General Information

Abstract

IEC 62621:2011 specifies characteristics for composite insulators of electric traction overhead contact line systems for railways, as defined in IEC 60913. Insulators specified in this standard are applied for electric traction supply voltages with a nominal voltage greater than 1 000 V for a.c. or a nominal voltage greater than 1 500 V for d.c.. The standard establishes the product characteristics, the test methods and acceptance criteria.

Status
Published
Publication Date
28-Jun-2011
Drafting Committee
PT 62621 - TC 9/PT 62621
Current Stage
PPUB - Publication issued
Start Date
29-Jun-2011
Completion Date
31-Jul-2011

Buy Documents

Standard

IEC 62621:2011 - Railway applications - Fixed installations - Electric traction - Specific requirements for composite insulators used for overhead contact line systems Released:6/29/2011

ISBN:978-2-88912-569-2
English and French language (55 pages)
sale 15% off
Preview
sale 15% off
Preview

Overview

IEC 62621:2011 establishes the specific requirements for composite insulators used in railway applications, particularly for fixed installations and electric traction overhead contact line systems. Developed by the International Electrotechnical Commission (IEC), this international standard addresses the unique challenges faced by insulators in railway environments, such as exposure to pollution, vandalism, mechanical stress, and variable weather conditions. IEC 62621:2011 applies to insulators used on systems with electric traction supply voltages exceeding 1,000 V (AC) or 1,500 V (DC), ensuring reliable performance under these demanding conditions. By specifying product characteristics, test methods, and acceptance criteria, the standard supports safe operation and long service life for overhead contact line systems.

Key Topics

IEC 62621:2011 covers several essential aspects of composite insulators for railway overhead contact lines:

  • Composite Insulator Definition: Clarifies that a composite insulator consists of a core, housing, and end fittings, and is distinct from other polymeric insulators.
  • Environmental Conditions: Establishes criteria to address issues such as temperature extremes, humidity, industrial pollution, mechanical vibrations, and UV radiation. Special attention is given to pollution accumulation in tunnels and bridges, areas not exposed to natural rainfall.
  • System Voltage Compatibility: Provides guidance for matching insulator performance to system voltages and frequencies, referencing standard values per IEC 60850.
  • Creepage Distance and Pollution Protection: Specifies minimum creepage distances based on voltage and pollution severity, with increased requirements for challenging environments.
  • Mechanical and Electrical Performance: Outlines mechanical requirements such as tension and bending loads, safety factors, and protection against corrosion and fire hazards.
  • Tracking, Erosion, and Arc Protection: Identifies the importance of surface resistance to tracking and erosion, and details arc protection measures for metal fittings.
  • Testing and Compliance: Defines comprehensive testing regimes, including design, type, sample, and routine tests to verify the reliability and suitability of composite insulators.

Applications

The practical value of IEC 62621:2011 lies in enhancing the performance and safety of electric railway networks. Key applications include:

  • New Overhead Line Installations: Ensures that newly designed and constructed electrified lines use insulators that meet strict international requirements for durability and compatibility.
  • System Upgrades and Refurbishments: Provides benchmarks and acceptance criteria when upgrading or fully refurbishing existing overhead contact line systems.
  • In-Running Insulator Solutions: Facilitates the application of insulators capable of withstanding direct contact with pantographs, supporting both electrical separation and mechanical robustness.
  • Challenging Environments: Addresses critical needs for installations in polluted urban areas, under bridges, within tunnels, and in regions with high vandalism risk or harsh environmental conditions.
  • Safety and Maintenance: Helps railway operators minimize maintenance requirements and maximize system uptime, ensuring reliable insulation and mechanical integrity in overhead systems.

Related Standards

To ensure comprehensive compliance and up-to-date best practices, IEC 62621:2011 references several important international standards, including:

  • IEC 60913 - Electric traction overhead lines
  • IEC 61109 - Composite suspension and tension insulators for a.c. systems
  • IEC 61952 - Composite line post insulators for a.c. systems
  • IEC 62217 - Polymeric insulators: definitions, test methods, acceptance criteria
  • IEC 62497-1 - Insulation coordination for railway applications
  • IEC 60826 - Design criteria of overhead transmission lines
  • IEC 60850 - Supply voltages of traction systems
  • ISO 34-1 / ISO 37 - Mechanical property tests for rubber and thermoplastic components

IEC 62621:2011 provides a unified approach for specifying, testing, and applying composite insulators, supporting world-class safety, reliability, and efficiency in railway electrification projects. This standard is essential for manufacturers, system designers, and operators seeking to ensure compliance and resilience in challenging operational environments.

Buy Documents

Standard

IEC 62621:2011 - Railway applications - Fixed installations - Electric traction - Specific requirements for composite insulators used for overhead contact line systems Released:6/29/2011

ISBN:978-2-88912-569-2
English and French language (55 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IRIS Certification (UNIFE)

International Railway Industry Standard certification.

BELAC Belgium Verified

TÜV SÜD Rail GmbH

TÜV SÜD railway certification services.

DAKKS Germany Verified

Bureau Veritas Railway Certification

Railway and transportation certification.

COFRAC France Verified

Sponsored listings

Frequently Asked Questions

IEC 62621:2011 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Railway applications - Fixed installations - Electric traction - Specific requirements for composite insulators used for overhead contact line systems". This standard covers: IEC 62621:2011 specifies characteristics for composite insulators of electric traction overhead contact line systems for railways, as defined in IEC 60913. Insulators specified in this standard are applied for electric traction supply voltages with a nominal voltage greater than 1 000 V for a.c. or a nominal voltage greater than 1 500 V for d.c.. The standard establishes the product characteristics, the test methods and acceptance criteria.

IEC 62621:2011 specifies characteristics for composite insulators of electric traction overhead contact line systems for railways, as defined in IEC 60913. Insulators specified in this standard are applied for electric traction supply voltages with a nominal voltage greater than 1 000 V for a.c. or a nominal voltage greater than 1 500 V for d.c.. The standard establishes the product characteristics, the test methods and acceptance criteria.

IEC 62621:2011 is classified under the following ICS (International Classification for Standards) categories: 45.060.01 - Railway rolling stock in general. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 62621:2011 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


IEC 62621 ®
Edition 1.0 2011-06
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Railway applications – Fixed installations – Electric traction – Specific
requirements for composite insulators used for overhead contact line systems

Applications ferroviaires – Installations fixes – Traction électrique – Exigences
particulières pour les isolateurs composites destinés aux réseaux de lignes
aériennes de contact
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
 Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
 IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
 Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
 Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
 Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
 Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
 Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
 Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 62621 ®
Edition 1.0 2011-06
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Railway applications – Fixed installations – Electric traction – Specific
requirements for composite insulators used for overhead contact line systems

Applications ferroviaires – Installations fixes – Traction électrique – Exigences
particulières pour les isolateurs composites destinés aux réseaux de lignes
aériennes de contact
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX U
ICS 45.060 ISBN 978-2-88912-569-2

– 2 – 62621 © IEC:2011
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
1 Scope . 6
2 Normative references. 6
3 Terms and definitions . 7
4 Characteristics of composite insulators for overhead contact line systems . 8
4.1 General . 8
4.2 Environmental conditions . 8
4.3 System voltages and frequencies . 9
4.4 Creepage distance . 9
4.5 Mechanical requirements . 10
4.6 Corrosion . 11
4.7 Fire safety . 11
4.8 Tracking and erosion . 11
4.9 Arc protection . 11
4.10 In-running insulators . 12
5 Testing . 12
5.1 General . 12
5.2 Design tests . 12
5.3 Type tests . 14
5.3.1 General . 14
5.3.2 Electrical tests . 14
5.3.3 Mechanical tests . 14
5.3.4 Verification of dimensions . 14
5.4 Sample tests . 15
5.5 Routine tests . 15
6 Identification . 15
7 Transport, storage, installation and maintenance . 15
Annex A (informative) Purchaser requirements . 16
Annex B (informative) Principles of the damage limit, load coordination and testing . 17
Annex C (informative) Guidance on non-standard mechanical stresses and dynamic
mechanical loading . 21
Annex D (informative) Determination of the equivalent bending moment caused by
combined loads . 23
Bibliography . 26

Figure B.1 − Load-time strength and damage limit of a core assembled with fittings . 18
Figure B.2 – Graphical representation of the relationship of the damage limit to the
mechanical characteristics and service loads of an insulator with a 16 mm diameter
core . 19
Figure B.3 – Test loads . 20
Figure D.1 – Combined loads applied to unbraced insulators . 24

Table 1 – Definition of relevant mechanical characteristics according to insulator type . 10
Table 2 – Design tests . 13

62621 © IEC:2011 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
RAILWAY APPLICATIONS –
FIXED INSTALLATIONS –
ELECTRIC TRACTION –
SPECIFIC REQUIREMENTS FOR COMPOSITE INSULATORS
USED FOR OVERHEAD CONTACT LINE SYSTEMS

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62621 has been prepared by IEC technical committee 9: Electrical
equipment and systems for railways.
This standard is based on EN 50151:2003.
The text of this standard is based on the following documents:
FDIS Report on voting
9/1539/FDIS 9/1560/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

– 4 – 62621 © IEC:2011
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
The committee has decided that the contents of this publication will remain unchanged until the
stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data related to
the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
62621 © IEC:2011 – 5 –
INTRODUCTION
This standard specifies requirements for the design and testing of composite insulators used
on railway electric traction overhead contact line systems. Such insulators, which are installed
at relatively low heights in the harsh environment of railway infrastructures, require specific
considerations during design to reduce the effects of vandalism and environmental pollution
from railway operations, especially when combined with a lack of natural washing. Insulators
may be included in arrangements in tunnels and over bridges or be in contact with traction unit
pantographs where combined mechanical loading (tension, bending and torsion) may require
special consideration.
The standard is intended to allow the manufacturer to comply with local working practices, to
ensure compatibility with existing electric traction overhead contact line systems, and provide
an insulator which will give reliable service over its target life span with minimum maintenance.
Insulators intended for overhead lines are predominately designed to resist tension and/or
bending loads and are not designed to resist torsional loads. Mitigating measures to reduce
torsional loading are generally introduced by the overhead contact lines design engineer. Some
combined loading (tension, compression and torsion) can be experienced and this is
represented in the testing procedure specified in this document.
The testing procedures given for railway applications in this standard are predominately
referenced from IEC 61109, IEC 61952 and IEC 62217.

– 6 – 62621 © IEC:2011
RAILWAY APPLICATIONS –
FIXED INSTALLATIONS –
ELECTRIC TRACTION –
SPECIFIC REQUIREMENTS FOR COMPOSITE INSULATORS
USED FOR OVERHEAD CONTACT LINE SYSTEMS

1 Scope
This International Standard specifies characteristics for composite insulators of electric traction
overhead contact line systems for railways, as defined in IEC 60913. Insulators specified in this
standard are applied for electric traction supply voltages with a nominal voltage greater than
1 000 V for a.c. or a nominal voltage greater than 1 500 V for d.c. Specific applications where
high torsional loads can occur are outside the scope of this standard and particular tests are
agreed between the supplier and customer to represent the critical loading arrangements.
This International Standard applies to composite insulators as defined in 3.1 below and not to
other polymeric insulators.
The provisions contained in this standard are intended for the design and construction of new
electric traction overhead contact line systems using insulators, or when complete
refurbishment of existing overhead contact line systems takes place.
This standard provides the purchaser and manufacturer with a range of tests which are used to
evaluate the suitability of an insulator product for a given railway environment. Additional tests
may be specified by the client to measure the compliance of the insulator under particular
operating conditions.
The standard establishes the product characteristics, the test methods and acceptance criteria.
The object of this standard is to stipulate the provisions for the design and provision of the
service indicated by the manufacturer to the customer or informed buyer for application on the
railway infrastructure.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
IEC 60587, Electrical insulating materials used under severe ambient conditions – Test
methods for evaluating resistance to tracking and erosion
IEC 60815-1:2008, Selection and dimensioning of high-voltage insulators intended for use in
polluted conditions – Part 1: Definitions, information and general principles
IEC 60815-3:2008, Selection and dimensioning of high-voltage insulators intended for use in
polluted conditions – Part 3: Polymer insulators for a.c. systems
IEC 60826, Design criteria of overhead transmission lines
IEC 60850:2007, Railway applications – Supply voltages of traction systems

62621 © IEC:2011 – 7 –
IEC 60913, Electric traction overhead lines
IEC 61109:2008, Insulators for overhead lines – Composite suspension and tension insulators
for a.c. systems with a nominal voltage greater than 1 000 V – Definitions, test methods and
acceptance criteria
IEC 61467:2008, Insulators for overhead lines – Insulator strings and sets for lines with a
nominal voltage greater than 1 000 V – AC power arc tests
IEC 61952:2008, Insulators for overhead lines – Composite line post insulators for A.C.
systems with a nominal voltage greater than 1 000 V – Definitions, test methods and
acceptance criteria
IEC 62217:2005, Polymeric insulators for indoor and outdoor use with a nominal voltage
> 1 000 V – General definitions, test methods and acceptance criteria
IEC 62497-1:2010, Railway applications – Insulation cordination – Part 1: Basic requirements
Clearances and creepage distances for all electrical and electronic equipment
ISO 34-1, Rubber, vulcanized or thermoplastic- determination of tear strength – Part 1: Trouser,
angle and crescent test pieces
ISO 37, Rubber, vulcanized or thermoplastic – Determination of tensile stress-strain properties
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
NOTE Certain terms from IEC 62217:2005 are reproduced here for ease of reference. Additional definitions
applicable to insulators can be found in IEC 60050-471[1] , IEC 61109:2008 and IEC 61952:2008.
3.1
composite insulator
insulator made of at least two insulating parts, namely a core and a housing equipped with end
fittings
NOTE Composite insulator, for example, can consist either of individual sheds mounted on the core, with or
without an intermediate sheath, or alternatively, of a housing directly moulded or cast in one or several pieces on to
the core.
3.2
nominal design load
load, specified by the customer, corresponding to the normal everyday permanent and dynamic
loads
___________
Figures in square brackets refer to the bibliography.

– 8 – 62621 © IEC:2011
4 Characteristics of composite insulators for overhead contact line systems
4.1 General
Composite materials and polymers permit the manufacture of insulators for use on outdoor
overhead contact line systems. The insulators consist of an insulating core which bears the
mechanical load, a polymeric housing which protects the core, and end fittings by which the
load is transmitted to the core. These materials allow special applications in overhead contact
line systems (including in-running section insulation and flexible supports) and are also used
for their advantages of lightness, resistance to vandalism and pollution performance. Despite
many common features of design, the materials used and the construction details employed by
different manufacturers may be quite different and may lead to different performance
parameters.
Electric traction overhead contact line systems applied for railways have several characteristics
not associated with power lines. They are of low height and run through urban areas, making
them targets for vandalism. They are incorporated in bridges and tunnels, built for rolling stock
only, and fit into small spaces. They suffer close proximity to railway generated pollution and, in
tunnels and bridges are not washed by natural rainfall. They suffer movement and snatch loads
due to normal pantograph contact with the wires. When used as in-running insulators, they
suffer mechanical forces and abrasion by the pantograph passing at high speed where the
polymeric housing may suffer deformation, tearing and parting from the core (see 4.10).
Some tests have been grouped together in this standard as “design tests”, to be performed
only once on insulators which satisfy the same design conditions. As far as practical, the
influence of time, circumstance and climate on electrical and mechanical properties of the
components (core material, housing, interfaces etc.) and of the complete composite insulators
has been considered in specifying the design tests so that a satisfactory life-time may be
expected under normally known stress conditions of overhead contact line systems.
The high number of insulators installed in a restricted environment of an operational railway
with limited access for maintenance or installed in harsh environmental conditions, requires a
high level of reliability at the appropriate electrical insulation level for the system voltage,
including temporary and transient overvoltages, and a high level of mechanical integrity. In this
case, a reasonable safety factor for mechanical and electrical properties of the insulators shall
be agreed between the manufacturer and customer.
4.2 Environmental conditions
Environmental conditions such as temperature, humidity, vibration, solar radiation, pollution,
etc., can have serious effects on the electrical and mechanical properties of insulators. The
aging of housing material and interfaces, exposure of the core to environment and the
corrosion of end fittings shall be given special consideration. When used for lower temperature,
the behaviour or brittle property of the housing material and interfaces shall be considered.
NOTE When temperature falls below the crystallisation or glass transition temperature of the housing, its elasticity
becomes lost. This change is reversible if a temperature increase takes place.
The normal environmental conditions to which insulators are submitted in service are defined in
IEC 62217:2005.
Since the insulators are intended for outdoor use and may be installed in harsh environmental
conditions, pollution shall be considered. The pollution degrees are defined in Table A.4 of
IEC 62497-1:2010.
62621 © IEC:2011 – 9 –
4.3 System voltages and frequencies
System voltages and frequencies specified by IEC 60850:2007 are generally applied for this
standard. Values of standard system voltages (phase to ground) and the correlation between
nominal voltages of the railway power distribution system and the required insulation voltages
for circuits of equipment which are intended to be connected to these systems are shown in
Table 1 of IEC 60850:2007.
The purchaser shall provide information on the railway electrification system and operating
requirements which may affect the design of insulators.
NOTE Purchaser requirements are given in Annex A.
The dry lightning impulse withstand voltage shall be at least equal to the rated impulse voltage
defined in IEC 62497-1:2010. The wet power frequency withstand voltage shall be at least
equal to the short duration power frequency test level defined in IEC 62497-1:2010.
The rated impulse voltage for circuits powered by electric traction contact lines are shown in
Table A.2 of IEC 62497-1:2010. Overhead lines are considered a case of inherent control. The
rated insulation level is based on statistical and risk considerations. Therefore the rated
impulse voltage is chosen among the preferred values given in Table A.2 of IEC 62497-1:2010,
but irrespective of the correspondence with the insulation voltages and of the overvoltage
levels stated in said table.
Table A.2 of IEC 62497-1:2010 is based on the worst dielectric conditions of electrodes. In
overhead lines, different conditions are present and by consequence different clearances given
in established standards or regulations such as IEC 60913 are allowed.
4.4 Creepage distance
The dry arcing distance, creepage distance and geometrical shed profile electrically define an
insulator. Creepage distances shall be dimensioned according to the highest permanent
voltage of the system. Consideration shall also be given to the insulation material and its
behaviour in polluted conditions. The manufacturer may recommend greater than the minimum
creepage distance to give adequate life for that material.
The overall shape and size of the insulator is defined by the customer’s spatial requirements,
the mechanical and electrical performance requirements and its compatibility with existing
equipment. The manufacturer can decide on shed profile.
Additional railway environmental pollution may be generated by traction braking systems, diesel
and steam trains which run under electrified lines. The exhaust from steam trains is very hot
(> 200 °C) and should not be allowed to play on insulators. This can be prevented by careful
positioning of insulators on the line or by a restriction on train movements and stopping
positions. The exhaust from diesel trains is less severe, but contains oil and carbonaceous
deposits, which can contaminate insulators. No additional creepage is necessary for diesel
usage but it is important to ensure that the diesel exhaust does not dwell on the insulators by
checking stopping positions etc.
Insulators positioned under bridges and in tunnels are not washed by natural rainfall which can
lead to pollution accumulation. In these harsh environmental conditions and in order to
minimise the degradation of the housing material, the creepage distance and the design need
to cover the specific application. This will also be particularly applicable to insulators which are
used in contact with the pantograph collector unit and which may require increased creepage
distance to allow for the width of the pantograph (see 4.10).

– 10 – 62621 © IEC:2011
Operating conditions and pollution level are specified in Table A.4 of IEC 62497-1:2010.
Dimensioning of creepage distance versus rated insulation voltage, as given in
IEC 62497-1:2010, is as follows:
– normal operating conditions: 24 mm/kV to 33 mm/kV;
– unfavourable operating conditions: 36 mm/kV to 40 mm/kV;
– extremely unfavourable operating conditions: > 48 mm/kV.
NOTE 1 Normal operating conditions exist when there is low industrial pollution, a low population density and no
thermal engines.
NOTE 2 Unfavourable operating conditions exist when there is high industrial pollution and industrial gases, a high
population density, mixed railway operation, road traffic and frequent fog.
NOTE 3 Extremely unfavourable operating conditions exist when large power plants, chemical industry, smelting
works near the ocean with frequent fog are close by.
NOTE 4 Clearances and creepage distances may be reduced by agreement between customer and supplier or in
product standards.
Composite insulators present certain advantages over ceramic and glass insulators due to their
form and materials. These advantages include a generally improved pollution withstand
behaviour when compared to similar ceramic or glass insulators of equal creepage distance;
this improvement is even more enhanced by use of hydrophobicity transfer material (HTM). In
principle and purely from a pollution withstand or flashover point of view, it can thus be
concluded that a reduced creepage distance may be used for such insulators. However,
compared to traditional insulating materials, polymer materials are more susceptible to
degradation by the environment, electric fields and arc activity which may, in certain conditions,
reduce insulator pollution performance or lifetime. Subclause 9.4 of IEC 60815-1:2008 gives
the considerations and Subclause 5.2 of IEC 60815-3:2008 gives issues specific to reduction of
creepage distance for polymeric housing materials.
For d.c. system voltages, some insulation may require a somewhat higher value of unified specific
creepage distance compared to a.c. insulation under the same conditions.
NOTE 5 This effect will be dealt with in detail in a forthcoming part of IEC 60815 for d.c. systems.
4.5 Mechanical requirements
The withstand loads defined by the manufacturer shall take into account the characteristics
shown in Table 1.
Table 1 – Definition of relevant mechanical characteristics according to insulator type
Type of insulator Mechanical characteristics Definitions
Stressed mainly in tension SML (specified mechanical load) According to IEC 61109:2008
/RTL (routine test load)
Stressed mainly in bending SCL (specified cantilever load) According to IEC 61952:2008
/MDCL (maximum design cantilever
load) /STL (specified tensile load)
/RTL (routine test load)
In all cases, the maximum working load (static and dynamic) shall be below the damage limit of
the insulator. It is normal practice to adopt a safety factor of at least 2,5 between the SML and
the maximum working load; this generally ensures that there is also a sufficient margin
between the damage limit of the insulator and all service loads. IEC 60826 and IEC 60913 give
guidance for calculation of loads and application of proper safety factors.
NOTE The MDCL may additionally be adjusted by any angular deflection criteria or bending deflection defined in
the client requirements.
62621 © IEC:2011 – 11 –
4.6 Corrosion
The end fittings shall be suitably protected from corrosion and be electrochemically compatible
with interface connections. Particular attention shall be made to the protection of the end
fittings and connecting zone sealing against moisture ingress, chemical activity or degradation
under temperature variations or unidirectional current flow.
4.7 Fire safety
The composite insulators shall not exhibit sustained self ignition, such as when subjected to a
power arc test. The location, maintenance, creepage distance and overvoltage protection shall
be chosen to minimise the possibility of a power arc flashover.
When used in particular environments or applications, particularly in tunnels and station areas,
composite insulators may be required to have safety behaviour in terms of flammability, smoke
emission and toxicity.
Flammability tests are intended to verify the housing material for ignition, flame propagation
and self-extinguishing properties. Flammability requirements are defined in the testing
requirements (see Clause 5).
Smoke emission tests are intended to identify the opacity of the smoke emission when the
insulator material burns.
Toxicity tests are intended to verify the toxicity of the smoke emission when the insulator
material burns.
4.8 Tracking and erosion
Surface damage may arise in severe environmental conditions due to surface leakage currents
and partial arcing.
Tracking and erosion tests are given in IEC 62217:2005. These tests are better described as
screening tests, which can be used to reject materials, or designs, which are inadequate.
NOTE 1 For further information, refer to Annex C of IEC 62217:2005 and CIGRE Technical Brochure No. 142: “Natural and
artificial ageing and pollution testing of polymeric insulators”, June 1999 [2].
NOTE 2 A review of the representativity, repeatability and reproducibility of ageing tests is under consideration
and guidance will be given in the future in a new Technical Report prepared by IEC TC 36. In the meantime, it is
recommended that particular care should be taken when specifying the type and parameters of such tests.
4.9 Arc protection
The heating effect of power arcs shall be considered in the design of metal fittings. Critical
damage to the metal fittings resulting from the magnitude and duration of the short-circuit
current can be avoided by properly designed arc-protection devices.
It has not been considered useful to specify a power arc test as a mandatory test for
suspension/tension and post insulators. The test parameters are manifold and can have very
different values depending on the configurations of the network and the supports and on the
design of arc-protection devices. This standard, however, does not exclude the possibility of a
power arc test by agreement between the manufacturer and customer.
IEC 61467:2008 gives details of a.c. power arc testing of insulator sets and tests for sustained
ignition.
In-running insulator arrangements regularly receive power arcs and the full insulating assembly
shall be power arc tested (see 4.10).

– 12 – 62621 © IEC:2011
4.10 In-running insulators
In railway applications, it is essential to divide the overhead contact lines into discrete electrical
sections. This requires breaks or insulators in the contact wire, on which the traction
pantograph runs. Composite insulators can provide versatile section insulators with a small
mass to minimise pantograph impacts and damage.
Insulators in the overhead contact lines which are designed to work in contact with the traction
pantograph unit require additional creepage distances depending upon the pantograph width,
system voltage and operating speed. The requirements for insulation length may exceed the
values in this standard and shall be agreed separately between the supplier and purchaser.
If the insulator surface wears, it may not accumulate pollution and testing for pollution deposits
may not be required. Alternatively if the surface does not wear, pollution can build up from the
pantograph strips, which could lead to flashover or surface degradation. This shall be borne in
mind when designing the insulators and drafting maintenance instructions or determining life
cycle costs.
In-running insulator arrangements regularly receive power arcs and the full insulating assembly
shall be power arc tested on the basis of Clause 8 of IEC 61467:2008 or by a field test
according to IEC 60913. In order to remove power arcs from insulators, arc extinguishing horn
gaps may be used.
Testing shall be in accordance with the requirements defined in Clause 5.
5 Testing
5.1 General
All tests, appropriate to the design requirements of the insulator, shall be undertaken in
accordance with current recognised international standards, such as IEC 61109:2008 which
applies for composite suspension/tension insulators, or IEC 61952:2008 which applies for
composite line post insulators.
For use in special environments, test conditions shall be agreed between manufacturer and
purchaser.
5.2 Design tests
These tests are intended to verify the suitability the design, materials and method of
manufacture (technology). A manufacturer is likely to have a family of composite insulator
designs which are defined by:
– materials of the core, housing and manufacturing method;
– material of the end fittings, their design and method of attachment;
– layer thickness of the housing over the core;
– diameter of the core.
The parameters of the design insulator shall be identified on the manufacturer’s drawing giving
all dimensional tolerances. Design tests shall be performed according to Table 2.

62621 © IEC:2011 – 13 –
Table 2 – Design tests
Test contents Test methods or standards
Tests on interfaces and connections of end fittings IEC 62217:2005
Pre-stressing IEC 61109:2008 or IEC 61952:2008
Water immersion pre-stressing IEC 62217:2005
Verification tests
– Visual examination
IEC 62217:2005
– Steep-front impulse voltage test
– Dry power-frequency voltage test
Tests on shed and housing material IEC 62217:2005
Hardness test IEC 62217:2005
a
Mechanical properties test
ISO 37
– Tension test (tension strength)
ISO 34-1
– Tear test (tear strength, angle test pieces)
Accelerated weathering test IEC 62217:2005
Housing tracking and erosion test IEC 62217:2005
Fire test IEC 62217:2005
b
IEC 60587
Shed and housing material tracking and erosion test
Tests on the core material IEC 62217:2005
Dye penetration test IEC 62217:2005
Water diffusion test IEC 62217:2005
Assembled core load-time test IEC 61109:2008 or IEC 61952:2008
NOTE Test methods or standards are referred to IEC 62217:2005 for general parts, IEC 61109:2008 for

composite suspension/tension insulators and IEC 61952:2008 for composite post insulators.
a
The range of the tension strength and the tear strength can be agreed between customer and supplier.
b
The test method, end-point criteria and classification of the material can be agreed between customer and
supplier.
When a composite insulator is submitted to the design tests, it becomes a parent insulator for a
design class and the results shall be considered valid for the whole class. This tested parent insulator
defines a design of insulators which have the following characteristics:
A: same materials for the core and housing and same manufacturing method;
B: same material for the end fittings, same design and same method of attachment;
C: same or greater minimum layer thickness of the housing over the core (including an
intermediate sheath where used) within a tolerance of 15 %;
D: same or smaller stress under mechanical loads;
E: same or greater diameter of the core;
F: same housing profile parameters within a tolerance of 15 %. For equivalent housing profile
parameters refer to footnote a) in Table 1 of IEC 61109:2008.
As far as practical, the influence of time on the electrical and mechanical properties of the
components (core material, housing, interfaces etc.) and of the complete composite insulators
has been considered in specifying the design tests to ensure a satisfactory life-time under
normally known stress conditions of transmission lines. An explanation of the principles of the
damage limit, load coordination and testing for composite suspension/tension insulators is
presented in Annex B.
– 14 – 62621 © IEC:2011
When changes in the design occur, re-qualification shall be performed according to Table 1 of
IEC 61952:2008 or Table 1 of IEC 61109:2008. If the housing materials or manufacture
process are changed, the mechanical properties test, shed and housing material tracking and
erosion test (see IEC 60587) shall also be repeated.
5.3 Type tests
5.3.1 General
Type tests are intended to verify the characteristics of a composite insulator, which depend
mainly on its shape and size. These tests shall be applied to composite insulators which have
passed the design tests.
Type tests are defined in IEC 61109:2008 for composite suspension/tension insulators and in
IEC 61952:2008 for composite line post insulators.
5.3.2 Electrical tests
An insulator type is defined for electrical testing purposes by the arcing distance, creepage
distance, shed inclination, shed diameter and shed spacing. The electrical type tests shall be
performed only once on insulators satisfying the above criteria for one type. The electrical type
tests shall be repeated only when any of the above characteristics is changed.
5.3.3 Mechanical tests
An insulator type is defined for mechanical testing purposes, by the parameters in Table 1,
core material, core diameter, the method of attachment and coupling design. The mechanical
type tests shall be performed only once on insulators satisfying the above criteria for each type.
The mechanical type tests shall be repeated only when any of the above characteristics are
changed.
Where combined loading (tension, compression or torsion) is expected of the insulator, the
customer shall define the loading conditions and expected duration of loading. The
manufacturer shall calculate the limiting stress on the core defined in Table 1, and to verify this
by type tests in accordance with IEC 61952:2008 "Cantilever failing load test" with the
combined loads applied. Annex B gives the principles of the damage limit, load coordination and
testing.
Where deflection of the insulator is a criteria set by the client, it shall be measured during the
“cantilever failing load test” to confirm the deflection limits are within the customer specification.
5.3.4 Verification of dimensions
If not already routine tested, the insulators shall be examined visually and their conformity with
the drawing shall be checked using the tolerances below.
Unless otherwise agreed, a tolerance of:
– ±(0,04 × d + 1,5) mm when d ≤ 300 mm,
– ± (0,025 × d + 6 ) mm when d > 300 mm with a maximum tolerance of ±50 mm,
shall be allowed on all dimensions for which specific tolerances are not requested (d being the
dimension in millimetres).
The measurement of creepage distance shall be related to the design dimensions and
tolerances as determined from the insulator drawing, even though this dimension may be
greater than the value originally specified by the purchaser. When a minimum creepage
distance is specified by the purchaser, the negative tolerance is also limited by this value.

62621 © IEC:2011 – 15 –
5.4 Sample tests
Sample tests are used to verify characteristics of composite insulators other than those
outlined in 5.2 and 5.3 and include characteristics which depend
...