Interpretation sheet 2 - Medical electrical equipment - Part 1: General requirements for basic safety and essential performance

Specifies the outline dimensions of transformers and inductors, using E and I laminations, built for the three most commonly used forms of mounting style, namely bracket mounting, U-clamp mounting and printed wiring board mounting.

Feuille d'interprétation 2 - Appareils électromédicaux - Partie 1: Exigences générales pour la sécurité de base et les performances essentielles

Spécifie les dimensions extérieures des transformateurs et inductances, utilisant des tôles découpées du type E et I, prévues pour les trois formes de montage les plus utilisées, à savoir: le montage sur cornières, le montage à étrier et le montage pour circuits imprimés.

General Information

Status
Published
Publication Date
27-Jan-2009
Current Stage
PPUB - Publication issued
Start Date
30-Mar-2009
Completion Date
28-Jan-2009
Ref Project

Relations

Buy Standard

Standard
IEC 60601-1:2005/ISH2:2009 - Interpretation sheet 2 - Medical electrical equipment - Part 1: General requirements for basic safety and essential performance Released:1/28/2009
English and French language
10 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


– 1 –
Publication IEC 60601-1 (Third edition – 2005) I-SH 02

MEDICAL ELECTRICAL EQUIPMENT –

Part 1: General requirements for basic safety
and essential performance
INTERPRETATION SHEET 2
This interpretation sheet has been prepared by subcomittee 62A: Common aspects of
electrical equipment used in medical practice, of IEC technical committee 62: Electrical
equipment in medical practice.
The text of this interpretation sheet is based on the following documents:
ISH Report on voting
62A/634/ISH 62A/640/RVD
Full information on the voting for the approval of this interpretation sheet can be found in the
report on voting indicated in the above table.
_____________
Subclause 11.3
This subclause is clarified by the following:
As stated in the rationale for this subclause, fire ENCLOSURES are intended to be used only
where there is a significant likelihood of fire due to the presence of a source of ignition (as
described in the subclause) and a significant source of fuel. Most materials used in the
construction of ME EQUIPMENT are not considered to be such a source of fuel unless they are
in the presence of an OXYGEN RICH ENVIRONMENT. MANUFACTURERS should determine, through
analyses documented in the RISK MANAGEMENT FILE, whether the ME EQUIPMENT contains
combustible materials (fuel) in sufficient quantities to support combustion in conjunction with
ignition sources (capable of releasing greater than 900 J).
Subclause 13.1.2
This subclause is clarified by the following:
As stated in subclause 4.7, it is the MANUFACTURER’S RISK ANALYSIS that determines which
components are subject to failure testing based on the associated RISK. Where the associated
RISK of fire exceeds the MANUFACTURER’S criteria for RISK acceptability, the MANUFACTURER’S
simulation analysis (such as FMEAs) should be accepted in lieu of physical testing. As also
stated in 4.7, component reliability and ratings are to be considered in such failure simulation
analyses. Common electronic components that have a history of use without causing
equipment fires should not be considered a likely source of ignition.
Where the subclause identifies “emission of flames, molten metal, poisonous or ignitable
substance in hazardous quantities;” as a hazardous situation, this refers to emissions from
the ENCLOSURE not from components themselves. Where it identifies “exceeding the allowable
values for ‘other components and materials’ identified in Table 22 times 1,5 minus 12,5 °C”,
this applies only where doing so would result in an unacceptable RISK (as identified in the
MANUFACTURER’S RISK ANALYSIS according to 4.7). Typically, this would be cases where
January 2009 ICS 11.040 French text overleaf

– 2 –
ESSENTIAL PERFORMANCE would not be maintained or where greater than 900 J of energy
would be released in the presence of flammable materials that could sustain combustion.
The first exemption to fault analysis or testing identified in subclause 13.1.2 (“The
construction or the supply circuit limits the power dissipation in SINGLE FAULT CONDITION to less
than 15 W or the energy dissipation to less than 900 J.”) is intended to apply where the
component design itself (“The construction”) or fusing (or other current limiting devices) in the
supply circuit (“or the supply circuit”) assure the energy released during failures will not
exceed the limits. For most common signal level components rated for operation below
5 Watts, the energy released by short-circuiting of outputs will not exceed the 900 J limit.
This clarification will remain valid until a new version of IEC 60601-1 is published.

___________
January 2009 ICS 11.040 French text overleaf

– 3 –
Publication CEI 60601-1 (Troisième édition – 2005) I-SH 02

APPAREILS ÉLECTROMÉDICAUX –
Partie 1: Exigences générales pour la sécurité de base et
les performances essentielles
FEUILLE D'INTERPRÉTATION 2
La présente feuille d'interprétation a été établie par le sous-comité 62A: Aspects généraux
des équipements électriques utilisés en pratique méd
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.