EN 777-3:1999/A1:2001
(Amendment)Multi-burner gas-fired overhead radiant tube heater systems for non-domestic use - Part 3: System F, safety
- BACK
- 20-Feb-2001
- 10-Mar-2009
- 97.100.20
- 90/396/EEC
- M/BC/CEN/89/6
- CEN/TC 180
Multi-burner gas-fired overhead radiant tube heater systems for non-domestic use - Part 3: System F, safety
This amendment modifies EN 777-3:1998. It has been prepared to incorporate requirements and test methods concerning NOx emissions of non-domestic gas-fired overhead radiant tube heaters.
Gasgeräte-Heizstrahler - Dunkelstrahlersysteme mit mehreren Brennern mit Gebläse für gewerbliche und industrielle Anwendung - Teil 3: System F, Sicherheit
Tubes radiants suspendus à multi-brûleurs à usage non-domestique utilisant les combustibles gazeux - Partie 3: Système F, sécurité
Stropna cevna sevala z več plinskimi gorilniki za nestanovanjske prostore – 3. del: Sistem F, varnost- Dopolnilo A1
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 777-3:2001/A1:2002
01-april-2002
6WURSQDFHYQDVHYDOD]YHþSOLQVNLPLJRULOQLNL]DQHVWDQRYDQMVNHSURVWRUH±GHO
6LVWHP)YDUQRVW'RSROQLOR$
Multi-burner gas-fired overhead radiant tube heater systems for non-domestic use - Part
3: System F, safety
Gasgeräte-Heizstrahler - Dunkelstrahlersysteme mit mehreren Brennern mit Gebläse für
gewerbliche und industrielle Anwendung - Teil 3: S
...
This May Also Interest You
This document specifies the requirements and test methods for the safety and efficiency of gas fired air heaters with or without a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances".
This standard also applies to warm air heaters having forced draught burners.
This European Standard applies to Type A2, A3 appliances, with an input not exceeding 300 kW (net CV basis), intended for non-domestic use.
This European Standard also applies to Type B11, B11AS, B11BS, B12, B12AS, B12BS, B13, B13AS, B13BS, B14, B14AS, B14BS, B22, B23, B41, B41AS, B41BS, B42, B42AS, B42BS, B43, B43AS, B43BS, B44, B44AS, B44BS, B52, B53, C11, C12, C13, C21, C31, C32, C33, C41, C62 and C63 appliances with an input not exceeding 300 kW (net CV basis), intended for domestic and non-domestic use.
Provision of the heated air may be by means of ducting.
This European Standard does not apply to:
a) dual purpose air conditioning appliances (heating and cooling);
b) appliances where the air is heated by an intermediate fluid;
c) portable or transportable forced convection appliances;
d) appliances fitted with manual or automatic means of adjusting the combustion products evacuation by means of flue dampers;
e) appliances having multiple heating units with a single draught diverter;
f) appliances fitted with more than one flue outlet;
g) appliances fitted with gas boosters;
h) C21 and C41 appliances for 3rd family gases.
NOTE For C41 appliances, see all requirements and test methods that are valid for C21 appliances, unless otherwise stated.
This European Standard is not intended to cover appliances projected for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance.
This European Standard is applicable to appliances which are intended to be type tested.
- Standard193 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft214 pagesEnglish languagesale 10% offe-Library read for×1 day
- 15-Oct-2019
- 29-Apr-2020
- 97.100.20
- 2009/142/EC
- 2016/2281
- 2016/426
- 2016/426/EU
- M/560
- M/BC/CEN/89/6
- CEN/TC 180
This European Standard specifies the requirements and test methods for the construction, safety, rational use of energy, classification and marking of non-domestic gas-fired overhead luminous radiant heaters for environmental comfort, referred to in the body of the text as "appliances".
This European Standard is applicable to Type A1 and Type A3 appliances only (see 4.2.2) intended for use in other than residential dwellings:
a) low gas pressure appliances operating at pressures up to and including 50 mbar;
b) medium gas pressure appliances operating at pressures above 50 mbar and up to 2 bar.
This European Standard is not applicable to:
- appliances designed for use in domestic dwellings;
- outdoor appliances;
- appliances of heat input in excess of 120 kW (based on the net calorific value of the appropriate reference gas);
This standard is applicable to appliances which are intended to be type tested.
- Standard114 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft115 pagesEnglish languagesale 10% offe-Library read for×1 day
- 15-Oct-2019
- 29-Apr-2020
- 97.100.20
- 2015/1188
- 2016/426
- M/550
- M/BC/CEN/89/6
- CEN/TC 180
This document specifies the requirements and test methods for the construction, safety, classification, marking and efficiency of non-domestic gas-fired overhead radiant strips heaters and multi-burner continuous radiant tube heater systems (referred to in the body of the text as the “system”) with each burner unit under the control of an automatic burner control system.
For radiant strip heaters incorporating a single burner, this standard is applicable to Type B22, B23, B52, B53, C12, C13, C32, C33 C52 and C53 appliances intended for use in other than domestic dwellings, in which the supply of combustion air and/or the evacuation of the products of combustion is achieved by mechanical means.
For multi-burner continuous radiant tube heater systems this standard is applicable to type B22, B52, and C52 appliances intended for use in other than domestic dwellings, in which the supply of combustion air and/or the evacuation of the products of combustion is achieved by mechanical means.
This standard also includes appliances incorporating a secondary heat exchanger in the flue system.
This standard is not applicable to:
a) appliances designed for use in domestic dwelling;
b) outdoor appliances;
c) radiant strip heaters where the heat input is in excess of 300 KW (based on the net calorific value of the appropriate reference test gas);
d) continuous radiant tube heater systems where the heat input of any individual burner unit is in excess of 70 kW (based on the net calorific value of the appropriate reference test gas);
e) appliances having combustion products evacuation ducts that are non-metallic in the flue system – except ducts downstream of a possible additional condensing exhaust gas heat exchanger.
In addition, for heater systems incorporating multiple tube heaters this standard is not applicable to:
f) appliances that are designed for continuous condensation within the flue system under normal operating conditions – except downstream a possible additional exhaust gas heat exchanger.
This standard is applicable to appliances which are intended to be type tested.
- Standard162 pagesEnglish languagesale 10% offe-Library read for×1 day
- Standard162 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft164 pagesEnglish languagesale 10% offe-Library read for×1 day
- 08-Oct-2019
- 29-Apr-2020
- 97.100.20
- 2015/1188
- 2016/426
- M/550
- M/BC/CEN/89/6
- CEN/TC 180
This European Standard specifies the requirements and test methods for the construction, safety, classification, marking and efficiency of non-domestic gas-fired overhead radiant tube heaters incorporating a single burner and multiple burner systems (referred to in the body of the text as the “system”) with each burner unit under the control of an automatic burner control system.
For radiant tube heaters incorporating a single burner, this standard is applicable to Type A2, A3, B12, B13, B22, B23, B42, B43, B52, B53, C12, C13, C32, C33, C52 and C53 appliances intended for use in other than domestic dwellings, in which the supply of combustion air and/or the evacuation of the products of combustion is achieved by mechanical means located upstream of the draught diverter, if provided.
For radiant tube heater systems incorporating multiple tube heater segments, this standard is applicable to Type B52, B52x, B53 and B53x systems intended for use in other than domestic dwellings, in which the supply of combustion air and/or the evacuation of the products of combustion is achieved by mechanical means.
This standard also includes appliances incorporating a secondary heat exchanger in the flue system.
This standard is not applicable to:
a) appliances designed for use in domestic dwelling;
b) outdoor appliances;
c) appliances where the heat input of any individual burner unit is in excess of 120 kW (based on the net calorific value of the appropriate reference test gas);
d) appliances having combustion products evacuation ducts that are non-metallic in the flue system - except ducts downstream of a possible additional condensing exhaust gas heat exchanger.
In addition, for heater systems incorporating multiple tube heaters this standard is not applicable to:
e) appliances and systems that are designed for continuous condensation within the flue system under normal operating conditions - except downstream a possible additional exhaust gas heat exchanger.
This standard is applicable to systems which are intended to be type tested.
- Standard167 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft170 pagesEnglish languagesale 10% offe-Library read for×1 day
- 08-Oct-2019
- 29-Apr-2020
- 97.100.20
- 2015/1188
- 2016/426
- M/550
- M/BC/CEN/89/6
- CEN/TC 180
TC - Foreword, 3rd paragraph to be slightly amended
- Corrigendum2 pagesEnglish, French and German languagesale 10% offe-Library read for×1 day
- 23-Jul-2002
- 91.140.30
- 97.100.20
- M/BC/CEN/89/6
- CEN/TC 180
This European Standard specifies the requirements for the ventilation of non-domestic premises where gas-fired radiant heaters complying with EN 416-1:1999 or EN 419-1:1999 are installed and operated.
This European Standard is applicable to type A appliances (see 3.2).
- Standard9 pagesEnglish languagesale 10% offe-Library read for×1 day
- 31-Jul-2001
- 27-Feb-2002
- 91.140.30
- 97.100.20
- M/BC/CEN/89/6
- CEN/TC 180
This document specifies the safety, design, construction, performance requirements and testing of Temperature Control Functions (TCF) and Combustion Product Discharge Safety Devices (TTB) for gas and liquid fuel burners and appliances burning one or more gaseous or liquid fuels, hereafter referred to as ‘TCF’ or ‘TTB’.
It also describes the test procedures for checking compliance with these requirements.
This document is applicable to AC and DC supplied TCF and TTB (for TCF and TTB supplied by stand-alone battery system, battery systems for mobile applications or systems which are intended to be connected to DC supply networks, see Annex I).
This document is applicable to electronically based TTB and TCF only.
For both TTB and TCF, the requirements in this document are applicable to the combination of sensing element and control.
- Standard32 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft31 pagesEnglish languagesale 10% offe-Library read for×1 day
This document specifies the requirements and test methods for the construction, safety, marking and rational use of energy.
This document is applicable to types B11AS, B11BS, B11CS, C11, C31 and C91 appliances (see 4.2) and those that:
— are closed-fronted;
— incorporate a natural draught burner;
— are connected directly to an open flue or to a device to evacuate the products of combustion (open-flued appliances, balanced-flued appliances);
— are wall mounted, free-standing or built-in;
— have a nominal heat input not exceeding 20 kW (based on the net calorific value).
This document is not applicable to:
— open fronted appliances as specified in EN 13278:2013;
— decorative fuel effect appliances as specified in EN 509:1999/A1:2003;
— catalytic combustion appliances;
— appliances in which the supply of combustion air and/or evacuation of products of combustion is achieved by mechanical means as specified in EN 1266:2002;
— ducted-air appliances;
— appliances installed by means of a closure plate (see 3.3.3.3).
Matters related to quality assurance systems, tests during production and to certificates of conformity of auxiliary devices are not dealt with by this standard.
- Standard82 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft93 pagesEnglish languagesale 10% offe-Library read for×1 day
- 21-Dec-2021
- 29-Jun-2022
- 97.100.20
- 2016/426
- M/BC/CEN/89/6
- CEN/TC 62
EN 13611:2019, Clause 1 is replaced by the following:
This document specifies methods for the classification and assessment of function blocks for burners and appliances burning one or more gaseous or liquid fuels with particular regards to their fault behaviour and preventative measures.
This document is applicable to new control function blocks, not covered by dedicated control standards.
- Standard41 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft42 pagesEnglish languagesale 10% offe-Library read for×1 day
- 23-Nov-2021
- 30-May-2022
- 91.140.40
- 97.100.20
- 2014/68/EU
- 2016/426
- CEN/TC 58
This document specifies the requirements and test methods for the safety and efficiency of gas fired air heaters with or without a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances".
This standard also applies to warm air heaters having forced draught burners.
This European Standard applies to Type A2, A3 appliances, with an input not exceeding 300 kW (net CV basis), intended for non-domestic use.
This European Standard also applies to Type B11, B11AS, B11BS, B12, B12AS, B12BS, B13, B13AS, B13BS, B14, B14AS, B14BS, B22, B23, B41, B41AS, B41BS, B42, B42AS, B42BS, B43, B43AS, B43BS, B44, B44AS, B44BS, B52, B53, C11, C12, C13, C21, C31, C32, C33, C41, C62 and C63 appliances with an input not exceeding 300 kW (net CV basis), intended for domestic and non-domestic use.
Provision of the heated air may be by means of ducting.
This European Standard does not apply to:
a) dual purpose air conditioning appliances (heating and cooling);
b) appliances where the air is heated by an intermediate fluid;
c) portable or transportable forced convection appliances;
d) appliances fitted with manual or automatic means of adjusting the combustion products evacuation by means of flue dampers;
e) appliances having multiple heating units with a single draught diverter;
f) appliances fitted with more than one flue outlet;
g) appliances fitted with gas boosters;
h) C21 and C41 appliances for 3rd family gases.
NOTE For C41 appliances, see all requirements and test methods that are valid for C21 appliances, unless otherwise stated.
This European Standard is not intended to cover appliances projected for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance.
This European Standard is applicable to appliances which are intended to be type tested.
- Standard193 pagesEnglish languagesale 10% offe-Library read for×1 day
- Draft214 pagesEnglish languagesale 10% offe-Library read for×1 day
- 15-Oct-2019
- 29-Apr-2020
- 97.100.20
- 2009/142/EC
- 2016/2281
- 2016/426
- 2016/426/EU
- M/560
- M/BC/CEN/89/6
- CEN/TC 180