IEC 61557-1:2007
(Main)Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements
Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements
This part of IEC 61557 specifies the general requirements for measuring and monitoring equipment for testing the electrical safety in low voltage distribution systems with nominal voltages up to 1 000 V a.c. and 1 500 V d.c. When measuring equipment or measuring installations involve measurement tasks of various measuring equipment covered by this series of standards, then the part of this series of standards relevant to each of the measurement tasks is applicable. This second edition replaces and cancels the first edition published in 1997. It constitutes a technical revision. The following changes were made with respect to the previous edition: a) revision of the definitions; b) addition of influence quantities E9 and E10; c) the subclause on Electromagnetic compatibility was complemented; d) inclusion of performance monitoring devices in the introduction; e) addition of new requirements for operating instructions.
Sécurité électrique dans les réseaux de distribution basse tension de 1 000 V c.a. et 1 500 V c.c. - Dispositifs de contrôle, de mesure ou de surveillance de mesures de protection - Partie 1: Exigences générales
La présente partie de la CEI 61557 établit les exigences générales applicables aux dispositifs de mesure et de surveillance destinés au contrôle de la sécurité électrique dans des installations à basse tension de 1 000 V c.a. et 1 500 V c.c. Lorsque des appareils ou des dispositifs de mesure réalisent des mesures pour lesquelles différents appareils de cette série de normes sont prévus, la partie appropriée de cette série de normes est applicable au type de mesure correspondant. Cette deuxième édition annule et remplace la première édition publiée en 1997. Elle constitue une révision technique. Les principales modifications apportées par cette nouvelle édition sont les suivantes: a) Révision des définitions; b) Ajout des grandeurs d'influence E9 et E10; c) Paragraphe relatif à la compatibilité électromagnétique complété; d) Prise en compte des dispositifs de surveillance de performance dans l'introduction; e) Introduction d'exigences nouvelles pour les instructions de fonctionnement.
General Information
Relations
Standards Content (Sample)
NORME CEI
INTERNATIONALE
IEC
61557-1
INTERNATIONAL
Deuxième édition
STANDARD
Second edition
2007-01
Sécurité électrique dans les réseaux
de distribution basse tension de 1 000 V c.a.
et 1 500 V c.c. –
Dispositifs de contrôle, de mesure ou de
surveillance de mesures de protection –
Partie 1: Exigences générales
Electrical safety in low voltage distribution
systems up to 1 000 V a.c. and 1 500 V d.c. –
Equipment for testing, measuring
or monitoring of protective measures –
Part 1: General requirements
Numéro de référence
Reference number
CEI/IEC 61557-1:2007
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE
IEC
61557-1
INTERNATIONAL
Deuxième édition
STANDARD
Second edition
2007-01
Sécurité électrique dans les réseaux
de distribution basse tension de 1 000 V c.a.
et 1 500 V c.c. –
Dispositifs de contrôle, de mesure ou de
surveillance de mesures de protection –
Partie 1: Exigences générales
Electrical safety in low voltage distribution
systems up to 1 000 V a.c. and 1 500 V d.c. –
Equipment for testing, measuring
or monitoring of protective measures –
Part 1: General requirements
© IEC 2007 Droits de reproduction réservés ⎯ Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
Q
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61557-1 © CEI:2007
SOMMAIRE
AVANT-PROPOS .4
INTRODUCTION.8
1 Domaine d’application.10
2 Références normatives .10
3 Termes et définitions .12
4 Exigences.20
4.1 Incertitude de fonctionnement (B), incertitude de fonctionnement en
pourcentage (B [%]).22
4.2 Conditions de fonctionnement assignées .24
4.3 Dispositif de contrôle de la pile .24
4.4 Bornes.24
4.5 Classe de protection .24
4.6 Degré de pollution .24
4.7 Catégorie de surtension.24
4.8 Catégorie de mesure .24
4.9 Compatibilité électromagnétique .26
4.10 Essai de vibrations .26
5 Marquages et instructions de fonctionnement.26
5.1 Marquage .26
5.2 Instructions de fonctionnement .28
6 Essais .28
6.1 Influence de la position .28
6.2 Influence de la température .28
6.3 Influence de la tension d’alimentation.30
6.4 Dispositif de contrôle de la pile .30
6.5 Classe de protection .30
6.6 Bornes.30
6.7 Exigences mécaniques .30
6.8 Marquages et instructions de fonctionnement.30
Bibliographie .32
61557-1 © IEC:2007 – 3 –
CONTENTS
FOREWORD.5
INTRODUCTION.9
1 Scope.11
2 Normative references.11
3 Terms and definitions .13
4 Requirements .21
4.1 Operating uncertainty (B), percentage operating uncertainty (B [%]) .23
4.2 Rated operating conditions .25
4.3 Battery check facility.25
4.4 Terminals .25
4.5 Class of protection.25
4.6 Class of pollution .25
4.7 Overvoltage category.25
4.8 Measuring category .25
4.9 Electromagnetic compatibility.27
4.10 Vibration test .27
5 Marking and operating instructions.27
5.1 Marking .27
5.2 Operating instructions.29
6 Tests .29
6.1 Influence of position.29
6.2 Influence of temperature.29
6.3 Influence of the supply voltage.31
6.4 Battery check facility.31
6.5 Protection class .31
6.6 Terminals .31
6.7 Mechanical requirements .31
6.8 Marking and operating instructions.31
Bibliography .33
– 4 – 61557-1 © CEI:2007
COMMISSION ELECTROTECHNIQUE INTERNATIONALE
____________
SÉCURITÉ ÉLECTRIQUE DANS LES RÉSEAUX DE DISTRIBUTION
BASSE TENSION DE 1 000 V c.a. ET 1 500 V c.c. –
DISPOSITIFS DE CONTROLE, DE MESURE OU DE SURVEILLANCE
DE MESURES DE PROTECTION –
Partie 1 : Exigences générales
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des comités d'études,
aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent également aux
travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La norme internationale CEI 61557-1 a été établie par le comité d’études 85 de la CEI :
Equipement de mesure des grandeurs électriques et électromagnétiques.
Cette deuxième édition annule et remplace la première édition publiée en 1997. Elle constitue
une révision technique.
Les principales modifications apportées par cette nouvelle édition sont les suivantes:
a) Révision des définitions
b) Ajout des grandeurs d’influence E et E
9 10
c) Paragraphe relatif à la compatibilité électromagnétique complété
d) Prise en compte des dispositifs de surveillance de performance dans l’introduction
e) Introduction d’exigences nouvelles pour les instructions de fonctionnement
61557-1 © IEC:2007 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTRICAL SAFETY IN LOW VOLTAGE DISTRIBUTION SYSTEMS
UP TO 1 000 V a.c. AND 1 500 V d.c. –
EQUIPMENT FOR TESTING, MEASURING OR MONITORING
OF PROTECTIVE MEASURES –
Part 1: General requirements
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61557-1 has been prepared by IEC technical committee 85:
Measuring equipment for electrical and electromagnetic quantities.
This second edition replaces and cancels the first edition published in 1997. It constitutes a
technical revision.
The following changes were made with respect to the previous edition:
a) revision of the definitions
b) addition of influence quantities E and E
9 10
c) the subclause on Electromagnetic compatibility was complemented
d) inclusion of performance monitoring devices in the introduction
e) addition of new requirements for operating instructions
– 6 – 61557-1 © CEI:2007
Le texte de cette norme est issu des documents suivants :
FDIS Rapport de vote
85/290/FDIS 85/300/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée conformément aux Directives ISO/CEI, Partie 2.
Une liste de toutes les parties de la série CEI 61557, présentées sous le titre général Sécurité
électrique dans les réseaux de distribution basse tension de 1 000 V c.a. et 1 500 V c.c. –
Dispositifs de contrôle, de mesure ou de surveillance de mesures de protection, peut être
consultée sur le site web de la CEI.
La présente Partie 1 donne les exigences générales. Les Parties 2 à 8 de la série CEI 61557,
qui doivent être utilisées conjointement avec la présente Partie 1, comprennent des exigences
spécifiques aux appareils de mesure individuels.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date du
résultat de la maintenance indiquée sur le site web de la CEI à l’adresse suivante:
"http://webstore.iec.ch", dans les données liées à la publication spécifique. A cette date, la
publication sera:
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
61557-1 © IEC:2007 – 7 –
The text of this standard is based on the following documents:
FDIS Report on voting
85/290/FDIS 85/300/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 61557 series, published under the general title Electrical safety in
low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. – Equipment for testing,
measuring or monitoring of protective measures, can be found on the IEC website.
This Part 1 specifies the general requirements. Parts 2 to 8 of IEC 61557, which are to be used
in conjunction with this Part 1, comprise specific specifications for individual measuring
equipment.
The committee has decided that the contents of this publication will remain unchanged until the
maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 8 – 61557-1 © CEI:2007
INTRODUCTION
La CEI 60364-6:2006, stipule les conditions normalisées du contrôle initial des installations de
distribution dans les réseaux TN, TT ou IT (CEI 60364), pour la surveillance permanente et
pour effectuer les essais de ces installations après modification. La CEI 60364-6 contient,
outre des indications d’ordre général relatives à la réalisation des essais, toute une série
d’exigences qui ont été vérifiées par des mesures. Dans certains cas seulement, comme par
exemple pour ce qui est de la mesure de la résistance d’isolement, la norme contient quelques
indications précises concernant les propriétés des appareils de mesure qui ont été utilisés.
Les circuits de mesure présentés dans la CEI 60364-6 à titre d’exemple ne sont généralement
pas adaptés à un usage pratique.
Les contrôles sont effectués dans des installations à tensions dangereuses où une
imprudence ou une panne peuvent facilement être à l’origine d’un accident. Le contrôleur est
donc tenu d’utiliser des appareils de mesure qui non seulement simplifient la réalisation des
mesures mais qui lui garantissent également un mesurage sûr.
L’application des normes de sécurité habituelles relatives aux appareils de mesure électriques
et électroniques (CEI 61010-1) est insuffisante en ce qui concerne les appareils destinés au
contrôle des dispositifs de protection. Lors des essais effectués dans des installations et, en
fonction de la méthode de mesure utilisée, des risques peuvent exister tant pour le contrôleur
lui-même que pour des tierces personnes.
De même, l’obtention de résultats de mesure comparables avec des appareils de mesure de
différents constructeurs lors de la remise d’une installation, de contrôles périodiques, de
contrôle permanent de l’isolement et en cas de prestations de garantie est une condition
importante pour porter un jugement objectif sur une installation.
Le but de cette série de normes est de définir des principes communs pour des dispositifs de
mesure et de surveillance destinés à contrôler la sécurité électrique et mesurer les
performances dans des réseaux à tensions nominales au plus égales à 1 000 V c.a. et 1 500 V
c.c. correspondant aux caractéristiques mentionnées plus haut.
Pour ces raisons, les exigences communes suivantes ont été stipulées dans la Partie 1 et les
exigences individuelles dans les différentes parties de série de normes.
– protection contre les tensions extérieures;
– classe de protection II (à l’exception des contrôleurs d’isolement);
– exigences et mesures de sécurité contre les risques que font encourir des tensions de
contact dangereuses sur l’objet de la mesure;
– exigences relatives à l’appréciation des configurations de branchement par rapport aux
incertitudes de câblage dans l’installation contrôlée;
– exigences mécaniques particulières;
– méthodes de mesure;
– grandeur mesurée
– exigences relatives à l’écart maximal de mesure en utilisation;
– exigences relatives aux contrôles des grandeurs d’influence et au calcul de l’écart de
mesure;
– prise en considération des incertitudes de mesure des appareils à l’intérieur des valeurs
limites qui sont prescrites par la norme de construction;
– spécification de la nature des essais de type et des essais individuels et conditions
requises pour ces différents essais.
61557-1 © IEC:2007 – 9 –
INTRODUCTION
IEC 60364-6:2006, stipulates standardized conditions for the initial test of power installations in
TN, TT or IT (IEC 60364) systems, for continuous monitoring and for testing these installations
after modifications. In addition to general references for the execution of the tests,
IEC 60364-6 contains requirements which have to be verified by measurement. Only in a few
instances, for example when measuring the insulation resistance, the standard contains details
of the characteristics of the measuring device to be used. Circuits which are given as examples
in IEC 60364-6, and referred to within the text, are generally not suitable for practical use.
The tests are carried out in installations where hazardous voltages can occur and where
careless use or a defect in the equipment can easily cause an accident. Therefore, the
technician has to rely on measuring devices which ensure, apart from simplification of the
measurements, safe test methods.
The application of the general safety regulations for electrical and electronic measuring devices
(IEC 61010-1) for testing the protective measures is not sufficient in itself. The execution of
measurements in the installation can cause hazards not only to the technician, but, depending
on the measuring method, also to third persons.
Likewise, reliable and comparable results of measurement with measuring devices from
different manufacturers are an important precondition in order to obtain an objective judgement
about the installation, for example when the installation is handed over for periodic tests, for
continuous insulation monitoring or in the case of performance warranty.
This series of standards has been established with the aim of stipulating common principles for
and measuring performances in
measuring and monitoring equipment for testing electrical safety
systems with nominal voltages up to 1 000 V a.c. and 1 500 V d.c. which correspond to the
above-mentioned characteristics.
For this reason, the following common specifications have been stipulated in Part 1 and other
individual parts of the series of standards:
– protection against extraneous voltages;
– protection class II (except insulation monitoring devices);
– specifications and safety precautions against hazardous touch voltages at the measuring
device;
– specifications for the judgement of connection configurations with respect to wiring errors
in the tested equipment;
– special mechanical requirements;
– measuring methods;
– measured quantity;
– specification of the maximum operating uncertainty;
– specifications for testing the influencing quantity and the calculation of the operational
uncertainty;
– uncertainties of the measuring device at the thresholds specified in the respective
standards;
– specification of the nature of type and routine tests and the required conditions for testing.
– 10 – 61557-1 © CEI:2007
SÉCURITÉ ÉLECTRIQUE DANS LES RÉSEAUX DE DISTRIBUTION
BASSE TENSION DE 1 000 V c.a. ET 1 500 V c.c. –
Dispositifs de contrôle, de mesure ou de surveillance
de mesures de protection –
Partie 1 : Exigences générales
1 Domaine d’application
La présente partie de la CEI 61557 établit les exigences générales applicables aux dispositifs
de mesure et de surveillance destinés au contrôle de la sécurité électrique dans des
installations à basse tension de 1 000 V c.a. et 1 500 V c.c.
Lorsque des appareils ou des dispositifs de mesure réalisent des mesures pour lesquelles
différents appareils de cette série de normes sont prévus, la partie appropriée de cette série de
normes est applicable au type de mesure correspondant.
NOTE Le terme «appareil de mesure» sera dorénavant utilisé pour désigner un «dispositif de contrôle, de mesure
et de surveillance».
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références non
datées, c'est l'édition la plus récente du document référencé (y compris tous ses
amendements).qui s’applique.
1)
CEI 60038:1983 , Tensions normales de la CEI
Amendement 1:1994
Amendement 2:1997
CEI 60364-6:2006, Installations électriques des bâtiments - Partie 6 : Vérification
CEI 60664-1, Coordination de l'isolement des matériels dans les systèmes (réseaux) à basse
tension – Partie 1: Principes, prescriptions et essais
CEI 60529: 2001, Degrés de protection procurés par les enveloppes (Code IP).
CEI 61010-1:2001, Règles de sécurité pour appareils électriques de mesurage, de régulation et
de laboratoire – Partie 1 : Prescriptions générales
CEI 61010-2-030, Règles de sécurité pour appareils électriques de mesurage, de régulation et
2)
de laboratoire – Partie 2-030 : Exigences particulières pour les circuits de test et de mesure
CEI 61326-2-2:2005, Matériel électrique de mesure, de commande et de laboratoire –
Exigences relatives à la CEM – Partie 2-2 : Exigences particulières – Configurations d’essai,
conditions de fonctionnement et critères d’aptitude à la fonction des matériels portatifs d’essai, de
mesure et de surveillance utilisés dans des systèmes de distribution basse tension
––––––––
1)
Il existe une édition consolidée (6.2), qui comprend la CEI 60038:1983 et ses Amendements 1 (1994) et 2 (1997).
2)
A publier
61557-1 © IEC:2007 – 11 –
ELECTRICAL SAFETY IN LOW VOLTAGE DISTRIBUTION SYSTEMS
UP TO 1 000 V a.c. AND 1 500 V d.c. –
EQUIPMENT FOR TESTING, MEASURING OR MONITORING OF
PROTECTIVE MEASURES –
Part 1: General requirements
1 Scope
This part of IEC 61557 specifies the general requirements for measuring and monitoring
equipment for testing the electrical safety in low voltage distribution systems with nominal
voltages up to 1 000 V a.c. and 1 500 V d.c.
When measuring equipment or measuring installations involve measurement tasks of various
measuring equipment covered by this series of standards, then the part of this series of
standards relevant to each of the measurement tasks is applicable.
NOTE The term "measuring equipment" will hereafter be used to designate "testing, measuring and monitoring
equipment".
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
1)
IEC 60038:1983 , IEC standard voltages
Amendment 1: 1994
Amendment 2: 1997
IEC 60364-6:2006, Electrical installations of buildings – Part 6: Verification
IEC 60664-1, Insulation coordination for equipment within low-voltage systems - Part 1:
Principles, requirements and tests
IEC 60529: 2001, Degrees of protection provided by enclosures (IP code)
IEC 61010-1:2001, Safety requirements for electrical equipment for measurement, control and
laboratory use – Part 1: General requirements
IEC 61010-2-030, Safety requirements for electrical equipment for measurement, control, and
2)
laboratory use – Part 2-030: Special requirements for testing and measuring circuits
IEC 61326-2-2:2005, Electrical equipment for measurement, control and laboratory use – EMC
requirements – Part 2-2: Particular requirements – Test configurations, operational conditions
and performance criteria for portable test, measuring and monitoring equipment used in low-
voltage distribution systems
––––––––
1)
There exists a consolidated edition (6.2), which includes IEC 60038:1983 and its Amendments 1 (1994) and 2
(1997).
2)
To be published.
– 12 – 61557-1 © CEI:2007
CEI 61326-2-4:2006, Matériel électrique de mesure, de commande et de laboratoire –
Exigences relatives à la CEM – Partie 2-4 : Exigences particulières – Configurations d’essai,
conditions de fonctionnement et critères d’aptitude à la fonction pour les dispositifs de surveillance
d’isolation en accord avec la CEI 61557-8 et pour les équipements de localisation de défaut d’isolation
en accord avec la CEI 61557-9
CEI 61557-2, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 2: Résistance d’isolement
CEI 61557-3, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 3: Impédance de boucle
CEI 61557-4, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 4: Résistance de conducteurs de terre et d’équipotentialité
CEI 61557-5, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 5: Résistance à la terre
CEI 61557-6, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 6: Dispositifs différentiels résiduels (DDR) dans des réseaux TN et TT
CEI 61557-7, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 7: Ordre de phases
CEI 61557-8, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 8: Contrôleurs d'isolement pour réseaux IT
CEI 61557-9, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V c.a.
et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 9: Dispositifs de localisation de défauts d'isolement pour réseaux IT
CEI 61557-10, Sécurité électrique dans les réseaux de distribution basse tension de 1000 V
c.a. et 1500 V c.c. – Dispositifs de contrôle, de mesure ou de surveillance de mesures de
protection – Partie 10: Appareils combinés de contrôle, de mesure ou de surveillance des
mesures de protection
3 Termes et définitions
Pour les besoins du présent document, les définitions suivantes s'appliquent.
3.1
tension nominale du réseau de distribution (U ):
n
tension par laquelle un réseau de distribution ou un matériel est dénommé et à laquelle
certaines caractéristiques de fonctionnement sont rattachées
[CEI 60038, Article 1, modifié]
61557-1 © IEC:2007 – 13 –
IEC 61326-2-4:2006, Electrical equipment for measurement, control and laboratory use, - EMC
requirements - Part 2: Particular requirements – Test configurations, operational conditions and
performance criteria for insulation monitoring devices according to IEC 61557-8 and for
equipment for insulation fault location according to IEC 61557-9
IEC 61557-2, Electrical safety in low voltage distribution systems up to 1000 V a.c.
and 1500 V d.c. – Equipment for testing, measuring or monitoring of protective measures –
Part 2: Insulation resistance
IEC 61557-3, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 3: Loop
impedance
IEC 61557-4, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 4:
Resistance of earth connection and equipotential bonding
IEC 61557-5, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 5:
Resistance to earth
IEC 61557-6, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 6: Residual
current devices (RCD) in TT and TN systems
IEC 61557-7, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 7: Phase
sequence
IEC 61557-8, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 8: Insulation
monitoring devices for IT systems
IEC 61557-9, Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V
d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 9:
Equipment for insulation fault location in IT systems
IEC 61557-10, Electrical safety in low voltage distribution systems up to 1000 V a.c. and
1500 V d.c. – Equipment for testing, measuring or monitoring of protective measures – Part 10:
Combined measuring equipment for testing, measuring or monitoring of protective measures
3 Terms and definitions
For the purposes of this document, the following definitions apply.
3.1
nominal voltage of the distribution system (U )
n
voltage by which a distribution system or equipment is designated and to which certain
operating characteristics are referred
[IEC 60038, Clause 1, modified]
– 14 – 61557-1 © CEI:2007
3.2
tension de service dans un réseau de distribution
valeur de la tension en service normal à un instant et en un lieu donnés de ce réseau de
distribution
[VEI 601-01-22, modifié]
3.3
tension par rapport à la terre
U
o
a) dans un réseau de distribution dont le point neutre est mis à la terre, la tension d’un
conducteur de phase par rapport au point neutre mis à la terre;
b) dans les autres types de réseaux de distribution, la tension qui apparaît entre la terre et les
phases restantes lorsque l’une des phases est mise à la terre
3.4
tension de défaut
U
f
tension apparaissant, lors d’une condition de défaut entre des parties conductrices accessibles
(et/ou des parties conductrices externes) et terre
3.5
tension de contact (efficace)
U
t
tension entre des parties conductrices lorsqu’elles sont touchées simultanément par une
personne ou un animal
[VEI 826-11-05]
3.6
tension limite conventionnelle de contact
U
L
valeur maximale de la tension de contact qu’il est admis de pouvoir maintenir indéfiniment
dans des conditions spécifiées d’influences externes et qui est égale habituellement à une
valeur efficace de 50 V c.a., ou 120 V c.c. libre d’ondulation
[VEI 826-02-04, modifiée]
3.7
domaine assigné de tensions
domaine de tension auquel le dispositif de mesure et surveillance est destiné et pour lequel il a
été conçu
3.8
tension d’alimentation assignée;
U
S
tension d’un appareil de mesure là où il prend, ou peut prendre, l’énergie électrique nécessaire
à son fonctionnement
3.9
tension de sortie
U
a
tension qui existe entre les bornes d’un appareil de mesure à l’endroit où cet équipement
délivre ou peut délivrer une énergie électrique
61557-1 © IEC:2007 – 15 –
3.2
operating voltage in a system
the value of the voltage under normal conditions, at a given instant and a given point of the
system
[IEV 601-01-22, modified]
3.3
voltage against earth
U
o
a) in distribution systems with an earthed neutral point, the voltage between a phase conductor
and the earthed neutral point;
b) in all other distribution systems, the voltage present between the remaining phase
cond
...