Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment

Corrigendum 1 - Compatibilité électromagnétique (CEM) - Partie 6-5: Normes génériques - Immunité pour les équipements utilisés dans les environnements de centrales électriques et de postes

General Information

Status
Published
Publication Date
06-Dec-2017
Drafting Committee
WG 13 - TC 77/WG 13
Current Stage
PPUB - Publication issued
Start Date
07-Dec-2017
Completion Date
27-Dec-2017

Relations

Effective Date
05-Sep-2023
Effective Date
05-Sep-2023
Standard

IEC 61000-6-5:2015/COR1:2017 - Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment Released:12/7/2017

English and French language
1 pages
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

TL 9000 QuEST Forum

Telecommunications quality management system.

ANAB United States Verified

ANCE

Mexican certification and testing association.

EMA Mexico Verified

Intertek Slovenia

Intertek testing, inspection, and certification services in Slovenia.

UKAS Slovenia Verified

Sponsored listings

Frequently Asked Questions

IEC 61000-6-5:2015/COR1:2017 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment". This standard covers: Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment

Corrigendum 1 - Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment

IEC 61000-6-5:2015/COR1:2017 is classified under the following ICS (International Classification for Standards) categories: 33.100.20 - Immunity. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61000-6-5:2015/COR1:2017 has the following relationships with other standards: It is inter standard links to IEC 61000-6-5:2015, IEC TS 61000-6-5:2001. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 61000-6-5:2015/COR1:2017 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


 IEC 2017
INTERNATIONAL ELECTROTECHNICAL COMMISSION
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
IEC 61000-6-5 IEC 61000-6-5
Edition 1.0  2015-08 Édition 1.0  2015-08

Electromagnetic compatibility (EMC) – Compatibilité électromagnétique (CEM) –
Part 6-5: Generic standards Partie 6-5: Normes génériques
– Immunity for equipment used in – Immunité pour les équipements utilisés dans
power station les environnements
and substation environment de centrales électriques et de postes

CORRIGENDUM 1
Corrections to the French version appear after the English text.
Les corrections à la version française sont données après le texte anglais.

Table 5 – Immunity specifications – Power station – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 3.5 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
– 2 – IEC 61000-6-5:2015/COR1:2017
 IEC 2017
Table 6 – Immunity specifications – Power station – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c

power supply
Replace in test 4.6 for interface type 3:
“0,5 kV
(differential mode,
10 MHz)”
by:
“1 kV
(common mode,
10 MHz)”
Replace in test 4.6 for interface type 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
Table 9 – Immunity specifications – Substation – Low voltage a.c. input and output
power ports
Replace in test 3.5 for interface types 2, 3 and 4:
“1 kV
(differential mode,
10 MHz)”
by:
“2 kV
(common mode,
10 MHz)”
 IEC 2017
Table 10 – Immunity specifications – Substation – Low voltage d.c. input and output
power ports
Replace in test 4.5:
“Ripple on d.c.
power supply”
by:
“Ripple on d.c.
c

power supply
Replace in test 4.6 for int
...