SIST EN 13501-5:2006
(Main)Fire classification of construction products and building elements - Part 5: Classification using data from external fire exposure to roofs tests
Fire classification of construction products and building elements - Part 5: Classification using data from external fire exposure to roofs tests
This European Standard provides the fire performance classification procedures for roofs/roof coverings exposed to external fire based on the four test methods given in ENV 1187:2002.
For the classification of a roof/roof covering, only those test methods need to be applied for which the corresponding classification is envisaged.
Products are considered in relation to their end use application.
NOTE The distinction between roofs with a steep slope and facades, in terms of the test and classification standard to be applied, may be subject to national regulations.
General information on the four test methods in ENV 1187:2002 is given in Annex A.
Klassifizierung von Bauprodukten und Bauarten zu ihrem Brandverhalten - Teil 5: Klassifizierung mit den Ergebnissen aus Prüfungen von Bedachungen bei Beanspruchung durch Feuer von außen
Diese Europäische Norm legt das Verfahren zur Klassifizierung des Brandverhaltens von Bedachungen/Dachhäuten, die durch Feuer von außen entsprechend den vier Prüfverfahren nach ENV 1187:2002 beansprucht wurden, fest.
Zur Klassifizierung von Bedachungen/Dachhäuten brauchen nur diejenigen Prüfverfahren angewandt zu werden, für die eine entsprechende Klassifizierung angestrebt wird.
Produkte werden in ihrer praktischen Anwendung betrachtet.
ANMERKUNG Die Unterscheidung zwischen Steildächern und Fassaden bezüglich der Prüfnorm und der anzuwendenden Klassifizierungsnorm kann Gegenstand nationaler Regelungen sein.
Allgemeine Informationen zu den vier in ENV 1187:2002 aufgeführten Prüfverfahren sind Anhang A zu entnehmen.
Classement au feu des produits de construction et éléments de bâtiment - Partie 5: Classement utilisant des données d'essais au feu des toitures exposées a un feu extérieur
Cette partie de la Norme européenne spécifie les méthodes de classement de performance au feu des toitures/couvertures de toiture exposées a un feu extérieur basées sur les quatre méthodes d'essais données dans l'ENV 1187:2002.
Pour le classement des toitures/couvertures de toiture, seules ces méthodes d'essai nécessitent etre appliquées pour lesquelles le classement est envisagé.
Les produits sont considérés en relation avec leur application d'utilisation finale.
NOTE La distinction entre les toitures avec une pente prononcée et les façades, en termes de norme d'essai et de classement a appliquer, peut etre soumise a des réglementations nationales.
L'Annexe A fournit des informations générales sur les quatre méthodes d'essai de l'ENV 1187:2002.
Požarna klasifikacija gradbenih proizvodov in elementov stavb - 5. del: Klasifikacija na podlagi podatkov iz preskusov pri izpostavljenosti streh požaru z zunanje strani
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Požarna klasifikacija gradbenih proizvodov in elementov stavb - 5. del: Klasifikacija na podlagi podatkov iz preskusov pri izpostavljenosti streh požaru z zunanje straniKlassifizierung von Bauprodukten und Bauarten zu ihrem Brandverhalten - Teil 5: Klassifizierung mit den Ergebnissen aus Prüfungen von Bedachungen bei Beanspruchung durch Feuer von außenClassement au feu des produits de construction et éléments de bâtiment - Partie 5: Classement utilisant des données d'essais au feu des toitures exposées a un feu extérieurFire classification of construction products and building elements - Part 5: Classification using data from external fire exposure to roofs tests91.060.20StreheRoofs13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 13501-5:2005SIST EN 13501-5:2006en01-maj-2006SIST EN 13501-5:2006SLOVENSKI
STANDARD
SIST EN 13501-5:2006
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 13501-5December 2005ICS 13.220.50 English VersionFire classification of construction products and building elements- Part 5: Classification using data from external fire exposure toroofs testsClassement au feu des produits et éléments deconstruction - Partie 5: Classement à partir des résultatsdes essais d'exposition des toitures à un feu extérieurKlassifizierung von Bauprodukten und Bauarten zu ihremBrandverhalten - Teil 5: Klassifizierung mit denErgebnissen aus den Dachprüfungen bei Feuer von außenThis European Standard was approved by CEN on 22 September 2005.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2005 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 13501-5:2005: ESIST EN 13501-5:2006
EN 13501-5:2005 (E) 2 Contents Page Foreword.3 Introduction.4 1 Scope.5 2 Normative references.5 3 Terms and definitions.5 4 Classes of external fire performance of roofs/roof coverings.8 5 Test methods.9 5.1 General.9 5.2 Test 1: Method with burning brands.9 5.3 Test 2: Method with burning brands and wind.9 5.4 Test 3: Method with burning brands, wind and supplementary radiant heat.9 5.5 Test 4: Two stage method incorporating burning brands, wind and supplementary radiant heat.9 6 Principles for specimen preparation, testing and classification.9 6.1 General requirements for specimen preparation.9 6.2 General requirements for testing.10 6.3 Selection of test methods.10 6.4 Specific requirements.11 7 Number of tests for classification.15 8 Classification parameters.16 8.1 Test 1.16 8.2 Test 2.16 8.3 Test 3.16 8.4 Test method 4.16 9 Classes and criteria.17 10 Classification report.19 10.1 General.19 10.2 Content and format.19 Annex A (informative)
General information on the four test methods in ENV 1187:2002.21 Annex B (normative)
Classification report for roofs/roof coverings exposed to external fire.22 B.1 General layout.22 B.2 Introduction.22 B.3 Description of the roof/roof covering.22 B.4 Test reports and test results in support of this classification.23 B.5 Classification and field of application.26 B.6 Limitations.27
SIST EN 13501-5:2006
EN 13501-5:2005 (E)
3 Foreword This European Standard (EN 13501-5:2005) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by June 2006, and conflicting national standards shall be withdrawn at the latest by June 2006. This European Standard has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of the Construction Products Directive. CEN, CENELEC and EOTA committees preparing technical specifications which contain performance requirements against external fire exposure of roofs should make reference to the classification given in this European Standard and not refer directly to any specific fire test method. EN 13501 consists of the following parts: Part 1: Classification using data from reaction to fire tests, Part 2: Classification using data from fire resistance tests, excluding ventilation services, Part 3: Classification using data from fire resistance tests on components of normal building service installations: fire resisting ducts and fire dampers Part 4: Classification using data from fire resistance tests on components of smoke control systems, Part 5: Classification using data from external fire exposure to roof tests. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
SIST EN 13501-5:2006
EN 13501-5:2005 (E) 4 Introduction The aim of this European Standard is to define a harmonized procedure for the classification of roofs/roof coverings exposed to external fire. This classification is based on the test methods listed in Clause 5. This European Standard has been prepared in support of the second essential requirement in the EC Construction Products Directive (89/106/EEC) and as detailed in the Interpretative Document Number 2: Safety in case of fire (OJ C62 Vol. 37). The European Commission has drawn up a list of products which, under specified conditions, may be considered to be Class BROOF without testing. This information is given in the Commission Decision of 2000-09-06 establishing the list of products belonging to Classes BROOF (Decision 2000/553/EC). SIST EN 13501-5:2006
EN 13501-5:2005 (E)
5 1 Scope This European Standard provides the fire performance classification procedures for roofs/roof coverings exposed to external fire based on the four test methods given in ENV 1187:2002. For the classification of a roof/roof covering, only those test methods need to be applied for which the corresponding classification is envisaged. Products are considered in relation to their end use application. NOTE The distinction between roofs with a steep slope and facades, in terms of the test and classification standard to be applied, may be subject to national regulations. General information on the four test methods in ENV 1187:2002 is given in Annex A. 2 Normative references The following referenced documents are indispensable for the application of this European Standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ENV 1187:2002, Test methods for external fire exposure to roofs EN 13501-1, Fire classification of construction products and building elements - Part 1: Classification using test data from reaction to fire tests EN ISO 13943:2000, Fire safety — Vocabulary (ISO 13943:2000) 3 Terms and definitions For the purposes of this European Standard, the terms and definitions given in EN ISO 13943:2000 and the following apply. 3.1 roof covering and sealing system, including any insulating layers or vapour barriers normally provided together with their supporting elements including attachment (glued, mechanically fastened etc.), and roof lights or other closures for roof apertures that are intended to provide a weatherproof surface [ENV 1187:2002] 3.2 material basic single substance or uniformly dispersed mixture of substances (e.g. metal, stone, wood, bitumen, concrete, mineral wool) [ENV 1187:2002] 3.3 damaged material material that has been burnt, charred, melted or otherwise visually changed by heat. Discolouration and soot deposits are not to be regarded as damaged material [ENV 1187:2002] SIST EN 13501-5:2006
EN 13501-5:2005 (E) 6 3.4 burnt material material that has been destroyed by combustion or pyrolysis [ENV 1187:2002] 3.5 composite combination of materials which is generally recognized in building construction as a discrete entity (e.g. coated or laminated products such as roofing felts) [ENV 1187:2002] 3.6 assembly fabrication of materials and/or composites (e.g. sandwich panels) [ENV 1187:2002] 3.7 product material, composite or assembly about which information is required [ENV 1187:2002] 3.8 specimen representative section of the roof/roof covering prepared for the purpose of the test [ENV 1187:2002] 3.9 continuous deck element with a continuous supporting function in which the nominal gap between adjacent elements is not greater than 0,5 mm (5,0 ± 0,5 mm in the case of wooden planks with plain edges) (for test 1 and test 3) [ENV 1187:2002] 3.10 exposed surface external surface of the specimen which is subject to the heating conditions of the test [ENV 1187:2002] 3.11 measuring zone area of the specimen within which measurements are made [ENV 1187:2002] 3.12 underside bottom surface of the specimen [ENV 1187:2002] SIST EN 13501-5:2006
EN 13501-5:2005 (E)
7 3.13 sustained flaming flames arising from an observed location, which persist for 5 s or longer [ENV 1187:2002] 3.14 external fire spread progression and extent of sustained flaming across the exposed surface of the specimen [ENV 1187:2002] 3.15 fire penetration appearance on the underside of the specimen of any sustained flaming or glowing due to combustion, including the occurrence of any flaming droplets falling from the underside. Charring and/or discolouration are not to be regarded as fire penetration (for tests 1 and 3) [ENV 1187:2002] 3.16 opening appearance during the test of any hole greater than 25 mm² in area or any crack greater than 2 mm wide, which penetrates completely through the specimen and which would allow burning materials to fall through the roof (for tests 1 and 3) [ENV 1187:2002] 3.17 internal damage extent of damaged material in each layer inside the specimen, measured from the edges of the projection of the ignition source in the upwards and downwards directions with respect to the pitch of the roof (for tests 1 and 3) [ENV 1187:2002] 3.18 fire spread within the roof/internal fire spread maximum burnt length measured from the upper edge of the projection of the ignition source in the upward direction and from the lower edge in the downward direction of each layer for sloped roofs, and in any direction for horizontal roofs (pitch of 0°) (for tests 1 and 3) [ENV 1187:2002] 3.19 flaming droplets or debris burning material falling from the specimen that continues to burn on the floor for at least 5 s [ENV 1187:2002] 3.20 joint any kind of connection or link within a layer in the roof, such as an overlap or seam [ENV 1187:2002] SIST EN 13501-5:2006
EN 13501-5:2005 (E) 8 3.21 roof covering uppermost layer of a roof. This layer can comprise single layer or multiple layer coverings [ENV 1187:2002] 3.22 damaged length length of damaged material of the roof covering and of the substrate respectively, expressed in mm as measured from the centre of the wood crib position (for test 2) [ENV 1187:2002] 3.23 substrate product which is used immediately beneath the roof covering about which information is required (for test 2) [ENV 1187:2002] 3.24 roof pitch inclination of the roof surface to the horizontal [ENV 1187:2002] 3.25 external fire spread time (TE) time for external fire spread to the edge of the measuring zone (for test 3) 3.26 time to fire penetration (Tp) time for fire penetration as defined in 3.15 3.27 non-combustible substrate or deck substrate or deck classified A1 or A2-s1,d0 according to EN 13501-1 (for the purpose of this European Standard only) 3.28 combustible substrate or deck substrate or deck not satisfying the definition of ‘non-combustible substrate or deck’ in 3.27 3.29 penetration by fire appearance on the underside of the specimen of any flaming or glowing other than that of the test flame (test 4 only), disregarding any test flame appearing through pre-existing openings in the test specimen 4 Classes of external fire performance of roofs/roof coverings The classification set out in this European Standard is based upon the test methods contained in ENV 1187:2002. That standard incorporates four distinct test methods that correspond to different fire hazard scenarios. There is no direct correlation between the test methods and hence no generally acceptable hierarchy of classification between them. SIST EN 13501-5:2006
EN 13501-5:2005 (E)
9 Products classified in a given class are deemed to satisfy all the requirements of any lower class for the same test method/fire hazard scenario. The classes with their corresponding fire performance are given in Table1. 5 Test methods 5.1 General The four test methods given in ENV 1187 are those to be used for classification purposes for roofs/roof coverings. The selection of the tests to be carried out is specified in 6.3. The classification parameters, the classes and the corresponding criteria are specified in Clauses 8 and 9. 5.2 Test 1: Method with burning brands The test evaluates the performance of a roof under the conditions of thermal attack with burning brands. The performance includes the fire spread across the external surface of the roof, the fire spread within the roof and the fire penetration. 5.3 Test 2: Method with burning brands and wind The test evaluates the performance of a roof covering under the conditions of thermal attack with burning brands and additional wind. The performance includes damaged length both on the roof covering and in the substrate. 5.4 Test 3: Method with burning brands, wind and supplementary radiant heat The test evaluates the performance of a roof under the conditions of thermal attack with burning brands, additional wind and radiant heat. The performance includes the external fire spread and the fire penetration. 5.5 Test 4: Two stage method incorporating burning brands, wind and supplementary radiant heat The test evaluates the performance of a roof under the conditions of thermal attack with burning brands, wind and radiant heat. The performance includes the external fire spread and the penetration by fire. 6 Principles for specimen preparation, testing and classification 6.1 General requirements for specimen preparation Before testing, the test specimens shall be prepared and conditioned and, where relevant, mounted in accordance with the relevant test method and product standards or other technical specifications. The external fire performance of a roof/roof covering includes such aspects as external and internal fire spread, external and internal damage, fire penetration and the occurrence of flaming droplets or debris. The external fire performance of a roof/roof covering therefore does not only depend on the burning behaviour of the exposed surface, the roof covering, but also on the influences of several components of the roof, such as the nature and thickness of insulating layers and vapour barriers together with their supporting elements. It may also depend on the systems of attachment of all components, e.g. glued or mechanically fastened. Therefore, the test specimens shall be representative, in all details of practical application with regard to: SIST EN 13501-5:2006
EN 13501-5:2005 (E) 10 a) substrate and deck; b) type, the number and the joining of all layers of roofing materials (including any insulation, vapour barriers, etc.); c) fixing of the layers. In order to reduce the amount of testing, individual test methods specify standard specimen arrangements, covering a wider field of application. Such standard specifications concern e.g. the supporting decks and substrates, and the types and positioning of joints. 6.2 General requirements for testing The external fire performance of a roof/roof covering does not only depend on the intrinsic properties of its components and the fire attack conditions, but also to a large extent on the pitch of the roof. In order to reduce the amount of testing, some standard pitches are defined, covering a wider field of application. However, in tests 1 and 3 a sponsor may choose none of the standard pitches, although this will limit the field of application of the classification to the pitch used for testing. 6.3 Selection of test methods Four different test methods, representing four different scenarios, are specified in ENV 1187. The methods assess the fire performance of roofs/roof coverings under the following conditions: a) test 1 assesses the performance of a roof under attack with burning brands; b) test 2 assesses the performance of a roof covering under attack with burning brands and wind; c) test 3 assesses the performance of a roof under attack with burning brands, wind and supplementary radiant heat; d) test 4 assesses the performance of a roof using a two stage test method incorporating burning brands, wind and supplementary radiant heat. The choice of the test method(s) to be applied depends on the classification envisaged by the sponsor. If only a classification BROOF (t1) is envisaged (see Table 1), only test 1 with burning brands is carried out. If only a classification BROOF (t2) is envisaged (see Table 1), only test 2 with burning brands and wind is carried out. If only a classification BROOF (t3) or CROOF (t3) or DROOF (t3) is envisaged (see Table 1), only test 3 with burning brands, wind and supplementary radiant heat is carried out. If only a classification BROOF(t4) or CROOF(t4) or DROOF(t4) or EROOF(t4) is envisaged (see Table 1), only test 4: two stage test method incorporating burning brands, wind and supplementary radiant heat is carried out. If more than one classification is required, all the corresponding tests are carried out, as there is no direct correlation between the test methods and hence, no generally accepted hierarchy of classification between them. SIST EN 13501-5:2006
EN 13501-5:2005 (E)
11 6.4 Specific requirements 6.4.1 General Each test specifies a series of standard specimen compositions and test conditions covering a wider field of direct application. The number of specimens to be prepared as well as the number of tests to be carried out depends on the envisaged field of application of the classification. Variables are the pitch of the roof, the deck and/or substrate applied for the test and the inclusion of joints. 6.4.2 Test 1 6.4.2.1 General Tests to be carried out are chosen to cover the envisaged field of direct application according to 6.4.2.5. 6.4.2.2 Pitch The standard test pitches are 15° and 45°. Tests may also be done at the actual intended pitch. 6.4.2.3 Nature of the deck The standard supporting decks for tests are specified in ENV 1187: a) wood particle board deck, constructed from planks 250 mm wide × 16 mm thick, density (680 ± 50) kg/m³ with plain edges and tightly but jointed so that gaps between planks do not exceed 0,5 mm; b) deck from wood particle board planks as under a) with plain edges with gaps of (5,0 ± 0,5) mm; c) deck of 10 mm thick reinforced calcium silicate board, dry density (680 ± 50) kg/m3; d) trapezoidal profiled steel deck; e) without any continuous deck. Tests may also be done with the actual intended deck. The classification so obtained is valid only for the deck tested. Table B.1 indicates how the deck can be selected taking into account the envisaged field of application. For each type of deck for which a classification is required, four test specimens are tested out of five types specified in 6.4.2.4 as shown in Table 1 of ENV 1187:2002. 6.4.2.4 Positioning of joints To assess the influence of the joints on the performance of the roof, five standard specimen types are defined out of which four shall be tested, details of which are given in ENV 1187. For every test on a given roof, four specimens are tested. SIST EN 13501-5:2006
EN 13501-5:2005 (E) 12 6.4.2.5 Direct field of application of test results 6.4.2.5.1 Pitch Test results obtained at 15° apply to roofs with pitches < 20°. Test results obtained at 45° apply to roofs with pitches ≥ 20°. Test results obtained at a single specified pitch other than 15° or 45° apply to roofs for that pitch only. 6.4.2.5.2 Nature of the deck Test with standard supporting decks Test results obtained with standard supporting decks shall apply to all systems with the same components (including the thickness) installed in the same way, but with different decks as follows. a) Test results obtained with a wood particle board deck with gaps between planks not
exceeding 0,5 mm apply to: any wooden continuous deck with a minimum thickness of 16mm and with gaps not exceeding 0,5 mm; any non-combustible continuous deck with a minimum thickness of 10 mm. b) Test results obtained with a wood particle board deck with gaps of (5,0 ± 0,5) mm
between planks, apply to: any wooden continuous deck; any non-combustible deck with gaps not exceeding 5 mm. c) Test results obtained with a reinforced calcium silicate board apply to: any non-combustible continuous deck with a minimum thickness of 10 mm. d) Test results obtained with a trapezoidal profiled steel deck apply to: any profiled and non-perforated steel deck; any non-combustible continuous deck with a minimum thickness of 10 mm. e) Test results obtained without any continuous deck apply to systems without continuous deck only. Test with alternative supporting deck Test results obtained with an alternative supporting deck apply only to that roof system (i.e. the constitution, materials, dimensions of components, thickness etc. are identical). 6.4.3 Test 2 6.4.3.1 General Tests to be carried out are chosen to cover the envisaged field of direct application according to 6.4.3.4. SIST EN 13501-5:2006
EN 13501-5:2005 (E)
13 6.4.3.2 Pitch The standard test pitch is 30°. 6.4.3.3 Nature and selection of the substrate The standard substrates are: a) wood particle board (not fire retardant treated), density (680 ± 50) kg/m³, (19 ± 2) mm thick; b) expanded polystyrene (EPS) (not fire retardant treated), density (20 ± 5) kg/m³, (50 ± 10) mm thick; c) fibre reinforced calcium silicate board, density (680 ± 50) kg/m³, (10 ± 2) mm thick; d) mineral wool, density (150 ± 20) kg/m³, (50 ± 10) mm thick. Table B.2 indicates how the substrate can be selected taking into account the envisaged direct field of application. Tests may be carried out using the end use substrate but in this case the test result obtained is applicable for this end use only. 6.4.3.4 Direct field of application of test results a) Test results obtained with a pitch of 30° are valid for all pitches. b) Test results obtained for a roof covering attached to a substrate apply only for the roof covering on substrates having a density greater than or equal to 0,75 times the density used in the test. c) Test results obtained on a non-combustible standard substrate apply only for non-combustible substrates which also comply with 6.4.3.4 b). d) Test results obtained on a combustible standard substrate apply to combustible and non-combustible substrates which also comply with 6.4.3.4 b). e) Test results obtained on a non-standard substrate apply only to that substrate which also complies with 6.4.3.4 b). 6.4.4 Test 3 6.4.4.1 General Tests to be carried out are chosen to cover the envisaged field of direct application according to 6.4.4.4. 6.4.4.2 Pitch The standard test pitches are 5° and 30°. Tests may also be done at the actual intended pitch. The classification so obtained is valid for that pitch only. 6.4.4.3 Nature of the deck The standard decks are: a) wood particle board deck, constructed from planks 250 mm wide × 16 mm thick having a density of (680 ± 50) kg/m³ with plain edges and tightly but jointed so that gaps between planks do not exceed 0,5 mm; b) deck from wood particle board planks as under a) with plain edges with gaps of (5 ± 0,5) mm; SIST EN 13501-5:2006
EN 13501-5:2005 (E) 14 c) deck of (12 ± 2) mm thick reinforced calcium silicate board of dry density (680 ± 50) kg/m³; d) trapezoidal profiled steel deck; e) without any continuous deck. Tests may also be done with the actual intended deck. The classification so obtained is valid only for the deck tested. Table B.3 indicates how the deck can be selected taking into account the envisaged direct field of application. 6.4.4.4 Direct field of application of test result 6.4.4.4.1 Pitch Test results obtained at 5° apply to roofs with pitches < 10°. Test results obtained at 30° apply to roofs with pitches ≥ 10° and ≤ 70°. Test results obtained at an alternative specified pitch apply to roofs for that pitch only. 6.4.4.4.2
Nature of the deck Test with standard supporting decks Test results obtained with standard supporting decks shall apply to all systems with the same components (including the thickness) install
...