IEC PAS 60099-7:2004
(Main)Surge arresters - Part 7: Glossary of terms and definitions from IEC publications 60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21, 61643-311, 61643-321, 61643-331 and 61643-341
General Information
- Abstract
Provides a list of terms and definitions relative to IEC publications from IEC technical committee 37: Surge Arresters, and subcommittees 37A: Surge protective devices, and 37B: Surge protective components, current at the date of this publication.
- Status
- Withdrawn
- Publication Date
- 26-Apr-2004
- Withdrawal Date
- 10-Jun-2019
- Technical Committee
- TC 37 - Surge arresters
- Drafting Committee
- WG 11 - TC 37/WG 11
- Current Stage
- WPUB - Publication withdrawn
- Start Date
- 11-Jun-2019
- Completion Date
- 11-Jun-2019
Buy Documents
IEC PAS 60099-7:2004 - Surge arresters - Part 7: Glossary of terms and definitions from IEC publications 60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21, 61643-311, 61643-321, 61643-331 and 61643-341 Released:4/27/2004
Buy Documents
IEC PAS 60099-7:2004 - Surge arresters - Part 7: Glossary of terms and definitions from IEC publications 60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21, 61643-311, 61643-321, 61643-331 and 61643-341 Released:4/27/2004
Get Certified
Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)
Italian electrical product certification.

SLG Prüf- und Zertifizierungs GmbH
German testing and certification body.

UL Solutions
Global safety science company with testing, inspection and certification.
Sponsored listings
Frequently Asked Questions
IEC PAS 60099-7:2004 is a technical specification published by the International Electrotechnical Commission (IEC). Its full title is "Surge arresters - Part 7: Glossary of terms and definitions from IEC publications 60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21, 61643-311, 61643-321, 61643-331 and 61643-341". This standard covers: Provides a list of terms and definitions relative to IEC publications from IEC technical committee 37: Surge Arresters, and subcommittees 37A: Surge protective devices, and 37B: Surge protective components, current at the date of this publication.
Provides a list of terms and definitions relative to IEC publications from IEC technical committee 37: Surge Arresters, and subcommittees 37A: Surge protective devices, and 37B: Surge protective components, current at the date of this publication.
IEC PAS 60099-7:2004 is classified under the following ICS (International Classification for Standards) categories: 01.040.29 - Electrical engineering (Vocabularies); 29.240.10 - Substations. Surge arresters. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC PAS 60099-7:2004 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
PUBLICLY
IEC
AVAILABLE
PAS 60099-7
SPECIFICATION
First edition
2004-04
Surge arresters –
Part 7:
Glossary of terms and definitions
from IEC publications 60099-1, 60099-4,
60099-6, 61643-1, 61643-12, 61643-21,
61643-311, 61643-321, 61643-331
and 61643-341
Reference number
IEC/PAS 60099-7:2004(E)
Publication numbering
As from 1 January 1997 all IEC publications are issued with a designation in the
60000 series. For example, IEC 34-1 is now referred to as IEC 60034-1.
Consolidated editions
The IEC is now publishing consolidated versions of its publications. For example,
edition numbers 1.0, 1.1 and 1.2 refer, respectively, to the base publication, the
base publication incorporating amendment 1 and the base publication incorporating
amendments 1 and 2.
Further information on IEC publications
The technical content of IEC publications is kept under constant review by the IEC,
thus ensuring that the content reflects current technology. Information relating to
this publication, including its validity, is available in the IEC Catalogue of
publications (see below) in addition to new editions, amendments and corrigenda.
Information on the subjects under consideration and work in progress undertaken
by the technical committee which has prepared this publication, as well as the list
of publications issued, is also available from the following:
• IEC Web Site (www.iec.ch)
• Catalogue of IEC publications
The on-line catalogue on the IEC web site (www.iec.ch/searchpub) enables you to
search by a variety of criteria including text searches, technical committees
and date of publication. On-line information is also available on recently issued
publications, withdrawn and replaced publications, as well as corrigenda.
• IEC Just Published
This summary of recently issued publications (www.iec.ch/online_news/ justpub)
is also available by email. Please contact the Customer Service Centre (see
below) for further information.
• Customer Service Centre
If you have any questions regarding this publication or need further assistance,
please contact the Customer Service Centre:
Email: custserv@iec.ch
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
PUBLICLY
IEC
AVAILABLE
PAS 60099-7
SPECIFICATION
First edition
2004-04
Surge arresters –
Part 7:
Glossary of terms and definitions
from IEC publications 60099-1, 60099-4,
60099-6, 61643-1, 61643-12, 61643-21,
61643-311, 61643-321, 61643-331
and 61643-341
© IEC 2004 ⎯ Copyright - all rights reserved
No part of this publication may be reproduced or utilized in any form or by any means, electronic or
mechanical, including photocopying and microfilm, without permission in writing from the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
PRICE CODE
Commission Electrotechnique Internationale
XA
International Electrotechnical Commission
Международная Электротехническая Комиссия
For price, see current catalogue
– 2 – PAS 60099-7 © IEC:2004 (E)
CONTENTS
FOREWORD.3
1 Scope .4
2 Surge arresters – Non-linear resistor type gapped surge arresters for a.c. systems
(IEC 60099-1:1991+A1:1999).4
3 Surge arresters – Metal-oxide surge arresters without gaps for a.c. systems (IEC
60099-4:1991+A1:1998+A2:2001).9
4 Surge protective devices connected to low-voltage power distribution systems –
Performance requirements and testing methods (IEC 61643-1:1998+A1:2001).16
5 Low-voltage surge protective devices – Surge protective devices connected to
telecommunications and signalling networks – Performance requirements and
testing methods (IEC 61643-21:2000) .21
6 Components for low-voltage surge protective devices – Specification for gas
discharge tubes (GDT) (IEC 61643-311:2001) .24
7 Components for low-voltage surge protective devices – Specifications for
avalanche breakdown diode (ABD) (IEC 61643-321:2001).26
8 Components for low-voltage surge protective devices – Specification for metal
oxide varistors (MOV) (IEC 61643-331:2001) .28
9 Components for low-voltage surge protective devices – Specification for thyristor
surge suppressors (TSS) (IEC 61643-341:2003).30
10 Low-voltage surge protective devices – Surge protective devices connected to low-
voltage power distribution systems – Selection and application prin-ciples (IEC
61643-12:2002) .40
11 Surge arresters – Surge arresters containing both series and parallel gapped
structures – Rated 52 kV and less (IEC 60099-6:2002).46
PAS 60099-7 © IEC:2004 (E) – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
SURGE ARRESTERS −
Part 7: Glossary of terms and definitions from IEC publications
60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21,
61643-311, 61643-321, 61643-331 and 61643-341
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
A PAS is a technical specification not fulfilling the requirements for a standard but made
available to the public.
IEC-PAS 60099-7 has been processed by IEC technical committee 37: Surge arresters.
The text of this PAS is based on the This PAS was approved for
following document: publication by the P-members of the
committee concerned as indicated in
the following document
Draft PAS Report on voting
37/291/NP 37/296/RVN
This PAS shall remain valid for an initial maximum period of three years starting from 2004-
05. The validity may be extended for a single three-year period, following which it shall be
revised to become another type of normative document or shall be withdrawn.
– 4 – PAS 60099-7 © IEC:2004 (E)
SURGE ARRESTERS −
Part 7: Glossary of terms and definitions from IEC publications
60099-1, 60099-4, 60099-6, 61643-1, 61643-12, 61643-21,
61643-311, 61643-321, 61643-331 and 61643-341
1 Scope
This PAS compiles a list of terms and definitions relative to IEC publications from IEC
technical committee 37: Surge arresters, and subcommittees 37A: Surge protective devices,
and 37B: Surge protective components, current at the date of this publication.
2 Surge arresters – Non-linear resistor type gapped surge arresters for a.c.
systems (IEC 60099-1:1991+A1:1999)
2.1
*
surge arrester
device designed to protect electrical apparatus from high transient voltage and to limit the
duration and frequently the amplitude of follow-current. The term "surge arrester" includes any
external series gap which is essential for the proper functioning of the device as installed for
service, regardless of whether or not it is supplied as an integral part of the device
NOTE Surge arresters are usually connected between the electrical conductors of a network and earth although
they may sometimes be connected across the windings of apparatus or between electrical conductors.
2.2
non-linear resistor type gapped arrester:
arrester having a single or a multiple spark-gap connected in series with one or more non-
linear resistors
2.3
series gap of an arrester:
intentional gap or gaps between spaced electrodes in series with the non-linear series resistor
or resistors of the arrester
2.4
non-linear series resistor of an arrester
part of the surge arrester which, by its non-linear voltage-current characteristics, acts as a low
resistance to the flow of high discharge currents thus limiting the voltage across the arrester
terminals, and as a high resistance at normal power-frequency voltage thus limiting the
magnitude of follow-current
2.5
section of an arrester
complete, suitably housed part of an arrester including series gaps and non-linear series
resistors in such a proportion as is necessary to represent the behaviour of a complete
arrester with respect to a particular test
2.6
unit of an arrester
completely housed part of an arrester which may be connected in series with other units to
construct an arrester of higher voltage rating. A unit of an arrester is not necessarily a section
of an arrester
———————
*
This type of equipment may be called "surge diverter" in some countries.
PAS 60099-7 © IEC:2004 (E) – 5 –
2.7
pressure-relief device of an arrester
means for relieving internal pressure in an arrester and preventing explosive shattering of the
housing following prolonged passage of follow-current or internal flashover of the arrester
2.8
rated voltage of an arrester
designated maximum permissible r.m.s. value of power-frequency voltage between its
terminals at which it is designated to operate correctly. This voltage may be applied to the
arrester continuously without changing its operating characteristics
2.9
rated frequency of an arrester
frequency of the power system on which the arrester is designed to be used
2.10
disruptive discharge
phenomena associated with the failure of insulation under electrical stress which include a
collapse of voltage and the passage of current; the term applies to electrical breakdown in
solid, liquid and gaseous dielectrics and combinations of these
NOTE A disruptive discharge in a solid dielectric produces permanent loss of electrical strength; in a liquid or
gaseous dielectric the loss may be only temporary.
2.11
puncture
disruptive discharge through a solid
2.12
flashover
disruptive discharge over a solid surface
2.13
sparkover of an arrester
disruptive discharge between the electrodes of the gaps of an arrester
2.14
impulse
unidirectional wave of voltage or current which, without appreciable oscillations, rises rapidly
to a maximum value and falls, usually less rapidly, to zero with small, if any, loops of opposite
polarity
The parameters which define a voltage or current impulse are polarity, peak value, front time,
and time to half-value on the tail
2.15
rectangular impulse
impulse which rises rapidly to a maximum value, remains substantially constant for a specified
period, and then falls rapidly to zero
The parameters which define a rectangular impulse are polarity, peak value, virtual duration
of the peak, and virtual total duration
2.16
peak (crest) value of an impulse
maximum value of voltage or current in an impulse. In case of superimposed oscillations (see
8.3.2, 8.5.2e), and 8.5.3.2c) of IEC 60099-1)
– 6 – PAS 60099-7 © IEC:2004 (E)
2.17
front of an impulse
that part of an impulse which occurs prior to the peak
2.18
tail of an impulse
that part of an impulse which occurs after the peak
2.19
full-wave voltage impulse
voltage impulse which is not interrupted by sparkover, flashover, or puncture
2.20
chopped voltage impulse
voltage impulse which is interrupted on the front, peak, or tail by sparkover, flashover or
puncture causing a sudden drop in the voltage
2.21
prospective peak (crest) value of a chopped voltage impulse
peak (crest) value of the full-wave voltage impulse from which a chopped voltage impulse is
derived
2.22
virtual origin of an impulse
point on a graph of voltage versus time or current versus time determined by the intersection
between the time axis at zero voltage or zero current and a straight line drawn through two
reference points on the front of the impulse
a) for voltage impulses with virtual front times equal to, or less than, 30 µs, the reference
points are at 30 % and 90 % of the peak value;
b) for voltage impulses with virtual front times greater than 30 µs, the origin is generally
well-defined and needs no artificial definition;
c) for current impulses, the reference points are 10 % and 90 % of the peak value
NOTE This definition applies only when scales of both ordinate and abscissa are linear. See also note to 3.23.
2.23
virtual front time of an impulse (T )
time, in µs, equal to:
a) for voltage impulses with front durations equal to, or less than, 30 µs, 1,67 times the
time taken by the voltage to increase from 30 % to 90 % of its peak value;
b) for voltage impulses with front durations greater than 30 µs, 1,05 times the time taken
by the voltage to increase from 0 % to 95 % of its peak value;
c) for current impulses, 1,25 times the time taken by the current to increase from 10 % to
90 % of its peak value
NOTE If oscillations are present on the front, the reference points at 10 %, 30 %, 90 % and 95 % should be taken
on the mean curve drawn through the oscillations.
2.24
virtual steepness of the front of an impulse
quotient of the peak value and the virtual front time of an impulse
PAS 60099-7 © IEC:2004 (E) – 7 –
2.25
virtual time to half-value on the tail of an impulse (T )
time interval between the virtual origin and the instant when the voltage or current has
decreased to half its peak value. This time is expressed in µs
2.26
designation of an impulse shape
combination of two numbers, the first representing the virtual front time (T ) and the second
the virtual time to half-value of the tail (T ). It is written as T /T , both in µs, the sign "/"
2 1 2
having no mathematical meaning
2.27
standard lightning voltage impulse
impulse voltage having a waveshape designation of 1,2/50.
2.28
switching voltage impulse
impulse having a virtual front time greater than 30 µs
2.29
virtual duration of the peak of a rectangular impulse
time during which the amplitude of the impulse is greater than 90 % of its peak value
2.30
virtual total duration of a rectangular impulse
time during which the amplitude of the impulse is greater than 10 % of its peak value. If small
oscillations are present on the front, a mean curve should be drawn in order to determine the
time at which the 10 % value is reached
2.31
peak (crest) value of opposite polarity of an impulse
maximum amplitude of opposite polarity reached by a voltage or current impulse when it
oscillates about zero before attaining a permanent zero value
2.32
discharge current of an arrester
surge or impulse current which flows through the arrester after a sparkover of the series gaps
2.33
nominal discharge current of an arrester
peak value of discharge current, having an 8/20 waveshape, which is used to classify an
arrester. It is also the discharge current which is used to initiate follow-current in the
operating duty test
2.34
follow-current of an arrester
current from the connected power source which flows through an arrester following the
passage of discharge current
2.35
residual voltage (discharge voltage) of an arrester
voltage that appears between the terminals of an arrester during the passage of discharge
current
– 8 – PAS 60099-7 © IEC:2004 (E)
2.36
impulse sparkover voltage of an arrester
highest value of voltage attained before sparkover during an impulse of given waveshape and
polarity applied between the terminals of an arrester
2.37
front-of-wave impulse sparkover of an arrester:
impulse sparkover voltage obtained on the wavefront the voltage of which increases linearly
with time
2.38
standard lightning impulse sparkover voltage of an arrester
lowest prospective peak value of a standard lightning voltage impulse which, when applied to
an arrester, causes sparkover on every application
2.39
time to sparkover of an arrester
time interval between virtual origin and the instant of sparkover of the arrester. The time is
expressed in µs
2.40
impulse sparkover-voltage/time curve
curve which relates the impulse sparkover voltage to the time to sparkover
2.41
prospective current
current which would flow at a given location in a circuit if it were short-circuited at that
location by a link of negligible impedance
2.42
type tests (design tests)
tests which are made upon the completion of the development of a new arrester design to
establish representative performance and to demonstrate compliance with this part of the
standard. Once made, these tests need not be repeated unless the design is so changed as
to modify its performance
2.43
routine tests
tests made on each arrester or on parts and materials as required to ensure that the product
meets the design specifications
2.44
acceptance tests
selected tests which are made when it has been agreed between the manufacturer and the
purchaser that the arresters or representative samples of an order are to be tested
2.45
protective characteristics of an arrester
combination of the following:
a) lightning impulse sparkover-voltage/time curve as determined in 8.3.3 of IEC 60099-1;
b) the residual-voltage/discharge-current curve as determined in 8.4 of IEC 60099-1;
c) for 10 000 A arresters rated 100 kV and higher, the switching-voltage impulse
sparkover-voltage/time curve as determined in 8.3.5 of IEC 60099-1
PAS 60099-7 © IEC:2004 (E) – 9 –
2.46
arrester disconnector
device for disconnecting an arrester from the system in the event of arrester failure to prevent
a persistent fault on the system and to give visible indication of the failed arrester
NOTE Clearing of the fault current through the arrester during disconnection generally is not a function of the
device, and it may not prevent explosive shattering of the housing following internal flashover of the arrester on
high fault currents.
3 Surge arresters – Metal-oxide surge arresters without gaps for a.c. systems
(IEC 60099-4:1991+A1:1998+A2:2001)
3.1
metal-oxide surge arrester without gaps
arrester having non-linear metal-oxide resistors connected in series and/or in parallel without
any integrated series or parallel spark gaps
3.2
non-linear metal-oxide resistor
part of the surge arrester which by its non-linear voltage versus current characteristics acts as
a low resistance to overvoltages, thus limiting the voltage across the arrester terminals, and
as a high resistance at normal power-frequency voltage
3.3
internal grading system of an arrester
grading impedances, in particular grading capacitors connected in parallel to one single or to
a group of non-linear metal-oxide resistors, to control the voltage distribution along the metal-
oxide resistor stack
3.4
grading ring of an arrester
metal part, usually circular in shape, mounted to modify electrostatically the voltage
distribution along the arrester
3.5
section of an arrester
complete, suitably assembled part of an arrester necessary to represent the behaviour of a
complete arrester with respect to a particular test. A section of an arrester is not necessarily a
unit of an arrester
3.6
unit of an arrester
completely housed part of an arrester which may be connected in series and/or in parallel with
other units to construct an arrester of higher voltage and/or current rating. A unit of an
arrester is not necessarily a section of an arrester
3.7
pressure relief device of an arrester
means for relieving internal pressure in an arrester and preventing violent shattering of the
housing following prolonged passage of fault current or internal flashover of the arrester
3.8
rated voltage of an arrester (U )
r
maximum permissible r.m.s. value of power-frequency voltage between its terminals at which
it is designed to operate correctly under temporary overvoltage conditions as established in
the operating duty tests (see 7.5 of IEC 60099-4). The rated voltage is used as a reference
parameter for the specification of operating characteristics
NOTE The rated voltage as defined in this document is the 10 s power-frequency voltage used in the operating
duty test after high-current or long-duration impulses. Tests used to establish the voltage rating in IEC 60099-1, as
– 10 – PAS 60099-7 © IEC:2004 (E)
well as some national standards, involve the application of repetitive impulses at nominal current with power-
frequency voltage applied. Attention is drawn to the fact that these two methods used to established rating do not
necessarily produce equivalent values. (A resolution to this discrepancy is under consideration.)
3.9
continuous operating voltage of an arrester (U )
c
continuous operating voltage is the designated permissible r.m.s. value of power-frequency
voltage that may be applied continuously between the arrester terminals in accordance with 7.5 of
IEC 60099-4
3.10
rated frequency of an arrester
frequency of the power system on which the arrester is designed to be used
3.11
disruptive discharge
phenomena associated with the failure of insulation under electric stress, which include a
collapse of voltage and the passage of current. The term applies to electrical breakdowns in
solid, liquid and gaseous dielectric, and combinations of these
NOTE A disruptive discharge in a solid dielectric produces permanent loss of electric strength. In a liquid or
gaseous dielectric the loss may be only temporary.
3.12
puncture (breakdown)
disruptive discharge through a solid
3.13
flashover
disruptive discharge over a solid surface
3.14
impulse
unidirectional wave of voltage or current which without appreciable oscillations rises rapidly to
a maximum value and falls – usually less rapidly – to zero with small, if any, excursions of
opposite polarity.
The parameters which define a voltage or current impulse are polarity, peak value, front time
and time to half value on the tail
3.15
designation of an impulse shape
combination of two numbers, the first representing the virtual front time (T ) and the second
the virtual time to half-value on the tail (T ). It is written as T /T , both in µs, the sign "/"
2 1 2
having no mathematical meaning
3.16
steep current impulse
current impulse with a virtual front time of 1 µs with limits in the adjustment of equipment such
that the measured values are from 0,9 µs to 1,1 µs. The virtual time to half-value on the tail
shall be not longer than 20 µs
NOTE The time to half value on the tail is not critical and may have any tolerance during the residual voltage type
tests (see 7.3 of IEC 60099-4).
3.17
lightning current impulse
8/20 current impulse with limits on the adjustment of equipment such that the measured
values are from 7 µs to 9 µs for the virtual front time and from 18 µs to 22 µs for the time to
half-value on the tail
PAS 60099-7 © IEC:2004 (E) – 11 –
NOTE The time to half-value on the tail is not critical and may have any tolerance during the residual voltage type
tests (see 7.3 of IEC 60099-4).
3.18
long-duration current impulse
rectangular impulse which rises rapidly to maximum value, remains substantially constant for
a specified period and then falls rapidly to zero.
The parameters which define a rectangular impulse are polarity, peak value, virtual duration
of the peak and virtual total duration
3.19
peak (crest) value of an impulse
maximum value of a voltage or current impulse. Superimposed oscillations may be
disregarded (see 7.4.2c) and 7.5.4.2e) of IEC 60099-4)
3.20
front of an impulse
part of an impulse which occurs prior to the peak
3.21
tail of an impulse
part of an impulse which occurs after the peak
3.22
virtual origin of an impulse
point on a graph of voltage versus time or current versus time determined by the intersection
between the time axis at zero voltage or zero current and the straight line drawn through two
reference points on the front of the impulse. For current impulses, the reference points shall
be 10 % and 90 % of the peak value
NOTE 1 This definition applies only when scales of both ordinate and abscissa are linear.
NOTE 2 If oscillations are present on the front, the reference points at 10 % and 90 % should be taken on the
mean curve drawn through the oscillations.
3.23
virtual front time of a current impulse (T )
time in µs equal to 1,25 multiplied by the time in µs for the current to increase from 10 % to 90
% of its peak value
NOTE If oscillations are present on the front, the reference points at 10 % and 90 % should be taken on the mean
curve drawn through the oscillations.
3.24
virtual steepness of the front of an impulse
quotient of the peak value and the virtual front time of an impulse
3.25
virtual time to half-value on the tail of an impulse (T )
time interval between the virtual origin and the instant when the voltage or current has
decreased to half its peak value. This time is expressed in µs
3.26
virtual duration of the peak of a rectangular impulse
time during which the amplitude of the impulse is greater than 90 % of its peak value
3.27
virtual total duration of a rectangular impulse
time during which the amplitude of the impulse is greater than 10 % of its peak value. If small
oscillations are present on the front, a mean curve should be drawn in order to determine the
time at which the 10 % value is reached
– 12 – PAS 60099-7 © IEC:2004 (E)
3.28
peak (crest) value of opposite polarity of an impulse
maximum amplitude of opposite polarity reached by a voltage or current impulse when it
oscillates about zero before attaining a permanent zero value
3.29
discharge current of an arrester
impulse current which flows through the arrester
3.30
nominal discharge current of an arrester (I )
n
peak value of lightning current impulse (see 3.17) which is used to classify an arrester
3.31
high current impulse of an arrester
peak value of discharge current having a 4/10 impulse shape which is used to test the stability
of the arrester on direct lightning strokes
3.32
switching current impulse of an arrester
peak value of discharge current having a virtual front time greater than 30 µs but less than
100 µs and a virtual time to half-value on the tail of roughly twice the virtual front time
3.33
continuous current of an arrester
continuous current is the current flowing through the arrester when energized at the
continuous operating voltage
NOTE The continuous current, which consists of a resistive and a capacitive component, may vary with
temperature, stray capacitance and external pollution effects. The continuous current of a test sample may,
therefore, not be the same as the continuous current of a complete arrester.
The continuous current is, for comparison purposes, expressed either by its r.m.s. or peak value.
3.34
reference current of an arrester
peak value (the higher peak value of the two polarities if the current is asymmetrical) of the
resistive component of a power-frequency current used to determine the reference voltage of
the arrester. The reference current shall be high enough to make the effects of stray
capacitances at the measured reference voltage of the arrester units (with designed grading
system) negligible and shall be specified by the manufacturer
NOTE Depending on the nominal discharge current and/or line discharge class of the arrester, the reference
current will be typically in the range of 0,05 mA to 1,0 mA per m of disc area for single column arresters.
3.35
reference voltage of an arrester (U )
ref
peak value of power-frequency voltage divided by which shall be applied to the arrester to
obtain the reference current. The reference voltage of a multi-unit arrester is the sum of the
reference voltages of the individual units
NOTE Measurement of reference voltage is necessary for the selection of a correct test sample in the operating
duty test (see 7.5 of IEC 60099-4).
3.36
residual voltage of an arrester (U )
res
peak value of voltage that appears between the terminals of an arrester during the passage of
discharge current
NOTE The term "discharge voltage" is used in some countries.
PAS 60099-7 © IEC:2004 (E) – 13 –
3.37
power-frequency withstand voltage versus time characteristic of an arrester
voltage which shows the maximum time durations for which corresponding power-frequency
voltages may be applied to arresters without causing damage or thermal instability, under
specified conditions in accordance with 5.10 of IEC 60099-4
3.38
prospective current of a circuit
current which would flow at a given location in a circuit if it were short-circuited at that
location by a link of negligible impedance
3.39
protective characteristics of an arrester
combination of the following:
a) residual voltage for steep current impulse according to 7.3.1 of IEC 60099-4;
b) residual voltage versus discharge current characteristic for lightning impulses according
to 6.3.2 of IEC 60099-4. The lightning impulse protection level of the arrester is the
maximum residual voltage for the nominal discharge current;
c) residual voltage for switching impulse according to 7.3.3 of IEC 60099-4
The switching impulse protection level of the arrester is the maximum residual voltage at the
specified switching impulse currents.
3.40
thermal runaway of an arrester
term used to describe a situation when the sustained power loss of an arrester exceeds the
thermal dissipation capability of the housing and connections, leading to a cumulative
increase in the temperature of the resistor elements culminating in failure
3.41
thermal stability of an arrester
an arrester is thermally stable if, after an operating duty causing temperature rise, the
temperature of the resistor elements decreases with time when the arrester is energized at
specified continuous operating voltage and at specified ambient conditions
3.42
arrester disconnector
device for disconnecting an arrester from the system in the event of arrester failure, to
prevent a persistent fault on the system and to give visible indication of the failed arrester
NOTE Clearing of the fault current through the arrester during disconnection generally is not a function of the
device.
3.43
type tests (design tests)
tests which are made upon the completion of the development of a new arrester design to
establish representative performance and to demonstrate compliance with the relevant
standard. Once made, these tests need not be repeated unless the design is changed so as
to modify its performance. In such a case only the relevant tests need be repeated
3.44
routine tests
tests made on each arrester, or on parts and materials, as required, to ensure that the
product meets the design specifications
– 14 – PAS 60099-7 © IEC:2004 (E)
3.45
acceptance tests
tests which are made when it has been agreed between the manufacturer and the purchaser
that the arresters or representative samples of an order are to be tested
3.46
housing
external insulating part of an arrester, which provides the necessary creepage distance and
protects the internal parts from the environment
NOTE Housing may consist of several parts providing mechanical strength and protection against the
environment.
3.47
shed
insulating part projecting from the housing, intended to increase the creepage distance
3.48
polymer housed surge arrester
see 3.60
3.49
fault indicator
device intended to provide an indication that the arrester is faulty and which does not
disconnect the arrester from the system
3.50
electrical unit
portion of an arrester in which each end of the unit is terminated with an electrode which is
exposed to the external environment
NOTE An electrical unit is identical to a "unit of an arrester" as defined in 3.6.
3.51
mechanical unit
portion of an arrester in which the resistors within the unit are mechanically restrained from
moving in an axial direction
3.52
gas-insulated metal enclosed surge arrester (GIS-arrester)
gas-insulated metal-enclosed metal-oxide surge arrester without any integrated series or
parallel spark gaps, filled with gas other than air
NOTE 1 The gas pressure is normally higher than 1 bar = 10 Pa.
NOTE 2 A surge-arrester used in gas-insulated switchgear.
3.53
arrester – separable type (separable arrester)
arrester assembled in an insulated or screened housing providing system insulation, intended
to be installed in an enclosure for the protection of distribution equipment and systems.
Electrical connection may be made by sliding contact or by bolted devices; however, all
separable arresters are deadbreak arresters
NOTE Separable arrester use is common European practice.
3.54
arrester – deadfront type (deadfront arrester)
arrester assembled in a shielded housing providing system insulation and conductive ground
shield, intended to be installed in an enclosure for the protection of underground and pad
mounted distribution equipment and circuits
PAS 60099-7 © IEC:2004 (E) – 15 –
NOTE 1 Most deadfront arresters are loadbreak arresters.
NOTE 2 Deadfront arrester use is common U.S.A. practice.
3.55
deadbreak arrester
arrester which can be connected and disconnected from the circuit only when the circuit is de-
energized
3.56
loadbreak arrester
arrester which can be connected and disconnected when the circuit is energized
3.57
arrester – liquid-immersed type (liquid-immersed arrester)
arrester designed to be immersed in an insulating liquid
3.58
fail-open current rating for liquid-immersed arrester
fault current level above which the arrester is claimed to evolve into an open circuit upon
failure
3.59
fail-short current rating for liquid-immersed arrester
fault current level below which the arrester is claimed to evolve into a short circuit upon failure
NOTE Definitions 3.57 and 3.58 are preliminary and may be superseded by more general definitions.
3.60
porcelain housed arrester
arrester using porcelain as housing material, with fittings and sealing systems
3.61
polymer housed arrester
arrester using polymeric and composite materials for housing, with fittings
NOTE Designs with an enclosed gas volume are possible. Sealing may be accomplished by use of the polymeric
material itself or by a separate sealing system.
3.62
bending moment
horizontal force acting on the arrester housing multiplied by the vertical distance between the
mounting base (lower level of the flange) of the arrester housing and the point of application
of the force
3.63
terminal line force
force perpendicular to the longitudinal axis of the arrester measured at the centre line of the arrester
3.64
torsional loading
each horizontal force at the top of a vertical mounted arrester housing which is not applied to
the longitudinal axis of the arrester
3.65
breaking load
force perpendicular to the longitudinal axis of a porcelain housed arrester leading to
mechanical failure of the arrester housing
– 16 – PAS 60099-7 © IEC:2004 (E)
3.66
damage limit
lowest value of a force perpendicular to the longitudinal axis of a polymer housed arrester
leading to mechanical failure of the arrester housing
3.67
maximum permissible service load (MPSL)
greatest force perpendicular to the longitudinal axis of a polymer housed arrester, allowed to
be applied during service without causing any mechanical damage to the arrester
3.68
maximum permissible dynamic service load (MPDSL)
greatest force perpendicular to the longitudinal axis of a porcelain housed arrester, allowed to
be applied during service for short periods (for example, short-circuit current forces, seismic
stress) without causing any mechanical damage to the arrester
3.69
permissible static service load (PSSL)
force perpendicular to the longitudinal axis of a porcelain housed arrester, allowed to be
continuously applied during service without causing any mechanical damage to the arrester
3.70
internal parts
metal-oxide resistor elements with supporting structure
3.71
seal (gas/water-tightness)
ability of an arrester to avoid ingress of matter affecting the electrical and/or mechanical
behaviour into the arrester
4 Surge protective devices connected to low-voltage power distribution
systems – Performance requirements and testing methods (IEC 61643-
1:1998+A1:2001)
4.1
surge protective device (SPD)
device that is intended to limit transient overvoltages and divert surge currents. It contains at
least one non-linear component
4.2
one-port SPD
SPD connected in shunt with the circuit to be protected. A one-port device may have separate
input and output terminals without a specific series impedance between these terminals
4.3
two-port SPD
SPD with two sets of terminals, input and output. A specific series impedance is inserted
between these terminals
4.4
voltage-switching type SPD
SPD that has a high impedance when no surge is present but can have a sudden change in
impedance to a low value in response to a voltage surge. Common examples of components
used as voltage-switching devices are spark gaps, gas tubes, thyristors (silicon-controlled
rectifiers) and triacs. These SPDs are sometimes called "crowbar type"
PAS 60099-7 © IEC:2004 (E) – 17 –
4.5
voltage-limiting type SPD
SPD that has a high impedance when no surge is present, but will reduce it continuously with
increased surge current and voltage. Common examples of components used as non-linear
devices are varistors and suppressor diodes. These SPDs are sometimes called "clamping
type"
4.6
combination type SPD
SPD that incorporates both voltage-switching type components and voltage-limiting type
components may exhibit voltage-switching, voltage-limiting or both voltage-switching and
voltage-limiting behaviour depending upon the characteristics of the applied voltage
4.7
modes of protection
SPDs protective component may be connected line-to-line or line-to-earth or line-to-neutral or
neutral-to-earth and combinations thereof. These paths are referred to as modes of protection
4.8
nominal discharge current I
n
crest value of the current through the SPD having a current waveshape of 8/20. This is used
for the classification of the SPD for class II test and also for preconditioning of the SPD for
class I and II tests
4.9
impulse current I
imp
current defined by a current peak value I and the charge Q and tested according to the
peak
test sequence of the operating duty test. This is used for the classification of the SPD for
class I test
4.10
maximum discharge current I for class II test
max
crest value of a current through the SPD having an 8/20 waveshape and magnitude according
to the test sequence of the class II operating duty test. I is greater than I
max n
4.11
maximum continuous operating voltage U
c
maximum r.m.s. or d.c. voltage which may be continuously applied to the SPDs mode of
protection. This is equal to the rated voltage
4.12
standby power consumption P
c
power consumed by the SPD when energized at the maximum continuous operating voltage
(U ) with balanced voltages and phase angles and no load. The SPD is connected in
c
accordance with the manufacturer's instructions
4.13
follow current I
f
current supplied by the electrical power system and flowing through the SPD after a discharge
current impulse. The follow current is significantly different from the continuous operating
current I
c
4.14
rated load current I
L
maximum continuous rated r.m.s. or d.c. current that can be supplied to a load connected to
the protected output of an SPD
– 18 – PAS 60099-7 © IEC:2004 (E)
4.15
voltage protection level U
p
parameter that characterizes the performance of the SPD in limiting the voltage across its
terminals, which is selected from a list of preferred values. This value shall be greater than
the highest value of the
...