed 1,000 V AC or 1,500 V DC. Furthermore, the technical revisions in this third edition signal a proactive approach to maintaining relevance in an evolving industry. The integration of modifications from IEC 61439-1:2020 indicates a commitment to align with contemporary standards, thereby reinforcing the overall interoperability of electrical components. The alignment of test procedures with the newest relevant standards underscores a dedication to high standards of safety and performance, ensuring that manufacturers can develop products that meet modern expectations. Moreover, the flexibility for indoor and outdoor applications broadens the utility of these enclosures, catering to diverse installation environments. The comprehensive nature of this document positions it as an essential reference for manufacturers in the electrical industry, solidifying its importance in the development of safe and effective low-voltage switchgear assemblies. Overall, the standard serves as a critical resource for enhancing product quality and compliance in the rapidly advancing field of electrical engineering.

SIST EN IEC 62208:2023 표준은 저전압 스위치기어 및 제어장치 조립체를 위한 빈 인클로저에 대한 일반 요구사항을 규정하고 있습니다. 이 표준은 스위치기어 및 제어장치 구성 요소가 조립 제조업체에 의해 통합되기 전에 인클로저 제조업체가 제공하는 빈 인클로저에 적용됩니다. 이 문서는 IEC 61439 시리즈에 따라 스위치기어 및 제어장치 조립체의 일환으로 사용될 인클로저의 일반 정의, 분류, 특성 및 시험 요구사항을 명시하고 있으며, 정격 전압이 1,000 V AC 또는 1,500 V DC를 초과하지 않고 실내 및 실외 애플리케이션에 일반적으로 적합합니다. 이번 2023년 제3판은 2011년에 발행된 제2판을 취소하고 대체하며, 기술적인 수정을 포함하고 있습니다. 표준의 주요 강점 중 하나는 IEC 61439-1:2020에서 도입된 수정 사항을 고려한 점입니다. 이러한 수정들은 스위치기어 및 제어장치 조립체의 안전성과 신뢰성을 더욱 높이는 데 기여합니다. 또한, 이번 판은 최신 관련 표준과의 시험 절차를 정렬하여, 보다 일관된 시험 기준을 제공합니다. 이는 업계에서 요구하는 일관성과 품질 보증을 강화하는 중요한 요소입니다. 이와 같은 특징들은 SIST EN IEC 62208:2023 표준이 현대 저전압 스위치기어 및 제어장치 인클로저 설계 및 구현에 있어 중대한 영향을 미치는 필수 문서임을 잘 보여줍니다.

Die Norm SIST EN IEC 62208:2023 bietet umfassende Richtlinien für leere Gehäuse, die von Herstellern für Niederspannungsschaltanlagen und Steuerungseinheiten bereitgestellt werden, bevor diese mit Schaltgeräten und Steuerungskomponenten ausgestattet werden. Der Anwendungsbereich dieser Norm erstreckt sich auf Gehäuse, die für Systemintegratoren von Bedeutung sind, da sie als Teil der Gesamtstruktur von Schaltanlagen dienen und sicherstellen, dass diese in Übereinstimmung mit den neuesten industriellen Standards entwickelt werden. Ein wesentliches Merkmal dieser Norm ist die Klarheit der allgemeinen Definitionen, Klassifikationen und charakteristischen Merkmale von Gehäusen. Die Norm legt spezifische Prüfanforderungen fest, die gewährleisten, dass die Gehäuse sowohl für die Verwendung in Innen- als auch Außenbereichen geeignet sind. Dies ist besonders relevant für Anwender, die sicherstellen möchten, dass ihre Produkte den neuesten Anforderungen hinsichtlich Sicherheit und Effizienz entsprechen. Ein herausragender Vorteil der dritten Auflage ist die Berücksichtigung der Änderungen, die in der IEC 61439-1:2020 eingeführt wurden. Diese Integration sorgt dafür, dass die Norm den aktuellen technologischen Entwicklungen Rechnung trägt. Die Harmonisierung der Prüfverfahren mit den neuesten relevanten Standards stärkt zusätzlich die Zuverlässigkeit und Interoperabilität der Gehäuse in verschiedenen Anwendungen. Dies ist besonders wichtig, da sich die Anforderungen an elektrische Einrichtungen ständig weiterentwickeln. Insgesamt stellt die SIST EN IEC 62208:2023 sicher, dass leere Gehäuse robuste, sichere und normgerechte Lösungen bieten, die für eine Vielzahl von Anwendungsbereichen geeignet sind. Dies macht die Norm nicht nur relevant, sondern auch unverzichtbar für Hersteller und Anwender, die in einem zunehmend regulierten und technisierten Umfeld operieren.

SIST EN IEC 62208:2023は、低電圧スイッチギアおよび制御機器アセンブリ用の空のエンクロージャに関する一般的な要件を定めた重要な標準です。この標準は、スイッチギアおよび制御機器のコンポーネントを組み込む前のエンクロージャメーカーが提供する空のエンクロージャに適用されます。また、IEC 61439シリーズにおける製品標準に従ったスイッチギアおよび制御機器アセンブリの一部として使用されるエンクロージャの一般的定義、分類、特性、試験要件を規定しています。 この第三版は、2011年に発行された第二版を取り消し、置き換えるものであり、技術的改訂を含んでいます。特に、IEC 61439-1:2020における修正点を考慮し、最新の関連標準により試験手順を整合させることが重要な改訂点として挙げられます。 この標準の強みは、その幅広い適用範囲にあります。定格電圧が1,000 V ACまたは1,500 V DCを超えないスイッチギアおよび制御機器アセンブリに対して適用可能であり、屋内および屋外での一般的な使用に適したエンクロージャを明確に定義している点が評価されます。これにより、ユーザーは安全性と信頼性を高めるための基準を持つことができ、エンクロージャの選択や設計時において重要な指針となります。 したがって、SIST EN IEC 62208:2023は、低電圧スイッチギアと制御機器アセンブリの設計と製造において不可欠な標準であり、その内容は業界全体における安全性と一貫性の向上に寄与するものです。

La norme SIST EN IEC 62208:2023 se concentre sur les enceintes vides destinées aux ensembles de matériel électrique basse tension. Elle définit un cadre clair pour les fabricants d'enceintes, à savoir les exigences générales relatives aux enclosures avant l'intégration des composants de commande et de protection. Le champ d'application de cette norme est crucial car il couvre des configurations d'applications tant intérieures qu'extérieures avec des tensions nominales ne dépassant pas 1 000 V AC ou 1 500 V DC. Les forces de cette norme résident dans sa précision et sa pertinence. En tant que document de référence, il fournit des définitions générales, des classifications, des caractéristiques et des exigences d'essai pour les enceintes. Les modifications apportées par rapport à la deuxième édition de 2011, notamment l'intégration des évolutions présentes dans l'IEC 61439-1:2020 et l'alignement des procédures d'essai avec les normes les plus récentes, témoignent d'un engagement à maintenir la norme au goût du jour et conforme aux meilleures pratiques de l'industrie. Cela renforce la crédibilité de la norme et son applicabilité dans les concepts contemporains de gestion des infrastructures électriques. La norme SIST EN IEC 62208:2023 est également pertinente pour les fabricants et les utilisateurs finaux en garantissant que toutes les enceintes sont conformes à des standards de sécurité et d'efficacité. En suivant ces lignes directrices, les professionnels du secteur de l'électrotechnique peuvent s'assurer que les produits développés respectent les critères de qualité les plus élevés, ce qui est fondamental pour la sécurité et la durabilité des installations électriques. En somme, cette norme représente un outil indispensable pour harmoniser les pratiques dans la fabrication des enceintes pour ensembles de matériel basse tension.