This document specifies the requirements and test methods for the safety and efficiency of gas fired air heaters with or without a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances".
This standard also applies to warm air heaters having forced draught burners.
This European Standard applies to Type A2, A3 appliances, with an input not exceeding 300 kW (net CV basis), intended for non-domestic use.
This European Standard also applies to Type B11, B11AS, B11BS, B12, B12AS, B12BS, B13, B13AS, B13BS, B14, B14AS, B14BS, B22, B23, B41, B41AS, B41BS, B42, B42AS, B42BS, B43, B43AS, B43BS, B44, B44AS, B44BS, B52, B53, C11, C12, C13, C21, C31, C32, C33, C41, C62 and C63 appliances with an input not exceeding 300 kW (net CV basis), intended for domestic and non-domestic use.
Provision of the heated air may be by means of ducting.
This European Standard does not apply to:
a)   dual purpose air conditioning appliances (heating and cooling);
b)   appliances where the air is heated by an intermediate fluid;
c)   portable or transportable forced convection appliances;
d)   appliances fitted with manual or automatic means of adjusting the combustion products evacuation by means of flue dampers;
e)   appliances having multiple heating units with a single draught diverter;
f)   appliances fitted with more than one flue outlet;
g)   appliances fitted with gas boosters;
h)   C21 and C41 appliances for 3rd family gases.
NOTE   For C41 appliances, see all requirements and test methods that are valid for C21 appliances, unless otherwise stated.
This European Standard is not intended to cover appliances projected for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance.
This European Standard is applicable to appliances which are intended to be type tested.

  • Standard
    193 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the additional requirements and test methods for gas-fired air heaters
which are designed so that water vapour condenses from combustion products. On this subject, it extends
the European Standards EN 778 and EN 1319 for domestic air heaters, and EN 1020 for non-domestic air
heaters.
This European Standard applies to gas-fired air heaters with or without a fan in the combustion circuit in
one of the following constructional types:
- an integral air heater with at least one condensing heat exchanger;
- a non-condensing air heater with an integrated additional condensing heat exchanger;
- a non-condensing air heater, with an integrated additional condensing heat exchanger for the recovery
of heat from combustion products and from ventilation air if appropriate.
This European Standard covers type-testing only.

  • Standard
    20 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the safety and efficiency of domestic gas-fired air heaters with a fan to assist the transportation of combustion air and/or combustion products, hereafter referred to as appliances.
This European Standard applies to Type B12, B12AS, B12BS, B13, B13AS, B13BS, B14, B14AS, B14BS, B22, B23, B42, B42AS, B42BS, B43, B43AS, B43BS, B44, B44AS, B44BS, B52, B53, C12, C13, C32, C33, C62 and C63 appliances with an input not exceeding 70 kW (net cv basis), intended primarily for use in single unit residential dwellings.  Provision of the heated air may be by means of ducting.
This standard does not apply to:
a)   appliances of the condensing type;
b)   appliances for outdoor installation;
c)   dual purpose air conditioning appliances (heating and cooling);
d)   appliances where the air is heated by an intermediate fluid;
e)   appliances with forced draught package burners or fully premixed burners;
f)   appliances fitted with a manual means of adjusting the combustion air supply or the evacuation of the combustion products;
g)   portable or transportable forced convection appliances;
h)   appliances having multiple heating units with a single draught diverter;
i)   appliances fitted with more than one flue outlet;
j)   Type C22, C23, C42, C43, C52 and C53 appliances;
k)   appliances that are designed for continuous condensation within the flue system under normal operating conditions;
l)   appliances having combustion products evacuation ducts, POCEDs, that are non-metallic.
This standard is applicable to appliances which are intended to be type tested. It also includes requirements concerning the evaluation of conformity, including factory production control, but these requirements only apply to POCEDs and their associated terminals.

  • Standard
    152 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the safety and efficiency of non-domestic gas-fired air heaters not exceeding a net heat input of 300 kW with (an) atmospheric burner(s) and without a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances".
This European Standard applies to Type B11, B41, C11 and C31 appliances intended for use in other than single unit residential dwellings. Provision of the heated air may be by means of ducting or may be directly into the heated space.
This standard does not apply to:
a)    appliances intended for use in a single unit residential dwelling;
b)    appliances of the condensing type;
c)    appliances for outdoor installation;
d)    dual purpose air conditioning appliances (heating and cooling);
e)    appliances where the air is heated by an intermediate fluid;
f)    appliances with forced draught burners;
g)    appliances fitted with a manual or automatic means of adjusting the combustion air supply or the combustion products evacuation (including flue dampers);
h)    portable or transportable forced convection appliances;
i)    appliances having multiple heating units with a single draught diverter;
j)    appliances fitted with more than one flue outlet;
k)   appliances that are designed for continuous condensation within the flue system under normal operating conditions;
l)   appliances having combustion products evacuation ducts, POCEDs, that are non-metallic.
This standard is applicable to appliances which are intended to be type tested.  It also includes requirements concerning the evaluation of conformity, including factory production control, but these requirements only apply to POCEDs and their associated terminals.
NOTE   Requirements for appliances which are not type tested would need to be subject to further consideration.

  • Standard
    112 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the safety and efficiency of non-domestic gas-fired air heaters having a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances". This includes appliances having forced draught burners.
This European Standard applies to Type B12, B13, B14, B22, B23, B42, B43, B44, B52, B53, C12, C13, C32, C33, C62 and C63 appliances with a heat input not exceeding 300 kW (based on net calorific value) intended for use in other than single unit residential dwellings. It also applies to appliances intended for outdoor installation. Provision of the heated air may be by means of ducting or may be directly into the heated space.
For Type C62 and C63 appliances, this European Standard only applies when such appliances are intended for final installation in a similar manner to Type C3 appliances.
This standard does not apply to:
a)   appliances intended for use in a single unit residential dwelling;
b)   appliances of the condensing type;
c)   appliances with atmospheric burners without a fan to assist the transportation of combustion air and/or flue gases;
d)   dual purpose air conditioning appliances (heating and cooling);
e)   appliances where the air is heated by an intermediate fluid;
f)   appliances fitted with manual or automatic flue dampers;
g)   portable or transportable forced convection appliances;
h)   appliances having multiple heating units with a single draught diverter;
i)   appliances fitted with more than one flue outlet;
j)   appliances that are designed for continuous condensation within the flue system under normal operating conditions;
k)   appliances having combustion products evacuation ducts, POCEDs, that are non-metallic.
This standard is applicable to appliances which are intended to be type tested. It also includes requirements concerning the evaluation of conformity, including factory production control, but these requirements only apply to ...

  • Standard
    152 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the safety and efficiency of domestic gas-fired air heaters with (an) atmospheric burner(s) and without a fan to assist the transportation of combustion air and/or flue gases, hereafter referred to as "appliances".
This European Standard applies to Type B11, B11AS, B11BS, B41, B41AS, B41BS C11, C21, C31 and C41 appliances with an input not exceeding 70 kW (net cv-basis), intended primarily for use in single unit residential dwellings. Provision of the heated air may be by means of ducting.
This European Standard does not apply to:
a)   appliances of the condensing type;
b)   appliances for outdoor installation;
c)   dual purpose air conditioning appliances (heating and cooling);
d)   appliances where the air is heated by an intermediate fluid;
e)   appliances with forced draught burners;
f)   appliances fitted with a manual or automatic means of adjusting the combustion air supply or the combustion products evacuation (including flue dampers);
g)   portable or transportable forced convection appliances;
h)   appliances having multiple heating units with a single draught diverter;
i)   appliances fitted with more than one flue outlet;
j)   C21 and C41 appliances for 3rd family gases;
NOTE   For C41 appliances, see all requirements and test methods that are valid for C21 appliances, unless otherwise stated.
k)   appliances that are designed for continuous condensation within the flue system under normal operating conditions;
l)   appliances having Products Of Combustion Evacuation Ducts (POCED), that are non-metallic.
This European Standard is applicable to appliances which are intended to be type tested. It also includes requirements concerning the evaluation of conformity, including factory production control, but these requirements only apply to POCEDs and their associated terminals.

  • Standard
    128 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the safety of non-domestic direct
gas-fired forced convection air heaters having fully automatic control systems, hereafter referred to as
"appliances".
This European Standard applies to appliances of Type A2 and Type A3 with heat input based on the net
calorific value of 300 kW or less fitted with integral burners intended for use other than in residential dwellings.
It also applies to appliances designed for outdoor installation. For indoor appliances provision of the heated air
may be by means of ducting or may be directly into the heated space.
This standard does not apply to:
a) appliances intended for use in residential dwellings;
b) portable or transportable forced convection appliances;
c) appliances fitted with gas boosters;
d) appliances fitted with air/gas ratio controls;
e) appliances which incorporate a main burner having more than one section under a common burner
control, of which one or more sections may be extinguished whilst another section remains in operation.
This European Standard is applicable to appliances which are intended to be type tested.