Abstract

This document specifies calculation methods for determining the required mass flow to be relieved for each specified conditions described in Table 1.
Recommendations for pressure relief devices for cryostats are given in Annex A.

Status
Not Published
Public Enquiry End Date
02-May-2025
Technical Committee
TLP - Pressure vessels
Current Stage
5020 - Formal vote (FV) (Adopted Project)
Start Date
22-Jul-2026
Due Date
09-Sep-2026
Completion Date
05-Aug-2026

Buy Documents

Draft

oSIST prEN ISO 21013-3:2025

English language (41 pages)
Preview
Preview
e-Library read for
×1 day

kSIST FprEN ISO 21013-3:2026 is a SIST publication of ISO 21013-3 for cryogenic vessels. It gives calculation methods for sizing pressure-relief accessories in cryogenic service by determining the mass flow that must be relieved for defined operating, loss-of-vacuum, fire, and condensation conditions. Engineers, designers, and assessors use it to size pressure relief valves and bursting discs, and to check piping, back pressure, and heat transfer in the relief path.

What does kSIST FprEN ISO 21013-3:2026 specify?

kSIST FprEN ISO 21013-3:2026 specifies separate calculation methods for determining the required mass flow to be relieved for the conditions listed in its scope table. The document is organized so the reader first selects the applicable condition, then calculates heat transfer, converts that into relieving mass flow, and finally sizes the pressure relief device and its piping.

The standard covers cryogenic vessels with and without vacuum insulation, normal operation, loss of vacuum, fire conditions, air or nitrogen condensation, and pressure build-up device cases. It also gives recommendations for cryostats in Annex A.

AnnexWhat it covers
Annex ACryostats and design recommendations for their pressure relief devices
Annex ZARelationship with Directive 2014/68/EU and the Pressure Equipment Directive essential requirements

The main clauses are:

  • Clause 1 Scope
  • Clause 2 Normative references
  • Clause 3 Symbols
  • Clause 4 Heat transfer calculations
  • Clause 5 Mass flow to be relieved
  • Clause 6 Piping for pressure relief devices
  • Clause 7 Sizing of pressure relief devices

What are the key requirements of kSIST FprEN ISO 21013-6?

Clause 4 sets the heat input that drives the relief sizing

kSIST FprEN ISO 21013-3:2026 calculates heat transfer for the vessel in several distinct cases, because the heat load is what creates vapor and therefore the required relief flow. Clause 4 separates normal operation, pressure build-up device operation, loss of vacuum, fire, and air or nitrogen condensation.

For practice, this means the user must choose the case that matches the installation and upset condition, then use the corresponding heat-transfer model. The clause gives formulas for insulation, vessel walls, supports, piping, and ambient air vaporizers, so the calculation reflects the actual thermal path instead of a single generic heat load.

Clause 4 also distinguishes fire and non-fire conditions

kSIST FprEN ISO 21013-3:2026 treats fire as a special case with an external temperature of 922 K and separate formulas depending on whether insulation stays in place. It also states that the fire case may not be the worst case, so fire and pressure build-up device conditions both need to be checked.

In practice, this prevents a design from being sized only for fire when pressure build-up or another condition creates a larger demand. For cryogenic systems, that matters because the relief device must cover whichever case produces the highest required flow.

Clause 5 converts heat input into the mass flow to be relieved

kSIST FprEN ISO 21013-3:2026 uses heat input, or alternatively the normal evaporation rate (NER), to calculate the required discharge mass flow. It gives separate methods for relieving pressure below the critical pressure and at or above the critical pressure.

For the reader, this means the thermodynamic state of the fluid matters. The calculation depends on relieving temperature, latent heat, specific volume, molar mass, compressibility factor, and related property data at the relieving conditions.

Clause 6 makes piping part of the relief capacity calculation

kSIST FprEN ISO 21013-3:2026 requires piping to be included when it can affect flow capacity, especially when the line between the outer jacket and the safety relief device is longer than 0.6 m. Clause 6 addresses pressure drop, built-up back pressure, and heat transfer into the discharged fluid.

In practice, this means a relief valve cannot be sized only from the vessel nozzle. The upstream and downstream lines can reduce capacity, raise outlet pressure, and increase gas temperature, so the piping layout must be checked as part of the sizing work.

Clause 6 gives design checks for pressure relief valves

kSIST FprEN ISO 21013-3:2026 recommends limiting the upstream pressure drop for conventional direct acting relief valves to 3 % of set pressure, and limiting built-up back pressure to 10 % of set pressure. It also notes that valve chatter is a concern and that internally pressure-balanced or externally pilot-operated valves may be used where needed.

For practice, that means the piping design is not only a hydraulic problem but also a stability problem. A valve may have enough nominal capacity and still perform poorly if the pressure drop or back pressure is too high.

Clause 7 sizes pressure relief valves and bursting discs

kSIST FprEN ISO 21013-3:2026 requires the combined relieving capacity of all devices operating together to be at least the required mass flow. It then gives separate sizing methods for pressure relief valves and bursting discs, including checks for critical and subcritical gas flow.

For pressure relief valves, the document walks through inlet and outlet conditions, flow regime selection, orifice area calculation, and selection of the next larger available orifice. For bursting discs, it uses the resistance of the complete pipe network and the net flow area after rupture, which is why certified post-rupture flow area from the manufacturer matters in practice.

What terms does kSIST FprEN ISO 21013-3:2026 define?

  • Normal evaporation rate (NER) - The NER is the boil-off rate of the vessel contents used as an alternative way to determine the required heat input and relieving mass flow.
  • Relieving pressure, P - P is the actual absolute pressure inside the vessel used for the relief calculation.
  • Derated coefficient of discharge, Kdr - Kdr is the discharge coefficient used in the sizing equations after applying the derating convention stated in the standard.
  • Built-up back pressure - Built-up back pressure is the pressure rise at the outlet of a pressure relief device caused by flow through the downstream piping.
  • Critical flow - Critical flow is the gas flow condition where lowering downstream pressure no longer increases discharge.
  • Subcritical flow - Subcritical flow is the gas flow condition where downstream pressure still affects the discharge rate.
  • Adjusted flow temperature - Adjusted flow temperature is the temperature used for piping heat-transfer calculations along the relief path.

Who uses kSIST FprEN ISO 21013-3:2026?

kSIST FprEN ISO 21013-3:2026 is used by engineers who size pressure relief systems for cryogenic vessels, piping, and cryostats. It is also used by manufacturers of pressure relief valves and bursting discs, and by designers who must check the effect of piping, heat leak, and back pressure on capacity.

Quality managers, buyers, and conformity assessment staff use it when they need a common sizing basis for cryogenic pressure equipment. Annex ZA also makes it relevant to EU pressure equipment conformity work.

The document is especially relevant where cryogenic liquids are stored or used with pressure build-up devices, vacuum insulation, or equipment such as superconducting magnets or cavities.

What changed in kSIST FprEN ISO 21013-3:2026 from the previous edition?

kSIST FprEN ISO 21013-3:2026 is the third edition and it replaces ISO 21013-3:2016 with a technical revision. The stated changes are:

  • More precision on the total outer surface area of the pipe network containing the flowing fluid
  • Inclusion of the coefficient of discharge symbol
  • More precision on the overall convective heat transfer coefficient of the ambient air vaporizer
  • Additional information on the fire case and pressure build-up device conditions
  • Correction of the molar mass in kg/kmol and changes to formulas 32 and 43
  • Supplementary information on cryostats

What does the kSIST FprEN ISO 21013-3:2026 document contain?

kSIST FprEN ISO 21013-3:2026 contains calculation methods, symbol definitions, property tables, worked examples, and an informative figure for air or nitrogen condensation. The tables support thermal conductivity, specific heat, flow resistance, and valve sizing calculations, while the formulas cover heat transfer, critical and subcritical flow, and pipe network resistance.

Clause 7 includes detailed sizing procedures for pressure relief valves and bursting discs, with examples showing how to check inlet pressure drop, back pressure, and orifice selection. Annex A adds cryostat-specific recommendations, and Annex ZA maps the standard to Directive 2014/68/EU.

Relations

Effective Date
01-Apr-2025

Buy Documents

Draft

oSIST prEN ISO 21013-3:2025

English language (41 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Institut za varilstvo d.o.o. (Welding Institute)

Slovenia's leading welding institute since 1952. ISO 3834, EN 1090, pressure equipment certification, NDT personnel, welder qualification. Only IIW Au

SA Slovenia Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

kSIST FprEN ISO 21013-3:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Cryogenic vessels - Pressure-relief accessories for cryogenic service - Part 3: Sizing and capacity determination (ISO/FDIS 21013-3:2026)". This standard covers: This document specifies calculation methods for determining the required mass flow to be relieved for each specified conditions described in Table 1. Recommendations for pressure relief devices for cryostats are given in Annex A.

This document specifies calculation methods for determining the required mass flow to be relieved for each specified conditions described in Table 1. Recommendations for pressure relief devices for cryostats are given in Annex A.

kSIST FprEN ISO 21013-3:2026 is classified under the following ICS (International Classification for Standards) categories: 13.240 - Protection against excessive pressure; 23.020.40 - Cryogenic vessels. The ICS classification helps identify the subject area and facilitates finding related standards.

kSIST FprEN ISO 21013-3:2026 has the following relationships with other standards: It is inter standard links to SIST EN ISO 21013-3:2016. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

kSIST FprEN ISO 21013-3:2026 is associated with the following European legislation: EU Directives/Regulations: 2008/68/EC, 2014/68/EU; Standardization Mandates: M/071, M/601, M/TDG. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

kSIST FprEN ISO 21013-3:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
oSIST prEN ISO 21013-3:2025
01-april-2025
Kriogene posode - Oprema za razbremenitev tlaka za kriogeno območje - 3. del:
Določanje velikosti in pretoka (ISO/DIS 21013-3:2025)
Cryogenic vessels - Pressure-relief accessories for cryogenic service - Part 3: Sizing and
capacity determination (ISO/DIS 21013-3:2025)
Kryo-Behälter - Druckentlastungseinrichtungen für den Kryo-Betrieb - Teil 3:
Bestimmung von Größe und Durchfluss (ISO/DIS 21013-3:2025)
Récipients cryogéniques - Dispositifs de sécurité pour le service cryogénique - Partie 3:
Détermination de la taille et du volume (ISO/DIS 21013-3:2025)
Ta slovenski standard je istoveten z: prEN ISO 21013-3
ICS:
13.240 Varstvo pred previsokim Protection against excessive
tlakom pressure
23.020.40 Proti mrazu odporne posode Cryogenic vessels
(kriogenske posode)
oSIST prEN ISO 21013-3:2025 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

oSIST prEN ISO 21013-3:2025
oSIST prEN ISO 21013-3:2025
DRAFT
International
Standard
ISO/DIS 21013-3
ISO/TC 220
Cryogenic vessels — Pressure-relief
Secretariat: AFNOR
accessories for cryogenic service —
Voting begins on:
Part 3: 2025-02-14
Sizing and capacity determination
Voting terminates on:
2025-05-09
Récipients cryogéniques — Dispositifs de sécurité pour le service
cryogénique —
Partie 3: Détermination de la taille et du volume
ICS: 23.020.40
THIS DOCUMENT IS A DRAFT CIRCULATED
FOR COMMENTS AND APPROVAL. IT
IS THEREFORE SUBJECT TO CHANGE
AND MAY NOT BE REFERRED TO AS AN
INTERNATIONAL STANDARD UNTIL
PUBLISHED AS SUCH.
This document is circulated as received from the committee secretariat.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL,
TECHNOLOGICAL, COMMERCIAL AND
USER PURPOSES, DRAFT INTERNATIONAL
STANDARDS MAY ON OCCASION HAVE TO
ISO/CEN PARALLEL PROCESSING
BE CONSIDERED IN THE LIGHT OF THEIR
POTENTIAL TO BECOME STANDARDS TO
WHICH REFERENCE MAY BE MADE IN
NATIONAL REGULATIONS.
RECIPIENTS OF THIS DRAFT ARE INVITED
TO SUBMIT, WITH THEIR COMMENTS,
NOTIFICATION OF ANY RELEVANT PATENT
RIGHTS OF WHICH THEY ARE AWARE AND TO
PROVIDE SUPPORTING DOCUMENTATION.
Reference number
ISO/DIS 21013-3:2025(en)
oSIST prEN ISO 21013-3:2025
DRAFT
ISO/DIS 21013-3:2025(en)
International
Standard
ISO/DIS 21013-3
ISO/TC 220
Cryogenic vessels — Pressure-relief
Secretariat: AFNOR
accessories for cryogenic service —
Voting begins on:
Part 3:
Sizing and capacity determination
Voting terminates on:
Récipients cryogéniques — Dispositifs de sécurité pour le service
cryogénique —
Partie 3: Détermination de la taille et du volume
ICS: 23.020.40
THIS DOCUMENT IS A DRAFT CIRCULATED
FOR COMMENTS AND APPROVAL. IT
IS THEREFORE SUBJECT TO CHANGE
AND MAY NOT BE REFERRED TO AS AN
INTERNATIONAL STANDARD UNTIL
PUBLISHED AS SUCH.
This document is circulated as received from the committee secretariat.
IN ADDITION TO THEIR EVALUATION AS
BEING ACCEPTABLE FOR INDUSTRIAL,
© ISO 2025
TECHNOLOGICAL, COMMERCIAL AND
USER PURPOSES, DRAFT INTERNATIONAL
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
STANDARDS MAY ON OCCASION HAVE TO
ISO/CEN PARALLEL PROCESSING
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
BE CONSIDERED IN THE LIGHT OF THEIR
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
POTENTIAL TO BECOME STANDARDS TO
WHICH REFERENCE MAY BE MADE IN
or ISO’s member body in the country of the requester.
NATIONAL REGULATIONS.
ISO copyright office
RECIPIENTS OF THIS DRAFT ARE INVITED
CP 401 • Ch. de Blandonnet 8
TO SUBMIT, WITH THEIR COMMENTS,
CH-1214 Vernier, Geneva
NOTIFICATION OF ANY RELEVANT PATENT
Phone: +41 22 749 01 11
RIGHTS OF WHICH THEY ARE AWARE AND TO
PROVIDE SUPPORTING DOCUMENTATION.
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland Reference number
ISO/DIS 21013-3:2025(en)
ii
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
Contents Page
Foreword .v
1 Scope . 1
2 Normative references . 2
3 Symbols . 2
4 Calculation of the total quantity of heat transferred per unit time from the hot wall
(outer jacket) to the cold wall (inner vessel) . 6
4.1 General .6
4.2 Under conditions other than fire .6
4.2.1 Vacuum-insulated vessels under normal vacuum .6
4.2.2 Pressure build-up device .7
4.2.3 Vacuum-insulated vessels in the case of loss of vacuum and non-vacuum
insulated vessels . .7
4.2.4 Supports and piping.8
4.3 Under fire conditions .9
4.3.1 Insulation system remains fully or partially in place during fire conditions .9
4.3.2 Insulation system does not remain in place during fire conditions .9
4.4 Air or Nitrogen condensation .10
4.4.1 General .10
4.4.2 Loss of vacuum with air and nitrogen .10
4.4.3 Fire with loss of vacuum with air or nitrogen .10
4.5 Heat transfer per unit time (watts) .11
4.5.1 General .11
4.5.2 Normal operation.11
4.5.3 Pressure build up regulator fully open . 12
4.5.4 Loss of vacuum condition . 12
4.5.5 Fire condition with loss of vacuum, vacuum jacket, and insulation fully or
partially in place . 12
4.5.6 Fire condition with loss of vacuum, insulation not in place . 13
4.5.7 Total heat transfer rate . 13
5 Calculation of the mass flow to be relieved by pressure relief devices .13
5.1 Relieving pressure, P, less than the critical pressure . 13
5.2 Relieving pressure, P, equal to or greater than the critical pressure .14
5.3 Example .14
6 Piping for pressure relief devices .15
6.1 Pressure drop . 15
6.1.1 General . 15
6.1.2 Relief valves . 15
6.1.3 Bursting discs . 15
6.2 Back pressure consideration . . 15
6.3 Heat transfer . 15
7 Sizing of pressure relief devices . 17
7.1 General .17
7.2 Sizing of pressure relief valves.17
7.2.1 Discharge capacity .17
7.2.2 Determination of critical vs. subcritical flow for gases .17
7.2.3 Critical flow .17
7.2.4 Subcritical flow .19
7.2.5 Recommended analysis method .19
7.2.6 Example .21
7.3 Sizing of bursting discs . 26
7.3.1 Discharge capacity . 26
7.3.2 Determination of critical vs. subcritical flow for gases . 26
7.3.3 Critical flow .27

iii
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
7.3.4 Subcritical flow .27
7.3.5 Recommended analysis method .27
7.3.6 Example . 30
Annex A (informative) Cryostats .34
Annex ZA (informative) Relationship between this European Standard and the essential
requirements of Directive 2014/68/UE (Pressure Equipment Directive) aimed to be
covered .35
Bibliography .36

iv
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out through
ISO technical committees. Each member body interested in a subject for which a technical committee
has been established has the right to be represented on that committee. International organizations,
governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are described
in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the different types
of ISO documents should be noted. This document was drafted in accordance with the editorial rules of the
ISO/IEC Directives, Part 2 (see www.iso.org/directives).
ISO draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). ISO takes no position concerning the evidence, validity or applicability of any claimed patent
rights in respect thereof. As of the date of publication of this document, ISO had not received notice of (a)
patent(s) which may be required to implement this document. However, implementers are cautioned that
this may not represent the latest information, which may be obtained from the patent database available at
www.iso.org/patents. ISO shall not be held responsible for identifying any or all such patent rights.
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and expressions
related to conformity assessment, as well as information about ISO's adherence to the World Trade
Organization (WTO) principles in the Technical Barriers to Trade (TBT), see www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 220, Cryogenic Vessels.
This third edition cancels and replaces the second edition (ISO 21013-3:2016), which has been technically
revised.
The main changes are as follows:
— Precision added on the total outer surface area of the pipe network containing flow of fluid,
— Inclusion of the coefficient of discharge symbol,
— Precision added on the overall convective heat transfer coefficient of the ambient air vaporizer,
— Additional information added on the fire case and PBU conditions,
— Correction of the molar mass in kg/kmol and modification of formulas 32 and 43,
— Supplementary information added on cryostats mentioned in this standard.
A list of all parts in the ISO 21013 series can be found on the ISO website.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.

v
oSIST prEN ISO 21013-3:2025
oSIST prEN ISO 21013-3:2025
DRAFT International Standard ISO/DIS 21013-3:2025(en)
Cryogenic vessels — Pressure-relief accessories for cryogenic
service —
Part 3:
Sizing and capacity determination
1 Scope
This part of ISO 21013 provides separate calculation methods for determining the required mass flow to be
relieved for each specified conditions described in the following table:
Insulation
system
Pressure
Type of Inner ves- (outer
Vacuum Ambient buildup Use clauses including
Condition insulation sel temper- jacket +
status: conditions: system con- any sub-clauses
system: ature: insulating
dition:
material)
condition:
normal
(ambient 4.2.3/4.2.4/4.5.1/4.5.2/4.5.
1 intact
tempera- 7/5/6/7
non-vacu-
ture)
N/A
um
normal con-
fully or
dition
2 partially in fire (922 K) 4.3.1/4.5.1/4.5.7/5/6/7
temperature
place
of the con-
4.2.1/4.2.4/4.5.1/4.5.2/4.5.
tents at the
7/5/6/7
specified
normal
normal
relieving
(ambient 4.2.1/4.2.2/4.2.4/4.5.1/4.5.
4 intact full open
pressure
tempera- 3/4.5.7/5/6/7
ture)
4.2.3/4.2.4/4.5.1/4.5.4/4.5.
7/5/6/7
loss of
fully or
vacuum vacuum
4.3.1/4.4.3/4.5.1/4.5.5/4.5.
6 partially in fire (922 K)
7/5/6/7
place
normal
(ambient normal con-
7 4.4.2/4.5.1/4.5.4/4.5.7/5/6/7
loss of
tempera- dition
intact
contents
vacuum
ture)
with reliev-
with air or
8 ing temper- 4.4.3/4.5.1/4.5.5/4.5.7/5/6/7
nitrogen in
ature below
vacu-
the vacu-
75 K
fire (922 K)
um and
um space
9 totally lost 4.5.1/4.5.6/4.5.7/5/6/7
non-vacu-
um
Good engineering practice based on well-established theoretical physical science needs to be adopted to
determine the required mass flow where an appropriate calculation method is not provided for an applicable
condition.
Recommendations for pressure relief devices for cryostats are given in Annex A.

oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
2 Normative references
There are no normative references in this document.
3 Symbols
A arithmetic mean of inner and outer surface areas of vessel insulating material m
A actual flow area of a pipe element m
B
A is the total outer surface area of the pipe network containing flow of fluid, from the m
e
outer jacket up to the flow temperature location x under consideration, in m ; Appli-
cable only when length > than 0,6 m (See 6.1.1)
A minimum flow area (reference area) in a pipe network m
F
A minimum flow area (reference area) in the pipe network, downstream of relief valve m
Fd
A minimum flow area (reference area) in the pipe network, upstream of relief valve m
Fu
A total outside surface area of inner vessel m
i
A total outer surface area of pipe network between the inner and outer jackets (inter- m
j
space)
A larger flow area of a pipe element containing two different flow area sizes m
L
A cross-sectional area, support, or pipe material m
n
A area ratio, A /A —
R S L
A smaller flow area of a pipe element containing two different flow area sizes m
S
A actual flow (orifice) area of a pressure relief valve mm
V
A actual flow (orifice) area of pressure relief valve selected for final analysis mm
Va
A minimum required relief valve flow (orifice) area mm
V1
A external heat transfer surface area of ambient air vaporizer m
c constant pressure specific heat capacity at the average of T and T kJ/(kg·K)
p n e
C experimentally determined flow rate through a pipe element or device gal/min/psi
V
e nominal insulating material thickness, normal vacuum, non-fire condition m
e minimum insulating material thickness, considering loss of vacuum, non-fire condi- m
tion
e insulating material thickness remaining in place during fire conditions m
f pipe flow friction coefficient —
T
h enthalpy of fluid at conditions of ν kJ/kg
h specific enthalpy at relief valve inlet and outlet kJ/kg
r
K flow resistance coefficient of a pipe element in terms of A —
A F
K flow resistance coefficient of a pipe element in terms of A —
B B
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
K subcritical flow coefficient —
b
Kd coefficient of discharge —
K derated coefficient of discharge —
dr
K derated coefficient of discharge of next largest available valve orifice area greater —
dr,a
than A
V1
K derated coefficient of discharge of initially analyzed valve —
dr,1
k mean thermal conductivity of an individual support or pipe, between T and T W/(m·K)
n a
K flow resistance coefficient of complete pipe network in terms of reference area, A —
R F
K flow resistance coefficient at the transition between critical and subcritical flow —
RC
K overall flow resistance coefficient of pipe network, downstream of pressure relief —
Rd
valve
K overall flow resistance coefficient of pipe network, upstream of pressure relief valve —
Ru
K total flow resistance coefficient of a series or parallel pipe network —
SUM
K experimentally determined flow rate through a pipe element or device m /h/bar
V
k mean thermal conductivity of insulating material, normal vacuum, W/(m·K)
non-fire condition
k mean thermal conductivity of insulating material with air or gaseous lading, W/(m·K)
non-fire condition
L latent heat of vaporization of cryogenic liquid at relieving conditions kJ/kg
l length, pipe element m
L latent heat of vaporization of cryogenic liquid at a pressure of 1,013 bar kJ/kg
a
l length of support or pipe in vacuum interspace m
n
L’ enthalpy-to-volume expansion ratio for critical or all-gas fluid flow conditions kJ/kg
M molar mass kg/kmol
m maximum mass capacity of vessel kg
max
N normal evaporation rate (NER) %/day
P relieving pressure, inner vessel in absolute pressure bar
P pressure, safety relief valve outlet in absolute pressure bar
b
P pressure at relief valve outlet for a downstream built-up backpressure of 10 % bar
b10
P pressure at pipe network exit in absolute pressure bar
exit
P pressure, safety relief valve inlet in absolute pressure bar
i
P pressure relief valve set pressure in absolute pressure bar
S
Q mass flow rate kg/h
m
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
Q mass flow rate of a relief valve within a given pipe network kg/h
ma
Q mass flow rate due to the normal evaporation rate kg/h
mNER
R universal gas constant J/(mol·K)
r pipe elbow transition radius m
T relieving temperature, inner vessel K
T maximum external ambient temperature, non-fire condition K
a
T temperature at relief valve outlet K
b,Pb
T temperature at relief valve outlet for a downstream built-up backpressure of 10 % K
b10
T external temperature for a given condition K
e
T temperature at pipe network exit K
exit,Pb
T external temperature, fire condition K
f
T temperature, safety relief valve inlet K
i
T temperature of fluid at a given flow start location along the pipe network K
n
T saturation temperature of fluid at a pressure of 1 bar K
sat
T temperature of fluid at a given location x along the pipe network K
x
U overall heat transfer coefficient of a pipe network for given temperature conditions W/ (m ·K)
p
U heat transfer coefficient of insulating material, normal vacuum, non-fire condition W/ (m ·K)
U overall convective heat transfer coefficient of ambient air vaporizer W/ (m ·K)
U heat transfer coefficient of insulating material with air or gaseous lading, non-fire W/ (m ·K)
condition
U heat transfer coefficient, air or nitrogen condensation, loss of vacuum, non-fire condi- W/m
3a
tion
U heat transfer coefficient of insulating material with air or gaseous lading, fire condi- W/ (m ·K)
tion
U heat transfer coefficient, air or nitrogen condensation, loss of vacuum, fire condition W/m
5a
w heat leak from an individual support or pipe W/K
n
W total heat transfer rate for specified conditions Watt [W]
T
W total heat transfer rate under normal operation Watt [W]
T1
W total NER heat transfer rate under normal operation Watt [W]
T1NER
W total heat transfer rate under normal operation, including pressure build-up device Watt [W]
T2
W total NER heat transfer rate under normal operation, including pressure build-up Watt [W]
T2NER
device
W total heat transfer rate, loss of vacuum, insulation in place, non-fire condition, Watt [W]
T3
T ˃ 75 K
sat
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
W total heat transfer rate, loss of vacuum, insulation in place, non-fire condition, Watt [W]
T3a
T ≤ 75 K
sat
W total heat transfer rate, loss of vacuum, insulation in place, fire condition, T ˃ 75 K Watt [W]
T5 sat
W total heat transfer rate, loss of vacuum, insulation in place, fire condition, T ≤ 75 K Watt [W]
T5a sat
W total heat transfer rate, loss of vacuum, insulation not in place, fire condition Watt [W]
T6
W heat transfer rate through insulation system, normal vacuum, non-fire condition Watt [W]
W heat transfer rate through pressure build-up device, fully open regulator Watt [W]
W heat transfer rate through insulation system, loss of vacuum, non-fire condition Watt [W]
W heat transfer rate through air or nitrogen condensation, loss of vacuum, Watt [W]
3a
non-fire condition
W heat transfer rate through interspace supports and piping Watt [W]
W heat transfer rate through vessel walls, insulation in place, fire condition Watt [W]
W heat transfer rate through air or nitrogen condensation, loss of vacuum, Watt [W]
5a
fire condition
W heat transfer rate through vessel walls, insulation not in place, fire condition Watt [W]
x lengthwise location along a pipe network m
X number of insulation layers —
Y heat transfer rate U or U —
3a 5a
Z compressibility factor at pressure, P , and temperature, T —
i i i
φ pressure ratio P /P —
exit
κ isentropic exponent —
λ subcritical flow coefficient —
λ subcritical flow coefficient —
ν specific volume of critical or all-gas fluid at a given temperature at pressure, P m /kg
ν specific volume at relief valve outlet for a downstream built-up backpressure of 10 % m /kg
b10
ν specific volume at pressure relief valve outlet, evaluated at h and a trial value of P m /kg
b,Pb r b
ν maximum average downstream specific volume, as per desired backpressure limit m /kg
dmax
ν average downstream specific volume, for a downstream built-up backpressure m /kg
d10
of 10 %
ν specific volume at pipe network exit, evaluated at P and T m /kg
exit,Pb exit exit,Pb
ν specific volume at pipe network exit for a downstream built-up backpressure of 10 % m /kg
exit10
ν specific volume of saturated gas at relieving pressure, P m /kg
g
ν specific volume of saturated gas at a pressure of 1,013 bar m /kg
ga
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
ν specific volume, safety relief valve inlet m /kg
i
ν specific volume of saturated liquid at relieving pressure, P m /kg
l
ν specific volume of saturated liquid at a pressure of 1,013 bar m /kg
la
ν average specific volume of flowing fluid upstream of pressure relief valve inlet m /kg
u
3/2 1/2
ψ expression for determining Q and T for critical or gas-full-vessel fluid flow condi- m ·kg /
m
tions kJ
4 Calculation of the total quantity of heat transferred per unit time from the hot wall
(outer jacket) to the cold wall (inner vessel)
4.1 General
P (in bar abs) is the actual relieving pressure inside the vessel which is used for calculating the required
mass flow through pressure relief devices.
T (in K) is the maximum ambient temperature for conditions other than fire (as specified, for example, by a
a
regulation or standard).
T (in K) is the external environment temperature under fire conditions which is taken to be 922 K in this
f
part of ISO 21013.
T (in K) is the relieving temperature in the vessel to be taken into account.
a) For subcritical fluids, T is the saturation temperature of the liquid at pressure, P.
b) For critical or supercritical fluids, T is calculated from 5.2.
4.2 Under conditions other than fire
4.2.1 Vacuum-insulated vessels under normal vacuum
W is the quantity of heat transferred per unit time (in watts) by heat leak through the insulation system.
WU=⋅AT −T (1)
()()
11 a
where
U is the overall heat transfer coefficient of the insulating material under normal vacuum,
in W/(m ⋅K);
k
U = ;
e
k is the mean thermal conductivity of the insulating material under normal vacuum, between
T and T , in W/(m⋅K);
a
e is the nominal insulating material thickness, in metres;
A is the arithmetic mean of the inner and outer surface areas of the vessel insulating material,
in m .
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
4.2.2 Pressure build-up device
W is the quantity of heat transferred per unit time (in watts) by the pressure build-up device circuit with
the regulator fully open. W is determined from the type (ambient air, water or steam, electrical, etc.) and
design of the pressure build-up device circuit. For example, in the case of an ambient air vaporizer.
WU=⋅()AT()−T (2)
22 2 a
where
U is the overall convective heat transfer coefficient of the ambient air vaporizer, in W/(m ⋅K);
A is the external heat transfer surface area of the vaporizer, in m .
As a first approximation, the following may be used:
UT −TT=≤19000W/mfor 75K (3)
()
2 a
UT()−TT=>2850W/mfor 75K (4)
2 a
U shall not be lower than the values proposed but manufacturers can use greater values if their design
requires.
4.2.3 Vacuum-insulated vessels in the case of loss of vacuum and non-vacuum insulated vessels
W is the quantity of heat transferred per unit time (in watts) by heat leak through the insulating material.
WU=⋅()AT()−T (5)
33 a
where If the insulation is fully effective for conduction, convection, and radiation heat transfer at 328 K, U
may be calculated using Formula (6).
k
U = (6)
e
U is the overall heat transfer coefficient of the insulating material when saturated with
gaseous lading or air at atmospheric pressure, whichever is greater, in W/(m ·K);
k is the mean thermal conductivity of the insulating material saturated with gaseous lading
or air at atmospheric pressure, whichever provides the greater coefficient, between
T and T , in W/(m·K). Values of k for gases are listed in Table 1;
a 3
e is the minimum insulating material thickness taking into account the manufacturing
tolerances or effects of sudden loss of vacuum, in metres.
NOTE This formula might not be applicable at temperatures below 75 K with a small thickness of insulating
material as the maximum heat transfer coefficient would be given by air condensation.
Vacuum space, gas space, or space occupied by the deteriorated insulation shall not be included in the
thickness of the insulation. The effectiveness of these spaces or deteriorated insulation in reducing
conduction, convection, or radiation heat transfer may be evaluated separately and included in the overall
heat transfer coefficient, U , using methods found in published heat transfer literature. Deterioration of the
insulation can be caused by the following:
— moisture condensation;
— air condensation;
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
— increase in the density of the insulation due to a sudden loss of vacuum.
Table 1 — Thermal conductivity for refrigerated (cryogenic) fluids at the mean temperature
between saturation and 328 K (k ) and 922 K (k ) at 1 bar
3 5
Fluid k [W/(m·K)] k [W/(m·K)]
3 5
Air 0,019 0,043
Argon 0,013 0,027
Carbon dioxide 0,017 0,039
Carbon monoxide 0,020 0,039
Helium 0,104 0,211
Hydrogen 0,116 0,217
Methane 0,024 0,074
Neon 0,034 0,067
Nitrogen 0,019 0,040
Oxygen 0,019 0,043
Krypton 0,007 0,015
Xenon 0,005 0,009
Ethane 0,016 0,064
Trifluoromethane 0,012 0,027
Ethylene (ethene) 0,015 0,056
Nitrous oxide 0,014 0,038
4.2.4 Supports and piping
W is the quantity of heat transferred per unit time (in watts) by supports and piping located in the
interspace.
Ww=+ww++…+wT −T (7)
()()
41 23 na
where w is the heat leak per degree K contributed by one of the supports or the pipes, in W/K.
n
 A 
n
wk= (8)
nn  
l
 
n
k is the mean thermal conductivity of the support or pipe material between T and T , in
n a
W/(m⋅K);
A is the support or pipe section area, in m ;
n
l is the support or pipe length in the vacuum interspace, in metres.
n
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
4.3 Under fire conditions
4.3.1 Insulation system remains fully or partially in place during fire conditions
W is the quantity of heat transferred per unit time (in watts) by heat leak through the vessel walls.
08, 2
WT=⋅26, 922− ⋅⋅UA (9)
()
where If the insulation is fully effective for conduction, convection, and radiation heat transfer for an
external temperature of 922 K, U may be calculated using Formula (10).
k
U = (10)
e
U is the overall heat transfer coefficient of the container-insulating material when saturated
with gaseous lading or air at atmospheric pressure, whichever is greater, in W/(m ·K);
k is the mean thermal conductivity of the insulating material saturated with gaseous lading
or air at atmospheric pressure, whichever provides the greater coefficient, between T and
922 K, in W/(m·K). Values of k for gases are listed in Table 1;
e is the thickness of the insulating material remaining in place during fire conditions, in metres;
A is the arithmetic mean of the inner and outer surface areas of the insulating material
remaining in place during fire conditions, in m .
Vacuum space, gas space, or space occupied by the deteriorated insulation shall not be included in the
thickness of the insulation. The effectiveness of these spaces or deteriorated insulation in reducing
conduction, convection, or radiation heat transfer may be evaluated separately and included in the overall
heat transfer coefficient, U , using methods found in published heat transfer literature. Deterioration of the
insulation can be caused by the following:
— moisture condensation;
— air condensation;
— increase in the density of the insulation due to a sudden loss of vacuum;
— degradation due to heat.
If the outer jacket remains in place during fire conditions, but the insulating material is entirely destroyed,
U is equal to the overall heat transfer coefficient with gaseous lading or air at atmospheric pressure in the
space between the outer jacket and the inner vessel, whichever provides the greater coefficient, between T
and 922 K. A is equal to the mean surface area of the interspace.
4.3.2 Insulation system does not remain in place during fire conditions
W is the quantity of heat transferred per unit time (in watts) by heat leak through the vessel walls.
40,82
WA=⋅71, 10 ⋅ (11)
6 i
where A is the total outside surface area of the inner vessel, in m .
i
The heat transferred by supports and piping located in the interspace can be neglected in this case.

oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
4.4 Air or Nitrogen condensation
4.4.1 General
The air or nitrogen condensation case for the loss of vacuum condition shall be considered for fluids with a
saturation temperature below 75 K at 1 bar.
Air condensation, for the case of loss of vacuum to the atmosphere on a vacuum insulated container,
is highly dependent on the type of insulation and how the insulation is designed. Since air condensation
occurs primarily below 75 K, and fluids with saturation temperatures below 75 K are generally stored
and transported in containers insulated with multi-layer insulation, this part of ISO 21013 covers air
condensation on multi-layer insulated containers only. In the absence of pertinent reliable data on perlite
insulated vessels, 4.2.3, 4.3.1, and 4.3.2 shall be used with thermal conductivity values shown in Table 1
increased by a factor of two in Formula (6) for k and Formula (10) for k , respectively.
3 5
Condensation of air on a multi-layer insulated surface below 75 K will depend on the rate of air access to the
insulated surface. On a multi-layer insulated container, the air condensation rate can vary depending on the
number of layers and the air access allowed by the design of the insulation.
Figure 1 provides heat transfer rates from air condensation to the stored fluid as a function of the number
of layers of insulation. The fire engulfment curve is an extrapolation for 922 K ambient temperature. Unless
heat transfer rates under the loss of vacuum condition from air condensation can be determined for the
same type and design of multi-layer insulation from prototype tests or actual incidents, heat transfer rates
from Figure 1 shall be used.
4.4.2 Loss of vacuum with air and nitrogen
W is the quantity of heat transferred per unit time (in watts) through air or nitrogen condensation for
3a
vacuum-insulated vessels in the case of a loss of vacuum with air or nitrogen.
WU=⋅A (12)
33aa i
where U is the heat transfer through air or nitrogen condensation, in watts per square metre of the
3a
inner vessel outer surface area, from Figure 1.
4.4.3 Fire with loss of vacuum with air or nitrogen
W is the quantity of heat transferred per unit time (in watts) through air or nitrogen condensation for
5a
vacuum-insulated vessels in the case of a fire and loss of vacuum with air or nitrogen.
08, 2
WU=⋅19, 5 ⋅A (13)
55aa i
where U is the heat transfer through air or nitrogen condensation during fire conditions, in watts per
5a
square metre of the inner vessel surface area, from Figure 1.

oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
Key
X number of insulation layers
Y heat transfer [W/m ]
07, 3
38400+⋅420 X
UY==
3a
07, 3
09, 6+X
07, 3
92160+⋅1000 X
UY==
5a
07, 3
09, 6+X
Figure 1 — Heat transfer rate for air or nitrogen condensation
4.5 Heat transfer per unit time (watts)
4.5.1 General
The required mass flow rate, Q , to be relieved can be calculated from the heat transfer, W , for the following
m T
specified conditions, where W is the total heat transfer applicable to the specified condition.
T
4.5.2 Normal operation
WW=+W (14)
T1 14
Alternatively, the heat transfer rate, W , can be determined from the normal evaporation rate (NER).
T1NER
v
 
QL⋅
  ga
mNER a
W = (15)
 
TN1 ER  
 
36, v −v
 
ga la
 
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
where
Q is the mass flow rate due to the normal evaporation rate, in kg/h;
mNER
L is the latent heat of vaporization of the cryogenic liquid at a pressure of 1,013 bar, in kJ/kg;
a
ν is the specific volume of saturated gas at a saturation pressure of 1,013 bar, in m /kg;
ga
ν is the specific volume of saturated liquid at a saturation pressure of 1,013 bar, in m /kg;
la
W is the total heat leak calculated from the experimentally determined normal evaporation
T1NER
rate, in watts.
4.5.3 Pressure build up regulator fully open
WW=+W (16)
TT21 2
Or for the NER method:
WW=+W (17)
TN21ER TNER 2
4.5.4 Loss of vacuum condition
The heat transfer rate is to be the larger of W or W .
T3 T3a
WW=+W (18)
T3 34
WW=+W (19)
Ta33a 4
where
W is the total heat transfer rate if the saturation temperature of the fluid is greater than or equal to
T3
75 K at 1 bar;
W is the total heat transfer rate if the saturation temperature of the fluid is less than 75 K at 1 bar.
T3a
Alternatively, W may be calculated using Formula (20)
T3
WW=+W (20)
TT31 3
or approximately, using Formula (21)
WW=+W (21)
TT31NER 3
W may be calculated using Formula (22)
T3a
WW=+W (22)
Ta31Ta3
or approximately, using Formula (23)
WW=+W (23)
Ta31TNER 3a
4.5.5 Fire condition with loss of vacuum, vacuum jacket, and insulation fully or partially in place
The heat transfer rate is to be the larger of W or W .
T5 T5a
oSIST prEN ISO 21013-3:2025
ISO/DIS 21013-3:2025(en)
where
W is equal to the heat transfer rate, W , if the saturation temperature of the fluid is greater than or
T5 5
equal to 75 K at 1 bar
W is equal to the heat transfer rate, W , if the saturation temperature of the fluid is less than 75 K
T5a 5a
at 1 bar
4.5.6 Fire condition with loss of vacuum, insulation not in place
The heat transfer rate is to be the larger of W = W or W = W , where W is calculated with U for the
T6 6 T5 5a 5a 5a
bare surface condition from Figure 1.
4.5.7 Total heat transfer rate
W is the total heat transfer rate and is equal to W , W , W , W , W , W , W , W , or W , as
T T1 T1NER T2 T2NER T3 T3a T5 T5a T6
applicable.
The fire case may not be the worst case, so fire and PBU conditions shall both be checked. If PBU is changed
later in the field, the sizing and capacity of pressure relief devices shall be verified according to new PBU
capacity.
5 Calculation of the mass flow to be relieved by pressure relief devices
5.1 Relieving pressure, P, less than the critical pressure
For a relieving pressure,
...