IEC 61000-6-5:2015/COR1:2017
(Corrigendum)Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment
Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment
Corrigendum 1 - Compatibilité électromagnétique (CEM) - Partie 6-5: Normes génériques - Immunité pour les équipements utilisés dans les environnements de centrales électriques et de postes
General Information
Relations
Standards Content (Sample)
IEC 2017
INTERNATIONAL ELECTROTECHNICAL COMMISSION
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
IEC 61000-6-5 IEC 61000-6-5
Edition 1.0 2015-08 Édition 1.0 2015-08
Electromagnetic compatibility (EMC) – Compatibilité électromagnétique (CEM) –
Part 6-5: Generic standards Partie 6-5: Normes génériques
– Immunity for equipment used in – Immunité pour les équipements utilisés dans
power station les environnements
and substation environment de centrales électriques et de postes
CORRIGENDUM 1
Corrections to the French version appear after the English text.
Les corrections à la version française sont données après le texte anglais.
Table 5 – Immunity specifications – Power station – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 3.5 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
– 2 – IEC 61000-6-5:2015/COR1:2017
IEC 2017
Table 6 – Immunity specifications – Power station – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c
”
power supply
Replace in test 4.6 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 4.6 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
Table 9 – Immunity specifications – Substation – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface types 2, 3 and 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
IEC 2017
Table 10 – Immunity specifications – Substation – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c
”
power supply
Replace in test 4.6 for int
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.