Fire resistance tests for service installations - Part 2: Fire dampers

This European Standard specifies a method for determining the fire resistance of fire dampers installed in fire separating elements designed to withstand heat and the passage of fire, smoke and gases at high temperature. This European Standard is used in conjunction with EN 1363-1.
This European Standard is not suitable for testing fire dampers in suspended ceilings.
This European Standard is not suitable for testing non-mechanical fire dampers (see prEN 1366-12).

Feuerwiderstandsprüfungen für Installationen - Teil 2: Brandschutzklappen

Dieser Teil von EN 1366 legt ein Verfahren für die Ermittlung der Feuerwiderstandsdauer von Brandschutz-klappen fest, die in feuerwiderstandsfähigen raumabschließenden Bauteilen eingebaut und dafür vorgesehen sind, dem Durchtritt von Rauch und Gasen bei hohen Temperaturen standzuhalten. Diese Norm gilt zusam¬men mit EN 1363-1.
Ohne Abänderung ist diese Norm für die Prüfung von Brandschutzklappen in Unterdecken nicht geeignet.

Essais de résistance au feu des installations techniques - Partie 2 : Clapets résistant au feu

La présente partie de la Norme européenne EN 1366 prescrit une méthode pour déterminer la résistance au
feu des clapets résistants au feu installés dans des éléments de séparation conçus pour résister à la chaleur
et au passage des fumées et des gaz à haute température. La présente norme est utilisée conjointement avec
l'EN 1363-1.
Sans modification, elle ne convient pas aux essais de clapets résistant au feu dans les plafonds suspendus.

Preskusi požarne odpornosti servisnih inštalacij – 2. del: Požarne lopute

General Information

Status
Not Published
Publication Date
09-Dec-2012
Current Stage
4598 - Decision to abandon - Finalization for Vote
Start Date
24-Sep-2012
Completion Date
24-Sep-2012

Relations

Buy Standard

Draft
prEN 1366-2:2010
English language
28 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-april-2010
Preskusi požarne odpornosti servisnih inštalacij – 2. del: Požarne lopute
Fire resistance tests for service installations - Part 2: Fire dampers
Feuerwiderstandsprüfungen für Installationen - Teil 2: Brandschutzklappen
Ta slovenski standard je istoveten z: prEN 1366-2
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
DRAFT
prEN 1366-2
NORME EUROPÉENNE
EUROPÄISCHE NORM
February 2010
ICS 13.220.50 Will supersede EN 1366-2:1999
English Version
Fire resistance tests for service installations - Part 2: Fire
dampers
Feuerwiderstandsprüfungen für Installationen - Teil 2:
Brandschutzklappen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2010 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 1366-2:2010: E
worldwide for CEN national Members.

prEN 1366-2:2010 (E)
Contents Page
Foreword .4
Introduction .5
1 Scope .5
2 Normative references .5
3 Terms and Definitions .6
4 Test equipment .7
4.1 General .7
4.2 Connecting duct .7
4.3 Volume flow measuring station .7
4.4 Condensing unit .7
4.5 Gas temperature measuring devices .7
4.6 Exhaust fan system .7
5 Test conditions .8
6 Test specimen .8
6.1 Size .8
6.2 Number of tests .8
6.3 Design .9
7 Installation of test specimen . 10
7.1 General . 10
7.2 Supporting construction . 10
7.3 Minimum separation . 11
8 Conditioning . 11
9 Application of instrumentation . 11
9.1 Thermocouples . 11
9.2 Furnace pressure . 12
10 Test procedure . 12
10.1 Determination of leakage of connecting duct and measuring station . 12
10.2 Opening and closing test . 13
10.3 Determination of leakage at ambient temperature . 13
10.4 Fire test procedure . 13
11 Performance criteria . 15
12 Test report . 16
13 Field of direct application of test results . 17
prEN 1366-2:2010 (E)
13.1 Size of fire damper . 17
13.2 Fire dampers installed within structural openings . 17
13.3 Fire dampers installed onto the face of a wall or a floor . 17
13.4 Fire dampers remote from a wall or floor . 18
13.5 Separation between fire dampers and between fire dampers and construction elements . 18
13.6 Supporting constructions . 18

prEN 1366-2:2010 (E)
Foreword
This document (prEN 1366-2:2010) has been prepared by Technical Committee CEN/TC 127 “Fire safety in
buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 1366-2:1999.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of 89/106/EEC.
EN 1366 ‘Fire resistance tests for service installations’ consists of the following
Part 1: Ducts
Part 2: Fire dampers
Part 3: Penetration seals (in course of preparation)
Part 4: Linear joint seals (in course of preparation)
Part 5: Service ducts and shafts (in course of preparation)
Part 6: Raised floors (in course of preparation)
Part 7: Closures for conveyors and trackbound transportation systems (in course of preparation)
Part 8: Smoke extraction ducts (in course of preparation)
Part 9: Single compartment smoke extraction ducts (in course of preparation)
Part 10: Smoke control dampers (in course of preparation)

prEN 1366-2:2010 (E)
Introduction
The purpose of the test is to evaluate the ability of a fire damper to prevent fire and smoke spreading from one
fire compartment to another through the air ductwork system which may penetrate fire separating walls and
floors.
The fire damper is attached (directly or remotely via a section of ducting), to a fire separating element in a
manner representative of practice. Tests are performed starting with the fire damper in the open position to
expose the temperature sensing element of the fire damper to furnace conditions.
Temperature and integrity measurements are carried out in various parts of the test construction during the
test. The leakage of the fire damper system is measured (continuously during the test) by direct flow
measurements whilst maintaining a constant pressure differential across the closed fire damper of 300 Pa.
The leakage of the fire damper in the closed position is also measured at ambient temperature, where a
reduced leakage classification is required to be achieved.
Caution
The attention of all persons concerned with managing and carrying out this fire resistance test is drawn to the
fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and
gases may be evolved during the test. Mechanical and operational hazards may also arise during the
construction of the test elements or structures, their testing and disposal of test residues.
An assessment of all potential hazards and risks to health shall be made and safety precautions shall be
identified and provided. Written safety instructions shall be issued. Appropriate training shall be given to
relevant personnel. Laboratory personnel shall ensure that they follow written safety instructions at all times.
1 Scope
This Part of EN 1366 specifies a method for determining the fire resistance of fire dampers installed in fire
separating elements designed to withstand heat and the passage of smoke and gases at high temperature.
The Standard is used in conjunction with EN 1363-1.
This standard is not suitable for testing fire dampers in suspended ceilings without modification.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
prEN 520, Gypsum plasterboards — Specification — Test method (ISO 6308:1980 modified).
EN 1363-1, Fire resistance tests — Part 1: General requirements.
EN 1363-2, Fire resistance tests — Part 2: Alternative and additional procedures.
prEN ISO 13943, Fire safety — Vocabulary (ISO/DIS 13943:1998).
EN ISO 5167-1, Measurement of fluid flow by means of orifice plates, nozzles and venturi tubes inserted in
circular cross-section conduits running full (ISO 5167-1:1991).
prEN 1366-2:2010 (E)
ISO 5221, Air distribution and air diffusion — Rules to methods of measuring air flow rate in an air handling
duct.
3 Terms and Definitions
For the purposes of this Part of EN 1366, the definitions given in EN 1363-1 and prEN ISO 13943, together
with the following, apply:
3.1
fire damper
a device for use in heating, ventilation and air-conditioning (HVAC) systems at fire boundaries to maintain
compartmentation and protect means of escape in case of fire – it may have reduced smoke leakage
characteristics
3.2
insulated fire damper
a fire damper which satisfies both the integrity and insulation criteria for the anticipated fire resistance period
3.3
uninsulated fire damper
a fire damper which satisfies the integrity criteria for the anticipated fire resistance period, but which does not
provide a long enough insulation period to gain an EI classification
3.4
fire damper actuating mechanism
a mechanism, integral or directly associated with the fire damper which, when initiated causes the damper to
change from the "open" to the "closed" position
3.5
temperature sensing element
a thermally actuated device designed to respond to a rise in temperature of the surrounding air and release
the fire damper blade(s) at a predetermined temperature. It can interface with mechanical, electrical,
electronic, or pneumatically operated actuating mechanisms which are positioned integrally or remotely from
the device
3.6
test specimen
the fire damper, connecting frame and (if applicable) the perimeter penetration sealing system
3.7
connecting duct
the duct section between the fire damper or supporting construction and the measuring station
3.8
test construction
the complete assembly of the test specimen, the connecting
...