ASTM E1974-19
(Specification)Standard Specification for Shelter, Electrical Equipment S-250/G
Standard Specification for Shelter, Electrical Equipment S-250/G
ABSTRACT
This specification establishes the requirements and the corresponding test methods for one type of lightweight field and mobile shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as electric equipment shelter S-250/G. These requirements include those for the material, construction, environmental performance, structural integrity, and tightness characteristics.
SCOPE
1.1 This specification covers one type of lightweight field and mobile rigid wall shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as Shelter, Electrical Equipment S-250/G.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 The following safety hazards caveat refers only to the test methods portion of this specification. This standard does not purport to address the safety concerns, if any, associated with its use. It is the responsibility of the user of the standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
- Status
- Published
- Publication Date
- 30-Jun-2019
- Technical Committee
- E06 - Performance of Buildings
Relations
- Effective Date
- 01-Jul-2019
- Effective Date
- 15-Feb-2020
- Effective Date
- 01-Sep-2019
- Effective Date
- 01-May-2019
- Effective Date
- 01-Nov-2018
- Effective Date
- 01-Oct-2018
- Effective Date
- 01-Oct-2018
- Effective Date
- 01-Oct-2018
- Effective Date
- 01-Mar-2015
- Effective Date
- 01-Nov-2014
- Effective Date
- 01-Oct-2012
- Effective Date
- 15-Nov-2011
- Effective Date
- 01-Nov-2010
- Effective Date
- 01-Nov-2010
- Effective Date
- 01-Oct-2010
Overview
ASTM E1974-19: Standard Specification for Shelter, Electrical Equipment S-250/G provides comprehensive requirements for the design, materials, construction, and testing of lightweight, rigid wall field and mobile shelters. Designed for transportability by cargo truck, aircraft (fixed or rotary wing), rail, and ship, these shelters are widely used to house electronic and electrical equipment in demanding field environments. The specification details the construction standards, environmental requirements, and integrity criteria essential for shelters delivering secure, transportable, and durable protection for sensitive equipment.
Key Topics
Scope and Purpose
- Covers lightweight, rigid wall, mobile shelters designated as S-250/G.
- Specifies requirements for shelter transportability, including air, land, and sea.
- Intended for use where reliable protection and mobility for electrical equipment is critical.
Materials & Construction
- Sets standards for adhesives, sealers, core materials, and hardware.
- Outlines lamination, sealing, cleaning, welding, and general assembly requirements.
- Ensures proper bonding, watertight sealing, and use of corrosion-resistant materials.
Performance & Environmental Testing
- Requires shelters to withstand humidity, water exposure, extreme temperatures, and physical impacts.
- Addresses tightness, watertightness, electromagnetic interference (EMI) shielding, and structural strength.
- Ensures functionality and structure are maintained under stipulated load, drop, and fording conditions.
Certifications & Documentation
- Compliance with referenced ASTM, military (MIL), Federal Aviation, and SAE standards.
- Requires records of serial numbers, weights, and any installed modification kits.
- Specifies first article inspection and ongoing quality control processes.
Applications
Military & Defense
- Widely adopted by agencies of the U.S. Department of Defense.
- Used for deployable command centers, mobile communications units, and electronic warfare shelters.
- Offers the ruggedization, EMI shielding, and environmental protection needed in military operations.
Emergency Response & Disaster Relief
- Provides portable, weather-resistant shelters for critical communications or power management systems.
- Supports rapid deployment needs in emergency or disaster recovery scenarios.
Commercial & Industrial
- Suitable for field offices, monitoring stations, or base units for remote industrial operations.
- Applied where insulated, mobile, and secure enclosures for electrical equipment are essential.
Related Standards
ASTM E1974-19 references and is used with several industry and military standards, including:
ASTM Standards
- C273/C273M: Shear Properties of Sandwich Core Materials
- D1621 & D1622/D1622M: Compressive Properties and Density of Rigid Cellular Plastics
- D2842: Water Absorption of Rigid Cellular Plastics
- E631: Terminology of Building Constructions
- E1370, E1749: Air Sampling and Shelter Terminology
- E1773: Sealing with Polysulfide-Based Sealants
- E1800, E1801: Adhesives for Bonding Panels
- E1851: Electromagnetic Shielding Effectiveness
Military and Commercial Standards
- MIL-F-14072, MIL-DTL-55507: Finishes and Packaging of Electronic Equipment Shelters
- MIL-STD-810: Environmental Testing for Military Equipment
- MIL-STD-2219, SAE AMS-W-6858: Welding Standards
- FAR 25.853: Interior Flammability for Aircraft Compartments
Drawings and Specifications
- Various detailed product and modification kit drawings for construction, hardware, and accessories.
Practical Value
Adhering to ASTM E1974-19 ensures standardization, interoperability, and safety in the construction and deployment of field shelters for electrical equipment. It guarantees shelters are robustly built, rigorously tested, and ready for reliable performance in harsh environments, supporting military, emergency, and commercial operations where uninterrupted electronic function is vital. Manufacturers, procurement officers, and field operators benefit from compliance, ensuring mission-critical shelter performance and logistics readiness.
Keywords: ASTM E1974-19, electrical equipment shelter, S-250/G, mobile shelter, field shelter, military shelter, electromagnetic shielding, environmental resistance, transportable enclosure, shelter standards, EMI protection.
Buy Documents
ASTM E1974-19 - Standard Specification for Shelter, Electrical Equipment S-250/G
REDLINE ASTM E1974-19 - Standard Specification for Shelter, Electrical Equipment S-250/G
Get Certified
Connect with accredited certification bodies for this standard
BRCGS (Brand Reputation Compliance Global Standards)
Global food safety and quality standards owner.
Sponsored listings
Frequently Asked Questions
ASTM E1974-19 is a technical specification published by ASTM International. Its full title is "Standard Specification for Shelter, Electrical Equipment S-250/G". This standard covers: ABSTRACT This specification establishes the requirements and the corresponding test methods for one type of lightweight field and mobile shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as electric equipment shelter S-250/G. These requirements include those for the material, construction, environmental performance, structural integrity, and tightness characteristics. SCOPE 1.1 This specification covers one type of lightweight field and mobile rigid wall shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as Shelter, Electrical Equipment S-250/G. 1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.3 The following safety hazards caveat refers only to the test methods portion of this specification. This standard does not purport to address the safety concerns, if any, associated with its use. It is the responsibility of the user of the standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
ABSTRACT This specification establishes the requirements and the corresponding test methods for one type of lightweight field and mobile shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as electric equipment shelter S-250/G. These requirements include those for the material, construction, environmental performance, structural integrity, and tightness characteristics. SCOPE 1.1 This specification covers one type of lightweight field and mobile rigid wall shelter designed for transport by cargo truck, fixed or rotary winged aircraft, by rail, and ship, designated as Shelter, Electrical Equipment S-250/G. 1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. 1.3 The following safety hazards caveat refers only to the test methods portion of this specification. This standard does not purport to address the safety concerns, if any, associated with its use. It is the responsibility of the user of the standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. 1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
ASTM E1974-19 is classified under the following ICS (International Classification for Standards) categories: 55.180.40 - Complete, filled transport packages. The ICS classification helps identify the subject area and facilitates finding related standards.
ASTM E1974-19 has the following relationships with other standards: It is inter standard links to ASTM E1974-11, ASTM C273/C273M-20, ASTM C273/C273M-19, ASTM D2842-19, ASTM C273/C273M-18, ASTM E1925-18, ASTM E1773-18, ASTM E1749-18, ASTM E631-15, ASTM E631-14, ASTM D2842-12, ASTM C273/C273M-11, ASTM E1773-10, ASTM E1749-10, ASTM E1925-10. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
ASTM E1974-19 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation:E1974 −19
Standard Specification for
Shelter, Electrical Equipment S-250/G
This standard is issued under the fixed designation E1974; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope E631 Terminology of Building Constructions
E1370 Guide for Air Sampling Strategies for Worker and
1.1 This specification covers one type of lightweight field
Workplace Protection
and mobile rigid wall shelter designed for transport by cargo
E1749 Terminology Relating to Rigid Wall Relocatable
truck, fixed or rotary winged aircraft, by rail, and ship,
Shelters
designated as Shelter, Electrical Equipment S-250/G.
E1773 Practice for Sealing RigidWallTactical Shelters with
1.2 The values stated in inch-pound units are to be regarded
Polysulfide Based Sealants
as standard. The values given in parentheses are mathematical
E1800 Specification for Adhesive for Bonding Foam Cored
conversions to SI units that are provided for information only
Sandwich Panels (160°F Elevated Humidity Service),
and are not considered standard.
Type I Panels
1.3 The following safety hazards caveat refers only to the
E1801 Practice forAdhesive Bonding ofAluminum Facings
test methods portion of this specification. This standard does in Foam and Beam Type Shelters
not purport to address the safety concerns, if any, associated
E1851 Test Method for Electromagnetic Shielding Effec-
with its use. It is the responsibility of the user of the standard tiveness of Durable Rigid Wall Relocatable Structures
to establish appropriate safety, health, and environmental
E1925 Specification for Engineering and Design Criteria for
practices and determine the applicability of regulatory limita- Rigid Wall Relocatable Structures
tions prior to use.
2.2 Commercial Standard:
1.4 This international standard was developed in accor-
SAE AMS-W-6858 Welding, Resistance: Spot and Seam
dance with internationally recognized principles on standard-
2.3 Federal Air Regulation (FAR):
ization established in the Decision on Principles for the
FAR 25.853 Compartment Interiors
Development of International Standards, Guides and Recom-
2.4 Military Standards:
mendations issued by the World Trade Organization Technical
MIL-F-14072 Finishes for Ground Based Electronic Equip-
Barriers to Trade (TBT) Committee.
ment
MIL-DTL-55507 Shelter, Electrical Equipment (With or
2. Referenced Documents
Without Equipment), Packaging of
2.1 ASTM Standards:
MIL-STD-252 Wired Equipment, Classification of Visual
C273/C273M Test Method for Shear Properties of Sandwich
and Mechanical Defects
Core Materials
MIL-STD-810 Environmental Engineering Considerations
D1621 Test Method for Compressive Properties of Rigid
and Laboratory Tests
Cellular Plastics
MIL-STD-2219 Fusion Welding forAerospaceApplications
D1622/D1622M Test Method forApparent Density of Rigid
MIL-STD-13231 Marking of Electronic Items
Cellular Plastics 6
2.5 Drawings:
D2842 Test Method for Water Absorption of Rigid Cellular
DL-SM-B-563500 Shelter, Electrical Equipment, S-250/G
Plastics
DL-SM-B-649950 Modification Kit, EMI, MK-1092/G
This specification is under the jurisdiction of ASTM Committee E06 on
Performance of Buildings and is the direct responsibility of Subcommittee E06.53 Available from AMS Publications, SAE International (SAE), 400 Common-
on Materials and Processes for Durable Rigidwall Relocatable Structures. wealth Dr., Warrendale, PA 15096, http://www.sae.org.
Current edition approved July 1, 2019. Published August 2019. Originally Available from Flight Standards Service, Federal Aviation Administration
approved in 1998. Last previous edition approved in 2011 as E1974–11. DOI: (FAA), 800 Independence Ave., SW, Washington, DC 20591, http://www.faa.gov.
10.1520/E1974–19. Available from DLA Document Services, Building 4/D, 700 Robbins Ave.,
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Philadelphia, PA 19111-5094, http://quicksearch.dla.mil.
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Available from U.S. Army Natick Soldier Systems Center (NSSC), ATTN:
Standards volume information, refer to the standard’s Document Summary page on AMSRD-NSC-CP-CS, General Greene Ave., Natick, MA 01760, http://
the ASTM website. www.army.mil/natick.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1974−19
DL-SM-B-650123 Shelter, Electrical Equipment, S-250/G Voids range from gaps as wide as the space created by a
(Shielded) missing piece of core material to as thin as a break in the
SM-D-208679 Outer Door Assembly continuity of material. Voids may be located solely within one
SM-D-208682 Inner Door Assembly type of material, such as a core material separation; they may
SM-C-435904 Keeper exist between adjacent materials, such as unbonded core
SM-C-435937 Nameplate material; or they may be located between other parts within a
SM-B-563559 Adhesive panel, such as where a piece of material is missing, damaged,
SM-B-563655 Foam, Rigid, Plastic or undersized. Voids may have been created at the time of
SM-D-563754 Diagram, Flatness and Squareness construction such as where a part was omitted; or may be
SM-C-564839 Gasket, Silicone created at a later time, such as a core separation or delaminated
SC-C-595537 Padlock and Key skin.
SC-B-595538 Bonding Procedure
NOTE1—Allotherterminologyrelatedtothisspecificationisdefinedin
SC-B-595539 Cleaning Procedure
Terminology E1749.
SC-B-595564 Core Material Urethane, Light
SC-B-595565 Core Material Urethane, Heavy
4. Materials Requirements
SM-D-649951 Modification Kit EMI MK-1092/G
4.1 General—The materials and components shall be as
SM-D-649952 Sling Assembly
specified herein and on the applicable drawings. Materials and
SM-D-649953 Shelter, Electrical Equipment S-250/G
components not definitely specified shall be of the quality
SM-C-650082 Skid Assembly
normally used by the manufacturer provided the completed
SM-D-650085 Test Weight Installation
item complies with all the provisions of this specification.
SM-C-650125 Nameplate
SC-D-781228 Door Fixture Construction Tightness Test
4.2 Adhesive—The adhesive used to laminate in accordance
SC-D-781235 Drain, Fixture, Construction Tightness Test
5.2 shall meet the requirements of Specification E1800 and the
SC-D-781236 Test Fixture Installation Construction Tight-
physical properties required by Drawing SM-B-563559 when
ness Test
tested in accordance with 10.1.
SC-B-964240 Nameplate, S-250 Shelter (With Rivnuts)
4.3 Sealer—The sealer, when tested in accordance with
10.1, used to meet the requirements of 5.3, shall have the
3. Terminology
following properties:
3.1 Definitions—For definitions of general terms related to
4.3.1 Sealer Shear, Ambient—The sealer and its bond to the
building construction used in this specification, refer to Termi-
aluminum shall have a minimum average shear strength of
nology E631, and for general terms related to rigid wall
200 psi (1.4 MPa) when tested at 80 6 10 °F (27 6 6 °C).
relocatable shelters, refer to Terminology E1749.
4.3.2 Sealer Shear, Temperature Extreme—The sealer and
3.1.1 delaminations—for purpose of this specification, a
its bond to the aluminum shall have a minimum average shear
delamination is defined as the condition that exists within a
strength of:
shelter section or panel when two surfaces that once were
4.3.2.1 200psi(1.4MPa)whentestedat–65 65 °F(–54 6
bonded together are no longer bonded together. Delaminations
3 °C), and
may occur between any two bonded surfaces; examples in-
4.3.2.2 75 psi (520 kPa) when tested at 200+0–5°F(93
clude: separations between thermal barriers and members,
+0–3°C)
between thermal barriers and skins, between members and
4.3.3 Sealer Shear, Humidity Exposure—The sealer and its
core, or between skins and core. They may be the result of a
bond to the aluminum shall withstand exposure to 95 %
poor quality bond or they could occur due to misuse or severe
relativehumidity 65 %at160 65 °F(71 63 °C)forfourteen
handling of the panels or the shelter after bonding. Test
days. After exposure the sealer shall have a minimum average
requirements of this specification shall not be construed as
shear strength of 75 psi (520 kPa) when tested at 160 65°F
misuseorseverehandlingasthesetermsapplytothedefinition
(71 6 3 °C).
of delaminations.
4.3.4 Sealer Shear, Salt Spray Exposure—The sealer and its
3.1.2 examination—examination consists of simple, gener-
bondtothealuminumshallwithstandexposuretothesaltspray
ally nondestructive determinations of compliance, without the
test, Method 509.4 of MIL-STD-810F using a 20 % NaCl
use of special testing equipment.
solution at 95 6 5 °F (35 6 3 °C) for fourteen days. After
3.1.3 inspection—inspection is the examination or testing,
exposure the sealer shall have a minimum average shear
or both, of supplies to determine compliance with the appli-
strength of 200 psi (1.4 MPa) when tested at 80 6 10 °F (27 6
cable requirements. Sampling an element of inspection.
6 °C).
3.1.4 testing—testing consists of determinations of compli-
4.4 Core Material—The core material shall be a slab type
ance using technical means.
foamed plastic. All three densities shall be used in the shelter.
3.1.5 voids—for the purpose of this specification, a void is Disbursement within the shelter shall be in accordance with
defined as any unauthorized separation or space within a Guide E1370 and the drawings listed on DL-SM-B-563500.
shelter panel or section, that is, any separation or space that is Density, compressive strength, flammability, water absorption,
in conflict with the drawings or other contractual requirements. and shear strength properties shall be in accordance with
E1974−19
Drawings SC-B-595564, SC-B-595565, and SM-B-563655, as and wood parts shall be cleaned in accordance with the
applicable when tested in accordance with 10.2. applicable portions of Practice E1801 and Drawing SC-B-
595538.
5. Construction Requirements
5.5 Welding—Arc and spot welding shall be applied as
5.1 General—Allparts,sub-assemblies,andthefinalassem-
specified by the drawings. No grinding of welds shall be
bly of Shelter, Electrical Equipment, S-250/G shall be con-
required except as specified by the drawings. The purchaser
structed as specified herein and in accordance with the draw-
reserves the right to perform any of the inspections where such
ings listed on DL-SM-B-563500 or DL-SM-B-650123 when
inspections are deemed necessary to ensure supplies and
electromagneticinterferencesuppressionisrequired(see15.2).
services conform to prescribed requirements.
Shelters shall not be fork lifted at anytime during or after
5.5.1 Arc Welding—Inert gas shielded arc welding shall be
construction.
in accordance with MIL-STD-2219.
5.5.2 Spot Welding—Spot welding shall be in accordance
5.2 Lamination—During the laminating (bonding) process
with SAE AMS-W-6858 Class B. Samples of the production
the mating of all panel constituents shall be bonded without
items produced in accordance with the drawings shall be
delaminations, that is, discontinuation in, or separation be-
inspected by the supplier for appearance, external defects,
tween the constituents. Bonding shall be in accordance with
sheet separation, surface identification, and weld location.
Practice E1801 and SC-B-595538. Both sides of all panels
5.5.2.1 Test specimens shall be used to represent the manu-
prior to assembly into shelter form and all shelters shall be
facturing practice. Three single-spot shear specimens shall be
acoustically interrogated for delaminations using a tap hammer
usedforcheckingpurposes.Threesingleshearspecimensshall
fabricated in accordance with Fig. 1. The shelter may be
be tested for ultimate strength and variation in shear strength.
considered acceptable if it contains less than twelve distinctly
5.5.2.2 Failure of a test specimen or samples of a welded
individual delaminations or unbond type voids, provided none
item shall be cause for rejection of the production quantity the
is greater than 2 in. (50 mm) across measured in any direction,
specimen or sample represents.
and provided the shelter meets all other requirements.
5.6 Riveting—No more than one rivet/rivnut in ten and no
5.3 Seal—All inner and outer skins, joints, edges, and
more than two adjacent rivets/rivnuts shall exhibit any of the
hardware shall be sealed in a manner that will prevent
defects specified below, when inspected as specified in 10.6.
collection and retention of water and provide a barrier against
5.6.1 Looseness—There shall be no evidence of looseness
the entrance of water into any panel or the interior of the
parallel to the plane of the mating surface due to oversized
shelter. Unless otherwise specified on the shelter drawings, all
holes or looseness perpendicular to the plane of the mating
exterior rivets, rivnuts, screws, and bolts shall be dipped in
surfaces due to rivets/rivnuts not being tightly seated.
sealer prior to installation and the heads of rivets shall be
5.6.2 Heads—Rivet and rivnut heads shall not be cut,
covered with sealant after installation. (See Practice E1773).
marred, chipped, eccentric, distorted, or otherwise mutilated.
5.4 Cleaning—All metal parts shall be cleaned at that stage
Countersunkrivetsandrivnutsshallnotprojectaboveorbelow
of assembly indicated on the applicable drawing listed on
the mating surface more than 15 % of the netting material
DL-SM-B-563500 or DL-SM-B-650123, by a process in ac-
thickness.
cordancewithPracticeE1773andDrawingSC-B-595539oras
5.6.3 Mating Surface and Materials—The mating surface
specified in the applicable portion of MIL-F-14072. All foam
shall not be marred or indented due to rivet or rivnut
installation, nor shall there be any distortion or warpage of the
mating materials. There shall be no foreign material between
riveted surfaces.
5.7 Hardware—All locks, latches, hinges, hinge pins,
fasteners, bolts lifting and towing eyes, steps and other shelter
hardware shall be made corrosion resistant in accordance with
the applicable drawings listed on DL-SM-B-563500 or DL-
SM-B-650123. The hardware shall be subjected to the test of
10.7 and shall show no evidence of corrosion or damage which
in any way impairs the specified performance of the individual
part.
5.7.1 Padlocks and Keys—All padlocks and keys shall be in
accordance with SC-C-595537 and shall be interchangeable to
the extent determined by 10.10.
5.8 Finish Protective—Protective finishes shall be in accor-
NOTE 1—Material—Aluminum 6061–T6 or equivalent.
dance with the applicable drawings listed on DL-SM-B-
NOTE 2—Tolerance—6 ⁄32 (1 mm).
FIG. 1Tap Hammer 563500 or DL-SM-B-650123 and shall be free of the defects
E1974−19
cited in the classification of visual finish defects of MIL-F- at 100 % relative humidity (with condensation) for 4 h when
14072 when inspected as specified in 10.8 and 10.12. tested as specified in 10.7.
5.9 Marking—Member centerline, punch marks,
6.3 Temperature—Thesheltershallbecapableofwithstand-
nameplates, instruction and data plates, and other markings
ing the following operating temperatures when tested as
shall be in accordance with MIL-STD-13231 and the appli-
specified in 10.14:
cable drawings listed on DL-SM-B-563500 or DL-SM-B-
6.3.1 Operating Temperature—Exposuretoanambienttem-
650123. Marking shall be inspected as specified in 10.9 and
perature in the range of –65 to 125 °F (–54 to 52 °C) plus a
10.12.
solar load such that the outside skin reaches a minimum
temperature of 195 °F (90 °C); exposure at any one time not to
5.10 Interchangeability—Like units, subassemblies, assem-
exceed 75 h at the low temperature extreme and4hatthe high
blies and replaceable parts shall be physically and functionally
temperature extreme.
interchangeable without modification of such items or of the
shelter. Dimensions shall be within the limits specified on the 6.3.2 Non-Operating Temperature—Exposure to an ambient
temperature in the range of –80 to 160 °F (–62 to 71 °C);
applicable drawings listed on DL-SM-B-563500 or DL-SM-B-
650123. Reliance shall not be placed on any unspecified exposure at any one time not to exceed 24 h at the low
temperature extreme and4hatthe high temperature extreme.
dimension, rating, characteristic, etc. Individual items shall not
be hand picked for fit or performance. To determine compli-
6.4 Heat Transfer—The thermal characteristics of the shel-
ance with this requirement the items listed in 10.10 shall be
ter shall be such that the overall coefficient of heat transfer of
measured and shall be in accordance with the dimensions and
thesheltershallnotexceed0.50BTUsperhourpersquarefoot
tolerances specified on the applicable drawings.
per degree Fahrenheit (2.9 Watts per square metre per degree
5.11 Facsimiles—When specified (see 15.2), the contractor Kelvin) when tested accordance with 10.15.
shall provide facsimiles of the nameplate and all data and
instruction plates required by DL-SM-B-563500 and DL-SM-
7. Structural Integrity Requirements
B-650123. Each facsimile shall be in accordance with its
7.1 General—The shelter shall be capable of complying
drawing and shall include any and all information required to
with the requirements of 7.2 – 7.6.When a payload is required,
be inserted, except shelter serial number.Artwork shall be of a
1900 lb (860 kg) in accordance with Drawing SM-D-650085
quality at least comparable to the drawings.
shall be used. The requirements of 5.13 are applicable to all
5.12 Shelter Weight—When inspected as specified in 10.12
tests.
and10.13,thegrossweightoftheshelter,excludingtheliftand
7.2 Transportability—The shelter, with payload, shall be
tie-down device, (Drawing SM-D-649952) shall be as follows:
capable of being picked up by a crane, transported while
5.12.1 770 6 20 lb (350 6 9 kg) without Mod Kit, EMI,
suspended from the crane, and lowered to any predetermined
MK-1092/G, and
point on the ground. The shelter shall also be capable of being
5.12.2 782 6 20 lb (355 6 9 kg) with Mod Kit, EMI,
transported as follows:
MK-1092/G installed.
7.2.1 Rail Transport—The shelter, with payload, shall be
5.12.3 Records—Records shall be maintained of Serial
capable of being transported by railroad. Compliance with
numbersandactualweightofsheltersandshallindicateifEMI
10.16 shall constitute compliance with this requirement.
Kit MK-1092/G is installed.
7.2.2 Lift Transport Simulated—The shelter, with payload,
5.13 Service Integrity—Unless otherwise specified, tests
shall be capable of being suspended by its lifting eyes and
specifiedhereinshallnotresultinanydiscontinuityinthebond
exposed to 3.5 g’s acceleration. Compliance with 10.17 shall
between the aluminum, foam, or wood thermal barriers, or all
constitute compliance with this requirement.
ofthese(thatis,adelamination),orinanybulking,splitting,or
7.3 Drop—The shelter, with payload, shall be capable of
any other deformation or structural weakening, or both of the
being dropped as specified in 10.18. Every shelter subjected to
shelter.Thesealof5.3shallremainintact.Alldimensionsshall
drop tests shall be shipped only to a depot and shall have its
remain in accordance with the drawings listed on DL-SM-B-
nameplate “S-250 Shelter” (with rivnuts) in accordance with
563500 or DL-SM-B-650123. Brackets, lugs, flanges, inserts,
Drawing SC-B-964240 attached with rivets over the shelter
bolts, and any other mounting arrangement shall securely
nameplate,DrawingSM-C-435937(SM-C-650125ifshielded)
retain test loads, doors, and hardware.Any deformation of any
priortoshipment.Shippingdocumentannotated(FORDEPOT
mounting arrangement resulting from any specified test shall
USE ONLY).
bewithindrawingtolerancesandshallnotcausedegradationof
its retaining ability or of specified shelter performance.
7.4 Towing Simulated—The shelter, with payload, shall
withstand a force of a least 2000 lb (900 kg) applied to each of
6. Environmental Requirements
the skid assemblies, and their attachment to the shelter, as
specified in 10.19.
6.1 General—The shelter shall be capable of meeting the
following environmental test requirements with no harmful
7.5 Lifting and Towing Eye Assembly—Each lifting and
effect to any finish or performance capability (see 5.13).
towing eye assembly, as attached to the shelter, shall withstand
6.2 Moisture Resistance—The shelter shall withstand daily a minimum load of 5000 lb (2270 kg) applied in accordance
exposureofupto97 %relativehumidityfor20handexposure with 10.20.
E1974−19
7.6 Steps, Roof Access—Each of the two recessed folding through the impact area and examined. Impact shall not result
steps installed to provide access to the shelter roof shall in rupture to either skin. No delaminations between skin and
withstand a load of 400 lb (180 kg) applied in accordance with core or crushing of core is allowed outside a 3 in. (75 mm)
10.21. radius from the center of impact.
9.4 Fabrication and Assembly—Samples (see 10.1.1) shall
8. Tightness Requirements
be assembled using parts, materials (and their amounts), and
8.1 General—The shelter shall be capable of complying
processes that will be employed in production, be fabricated
with the following:
and assembled in accordance with the specification, and meet
8.2 Torque, Door Latches—Torques shall be measured as all requirements specified herein.
specified on Drawings SM-D-649951 and SM-D-649953 and
9.5 Workmanship—The shelter shall be manufactured with
shall be as specified in 10.22.
the degree of workmanship normally considered appropriate
8.3 Electromagnetic Interference (EMI) Shielding—The for each of the areas listed under 5.0 (see 10.12).
shelter shall be capable of being shielded from electromagnetic
interference (EMI) by the installation of Modification Kit,
10. Tests Required
electromagnetic interference, MK-1092/G in accordance with
10.1 Coupon Samples—Fabricate coupon samples for both
DL-SM-B-649950 and with no other modification. Shielding
adhesive and sealer tests in accordance with the physical
shall provide a minimum attenuation of radiated and induced
properties paragraph of Drawing SM-B-563559. Ten coupons
EMI fields as specified in Specification E1925 within the
are required for each of the five conditions for first article
frequency range of 100 kHz to 10 Ghz when tested in
samples. Five coupons are required for each of the test
accordance with 10.23. Should a shelter subjected to the EMI
conditions for production inspection.
test fail to pass, another shelter from the same lot shall be
10.1.1 Comparability of Fabrication and Cure—Fabricate
subjected to the EMI test.
samples and cure using materials, processes, and conditions
8.4 Construction Tightness—The shelter shall be airtight to
compatible with those used on panels or shelters, or both,
the extent that it shall be capable of achieving and maintaining
including:
a pressurized state without leakage when tested in accordance
10.1.1.1 Surface conditions of and method of preparing
with 10.24.
materials to be bonded,
10.1.1.2 Same batch and type of material,
8.5 Watertightness—The shelter shall be watertight when
10.1.1.3 Duration of, temperature, and pressure during cure,
tested in accordance with 10.25. Shelter weight after testing
10.1.1.4 Minimum cure time before handling, and
shall be as specified in 5.12 after allowing 2 lb (1 kg) for the
test weight mounting hardware of Drawing SM-D-650085, if 10.1.1.5 Time elapsed between application of adhesive to
applicable. the first item (coupon or panel) in a lot to the application of
pressure to the lot of items. Verify two or more part mixes of
8.6 Fording—The shelter, without the use of special fording
adhesive or sealer, or both, as being in accordance with the
kits, shall be capable of being immersed in water to a depth of
manufacturer’s recommendations before shear tests and range
30 in. (760 mm), as measured from the bottom of the shelter
on coupons. Calibrate automatic dispensing machines, when
skids, with no failure of the seal specified in 5.3 or damage to
used to mix or deliver, or both, two or more part adhesive or
the structure when tested and inspected as specified in 10.26.
sealer, or both, at least once every 4 h. Cure sealer coupons at
Shelter weight after testing shall be as specified in 5.12 after
ambient temperature and the lap joint shall be under a pressure
allowing 2 lb (1 kg) for the test weight mounting hardware of
of approximately 5 psi (34 kPa).
Drawing SM-D-650085 if applicable.
10.1.2 Shear Strength Tests—Test coupons after being sub-
8.7 Light Tightness—No direct rays of light shall be visible
jected to the specified exposure, if applicable, and at the
through or around the air inlet louver assembly, as installed in
specified temperature. Stabilize the temperature of the coupons
the shelter and with the weather cover fully open, when tested
at the specified level and measure by a thermocouple attached
in accordance with 10.27.
tothecouponsoverthelapjoint.Thethermocoupleshallnotbe
attached on that side of the lap joint closest to the heat or cold
9. Other Requirements
source nor shall the method of attachment impair the applica-
9.1 First Article—When specified (see 15.2), a sample shall
tion or measurement of the shear force in any way. Apply the
be subjected to first article inspection (see 15.3) in accordance
shear force to destruction with the rate of application constant
with 11.1.
at less than or equal to 1 in./min (25 mm/min). Any noncom-
pliance with 4.2 for adhesive and 4.3 for sealer shall constitute
9.2 Lift and Tie Down Device—A combination lift and tie
down device (sling) conforming to Drawing SM-D-649952 failure of this test.
shall be provided as part of each shelter. Each leg of the device
10.2 Core Material Tests—Subject core material samples to
shall be capable of exceeding a tensile load of 9500 lb (4300
the following tests: for each test a set of five specimens is
kg) as specified on the drawing and shall fail before slippage
required for each type or grade of core material used in the
occurs at the sling sleeves when tested as specified in 10.28.
shelter. Fabricate specimens from actual shelter core material
9.3 Impact Panel—The shelter panels shall withstand the pieces randomly selected from production core material parts.
test of 10.29. After the test, the panel shall be cross sectioned Specimen dimensions shall be within 60.015 in (60.40 mm).
E1974−19
Except for flammability, compliance with 4.4 shall be deter- allowed to fall against the panel. A hammer blow on a
mined by the average of the specimen results, with the lowest laminated area produces a solid or firm or ringing sound
result no less than 90 % of the required value. Failure to meet whereas a delaminated area produces a deadened or hollow or
the requirements of 4.4 shall constitute failure of this test. metallic slap sound. Use the flat end of the hammer for tapping
10.2.1 Apparent Density, Core Material—Test five
into corners. The extent of interrogation of each side of each
specimens, each 2 by 3 by 3 in. (50 by 75 by 75 mm) in panel shall be at least four hammer impacts per square foot of
accordance with Test Method D1622/D1622M.
panel area between members and at least four hammer impacts
10.2.2 Compressive Strength, Core Material—Test five per square foot over members on the interior side of the panel.
specimens each 2 by 3 by 3 in. (50 by 75 by 75 mm) in
Once a suspect area has been located, interrogate said area in
accordance with Procedure A of Test Method D1621, with the detail by at least one hammer impact per inch in all directions.
load applied to the 3 by 3 in. (75 by 75 mm) faces.
The delamination boundaries shall be marked as the point of
10.2.3 Flammability—Determine flame resistance of the
acoustic change (deadening) plus ⁄2 in. (13 mm). Failure to
five specimens, each ⁄2 by 2 by 6 in. (13 by 50 by 150 mm),
meet the requirements of 5.2 shall constitute failure of this test.
in accordance with Appendix F of FAR 25.853. The average
10.3.1 Disposition of Delaminated Panels—Reject all de-
extinguishtimeshallnotexceed15sandaverageburndistance
laminated panels found before assembly into shelter form.
shall not exceed 6 in. (150 mm).
Limit the number of rejected panels per calendar month to 5 %
10.2.4 WaterAbsorption—Testthreespecimens,each6by6
of all panels fabricated during that entire calendar month.
by 3 in. (150 by 150 by 75 mm) in accordance with Test
Rejectedpanelsinexcessofthisamount,eventhoughrepaired,
Method D2842 with the following changes: weigh each speci-
shall not be accepted without the written approval from the
men as it is first submerged; the weighing jig shall also be
purchaser.
weighed at this time; for the final weight, the specimens must
10.3.2 Disposition of Shelters Containing Delaminated
be weighed and removed from the water in reverse order, the
Panels—Reject all shelters found to contain delaminated pan-
water absorption shall be calculated as follows (see Table 1):
els.Limitthenumberofrejectedshelterspercalendarmonthto
2 2 2
lb water/ft 5 W 2 W 2 W 2 W /A 32.048 lb/ft /g/cm (1)
~ ! ~ !
2a 1a 2 3 1.0 % of the total contract quantity with the total no more than
5 % of the total contract quantity. A shelter shall not contain
where:
more than two repaired panels regardless of when it was
W = initial submerged weight of jig and samples (gm)
1a
repaired, that is, before or after use in the shelter. Shelters not
W = initial submerged weight of jig (gm),
2a
complying with these limitations shall only be accepted by
W = final submerged weight of jig (gm),
written approval of the purchaser. Maintain a record of the
W = final submerged weight of jig and samples (gm), and
shelters containing a repaired panel, including which panel,
A = specimen surface area (cm ).
location, and extent, and report as required elsewhere in the
1 1
10.2.5 Shear Strength—Test five specimens, each ⁄2 by 1 ⁄2
contract.
by 6 in. (13 by 38 by 150 mm) in accordance withTest Method
10.3.3 Condition of Shelter Exterior Skins—The exterior
C273/C273M, except that the load shall be applied at a
skin of the shelter panels may contain dents between structural
constant rate such that the maximum load will occur in one
members provided the skin is not punctured and provided the
minute or more.
maximum depth of the dent does not exceed ⁄16 in. (1.5 mm)
10.3 Delamination Testing and Repair—Individual panels
and no more than one shelter in ten contains one dent not
and shelters shall be tested for delaminations by use of the tap
exceeding ⁄8 in. (3 mm) in depth.
hammer (see Fig. 1).Accomplish detection by tapping with the
10.3.4 Delamination Repair:
sphericalendwithaforceequaltothatproducedwhenthehead
10.3.4.1 Document repair procedures for delaminations.
is raised approximately 1 in. (25 mm) above the panel and
The contractor may utilize a procedure only after receiving
approval from the purchaser designated in the contract. The
TABLE 1 First Article Specimens
contractor should be aware and fully understand, however that
Requirements Test
Inspection Quantity
should the purchaser later determine that the procedure is
Subsection Subsection
Adhesive 50 coupons 4.2 10.1 objectionable or inadequate, or its implementation does not
Sealer 50 coupons 4.3 10.1
fulfill its intended purpose, the purchaser may require that its
Core material:
usebediscontinuedandanotherconsultationbeheldtoresolve
Density 5 for every grade or 4.4 10.2.1
type the inadequacy.
Compressive strength 5 for every grade or 4.4 10.2.2
10.3.4.2 The maximum area of any single delamination and
type
Flammability 5 for every grade or 4.4 10.2.3 the maximum number of single delaminations per panel
type
allowedisstatedin5.2.Multipledelaminationsonapanelshall
Water absorption 3 for every grade or 4.4 10.2.4
be separated by a structural member in order for that panel to
type of urethane
Shear strength 5 for every grade or 4.4 10.2.5 be considered eligible for repair.Adelamination on the interior
type
side of a panel and another delamination on the exterior side of
Lift and tie down device 1 complete 9.2 10.28
the same panel and with both delaminations being between the
Impact panel 1 for every type core 9.3 10.29
same two members shall not be considered separated.
E1974−19
TABLE 2 Dimensional Inspection
10.4 Cleaning Inspection—Inspection of the cleaning pro-
cess shall be in accordance with Practice E1773 and SC-B- Inspection Drawing Flatness Required
A
595539. Any noncompliance shall require re-cleaning of the Frame flatness Within 0.03 in.
Torque required:
parts processed since the last acceptable inspection.
Door handle torque SM-D-649953 Small door 10 ft-lb (14 j)
Large door 15 ft-lb (20 j)
10.5 Welding Inspection—Visually inspect arc welding in
Door handle torque SM-D-649951 Small door 20 ft-lb (27 j)
accordance with the requirements of maintenance sampling for
(Shielded shelter) Large door 25 ft-lb (34 j)
production in accordance with MIL-STD-2219. For resistance
Deviation allowed:
B, C D
Shelter flatness SM-D-563754 3 out of 36
welding, fabrication and inspection of production specimens
B, C E, F
Shelter squareness SM-D-563754 6 out of 36
and inspection of production parts shall be in accordance with
A
Flatness of doors and openings at gasket and contact surfaces. This shall be
SAE AMS-W-6858. Failure to meet the requirements of 5.5,
inspected by checking the flatness of the four sides and the flatness at the corners
with sub-paragraphs, shall constitute failure of this test.
using a straight edge. JO-Blocks, dial indicator height gauge or surface plate, or
both. Flatness shall be within 0.030 in. (1 mm) total.
10.6 Riveting Inspection—Examine riveted joints or rivnuts
B
Method of measurement and tolerances with tools and gauges used shall be
for tightness, the joined parts for damage, and for the rivet/
subjected to approval by the purchaser technical activity designated in the
contract.
rivnut heads to be properly seated and tight against their
C
The purchaser technical activity designated in the contract shall be notified by
bearing surfaces. Replace rivets/rivnuts not meeting the re-
the contractor 15 days before this inspection is to be performed.
D
quirements of 5.6 with properly installed rivets/rivnuts and Four deviations out of the 36 interior measurements on any one sample shall be
cause for rejection of the shelter.
then reinspect as specified above.
E
Seven deviations out of the 36 interior measurements on any one sample shall
be cause for rejection of the shelter.
10.7 Moisture Resistance Test—Subject the shelter with
F
More than two deviations in any one corner of the shelter be cause for rejection
doors open to the moisture resistance test of MIL-STD-810E,
of the shelter.
Method 507.3, Procedure II.After cycling has been completed,
thereshallbenoevidenceofdelamination,cracking,corrosion,
or deterioration to any part of the shelter and there shall be no
malfunction of doors, latches, hinges, or any other hardware.
10.12 Visual and Mechanical Inspection—Examine equip-
Failure to meet the requirements of 5.7 and 6.2 shall constitute ment for the requirements of construction (see Section 5).
failure of this test.
Comply with the item requirements listed in MIL-STD-252,
Type 4, 5, 7, 8, 9 and 11 defects only. Further, classify a shelter
10.8 Finish Inspection—Inspect finish in accordance with
weight above the required maximum (see 5.12) as a major
the quality assurance provisions of MIL-F-14072 including
defect.
paint adhesion, and 10.12 of this specification. Failure to meet
the requirements of 5.8 shall constitute failure of this test.
10.13 ShelterWeightTest—Determinecompliancewith5.12
by weighing on a platform beam or dial indicator scale. The
10.9 Marking Inspection—Visually inspect marking to de-
platform of the scale shall be of sufficient extent so as to allow
termine compliance with 5.9. Failure to meet the requirements
the placement of the entire shelter on it. The beam or indicator
of 5.9 shall constitute failure of this test.
shall have 1 lb (60.5 kg) or less graduations. The scale shall
10.10 Interchangeability Inspection—Gauge or measure the
have an accuracy of at least 61lb(60.5 kg) or one-sixth of
dimensions listed below to determine compliance with the
1 % of full scale reading, whichever is smaller. Calibrate the
physical interchangeability requirements of 5.10. When a
scale at least twice per month using standard weights traceable
dimension is not within specified or design limits, it shall be
to the National Institute for Standards and Technology. Failure
considered a defect:
to meet the requirements of 5.12 shall constitute failure of this
10.10.1 Dimension of doors and door openings,
test.
10.10.2 Mounting dimensions of hinges and latches,
10.14 Temperature Test—Place the shelter, with both doors
10.10.3 Size and mounting dimensions of skids,
and the louver cover closed and with the drain hole closed in
10.10.4 Size and mounting dimensions of towing eyes,
a manner acceptable to the purchaser in a temperature con-
10.10.5 Size and mounting dimensions of lifting eyes,
trolled room and subjected to the tests of 10.24.1 and 10.24.2.
10.10.6 Dimensions of drain and drain plug, and
Measure air temperature by ten thermocouples located in
10.10.7 Check padlocks and keys for proper operation.
accordance with Fig. 2. Outside thermocouples shall be pro-
Keys (four) shall be checked against at least three different
vided with radiation shields of aluminum foil between the
padlocks.
thermocouple and radiation surface. Air circulation shall not
10.11 Dimensional Inspection—Inspect the shelters and
exceedavelocityof7milesperhour(11kg/h)at3in.(75mm)
panels for conformance with the drawings in the following
away from any shelter surface. Conduct inspection to deter-
areas (see Footnotes A and B of Table 2):
mine compliance with 5.13 after completion of each test.
10.11.1 Items listed in Table 2,
10.14.1 Operating Temperature—Stabilize the air tempera-
10.11.2 Interior and exterior dimensions,
ture inside and outside the shelter at 120 to 125 °F (49 to
10.11.3 Location and visibility of punch marks for mount- 52 °C)foraperiodof5min,duringwhichtimecheckthedoors
ing members. Verify location at the individual panel stage of
and latches for ease of operation and freedom from binding.
fabrication, and Then subject the exterior of the shelter roof panel to an
10.11.4 Verify locations of holes on painted interior shelter additionalsimulatedsolarloadappliedasrapidlyaspossibleto
panel surfaces at the shelter assembled stage of fabrication. produce a temperature of 195 °F (90 °C) (minimum) on the
E1974−19
outsideskinoftheroofpanelasmeasuredby12thermocouples
located in accordance with Fig. 3. Obtain the simulated solar
load using at least 28 lamps, type 1000T3, 230 volts. Arrange
the lamps in four rows of seven lamps each and operate within
10 %ofratedvoltage.Maintainthe120to125° F(49to52 °C)
ambient air temperature plus the roof solar load for a period of
4 h at which time remove the solar load and increase the air
temperature both inside and outside the shelter to 160–0+
5°F(71–0+3°C)(as measured by the ten thermocouples of
Fig. 2) as rapidly as possible and maintain for 5 min. Then
completely remove the shelter from the heated chamber to an
ambient temperature between 60 and 85 °F (16 and 29 °C).
NOTE 2—The length and position of the thermocouple’s wires shall
permit complete removal. Open the shelter drain hole prior to shelter
removal.
10.14.2 Storage Test—Subject the shelter alternately to
Method 501.4 and Method 502.4 of MIL-STD-810EF, except
perform three cycles of each test (high temperature and low
temperature). The cycles shall range from 160 °F (71 °C) for
the high temperature tests and –80 °F (–62 °C) for low tem-
peraturetests(asmeasuredbythetenthermocouplesofFig.2).
NOTE 1—A = Outside T.C.s approximately 10 in. (250 mm) from
In addition, all doors and latches shall operate freely without
corners.
binding at either temperature extreme.
NOTE 2—B = Inside T.C.s as shown
FIG. 2Thermocouple Location on Sidewalls 10.15 Heat Transfer Test—Placetheshelterinatemperature
controlled room that is at a constant temperature of –40 + 5 °F
A
(–40 + 3 °C) outside the shelter. The walls and ceiling of the
TABLE 3 Sequence of First Article Inspection
chamber shall be a minimum distance of 2 ⁄2 ft (750 mm) from
Inspection Requirements Test
Subsection Subsection
the walls and ceiling of the shelter. Place a 3KW electric coil
Cleaning 5.4 10.4
open frame heater at the center of the shelter floor. Place a
Welding 5.5 10.5
multi-speed 10 or 12 in. (250 or 300 mm) diameter fan 6 in.
Lamination 5.2 10.3
(150 mm) in the back of the heater such as to direct air through
Interchangeability 5.10 10.10
Riveting 5.6 10.6
the heater toward the front of the shelter at an inclined angle of
Construction tightness 8.4 10.24
15 degrees. Maintain a stabilized temperature inside the shelter
Finish 5.8 10.8
Marking 5.9 10.9 of not less than 100 °F (38 °C) above the outside. Air circula-
Dimensional (in accordance with 5.1 10.11
tion shall not exceed a velocity of seven miles per hour (11
stated drawing
kg/h) at 3 in. (75 mm) away from any shelter surface. Stabilize
Visual and mechanical 5.1 10.12
Shelter weight 5.12 10.13 electrical power input and temperatures when the inside and
Door latch torque 8.2 10.22 1
outside groups of thermocouples each vary less than 2 ⁄2 °F
B
Moisture resistance 6.2 10.7
(1.5 °C) while maintaining the minimum differential of 100 °F
Temperature 6.3 10.14
Heat transfer 6.4 10.15
(38 °C) located in accordance with Fig. 2. Temperature and
Rail transport 7.2.1 10.16
electrical power input stabilization for at least 30 min. In the
C
Drops 7.3 10.18
D, E
stabilized condition the electrical power input will equal the
Construction tightness 8.4 10.24
Towing, simulated 7.4 10.19 heat loss. Do not change the rpm of the fan. The power input
Lifting and towing eye pulls 7.5 10.20
to the fan and heater shall be constant during the stabilization
Lift transport, simulated 7.2.2 10.17
period and measured by an ammeter, voltmeter, and wattmeter
Steps, roof access 7.6 10.21
Light tightness 8.7 10.27 in the electrical circuit. Use the power input, the average inside
EMI shielding 8.3 10.23
and outside temperature, and the inside surface area of the
Watertightness 8.5 10.25
shelter in calculating the overall coefficient of heat transfer,
Fording 8.6 10.26
Door latch torque (second time) 8.2 10.22
that shall be no greater than that specified in 6.4. Failure to
A
meet the requirements of 6.4 shall constitute failure of this test.
First article sample testing and shelter testing shall not begin until at least seven
days after the sealer application, including application of touch-up sealer.
B
NOTE 3—To avoid a large pressure differential between the inside and
First article specimen testing shall be completed no later than the end of this test
(see 11.1.1). This inspection shall not begin until at least seven days after final outside of the shelter, a form of pressure relief should be incorporated into
finish application including touch-up paint. the drain hole.
C
See Note 10 of Table 7.
D 10.16 Rail Transport, Impact Test—Load the shelter with a
For correlation data purposes only. CTT (construction tightness test) results are
not to be used as accept/reject criteria for the drop test.
1900 lb (860 kg) load in accordance with Drawing SM-D-
E
Door portion and gasket portion only.
650085 and load on a railroad flat car. Perform the test in
Commercially available from several sources.
E1974−19
NOTE 1—Tolerance 6 ⁄2 in. (13 mm).
FIG. 3Thermocouple Location of Roof
accordance with MIL-STD-810F Procedure VII. Impact test 10.18.1 Flat Drop—Lift the entire shelter 18 in. (460 mm)
the shelter and position in both the longitudinal and lateral anddroponce.Initialcontactshallbealongtheentirelengthof
directions on the flat car. Rail transportability tests shall be both skids.
performed for impacts at
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E1974 − 11 E1974 − 19
Standard Specification for
Shelter, Electrical Equipment S-250/G
This standard is issued under the fixed designation E1974; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This specification covers one type of lightweight field and mobile rigid wall shelter designed for transport by cargo truck,
fixed or rotary winged aircraft, by rail, and ship, designated as Shelter, Electrical Equipment S-250/G.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information
only.mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 The following safety hazards caveat refers only to the test methods portion of this specification. This standard does not
purport to address the safety concerns, if any, associated with its use. It is the responsibility of the user of the standard to establish
appropriate safety safety, health, and healthenvironmental practices and determine the applicability of regulatory limitations prior
to use.
1.4 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
C273C273/C273M Test Method for Shear Properties of Sandwich Core Materials
D1621 Test Method for Compressive Properties of Rigid Cellular Plastics
D1622D1622/D1622M Test Method for Apparent Density of Rigid Cellular Plastics
D2842 Test Method for Water Absorption of Rigid Cellular Plastics
E631 Terminology of Building Constructions
E1370 Guide for Air Sampling Strategies for Worker and Workplace Protection
E1749 Terminology Relating to Rigid Wall Relocatable Shelters
E1773 Practice for Sealing Rigid Wall Tactical Shelters with Polysulfide Based Sealants
E1800 Specification for Adhesive for Bonding Foam Cored Sandwich Panels (160°F Elevated Humidity Service), Type I Panels
E1801 Practice for Adhesive Bonding of Aluminum Facings in Foam and Beam Type Shelters
E1851 Test Method for Electromagnetic Shielding Effectiveness of Durable Rigid Wall Relocatable Structures
E1925 Specification for Engineering and Design Criteria for Rigid Wall Relocatable Structures
2.2 Commercial Standards:Standard:
SAE AMS-W-6858 Welding, Resistance: Spot and Seam
2.3 Federal Air Regulation (FAR):
FAR 25.853 Compartment Interior Interiors
2.4 Military Standards:
MIL-F-14072 Finishes for Ground Based Electronic Equipment
MIL-DTL-55507 Shelter, Electrical Equipment (With or Without Equipment), Packaging of
This specification is under the jurisdiction of ASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.53 on Materials
and Processes for Durable Rigidwall Relocatable Structures.
Current edition approved Sept. 1, 2011July 1, 2019. Published October 2011August 2019. Originally approved in 1998. Last previous edition approved in 20062011 as
E1974 – 06.E1974–11. DOI: 10.1520/E1974-11.10.1520/E1974–19.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’sstandard’s Document Summary page on the ASTM website.
Available from AMS Publications, Society of Automotive Engineers SAE International (SAE), 400 Commonwealth Dr., Warrendale, PA 15096-0001,15096,
http://www.sae.org.
Available from Flight Standards Service, Federal Aviation Administration (FAA), 800 Independence Ave., SW, Washington, DC 20591, http://www.faa.gov.
Available from Standardization Documents Order Desk, DODSSP, Bldg. 4, Section D, DLA Document Services, Building 4/D, 700 Robbins Ave., Philadelphia, PA
19111-5098, http://www.dodssp.daps.mil.19111-5094, http://quicksearch.dla.mil.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1974 − 19
MIL-STD-252 Wired Equipment, Classification of Visual and Mechanical Defects
MIL-STD-810 Environmental Engineering Considerations and Laboratory Tests
MIL-STD-2219 Fusion Welding for Aerospace Applications
MIL-STD-13231 Marking of Electronic Items
2.5 Drawings:
DL-SM-B-563500 Shelter, Electrical Equipment, S-250/G
DL-SM-B-649950 Modification Kit, EMI, MK-1092/G
DL-SM-B-650123 Shelter, Electrical Equipment, S-250/G (Shielded)
SM-D-208679 Outer Door Assembly
SM-D-208682 Inner Door Assembly
SM-C-435904 Keeper
SM-C-435937 Nameplate
SM-B-563559 Adhesive
SM-B-563655 Foam, Rigid, Plastic
SM-D-563754 Diagram, Flatness and Squareness
SM-C-564839 Gasket, Silicone
SC-C-595537 Padlock and Key
SC-B-595538 Bonding Procedure
SC-B-595539 Cleaning Procedure
SC-B-595564 Core Material Urethane, Light
SC-B-595565 Core Material Urethane, Heavy
SM-D-649951 Modification Kit EMI MK-1092/G
SM-D-649952 Sling Assembly
SM-D-649953 Shelter, Electrical Equipment S-250/G
SM-C-650082 Skid Assembly
SM-D-650085 Test Weight Installation
SM-C-650125 Nameplate
SC-D-781228 Door Fixture Construction Tightness Test
SC-D-781235 Drain, Fixture, Construction Tightness Test
SC-D-781236 Test Fixture Installation Construction Tightness Test
SC-B-964240 Nameplate, S-250 Shelter (With Rivnuts)
3. Terminology
3.1 Definitions:Definitions—For definitions of general terms related to building construction used in this specification, refer to
Terminology E631, and for general terms related to rigid wall relocatable shelters, refer to Terminology E1749.
3.1.1 delaminations—for purpose of this specification, a delamination is defined as the condition that exists within a shelter
section or panel when two surfaces that once were bonded together are no longer bonded together. Delaminations may occur
between any two bonded surfaces; examples include: separations between thermal barriers and members, between thermal barriers
and skins, between members and core, or between skins and core. They may be the result of a poor quality bond or they could
occur due to misuse or severe handling of the panels or the shelter after bonding. Test requirements of this specification shall not
be construed as misuse or severe handling as these terms apply to the definition of delaminations.
3.1.2 examination—examination consists of simple, generally nondestructive determinations of compliance, without the use of
special testing equipment.
3.1.3 inspection—inspection is the examination or testing, or both, of supplies to determine compliance with the applicable
requirements. Sampling an element of inspection.
3.1.4 testing—testing consists of determinations of compliance using technical means.
3.1.5 voids—for the purpose of this specification, a void is defined as any unauthorized separation or space within a shelter panel
or section, that is, any separation or space that is in conflict with the drawings or other contractual requirements. Voids range from
gaps as wide as the space created by a missing piece of core material to as thin as a break in the continuity of material. Voids may
be located solely within one type of material, such as a core material separation; they may exist between adjacent materials, such
as unbonded core material; or they may be located between other parts within a panel, such as where a piece of material is missing,
damaged, or undersized. Voids may have been created at the time of construction such as where a part was omitted; or may be
created at a later time, such as a core separation or delaminated skin.
NOTE 1—All other terminology related to this specification is defined in Terminology E1749.
Available from USU.S. Army Natick Soldier Center, Systems Center (NSSC), ATTN: AMSRD-NSC-CP-CS, Kansas Street, General Greene Ave., Natick, MA
01760-5018.01760, http://www.army.mil/natick.
E1974 − 19
4. Materials Requirements
4.1 General—The materials and components shall be as specified herein and on the applicable drawings. Materials and
components not definitely specified shall be of the quality normally used by the manufacturer provided the completed item
complies with all the provisions of this specification.
4.2 Adhesive—The adhesive used to laminate in accordance 5.2 shall meet the requirements of Specification E1800 and the
physical properties required by Drawing SM-B-563559 when tested in accordance with 10.1.
4.3 Sealer—The sealer, when tested in accordance with 10.1, used to meet the requirements of 5.3, shall have the following
properties:
4.3.1 Sealer Shear, Ambient—The sealer and its bond to the aluminum shall have a minimum average shear strength of 200 psi
200 psi (1.4 MPa) when tested at 80 6 10°F10 °F (27 6 6°C).6 °C).
4.3.2 Sealer Shear, Temperature Extreme—The sealer and its bond to the aluminum shall have a minimum average shear
strength of:
4.3.2.1 200 psi (1.4 MPa) when tested at –65 6 5°F5 °F (–54 63°C), 6 3 °C), and
4.3.2.2 75 psi (520 KPa)kPa) when tested at 200 + 0 – 5°F5 °F (93 + 0 – 3°C)3 °C)
4.3.3 Sealer Shear, Humidity Exposure—The sealer and its bond to the aluminum shall withstand exposure to 95 % relative
humidity 6 5 % 65 % at 160 6 5°F5 °F (71 6 3°C)3 °C) for fourteen days. After exposure the sealer shall have a minimum
average shear strength of 75 psi (520 kPa) when tested at 160 6 5°F5 °F (71 6 3°C).3 °C).
4.3.4 Sealer Shear, Salt Spray Exposure—The sealer and its bond to the aluminum shall withstand exposure to the salt spray
test, Method 509.4 of MIL-STD-810F using a 20 % NaCl solution at 95 6 5°F5 °F (35 63°C) 6 3 °C) for fourteen days. After
exposure the sealer shall have a minimum average shear strength of 200 psi (1.4 MPa) when tested at 80 6 10°F10 °F (27 6
6°C).6 °C).
4.4 Core Material—The core material shall be a slab type foamed plastic. All three densities shall be used in the shelter.
Disbursement within the shelter shall be in accordance with SpecificationGuide E1370 and the drawings listed on DL-SM-B-
563500. Density, compressive strength, flammability, water absorption, and shear strength properties shall be in accordance with
Drawings SC-B-595564, SC-B-595565, and SM-B-563655, as applicable when tested in accordance with 10.2.
5. Construction Requirements
5.1 General—All parts, sub-assemblies, and the final assembly of Shelter, Electrical Equipment, S-250/G shall be constructed
as specified herein and in accordance with the drawings listed on DL-SM-B-563500 or DL-SM-B-650123 when electromagnetic
interference suppression is required (see 15.2). Shelters shall not be fork lifted at anytime during or after construction.
5.2 Lamination—During the laminating (bonding) process the mating of all panel constituents shall be bonded without
delaminations, that is, discontinuation in, or separation between the constituents. Bonding shall be in accordance with Practice
E1801 and SC-B-595538. Both sides of all panels prior to assembly into shelter form and all shelters shall be acoustically
interrogated for delaminations using a tap hammer fabricated in accordance with Fig. 1. The shelter may be considered acceptable
if it contains less than twelve distinctly individual delaminations or unbond type voids, provided none is greater than 2 in. (50 mm)
across measured in any direction, and provided the shelter meets all other requirements.
5.3 Seal—All inner and outer skins, joints, edges, and hardware shall be sealed in a manner that will prevent collection and
retention of water and provide a barrier against the entrance of water into any panel or the interior of the shelter. Unless otherwise
NOTE 1—Material—Aluminum 6061–T6 or equivalent.
NOTE 2—Tolerance—6 ⁄32 (1 mm).
FIG. 1 Tap Hammer
E1974 − 19
specified on the shelter drawings, all exterior rivets, rivnuts, screws, and bolts shall be dipped in sealer prior to installation and
the heads of rivets shall be covered with sealant after installation. (See Practice E1773).
5.4 Cleaning—All metal parts shall be cleaned at that stage of assembly indicated on the applicable drawing listed on
DL-SM-B-563500 or DL-SM-B-650123, by a process in accordance with Practice E1773 and Drawing SC-B-595539 or as
specified in the applicable portion of MIL-F-14072. All foam and wood parts shall be cleaned in accordance with the applicable
portions of Practice E1801 and Drawing SC-B-595538.
5.5 Welding—Arc and spot welding shall be applied as specified by the drawings. No grinding of welds shall be required except
as specified by the drawings. The purchaser reserves the right to perform any of the inspections where such inspections are deemed
necessary to ensure supplies and services conform to prescribed requirements.
5.5.1 Arc Welding—Inert gas shielded arc welding shall be in accordance with MIL-STD-2219.
5.5.2 Spot Welding—Spot welding shall be in accordance with SAE AMS-W-6858 Class B. Samples of the production items
produced in accordance with the drawings shall be inspected by the supplier for appearance, external defects, sheet separation,
surface identification, and weld location.
5.5.2.1 Test specimens shall be used to represent the manufacturing practice. Three single-spot shear specimens shall be used
for checking purposes. Three single shear specimens shall be tested for ultimate strength and variation in shear strength.
5.5.2.2 Failure of a test specimen or samples of a welded item shall be cause for rejection of the production quantity the
specimen or sample represents.
5.6 Riveting—No more than one rivet/rivnut in ten and no more than two adjacent rivets/rivnuts shall exhibit any of the defects
specified below, when inspected as specified in 10.6.
5.6.1 Looseness—There shall be no evidence of looseness parallel to the plane of the mating surface due to oversized holes or
looseness perpendicular to the plane of the mating surfaces due to rivets/rivnuts not being tightly seated.
5.6.2 Heads—Rivet and rivnut heads shall not be cut, marred, chipped, eccentric, distorted, or otherwise mutilated. Countersunk
rivets and rivnuts shall not project above or below the mating surface more than 15 % of the netting material thickness.
5.6.3 Mating Surface and Materials—The mating surface shall not be marred or indented due to rivet or rivnut installation, nor
shall there be any distortion or warpage of the mating materials. There shall be no foreign material between riveted surfaces.
5.7 Hardware—All locks, latches, hinges, hinge pins, fasteners, bolts lifting and towing eyes, steps and other shelter hardware
shall be made corrosion resistant in accordance with the applicable drawings listed on DL-SM-B-563500 or DL-SM-B-650123.
The hardware shall be subjected to the test of 10.7 and shall show no evidence of corrosion or damage which in any way impairs
the specified performance of the individual part.
5.7.1 Padlocks and Keys—All padlocks and keys shall be in accordance with SC-C-595537 and shall be interchangeable to the
extent determined by 10.10.
5.8 Finish Protective—Protective finishes shall be in accordance with the applicable drawings listed on DL-SM-B-563500 or
DL-SM-B-650123 and shall be free of the defects cited in the classification of visual finish defects of MIL-F-14072 when inspected
as specified in 10.8 and 10.12.
5.9 Marking—Member centerline, punch marks, nameplates, instruction and data plates, and other markings shall be in
accordance with MIL-STD-13231 and the applicable drawings listed on DL-SM-B-563500 or DL-SM-B-650123. Marking shall
be inspected as specified in 10.9 and 10.12.
5.10 Interchangeability—Like units, subassemblies, assemblies and replaceable parts shall be physically and functionally
interchangeable without modification of such items or of the shelter. Dimensions shall be within the limits specified on the
applicable drawings listed on DL-SM-B-563500 or DL-SM-B-650123. Reliance shall not be placed on any unspecified dimension,
rating, characteristic, etc. Individual items shall not be hand picked for fit or performance. To determine compliance with this
requirement the items listed in 10.10 shall be measured and shall be in accordance with the dimensions and tolerances specified
on the applicable drawings.
5.11 Facsimiles—When specified (see 15.2), the contractor shall provide facsimiles of the nameplate and all data and instruction
plates required by DL-SM-B-563500 and DL-SM-B-650123. Each facsimile shall be in accordance with its drawing and shall
include any and all information required to be inserted, except shelter serial number. Artwork shall be of a quality at least
comparable to the drawings.
5.12 Shelter Weight—When inspected as specified in 10.12 and 10.13, the gross weight of the shelter, excluding the lift and
tie-down device, (Drawing SM-D-649952) shall be as follows:
5.12.1 770 6 20 lb (350 6 9kg) 9 kg) without Mod Kit, EMI, MK-1092/G, and
5.12.2 782 6 20 lb (355 6 9 kg) with Mod Kit, EMI, MK-1092/G installed.
5.12.3 Records—Records shall be maintained of Serial numbers and actual weight of shelters and shall indicate if EMI Kit
MK-1092/G is installed.
5.13 Service Integrity—Unless otherwise specified, tests specified herein shall not result in any discontinuity in the bond
between the aluminum, foam, or wood thermal barriers, or all of these (that is, a delamination), or in any bulking, splitting, or any
E1974 − 19
other deformation or structural weakening, or both of the shelter. The seal of 5.3 shall remain intact. All dimensions shall remain
in accordance with the drawings listed on DL-SM-B-563500 or DL-SM-B-650123. Brackets, lugs, flanges, inserts, bolts, and any
other mounting arrangement shall securely retain test loads, doors, and hardware. Any deformation of any mounting arrangement
resulting from any specified test shall be within drawing tolerances and shall not cause degradation of its retaining ability or of
specified shelter performance.
6. Environmental Requirements
6.1 General—The shelter shall be capable of meeting the following environmental test requirements with no harmful effect to
any finish or performance capability (see 5.13).
6.2 Moisture Resistance—The shelter shall withstand daily exposure of up to 97 % relative humidity for 20 h and exposure at
100 % relative humidity (with condensation) for 4 h when tested as specified in 10.7.
6.3 Temperature—The shelter shall be capable of withstanding the following operating temperatures when tested as specified
in 10.14:
6.3.1 Operating Temperature—Exposure to an ambient temperature in the range of –65 to 125°F125 °F (–54 to 52°C)52 °C)
plus a solar load such that the outside skin reaches a minimum temperature of 195°F (90°C);195 °F (90 °C); exposure at any one
time not to exceed 75 h at the low temperature extreme and 4 h at the high temperature extreme.
6.3.2 Non-Operating Temperature—Exposure to an ambient temperature in the range of –80 to 160°F160 °F (–62 to
71°C);71 °C); exposure at any one time not to exceed 24 h at the low temperature extreme and 4 h at the high temperature extreme.
6.4 Heat Transfer—The thermal characteristics of the shelter shall be such that the overall coefficient of heat transfer of the
shelter shall not exceed 0.50 BTUs per hour per square foot per degree Fahrenheit (2.9 Watts per square metre per degree Kelvin)
when tested accordance with 10.15.
7. Structural Integrity Requirements
7.1 General—The shelter shall be capable of complying with the requirements of 7.2 – 7.6. When a payload is required, 1900
lb (860 kg) in accordance with Drawing SM-D-650085 shall be used. The requirements of 5.13 are applicable to all tests.
7.2 Transportability—The shelter, with payload, shall be capable of being picked up by a crane, transported while suspended
from the crane, and lowered to any predetermined point on the ground. The shelter shall also be capable of being transported as
follows:
7.2.1 Rail Transport—The shelter, with payload, shall be capable of being transported by railroad. Compliance with 10.16 shall
constitute compliance with this requirement.
7.2.2 Lift Transport Simulated—The shelter, with payload, shall be capable of being suspended by its lifting eyes and exposed
to 3.5 g’sg’s acceleration. Compliance with 10.17 shall constitute compliance with this requirement.
7.3 Drop—The shelter, with payload, shall be capable of being dropped as specified in 10.18. Every shelter subjected to drop
tests shall be shipped only to a depot and shall have its nameplate “S-250 Shelter” (with rivnuts) in accordance with Drawing
SC-B-964240 attached with rivets over the shelter nameplate, Drawing SM-C-435937 (SM-C-650125 if shielded) prior to
shipment. Shipping document annotated (FOR DEPOT USE ONLY).
7.4 Towing Simulated—The shelter, with payload, shall withstand a force of a least 2000lb 2000 lb (900 kg) applied to each of
the skid assemblies, and their attachment to the shelter, as specified in 10.19.
7.5 Lifting and Towing Eye Assembly—Each lifting and towing eye assembly, as attached to the shelter, shall withstand a
minimum load of 5000 lb (2270 kg) applied in accordance with 10.20.
7.6 Steps, Roof Access—Each of the two recessed folding steps installed to provide access to the shelter roof shall withstand
a load of 400 lb (180 kg) applied in accordance with 10.21.
8. Tightness Requirements
8.1 General—The shelter shall be capable of complying with the following:
8.2 Torque, Door Latches—Torques shall be measured as specified on Drawings SM-D-649951 and SM-D-649953 and shall be
as specified in 10.22.
8.3 Electromagnetic Interference (EMI) Shielding—The shelter shall be capable of being shielded from electromagnetic
interference (EMI) by the installation of Modification Kit, electromagnetic interference, MK-1092/G in accordance with
DL-SM-B-649950 and with no other modification. Shielding shall provide a minimum attenuation of radiated and induced EMI
fields as specified in Specification E1925 within the frequency range of 100 kHz to 10 Ghz when tested in accordance with 10.23.
Should a shelter subjected to the EMI test fail to pass, another shelter from the same lot shall be subjected to the EMI test.
8.4 Construction Tightness—The shelter shall be airtight to the extent that it shall be capable of achieving and maintaining a
pressurized state without leakage when tested in accordance with 10.24.
E1974 − 19
8.5 Watertightness—The shelter shall be watertight when tested in accordance with 10.25. Shelter weight after testing shall be
as specified in 5.12 after allowing 2 lb (1 kg) for the test weight mounting hardware of Drawing SM-D-650085, if applicable.
8.6 Fording—The shelter, without the use of special fording kits, shall be capable of being immersed in water to a depth of 30
in. (760 mm), as measured from the bottom of the shelter skids, with no failure of the seal specified in 5.3 or damage to the structure
when tested and inspected as specified in 10.26. Shelter weight after testing shall be as specified in 5.12 after allowing 2 lb (1 kg)
for the test weight mounting hardware of Drawing SM-D-650085 if applicable.
8.7 Light Tightness—No direct rays of light shall be visible through or around the air inlet louver assembly, as installed in the
shelter and with the weather cover fully open, when tested in accordance with 10.27.
9. Other Requirements
9.1 First Article—When specified (see 15.2), a sample shall be subjected to first article inspection (see 15.3) in accordance with
11.1.
9.2 Lift and Tie Down Device—A combination lift and tie down device (sling) conforming to Drawing SM-D-649952 shall be
provided as part of each shelter. Each leg of the device shall be capable of exceeding a tensile load of 9500 lb (4300 kg) as specified
on the drawing and shall fail before slippage occurs at the sling sleeves when tested as specified in 10.28.
9.3 Impact Panel—The shelter panels shall withstand the test of 10.29. After the test, the panel shall be cross sectioned through
the impact area and examined. Impact shall not result in rupture to either skin. No delaminations between skin and core or crushing
of core is allowed outside a 3 in. (75 mm) radius from the center of impact.
9.4 Fabrication and Assembly—Samples (see 10.1.1) shall be assembled using parts, materials (and their amounts), and
processes that will be employed in production, be fabricated and assembled in accordance with the specification, and meet all
requirements specified herein.
9.5 Workmanship—The shelter shall be manufactured with the degree of workmanship normally considered appropriate for each
of the areas listed under 5.0 (see 10.12).
10. Tests Required
10.1 Coupon Samples—Fabricate coupon samples for both adhesive and sealer tests in accordance with the physical properties
paragraph of Drawing SM-B-563559. Ten coupons are required for each of the five conditions for first article samples. Five
coupons are required for each of the test conditions for production inspection.
10.1.1 Comparability of Fabrication and Cure—Fabricate samples and cure using materials, processes, and conditions
compatible with those used on panels or shelters, or both, including:
10.1.1.1 Surface conditions of and method of preparing materials to be bonded,
10.1.1.2 Same batch and type of material,
10.1.1.3 Duration of, temperature, and pressure during cure,
10.1.1.4 Minimum cure time before handling, and
10.1.1.5 Time elapsed between application of adhesive to the first item (coupon or panel) in a lot to the application of pressure
to the lot of items. Verify two or more part mixes of adhesive or sealer, or both, as being in accordance with the manufacturer’s
recommendations before shear tests and range on coupons. Calibrate automatic dispensing machines, when used to mix or deliver,
or both, two or more part adhesive or sealer, or both, at least once every 4 h. Cure sealer coupons at ambient temperature and the
lap joint shall be under a pressure of approximately 5 psi (34 KPa).kPa).
10.1.2 Shear Strength Tests—Test coupons after being subjected to the specified exposure, if applicable, and at the specified
temperature. Stabilize the temperature of the coupons at the specified level and measure by a thermocouple attached to the coupons
over the lap joint. The thermocouple shall not be attached on that side of the lap joint closest to the heat or cold source nor shall
the method of attachment impair the application or measurement of the shear force in any way. Apply the shear force to destruction
with the rate of application constant at less than or equal to 1 in./min (25 mm/min). Any noncompliance with 4.2 for adhesive and
4.3 for sealer shall constitute failure of this test.
10.2 Core Material Tests—Subject core material samples to the following tests: for each test a set of five specimens is required
for each type or grade of core material used in the shelter. Fabricate specimens from actual shelter core material pieces randomly
selected from production core material parts. Specimen dimensions shall be within 60.015 in (60.40 mm). Except for
flammability, compliance with 4.4 shall be determined by the average of the specimen results, with the lowest result no less than
90 % of the required value. Failure to meet the requirements of 4.4 shall constitute failure of this test.
10.2.1 Apparent Density, Core Material—Test five specimens, each 2 by 3 by 3 in. (50 by 75 by 75 mm) in accordance with
Test Method D1622D1622/D1622M.
10.2.2 Compressive Strength, Core Material—Test five specimens each 2 by 3 by 3 in. (50 by 75 by 75 mm) in accordance with
Procedure A of Test Method D1621, with the load applied to the 3 by 3 in. (75 by 75 mm) faces.
E1974 − 19
10.2.3 Flammability—Determine flame resistance of the five specimens, each ⁄2 by 2 by 6 in. (13 by 50 by 150 mm), in
accordance with Appendix F of FAR 25.853. The average extinguish time shall not exceed 15 s and average burn distance shall
not exceed 6 in. (150 mm).
10.2.4 Water Absorption—Test three specimens, each 6 by 6 by 3 in. (150 by 150 by 75 mm) in accordance with Test Method
D2842 with the following changes: weigh each specimen as it is first submerged; the weighing jig shall also be weighed at this
time; for the final weight, the specimens must be weighed and removed from the water in reverse order, the water absorption shall
be calculated as follows:follows (see Table 1):
2 2 2
lb water/ft 5 ~W 2 W ! 2 ~W 2 W !/A32.048 lb/ft /g/cm (1)
2a 1a 2 3
where:
W = initial submerged weight of jig and samples (gm)
1a
W = initial submerged weight of jig (gm),
2a
W = final submerged weight of jig (gm),
W = final submerged weight of jig and samples (gm), and
A = specimen surface area (cm ).
1 1
10.2.5 Shear Strength—Test five specimens, each ⁄2 by 1 ⁄2 by 6 in. (13 by 38 by 150 mm) in accordance with Test Method
C273C273/C273M, except that the load shall be applied at a constant rate such that the maximum load will occur in one minute
or more.
10.3 Delamination Testing and Repair—Individual panels and shelters shall be tested for delaminations by use of the tap
hammer (see Fig. 1). Accomplish detection by tapping with the spherical end with a force equal to that produced when the head
is raised approximately 1 in. (25 mm) above the panel and allowed to fall against the panel. A hammer blow on a laminated area
produces a solid or firm or ringing sound whereas a delaminated area produces a deadened or hollow or metallic slap sound. Use
the flat end of the hammer for tapping into corners. The extent of interrogation of each side of each panel shall be at least four
hammer impacts per square foot of panel area between members and at least four hammer impacts per square foot over members
on the interior side of the panel. Once a suspect area has been located, interrogate said area in detail by at least one hammer impact
per inch in all directions. The delamination boundaries shall be marked as the point of acoustic change (deadening) plus ⁄2 in. (13
mm). Failure to meet the requirements of 5.2 shall constitute failure of this test.
10.3.1 Disposition of Delaminated Panels—Reject all delaminated panels found before assembly into shelter form. Limit the
number of rejected panels per calendar month to 5 % of all panels fabricated during that entire calendar month. Rejected panels
in excess of this amount, even though repaired, shall not be accepted without the written approval from the purchaser.
10.3.2 Disposition of Shelters Containing Delaminated Panels—Reject all shelters found to contain delaminated panels. Limit
the number of rejected shelters per calendar month to 1.0 % of the total contract quantity with the total no more than 5 % of the
total contract quantity. A shelter shall not contain more than two repaired panels regardless of when it was repaired, that is, before
or after use in the shelter. Shelters not complying with these limitations shall only be accepted by written approval of the purchaser.
Maintain a record of the shelters containing a repaired panel, including which panel, location, and extent, and report as required
elsewhere in the contract.
10.3.3 Condition of Shelter Exterior Skins—The exterior skin of the shelter panels may contain dents between structural
members provided the skin is not punctured and provided the maximum depth of the dent does not exceed ⁄16 in. (1.5 mm) and
no more than one shelter in ten contains one dent not exceeding ⁄8 in. (3 mm) in depth.
10.3.4 Delamination Repair:
10.3.4.1 Document repair procedures for delaminations. The contractor may utilize a procedure only after receiving approval
from the purchaser designated in the contract. The contractor should be aware and fully understand, however that should the
TABLE 1 First Article Specimens
Requirements Test
Inspection Quantity
Subsection Subsection
Adhesive 50 coupons 4.2 10.1
Sealer 50 coupons 4.3 10.1
Core material:
Density 5 for every grade or 4.4 10.2.1
type
Compressive strength 5 for every grade or 4.4 10.2.2
type
Flammability 5 for every grade or 4.4 10.2.3
type
Water absorption 3 for every grade or 4.4 10.2.4
type of urethane
Shear strength 5 for every grade or 4.4 10.2.5
type
Lift and tie down device 1 complete 9.2 10.28
Impact panel 1 for every type core 9.3 10.29
E1974 − 19
purchaser later determine that the procedure is objectionable or inadequate, or its implementation does not fulfill its intended
purpose, the purchaser may require that its use be discontinued and another consultation be held to resolve the inadequacy.
10.3.4.2 The maximum area of any single delamination and the maximum number of single delaminations per panel allowed
is stated in 5.2. Multiple delaminations on a panel shall be separated by a structural member in order for that panel to be considered
eligible for repair. A delamination on the interior side of a panel and another delamination on the exterior side of the same panel
and with both delaminations being between the same two members shall not be considered separated.
10.4 Cleaning Inspection—Inspection of the cleaning process shall be in accordance with Practice E1773 and SC-B-595539.
Any noncompliance shall require re-cleaning of the parts processed since the last acceptable inspection.
10.5 Welding Inspection—Visually inspect arc welding in accordance with the requirements of maintenance sampling for
production in accordance with MIL-STD-2219. For resistance welding, fabrication and inspection of production specimens and
inspection of production parts shall be in accordance with SAE AMS-W-6858. Failure to meet the requirements of 5.5, with
sub-paragraphs, shall constitute failure of this test.
10.6 Riveting Inspection—Examine riveted joints or rivnuts for tightness, the joined parts for damage, and for the rivet/rivnut
heads to be properly seated and tight against their bearing surfaces. Replace rivets/rivnuts not meeting the requirements of 5.6 with
properly installed rivets/rivnuts and then reinspect as specified above.
10.7 Moisture Resistance Test—Subject the shelter with doors open to the moisture resistance test of MIL-STD-810E, Method
507.3, Procedure II. After cycling has been completed, there shall be no evidence of delamination, cracking, corrosion, or
deterioration to any part of the shelter and there shall be no malfunction of doors, latches, hinges, or any other hardware. Failure
to meet the requirements of 5.7 and 6.2 shall constitute failure of this test.
10.8 Finish Inspection—Inspect finish in accordance with the quality assurance provisions of MIL-F-14072 including paint
adhesion, and 10.12 of this specification. Failure to meet the requirements of 5.8 shall constitute failure of this test.
10.9 Marking Inspection—Visually inspect marking to determine compliance with 5.9. Failure to meet the requirements of 5.9
shall constitute failure of this test.
10.10 Interchangeability Inspection—Gauge or measure the dimensions listed below to determine compliance with the physical
interchangeability requirements of 5.10. When a dimension is not within specified or design limits, it shall be considered a defect:
10.10.1 Dimension of doors and door openings,
10.10.2 Mounting dimensions of hinges and latches,
10.10.3 Size and mounting dimensions of skids,
10.10.4 Size and mounting dimensions of towing eyes,
10.10.5 Size and mounting dimensions of lifting eyes,
10.10.6 Dimensions of drain and drain plug, and
10.10.7 Check padlocks and keys for proper operation. Keys (four) shall be checked against at least three different padlocks.
10.11 Dimensional Inspection—Inspect the shelters and panels for conformance with the drawings in the following areas (see
Footnotes A and B of Table 2):
10.11.1 Items listed in Table 2,
10.11.2 Interior and exterior dimensions,
10.11.3 Location and visibility of punch marks for mounting members. Verify location at the individual panel stage of
fabrication, and
10.11.4 Verify locations of holes on painted interior shelter panel surfaces at the shelter assembled stage of fabrication.
10.12 Visual and Mechanical Inspection—Examine equipment for the requirements of construction (see Section 5). Comply
with the item requirements listed in MIL-STD-252, Type 4, 5, 7, 8, 9 and 11 defects only. Further, classify a shelter weight above
the required maximum (see 5.12) as a major defect.
10.13 Shelter Weight Test—Determine compliance with 5.12 by weighing on a platform beam or dial indicator scale. The
platform of the scale shall be of sufficient extent so as to allow the placement of the entire shelter on it. The beam or indicator shall
have 1 lb (6 0.5 (60.5 kg) or less graduations. The scale shall have an accuracy of at least 61 lb (6 0.5 (60.5 kg) or one-sixth
of 1 % of full scale reading, whichever is smaller. Calibrate the scale at least twice per month using standard weights traceable
to the National Institute for Standards and Technology. Failure to meet the requirements of 5.12 shall constitute failure of this test.
10.14 Temperature Test—Place the shelter, with both doors and the louver cover closed and with the drain hole closed in a
manner acceptable to the purchaser in a temperature controlled room and subjected to the tests of 10.24.1 and 10.24.2. Measure
air temperature by ten thermocouples located in accordance with Fig. 2. Outside thermocouples shall be provided with radiation
shields of aluminum foil between the thermocouple and radiation surface. Air circulation shall not exceed a velocity of 7 miles
per hour (11 kg/h) at 3 in. (75 mm) away from any shelter surface. Conduct inspection to determine compliance with 5.13 after
completion of each test.
10.14.1 Operating Temperature—Stabilize the air temperature inside and outside the shelter at 120 to 125°F125 °F (49 to
52°C)52 °C) for a period of 5 min, during which time check the doors and latches for ease of operation and freedom from binding.
E1974 − 19
TABLE 2 Dimensional Inspection
Inspection Drawing Flatness Required
A
Frame flatness Within 0.03 in.
Torque required:
Door handle torque SM-D-649953 Small door 10 ft-lb (14 j)
Large door 15 ft-lb (20 j)
Door handle torque SM-D-649951 Small door 20 ft-lb (27 j)
(Shielded shelter) Large door 25 ft-lb (34 j)
Deviation allowed:
B C D
Shelter flatness , SM-D-563754 3 out of 36
B, C D
Shelter flatness SM-D-563754 3 out of 36
B C EF
Shelter squareness , SM-D-563754 6 out of 36
B, C E, F
Shelter squareness SM-D-563754 6 out of 36
A
Flatness of doors and openings at gasket and contact surfaces. This shall be
inspected by checking the flatness of the four sides and the flatness at the corners
using a straight edge. JO-Blocks, dial indicator height gagegauge or surface plate,
or both. Flatness shall be within 0.030 in. (1 mm) total.
B
Method of measurement and tolerances with tools and gagesgauges used shall
be subjected to approval by the purchaser technical activity designated in the
contract.
C
The purchaser technical activity designated in the contract shall be notified by
the contractor 15 days before this inspection is to be performed.
D
Four deviations out of the 36 interior measurements on any one sample shall be
cause for rejection of the shelter.
E
Seven deviations out of the 36 interior measurements on any one sample shall
be cause for rejection of the shelter.
F
More than two deviations in any one corner of the shelter be cause for rejection
of the shelter.
NOTE 1—A = Outside T.C.s approximately 10 inin. (250 mm) from corners.
NOTE 2—B = Inside T.C.s as shown
FIG. 2 Thermocouple Location on Sidewalls
Then subject the exterior of the shelter roof panel to an additional simulated solar load applied as rapidly as possible to produce
a temperature of 195°F (90°C)195 °F (90 °C) (minimum) on the outside skin of the roof panel as measured by 12 thermocouples
located in accordance with Fig. 3. Obtain the simulated solar load using at least 28 lamps, type 1000T3, 230 volts. Arrange the
lamps in four rows of seven lamps each and operate within 10 % of rated voltage. Maintain the 120 to 125°125° F (49 to
52°C)52 °C) ambient air temperature plus the roof solar load for a period of 4 h at which time remove the solar load and increase
the air temperature both inside and outside the shelter to 160 – 0 + 5°F5 °F (71 – 0 + 3°C)3 °C) (as measured by the ten
Commercially available from several sources.
E1974 − 19
A
TABLE 3 Sequence of First Article Inspection
Inspection Requirements Test
Subsection Subsection
Cleaning 5.4 10.4
Welding 5.5 10.5
Lamination 5.2 10.3
Interchangeability 5.10 10.10
Riveting 5.6 10.6
Construction tightness 8.4 10.24
Finish 5.8 10.8
Marking 5.9 10.9
Dimensional (in accordance with 5.1 10.11
stated drawing
Visual and mechanical 5.1 10.12
Shelter weight 5.12 10.13
Door latch torque 8.2 10.22
B
Moisture resistance 6.2 10.7
Temperature 6.3 10.14
Heat transfer 6.4 10.15
Rail transport 7.2.1 10.16
C
Drops 7.3 10.18
D,E
Construction tightness 8.4 10.24
D, E
Construction tightness 8.4 10.24
Towing, simulated 7.4 10.19
Lifting and towing eye pulls 7.5 10.20
Lift transport, simulated 7.2.2 10.17
Steps, roof access 7.6 10.21
Light tightness 8.7 10.27
EMI shielding 8.3 10.23
Watertightness 8.5 10.25
Fording 8.6 10.26
Door latch torque (second time) 8.2 10.22
A
First article sample testing and shelter testing shall not begin until at least seven
days after the sealer application, including application of touch-up sealer.
B
First article specimen testing shall be completed no later than the end of this test
(see 11.1.1). This inspection shall not begin until at least seven days after final
finish application including touch-up paint.
C
See Note 10 of Table 7.
D
For correlation data purposes only. CTT (construction tightness test) results are
not to be used as accept/reject criteria for the drop test.
E
Door portion and gasket portion only.
thermocouples of Fig. 2) as rapidly as possible and maintain for 5 min. Then completely remove the shelter from the heated
chamber to an ambient temperature between 60 and 85°F85 °F (16 and 29°C).29 °C).
NOTE 2—The length and position of the thermocouple’s wires shall permit complete removal. Open the shelter drain hole prior to shelter removal.
10.14.2 Storage Test—Subject the shelter alternately to Method 501.4 and Method 502.4 of MIL-STD-810EF, except perform
three cycles of each test (high temperature and low temperature). The cycles shall range from 160°F (71°C)160 °F (71 °C) for the
high temperature tests and –80°F (–62°C)–80 °F (–62 °C) for low temperature tests (as measured by the ten thermocouples of Fig.
2). In addition, all doors and latches shall operate freely without binding at either temperature extreme.
10.15 Heat Transfer Test—Place the shelter in a temperature controlled room that is at a constant temperature of –40 + 5°F5 °F
(–40 + 3°C)3 °C) outside the shelter. The walls and ceiling of the chamber shall be a minimum distance of 2 ⁄2 ft (750 mm) from
the walls and ceiling of the shelter. Place a 3KW electric coil open frame heater at the center of the shelter floor. Place a multi-speed
10 or 12 in. (250 or 300 mm) diameter fan 6 in. (150 mm) in the back of the heater such as to direct air through the heater toward
the front of the shelter at an inclined angle of 15 degrees. Maintain a stabilized temperature inside the shelter of not less than 100°F
(38°C)100 °F (38 °C) above the outside. Air circulation shall not exceed a velocity of seven miles per hour (11 kg/h) at 3 in. (75
mm) away from any shelter surface. Stabilize electrical power input and temperatures when the inside and outside groups of
thermocouples each vary less than 2 ⁄2 °F (1.5°C) °F (1.5 °C) while maintaining the minimum differential of 100°F (38°C)100 °F
(38 °C) located in accordance with Fig. 2. Temperature and electrical power input stabilization for at least 30 min. In the stabilized
condition the el
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...