Abstract

This European Standard is applicable to high-calcium lime used for treatment of water intended for human consumption. It describes the characteristics of high-calcium lime and specifies the requirements and the corresponding test methods for high-calcium lime. It gives information on its use in water treatment. It also determines the rules relating to safe handling and use (see Annex B).

Status
Not Published
Public Enquiry End Date
14-Jan-2027
Current Stage
4020 - Public enquire (PE) (Adopted Project)
Start Date
18-Nov-2026
Due Date
07-Apr-2027

Buy Documents

Draft

oSIST prEN 12518:2027 - BARVE

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

oSIST prEN 12518:2027 is a CEN draft European Standard for high-calcium lime used in the treatment of water intended for human consumption. It specifies the product description, purity criteria, test methods, and the rules for labelling, transport, storage, and safe handling for producers, suppliers, laboratories, and water-treatment users.

What does oSIST prEN 12518:2027 specify?

oSIST prEN 12518:2027 applies to high-calcium lime used for drinking-water treatment. It describes the product, sets requirements and test methods, and gives guidance on use in water treatment.

The document is organized into:

  • Clause 1 - Scope
  • Clause 2 - Normative references
  • Clause 3 - Terms and definitions
  • Clause 4 - Description
  • Clause 5 - Purity criteria
  • Clause 6 - Test methods
  • Clause 7 - Labelling, transportation, and storage
  • Annex A - General information on high-calcium lime

In practice, this means the standard is not only about what the product is, but also how to check it, label it, move it, and store it without affecting water quality.

What are the key requirements of oSIST prEN 12518:2027?

Product description and commercial forms

oSIST prEN 12518:2027 identifies high-calcium lime as calcium oxide, calcium dihydroxide, and aqueous suspension of calcium dihydroxide. It also lists the commercial forms used in supply, including pulverized, lump, hydrated, and milk of lime.

For users, this matters because the same product family is supplied in different physical forms, and each form behaves differently in dosing, handling, and storage.

Composition and grading

oSIST prEN 12518:2027 sets requirements for the major constituents and grading of the commercial product in Clause 5.2. The document distinguishes product classes for different forms and uses minimum active lime content together with sieve-retention limits.

For a buyer or plant operator, this is the section that helps confirm whether the delivered product matches the form and grade needed for metering, slaking, and process performance.

Impurities and trace substances

oSIST prEN 12518:2027 limits common impurities in Clause 5.3, including silicon, aluminium, iron, manganese, and calcium carbonate. Clause 5.5 also limits chemical parameters such as arsenic, cadmium, chromium, mercury, nickel, lead, antimony, and selenium.

This is important because impurity control affects drinking-water quality, sludge formation, and whether the product fits the intended treatment target.

Water insoluble matter and free water

oSIST prEN 12518:2027 limits water insoluble matter in Clause 5.4 and sets a maximum free-water content in Clause 5.6. The document treats these as product-quality controls for both dry products and suspensions.

In practice, these limits affect flowability, storage in silos, ease of discharge, and the risk of settled solids or operational problems during dosing.

Sampling and analysis

oSIST prEN 12518:2027 requires sampling of laboratory samples in accordance with EN 12485, and it directs users to EN 12485 for the relevant analytical methods in Clause 6. That means compliance checks are tied to the companion test standard.

For laboratories and quality teams, this avoids using ad hoc methods and gives a common basis for acceptance testing.

Delivery, labelling, transport, and storage

oSIST prEN 12518:2027 requires delivery in bags, containers, or bulk, and the delivery equipment must not contaminate the product. Clause 7 also specifies labelling items, transport information for calcium oxide and calcium dihydroxide forms, and storage precautions.

For day-to-day use, this is the part that matters most on site: it tells handlers how to keep the product dry, separate it from acids, and protect product quality during receipt and storage.

What terms does oSIST prEN 12518:2027 define?

  • High-calcium lime - The product family covered by the standard, including calcium oxide, calcium dihydroxide, and calcium dihydroxide suspension for water treatment.
  • Calcium oxide - The quicklime form, supplied as white lumps or powder and used as a starting material for other lime forms.
  • Calcium dihydroxide - The hydrated lime form, used as a powder or in aqueous form for treatment applications.
  • Milk of lime - An aqueous suspension of calcium dihydroxide used for dosing in water treatment.
  • Water insoluble matter - The part of the product that does not dissolve in water and is limited to protect product performance.
  • Free water - Water present in the delivered product; too much free water affects flowability and storage behavior.
  • Type 1 / Type 2 - Chemical-parameter categories used in Clause 5.5 to distinguish different trace-metal limits.
  • Grade 1 / Grade 2 / Grade 3 - Purity grades used for impurity limits in Clause 5.3.

Who uses oSIST prEN 12518:2027?

oSIST prEN 12518:2027 is used by drinking-water treatment operators, chemical manufacturers, distributors, laboratory staff, and procurement or quality managers. It helps them specify the right form of high-calcium lime, verify incoming deliveries, check purity, and handle the product safely in water-treatment plants.

What changed in oSIST prEN 12518:2027 from the previous edition?

oSIST prEN 12518:2027 will supersede EN 12518:2014. The foreword states these changes from the earlier edition:

  • calcium hydroxide was amended to calcium dihydroxide throughout the document;
  • the note to Table 3 in 5.4 was adjusted;
  • a new A.2 subclause and Tables A.1 and A.2 were added on impact on drinking-water quality;
  • Annex B was deleted and its text incorporated into Annex A;
  • the older Drinking Water Directive was replaced in the bibliography.

Which standards are used with oSIST prEN 12518:2027?

The normative reference is EN 12485, which provides the sampling and analytical methods used by this document. The text also refers to Directive 2020/2184 for drinking-water quality context and Regulation (EC) No 1272/2008 for classification, labelling, and packaging of substances and mixtures.

What does the oSIST prEN 12518:2027 document contain?

The document contains product identification data, physical and chemical property descriptions, purity tables, and transport and storage instructions. It includes tables for major constituents, impurities, water insoluble matter, and chemical parameters, plus labelling and transport notes for the different lime forms.

Annex A adds general information on origin, manufacture, use, treatment dose, secondary effects, safe handling, first aid, spillage response, and fire precautions. It also includes tables A.1 and A.2 showing the expected impact of Type 1 and Type 2 products on drinking-water chemical parameters.

Relations

Effective Date
06-May-2026

Buy Documents

Draft

oSIST prEN 12518:2027 - BARVE

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ECOCERT

Organic and sustainability certification.

COFRAC France Verified

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Eurofins Food Testing Global

Global leader in food, environment, and pharmaceutical product testing.

COFRAC Luxembourg Verified

Sponsored listings

Frequently Asked Questions

oSIST prEN 12518:2027 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Chemicals used for treatment of water intended for human consumption - High-calcium lime". This standard covers: This European Standard is applicable to high-calcium lime used for treatment of water intended for human consumption. It describes the characteristics of high-calcium lime and specifies the requirements and the corresponding test methods for high-calcium lime. It gives information on its use in water treatment. It also determines the rules relating to safe handling and use (see Annex B).

This European Standard is applicable to high-calcium lime used for treatment of water intended for human consumption. It describes the characteristics of high-calcium lime and specifies the requirements and the corresponding test methods for high-calcium lime. It gives information on its use in water treatment. It also determines the rules relating to safe handling and use (see Annex B).

oSIST prEN 12518:2027 is classified under the following ICS (International Classification for Standards) categories: 13.060.20 - Drinking water; 71.100.80 - Chemicals for purification of water. The ICS classification helps identify the subject area and facilitates finding related standards.

oSIST prEN 12518:2027 has the following relationships with other standards: It is inter standard links to SIST EN 12518:2014. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

oSIST prEN 12518:2027 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 4 Description
  • 4.1 Identification
  • 4.2 Commercial forms
  • 4.3 Physical properties
  • 4.4 Chemical properties
  • 5 Purity criteria
  • 5.1 General
  • 5.2 Composition of commercial product
  • 5.3 Impurities
  • 5.4 Water insoluble matter
  • 5.5 Chemical parameters
  • 5.6 Free water
  • 6 Test methods
  • 6.1 Sampling
  • 6.2 Analyses
  • 7 Labelling - Transportation - Storage
  • 7.1 Means of delivery
  • 7.2 Labelling according to the EU legislation
  • 7.3 Transportation regulations and labelling
  • 7.4 Marking
  • 7.5 Storage
  • Annex A
  • Bibliography

Introduction

In respect of potential adverse effects on the quality of water intended for human consumption, caused by the product covered by this document:

a) this document provides no information as to whether the product may be used without restriction in any of the Member States of the EU or EFTA; b) it should be noted that, while awaiting the adoption of verifiable European criteria, existing national regulations concerning the use and/or the characteristics of this product remain in force. NOTE Conformity with this document does not confer or imply acceptance or approval of the product in any of the Member States of the EU or EFTA. The use of the product covered by this document is subject to regulation or control by National Authorities.

oSIST prEN 12518:2027 prEN 12518:2026(E)

1 Scope

This document is applicable to high-calcium lime used for treatment of water intended for human consumption. It describes the characteristics of high-calcium lime and specifies the requirements and the corresponding test methods for high-calcium lime. It gives information on its use in water treatment. It also determines the rules relating to safe handling and use (see Annex B).

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. <std>EN 12485, Chemicals used for treatment of water intended for human consumption - Calcium carbonate, high-calcium lime, half-burnt dolomite, magnesium oxide, calcium magnesium carbonate and dolomitic lime - Test methods</std>

3 Terms and definitions

No terms and definitions are listed in this document.

ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/

4 Description

4.1 Identification

4.1.1 General

High-calcium limes are calcium oxide, Calcium dihydroxide and aqueous suspension of Calcium dihydroxide (milk of lime).

4.1.2 Chemical names

a) Calcium oxide.

b) Calcium dihydroxide.

4.1.3 Synonym or common names

a) Calcium oxide: Pulverized high-calcium lime, quicklime, lump high-calcium lime. b) Calcium dihydroxide: Hydrated high-calcium lime, Calcium dihydroxide - aqueous suspension (milk of lime).

4.1.4 Relative molecular mass

a) Calcium oxide: 56,08.

b) Calcium dihydroxide: 74,09.

oSIST prEN 12518:2027 prEN 12518:2026 (E)

4.1.5 Empirical formula

a) Calcium oxide: CaO b) Calcium dihydroxide: Ca(OH) .

4.1.6 Chemical formula

a) Calcium oxide: CaO.

b) Calcium dihydroxide: Ca(OH) .

1)

4.1.7 CAS Registry Number

a) Calcium oxide: 1305-78-8.

b) Calcium dihydroxide: 1305-62-0.

2)

4.1.8 EINECS reference

a) Calcium oxide: 215-138-9.

b) Calcium dihydroxide: 215-137-3.

4.2 Commercial forms

High-calcium lime is available in the following commercial forms:

  • pulverized high calcium lime (quicklime) : white powder (CaO);
  • lump high-calcium lime (quicklime) : white lump (CaO);
  • hydrated high-calcium lime : white powder, (Ca(OH) );
  • milk of lime: aqueous suspension of Calcium dihydroxide (usual content of Calcium dihydroxide is a mass fraction between 10 % to 40 %.

4.3 Physical properties

4.3.1 Appearance

a) Calcium oxide: white, lumps or powder.

b) Calcium dihydroxide: white powder.

Calcium dihydroxide suspension: aqueous, milky suspension.

1) Chemical Abstracts Service Registry Number.

2) European Inventory of Existing Commercial Chemical Substances.

oSIST prEN 12518:2027 prEN 12518:2026(E)

4.3.2 Density

a) Calcium oxide : 3,35 kg/dm at 20 °C.

3 3 Bulk density : 800 kg/m to 1 200 kg/m .

b) Calcium dihydroxide : 2,24 kg/dm at 20 °C.

3 3 Bulk density : 300 kg/m to 600 kg/m .

4.3.3 Solubility (in water)

Calcium oxide: not applicable.

Calcium dihydroxide: 1,85 g/l at 0 °C 1,65 g/l at 20 °C 1,53 g/l at 30 °C 1,40 g/l at 40 °C 1,28 g/l at 50 °C 1,16 g/l at 60 °C 1,04 g/l at 70 °C 0,92 g/l at 80 °C 0,81 g/l at 90 °C 0,71 g/l at 100 °C

4.3.4 Vapour pressure

Not applicable.

3)

4.3.5 Boiling point at 100 kPa

a) Calcium oxide: 2 850 °C.

b) Calcium dihydroxide: Decomposes at 580 °C and forms calcium oxide and water.

4.3.6 Melting point

a) Calcium oxide: 2570 °C.

b) Calcium dihydroxide: Decomposes at 580 °C and forms calcium oxide and water. Calcium dihydroxide suspension freezes at 0 °C.

4.3.7 Specific heat

Not applicable.

4.3.8 Viscosity (dynamic)

For Calcium dihydroxide suspension depends on concentration and particle size.

3) 100 kPa = 1 bar.

oSIST prEN 12518:2027 prEN 12518:2026 (E)

4.3.9 Critical temperature

Not applicable.

4.3.10 Critical pressure

Not applicable.

4.3.11 Physical hardness

Not applicable.

4.4 Chemical properties

Aqueous suspensions are strongly alkaline. Calcium oxide (CaO) reacts with water to form Calcium dihydroxide Ca(OH) , and with acids to form calcium salts. These reactions are highly exothermic.

5 Purity criteria

5.1 General

This document specifies the minimum purity requirements for high-calcium lime used for the treatment of water intended for human consumption. Limits are given for impurities commonly present in the product. Depending on the raw material and the manufacturing process other impurities may be present and, if so, this shall be notified to the user and when necessary to relevant authorities. NOTE Users of this product should check the national regulations in order to clarify whether it is of appropriate purity for treatment of water intended for human consumption, taking into account raw water quality, required dosage, contents of other impurities and additives used in the product not stated in this product standard.

...