This European Standard specifies the requirements for factory made products of expanded polystyrene which are used for the thermal insulation of building equipment and industrial installations with an operating temperature range of approximately - 180 °C to + 80 °C. Modified expanded polystyrene polymers with a higher temperature resistance are also covered by this standard.
Below an operating temperature of - 50 °C, special tests regarding the suitability of the product in the intended application are advised (e.g. liquefaction of oxygen). Manufacturers’ advice should be heeded in all cases.
The products are manufactured in the form of faced or unfaced boards, rolls, lags, pipe sections or other prefabricated ware.
This standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling.
Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered.
This standard does not specify the required level or class of a given property that should be achieved by a product to demonstrate fitness for purpose in a particular application. The classes and levels required for a given application can be found in regulations and invitations to tender.
Products with a declared thermal conductivity greater than 0,060 W/(m·K) at 10 °C are not covered by this standard.
This standard does not cover products for in situ insulation (for loose fill or poured insulation) or products for the insulation of the building structure.
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus expandiertem Polystyrol (EPS) - Spezifikation
Diese Europäische Norm legt die Anforderungen an werkmäßig hergestellte Produkte aus expandiertem Polystyrol fest, die als Wärmedämmstoffe für die technische Gebäudeausrüstung und betriebstechnische Anlagen in der Industrie in einem Betriebstemperaturbereich von etwa 180 °C bis +80 °C benutzt werden. Diese Europäische Norm gilt auch für modifizierte expandierte Polystyrol-Polymere mit einem höheren Temperaturwiderstand.
Bei einer Betriebstemperatur unterhalb von −50 °C sind besondere Prüfungen bezüglich der Eignung der Produkte für den beabsichtigten Anwendungsfall ratsam (z. B. Sauerstoffverflüssigung). In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden in Form von kaschierten oder unkaschierten Platten, Rohrschalen, Segmenten und anderen vorgeformten Dämmungen hergestellt.
Diese Europäische Norm beschreibt die Produkteigenschaften und enthält Verfahren zur Prüfung, Konformitätsbewertung, Kennzeichnung und Etikettierung.
Die von dieser Norm abgedeckten Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehrschicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Diese Norm legt für die einzelnen Eigenschaften keine Leistungsstufen oder -klassen fest, die ein Produkt erreichen sollte, um für einen bestimmten Anwendungsfall tauglich zu sein. Die für bestimmte Anwendungen benötigten Stufen und Klassen können Regelwerken oder Ausschreibungen entnommen werden.
Diese Norm gilt nicht für Produkte mit einem Nennwert der Wärmeleitfähigkeit größer als 0,060 W/(m ⋅ K) bei 10 °C.
Diese Norm gilt nicht für Produkte für an der Verwendungsstelle hergestellte Wärmedämmung (eingeblasen oder geschüttet) oder Produkte, die zur Dämmung des Bauwerks bestimmt sind.
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en polystyrène expansé (PSE) - Spécification
La présente Norme européenne spécifie les exigences relatives aux produits manufacturés en polystyrène expansé, utilisés pour l’isolation thermique de l’équipement du bâtiment et des installations industrielles, dont la température de service est approximativement comprise entre - 180 °C et + 80 °C. Des polymères modifiés de polystyrène expansé ayant une résistance accrue à la température sont également couverts par la présente norme.
Pour une température de service inférieure à – 50 °C, des essais particuliers sont recommandés pour s'assurer de l'aptitude à l'emploi du produit dans l'application visée (par exemple, liquéfaction de l'oxygène). Il convient de se référer systématiquement aux conseils du fabricant.
Les produits sont fabriqués sous la forme de panneaux avec ou sans parements, de rouleaux, de segments, de coquilles et autres pièces préfabriquées.
La présente norme décrit les caractéristiques des produits et comporte des modes opératoires d'essai, d'évaluation de conformité, de marquage et d’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans des systèmes préfabriqués d'isolation thermique et dans des panneaux composites ; les performances des systèmes incorporant ces produits ne sont pas traitées.
La présente norme ne spécifie pas le niveau ou la classe requis pour une propriété donnée qu'il convient qu'un produit possède pour démontrer son aptitude à une application particulière. Les classes ou niveaux requis pour une application particulière peuvent être trouvés dans les réglementations et les appels d'offres.
Les produits dont la conductivité thermique déclarée supérieure à 0,060 W/(m·K) à 10 °C ne sont pas couverts par la présente norme.
La présente norme ne couvre pas les produits pour isolation in situ (en vrac ou par déversement) ni ceux destinés à l’isolation de la structure du bâtiment.
Les produits couverts par la présente norme sont également utilisés dans des systèmes préfabriqués d'isolation thermique et dans des panneaux composites ; les performances des systèmes incorporant ces produits ne sont pas traitées.
La présente norme ne spécifie pas le niveau ou la classe requis pour une propriété donnée qu'il convient qu'un produit possède pour démontrer son aptitude à une application particulière. Les classes ou niveaux requis pour une application particulière peuvent être trouvés dans les réglementations et les appels d'offres.
Les produits dont la conductivité thermique déclarée supérieure à 0,060 W/(m.K) à 10 °C ne sont pas couverts par la présente norme.
La présente norme ne couvre pas les produits pour isolation in situ (en vrac ou par déversement) ni ceux destinés à l’isolation de la structure du bâtiment.
Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz ekspandiranega polistirena (EPS) - Specifikacija
Ta evropski standard določa zahteve za proizvode iz ekspandiranega polistirena, ki se uporabljajo za toplotno izolacijo opreme stavb in industrijskih inštalacij z razponom delovne temperature približno od –180 °C do 80 °C. Modificirani polimeri ekspandiranega polistirena z višjo temperaturno odpornostjo so prav tako zajeti v tem standardu. OPOMBA Pod delovno temperaturo –50 °C se priporočajo posebni preskusi glede primernosti proizvoda za predvideno vrsto uporabe (npr. utekočinjenje kisika). V vseh primerih naj bi upoštevali napotke proizvajalca. Proizvodi so izdelani v obliki prevlečenih ali neprevlečenih plošč, kolutov, oblog, vodovodnih odsekov ali druge montažne opreme. Ta standard opisuje lastnosti proizvodov ter zajema postopke za preskušanje, vrednotenje skladnosti, označevanje in etiketiranje. Proizvodi iz tega standarda se uporabljajo tudi v montažnih sistemih toplotne izolacije in vezanih ploščah; lastnosti sistemov iz teh proizvodov niso opisane. Ta standard ne določa zahtevane ravni ali razreda določene lastnosti, ki jo mora proizvod doseči, da se dokaže njegova primernost namenu za posamezno vrsto uporabe. Zahtevane razrede in ravni za posamezno uporabo je mogoče najti v uredbah in javnih razpisih. Proizvodi z deklarirano toplotno prevodnostjo, višjo od 0,060 W/mK pri 10 °C, v tem standardu niso zajeti. Ta standard ne zajema proizvodov za izolacijo na kraju samem (za izolacijo s prostim polnilom ali vlivano izolacijo) ali proizvodov za izolacijo stavbne strukture.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz ekspandiranega polistirena (EPS) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus expandiertem Polystyrol (EPS) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en polystyrène expansé (PSE) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made products of expanded polystyrene (EPS) - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14309:2015SIST EN 14309:2016en,fr,de01-februar-2016SIST EN 14309:2016SLOVENSKI
STANDARDSIST EN 14309:2010+A1:20131DGRPHãþD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14309
December
t r s w ICS
{ sä s r rä x r Supersedes EN
s v u r {ã t r r { ªA sã t r s uEnglish Version
Thermal insulation products for building equipment and industrial installations æ Factory made products of Produits isolants thermiques pour l 5équipement du bâtiment et les installations industrielles æ Produits Spécification
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie æ Werkmäßig hergestellte Spezifikation This European Standard was approved by CEN on
t v October
t r s wä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey andUnited Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
t r s w CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s v u r {ã t r s w ESIST EN 14309:2016
Factory production control . 27 A.1 Indirect testing . 30 Annex B (normative)
Product classification . 34 Annex C (normative)
Determination of minimum service temperature . 35 C.1 Definitions . 35 C.2 Principle . 35 C.3 Apparatus . 35 C.4 Test specimens . 35 C.5 Procedure . 36 C.6 Calculation and expression of results . 36 C.7 Accuracy of measurements . 37 C.8 Test report . 37 Annex D (informative)
Additional properties . 39 D.1 General . 39 D.2 Long-term compressive behaviour . 39 D.3 Shear behaviour . 39 D.4 Water vapour diffusion resistance factor . 40 D.5 Coefficient of thermal expansion . 40 D.6 Behaviour under cyclic loading . 40 D.7 Test methods . 41 D.8 Additional information . 41 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Regulation . 42 ZA.1 Scope and relevant characteristics . 42 ZA.2 Procedures for AVCP of factory made products of expanded polystyrene (EPS) . 44 ZA.3 CE Marking and labelling . 51 Bibliography . 53 SIST EN 14309:2016
is the confidence level — b is the width mm d is the thickness mm Di is the inside diameter mm D is the water vapour permeability mg/(m·h·Pa) dD is the declared thickness of a product mm b is the relative change in width % l is the relative change in length % d is the relative change in thickness % Edyn is the dynamic elasticity modulus MN/m2 k is a factor related to the number of test results available — l is the length mm L is the deviation from linearity mm 90, 90=is the thermal conductivity of 90 % fractile and 90 % confidence level W/(m·K) D is the declared thermal conductivity W/(m·K) i is one test result of thermal conductivity W/(m·K) mean is the mean value of the measured thermal conductivity W/(m·K)
is the water vapour diffusion resistance factor — p is the fractile value (quantile) — a is the apparent density kg/m3 s' is the dynamic stiffness MN/m3 10 is the compressive stress at 10 % deformation kPa b is the bending strength kPa mt is the tensile strength perpendicular to faces kPa Sb s the deviation from squareness mm/m s is the estimate of the standard deviation of the thermal conductivity W/(m·K) Smax is the deviation from flatness mm sR is the estimate of the standard deviation of the thermal resistance (m2·K)/W
is the shear strength kPa SIST EN 14309:2016
Z is the water vapour resistance (m2·h·Pa)/mg BS is the symbol of the declared level for bending strength
CC(i1/i2/y)c is the symbol of the declared level for compressive creep
CL is the symbol of the declared level for water soluble chloride ions
CS(10) is the symbol of the declared level for compressive stress at 10 % deformation
DS(N) is the symbol of the declared class for dimensional stability under normal laboratory conditions
DS(T\L) is the symbol of the declared level for dimensional stability under load and temperature
F is the symbol of the declared level of water soluble fluoride ions
L is the symbol of the declared class for length tolerances
MU is the symbol for the declared water vapour diffusion factor
NA is the symbol of the declared level of water soluble sodium ions
P is the symbol of the declared class for flatness tolerance
pH is the symbol of the declared level for the pH-value
S is the symbol of the declared class for squareness tolerance
SI is the symbol of the declared level of water soluble silicate ions
ST(+) is the symbol of the declared level of maximum service temperature
ST(-) is the symbol of the declared level of minimum service temperature
T is the symbol of the declared class for thickness tolerance
TR is the symbol of the declared level for tensile strength perpendicular to faces
W is the symbol of the declared class for width tolerance
WD(V) is the symbol of the declared level for water absorption by diffusion
WL(T) is the symbol of the declared level for water absorption by total immersion
WS is the symbol of the declared level for short-term water absorption
Z is the symbol of the declared water vapour resistance value
values below 0,1 W/(m·K) and in 0,001 W/(m·K) for
values above 0,1 W/(m·K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as a table derived from the equation, rounding upwards to the next 0,001 W/(m·K) has to be done for the full range of the thermal conductivity. NOTE Determinations of the declared thermal conductivity of pipe sections, following EN ISO 8497, having joints in the metering area, include the effects of these joints as defined in EN ISO 23993. SIST EN 14309:2016
±5 mm/m Pipe section or segment, prefabricated ware ±0,6 % or ± 3 mm a
±2 mm + 2 % or +3 mm ±3 mm/m a Whichever gives the greatest numerical tolerance. 4.2.2.2 Squareness Deviation of squareness, Sb, of boards shall be determined in accordance with EN 824. Deviation of squareness of pipe sections shall be determined in accordance with EN 13467. No test result shall exceed the corresponding tolerance given in Table 1. 4.2.2.3 Flatness Flatness shall be determined in accordance with EN 825 for boards. The deviation from flatness, Smax, shall not exceed 3 mm. 4.2.2.4 Pipe section linearity Linearity shall be determined in accordance with EN 13467 for pipe sections and segments. The deviation from linearity, L, shall not exceed 3 mm. 4.2.3 Dimensional stability 4.2.3.1 Dimensional stability under normal laboratory conditions Dimensional stability under normal laboratory conditions (23 °C, 50 % relative humidity) shall be determined in accordance with EN 1603.The relative changes in length, l, and width, b, shall not exceed the values given in Table 2 for the declared class. Table 2 — Classes of dimensional stability under normal laboratory conditions Classes Requirement % DS(N) 5 ±0,5 DS(N) 2 ±0,2 SIST EN 14309:2016
· 30 CS(10)50
· 50 CS(10)60
· 60 CS(10)70
· 70 CS(10)80
· 80 CS(10)90
· 90 CS(10)100
· 100 CS(10)120
· 120 CS(10)150
· 150 CS(10)200
· 200 CS(10)250
· 250 CS(10)300
· 300 CS(10)350
· 350 CS(10)400
· 400 CS(10)500
· 500 4.3.6 Tensile strength perpendicular to faces Tensile strength perpendicular to faces, mt, shall be determined in accordance with EN 1607. No test result shall for the declared level be less than the value given in Table 5. Table 5 — Levels for tensile strength perpendicular to faces Level Requirement kPa TR20
· 20 TR50
· 50 TR80
· 80 TR100
· 100 TR150
· 150 TR200
· 200 TR400
· 400 4.3.7 Bending strength Bending strength, b, shall be determined in accordance with EN 12089. No test result shall for the declared level be less than the value given in Table 6. SIST EN 14309:2016
· 50 BS 75
· 75 BS 100
· 100 BS 115
· 115 BS 125
· 125 BS 135
· 135 BS 150
· 150 BS 170
· 170 BS 200
· 200 BS 250
· 250 BS 350
· 350 BS 450
· 450 BS 525
· 525 BS 600
· 600 BS 750
· 750 4.3.8 Compressive creep Compressive creep, Xct, and the total thickness reduction, Xt, shall be determined after at least one hundred and 22 days of testing at a declared compressive stress, c, given in steps of at least 1 kPa and the results extrapolated 30 times corresponding to 10 years to obtain the declared levels in accordance with EN 1606. Compressive creep shall be declared in levels, i2, and the total thickness reduction shall be declared in levels, i1, with steps of 0,5 % at the declared stress. No test result shall exceed the declared levels at the declared stress. NOTE 1 Examples for declaration of levels for compressive creep. Level Test time t Days Extrapolation time Years Declared stress c kPa Requirement % CC(i1/i2/10)c 122 10 c t < i1 and ct < i2 CC(i1/i2/25)c 304 25 c CC(i1/i2/50)c 608 50 c NOTE 2 Referring to the designation code CC(i1/i2/y) c, according to Clause 6, a declared level CC(2,5/2/50)100, as for example, indicates a value not exceeding 2 % for compressive creep and 2,5 % for total thickness reduction after extrapolation at 50 years (i.e. 30 times six hundred and eight days of testing) under a declared stress of 100 kPa. SIST EN 14309:2016
¶ 5,0 WL(T)3
¶ 3,0 WL(T)2