IEC 60079-26:2014
(Main)Explosive atmospheres - Part 26: Equipment with Equipment Protection Level (EPL) Ga
Explosive atmospheres - Part 26: Equipment with Equipment Protection Level (EPL) Ga
IEC 60079-26:2014 specifies alternative requirements for construction, test and marking for electrical equipment that provides Equipment Protection Level (EPL) Ga when single standardised Types of Protection (e.g. Ex "ia", Ex "ma", Ex "da") cannot be applied. This standard also applies to equipment mounted across a boundary where different Equipment Protection Levels may be required. This electrical equipment, within the operational parameters specified by the manufacturer, ensures a very high Level of Protection that includes rare malfunctions related to the equipment or two malfunctions occurring independently of each other. This standard supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. This third edition cancels and replaces the second edition published in 2006 and constitutes a technical revision. The numerous changes are identified in the Foreword of the document. Keywords: Equipment Protection Level (EPL) Ga
Atmosphères explosives - Partie 26: Matériel d'un niveau de protection du matériel (EPL) Ga
IEC 60079-26:2014 spécifie les exigences alternatives relatives à la construction, aux essais et au marquage du matériel électrique fournissant le niveau de protection du matériel (EPL, Equipment Protection Level) Ga lorsque des types normalisés uniques de Protection (comme par ex. Ex "ia", Ex "ma", Ex "da") ne peuvent pas être appliqués. La présente norme s'applique au matériel installé en chevauchement sur des emplacements pour lesquels différents niveaux de protection du matériel peuvent être exigés.Ce matériel électrique assure, dans les limites des paramètres de fonctionnement spécifiés par le constructeur, un très haut niveau de protection prenant en compte le cas de rares dysfonctionnements liés au matériel, ou d'apparition simultanée de deux dysfonctionnements indépendants l'un de l'autre. La présente norme complète et modifie les exigences générales de l'IEC 60079-0. Lorsqu'une exigence de la présente norme entre en contradiction avec une exigence de l'IEC 60079-0, l'exigence de la présente norme prévaut. Cette troisième édition annule et remplace la deuxième édition parue en 2006 et constitue une révision technique. Les nombreux changements sont identifiés dans l'avant-propos du document. Mots clés: protection du matériel (EPL) Ga
General Information
Relations
Overview
IEC 60079-26:2014 - Explosive atmospheres - Part 26: Equipment with Equipment Protection Level (EPL) Ga - specifies alternative construction, test and marking requirements for electrical equipment that must provide EPL Ga when a single standardized Type of Protection (for example Ex “ia”, Ex “ma”, Ex “da”) cannot be applied. EPL Ga corresponds to the very high level of protection required for Zone 0 (explosive gas atmosphere present continuously or for long periods). This third edition (2014) supplements and modifies IEC 60079-0 and takes precedence where the two standards conflict.
Key topics and technical requirements
- Scope and intent: Defines requirements for equipment that ensures protection against rare malfunctions and combinations of two independent malfunctions under manufacturer‑specified operational parameters. Applicable also where equipment is mounted across a boundary between zones (e.g., Zone 0 / Zone 1).
- Design and construction: Alternative measures where single standardized Types of Protection are infeasible. Topics include intrinsic safety, encapsulation, separation elements and construction rules for moving parts.
- Separation elements and process connections: Requirements and type tests for separation elements that prevent gas diffusion; process connections must provide sufficiently tight joints (IP66 added as an alternative to IP67 in this edition).
- Type tests and temperature evaluation: Defines tests to demonstrate compliance for separation elements and temperature assessment under specified conditions.
- Marking and instructions: Requirements for marking examples, EPL allocation and user information (including material specification for partition walls and guidance for separation elements and process connections).
- Relationship to IEC 60079-0: This part supplements/modifies general requirements; where conflicts exist, IEC 60079-26 takes precedence.
Practical applications
- Equipment that must operate inside Zone 0 but is mounted at a boundary with less-hazardous areas (e.g., sensors, transmitters, or actuators installed in vessel walls).
- Design of enclosures, feedthroughs and separation barriers where conventional single protection methods are not practical.
- Situations requiring documented type tests and marking to prove a very high level of protection for continuous explosive atmospheres.
Who should use this standard
- Electrical equipment designers and manufacturers targeting Zone 0 applications
- Certification and conformity assessment bodies
- Plant engineers, safety managers and procurement specialists in oil & gas, chemical and pharmaceutical industries
- Test laboratories and regulatory inspectors verifying EPL Ga claims
Related standards and keywords
- Related: IEC 60079-0 (general requirements for explosive atmospheres) and other parts of the IEC 60079 series (Types of Protection such as Ex “ia”, “ma”, “da”).
- Keywords: Equipment Protection Level Ga, EPL Ga, explosive atmospheres, Zone 0, separation element, process connection, intrinsic safety, encapsulation, IEC 60079-26:2014.
Standards Content (Sample)
IEC 60079-26 ®
Edition 3.0 2014-10
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
Explosive atmospheres –
Part 26: Equipment with Equipment Protection Level (EPL) Ga
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
IEC Catalogue - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
The stand-alone application for consulting the entire The world's leading online dictionary of electronic and
bibliographical information on IEC International Standards, electrical terms containing 21 000 terms and definitions in
Technical Specifications, Technical Reports and other English and French, with equivalent terms in 16 additional
documents. Available for PC, Mac OS, Android Tablets and languages. Also known as the International Electrotechnical
iPad. Vocabulary (IEV) online.
IEC publications search - webstore.iec.ch/advsearchform IEC Glossary - std.iec.ch/glossary
The advanced search enables to find IEC publications by a 67 000 electrotechnical terminology entries in English and
variety of criteria (reference number, text, technical French extracted from the Terms and Definitions clause of
committee,…). It also gives information on projects, replaced IEC publications issued since 2002. Some entries have been
and withdrawn publications. collected from earlier publications of IEC TC 37, 77, 86 and
CISPR.
IEC Just Published - webstore.iec.ch/justpublished
Stay up to date on all new IEC publications. Just Published IEC Customer Service Centre - webstore.iec.ch/csc
details all new publications released. Available online and If you wish to give us your feedback on this publication or
also once a month by email. need further assistance, please contact the Customer Service
Centre: sales@iec.ch.
IEC 60079-26 ®
Edition 3.0 2014-10
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
Explosive atmospheres –
Part 26: Equipment with Equipment Protection Level (EPL) Ga
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 29.260.20 ISBN 978-2-8322-1912-6
– 2 – IEC 60079-26:2014 RLV © IEC 2014
CONTENTS
FOREWORD . 4
1 Scope . 7
2 Normative references . 8
3 Terms and definitions . 8
4 Requirements for design and construction . 8
4.1 General .
4.1 Protection measures against ignition hazards of the electrical circuits. 8
4.1.1 General . 8
4.2.2 Intrinsic safety as a sole means of protection.
4.2.3 Encapsulation as a sole means of protection .
4.1.2 Application of two independent Types of Protection providing EPL Gb . 9
4.1.3 Application of a Type of Protection providing EPL Gb and a separation
element . 10
4.2 Equipment with moving parts . 14
4.2.1 Frictional heating . 14
4.2.2 Damage arising from failure of moving parts . 14
4.2.3 Light metals . 15
4.4 Isolated conductive components .
4.5 Non-conductive enclosures and accessible non-conductive components .
4.5.1 General .
4.5.2 Limitation of the size of chargeable non-conductive surfaces .
4.5.3 Limitation of the thickness of chargeable non-conductive layers .
4.5.4 Provision of a conductive coating.
4.3 Process connection . 16
5 Type tests . 16
5.1 Standardized types of protection . 16
5.2 Separation elements . 17
5.3 Temperature evaluation . 17
6 Marking . 17
6.1 General . 17
6.2 Examples of marking . 17
7 Information for use .
7 Instructions . 18
7.1 Separation elements: . 18
7.2 Process connection: . 18
7.3 EPL allocation . 18
Annex A (informative) Introduction of an alternative risk assessment method
encompassing “equipment protection levels” for Ex equipment .
Bibliography . 23
Figure 1 – Example of a partition wall with a conductor bushing considered as gas
diffusion tight . 11
Figure 2 – Example of a separation element with a cylindrical shaft joint and
naturalventilation . 14
Table 1 – Separation elements . 13
– 4 – IEC 60079-26:2014 RLV © IEC 2014
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EXPLOSIVE ATMOSPHERES –
Part 26: Equipment with Equipment Protection Level
(EPL) Ga
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
This redline version of the official IEC Standard allows the user to identify the changes
made to the previous edition. A vertical bar appears in the margin wherever a change
has been made. Additions are in green text, deletions are in strikethrough red text.
International Standard IEC 60079-26 has been prepared by IEC technical committee 31:
Equipment for explosive atmospheres.
This third edition cancels and replaces the second edition published in 2006 and constitutes a
technical revision.
This edition includes the following significant changes with respect to the previous edition:
Type
Changes Clause Minor and Extension Major
editorial technical
changes changes
Notes deleted 1 X
Reference to associated apparatus deleted 1 X
Additional normative references included 3 X
Requirements against mechanical and
electrostatic ignition hazards deleted (now 4.1 X
covered in IEC 60079-0)
Requirement for separation element detailed
4.1.3.2 X
regarding external influences
Intrinsic safety Ex ia as single type of protection
4.2.2
including associated apparatus deleted (now X
(ed.2)
covered by EPL)
Encapsulation Ex ma as single type of protection 4.2.3
X
deleted (now covered by EPL) (ed.2)
Conditions a) and b) linked with an “and” ,
therefore requirement of “flameproof joint” deleted
in following clause. Both requirements already 4.3 X
covered by separation elements and standardised
process connections.
Process connection requires a sufficiently tight
4.3 X
joint: IP66 added alternatively to IP67
Requirement for isolated conductive components 4.4
X
deleted (now covered in IEC 60079-0) (ed.2)
Requirements for non-conductive enclosures 4.5
X
deleted (now covered in IEC 60079-0) (ed.2)
Test of partition walls according to 4.1.3.2 b) is
5.2 C1
specified in more detail
Marking example for associated apparatus deleted 6.2 b) X
Note 3 with an additional example added 6.2 X
Specification of material of partition wall required
7 X
in instructions (also required in 4.1.3.2)
Alternative risk assessment method deleted (is AnnexA
X
now generally introduced) (ed.2)
NOTE The technical changes referred to include the significance of technical changes in the revised IEC
Standard, but they do not form an exhaustive list of all modifications from the previous version.
Explanation of the types of changes:
A) Definitions
1) Minor and editorial changes:
• Clarification
• Decrease of technical requirements
• Minor technical change
• Editorial corrections
– 6 – IEC 60079-26:2014 RLV © IEC 2014
These are changes which modify requirements in an editorial or a minor technical way.
They include changes of the wording to clarify technical requirements without any
technical change, or a reduction in level of existing requirement.
2) Extension: Addition of technical options
These are changes which add new or modify existing technical requirements, in a way
that new options are given, but without increasing requirements for equipment that was
fully compliant with the previous standard.Therefore, these will not have to be
considered for products in conformity with the preceding edition.
3) Major technical changes:
• addition of technical requirements
• increase of technical requirements
These are changes to technical requirements (addition, increase of the level or
removal) made in a way that a product in conformity with the preceding edition will not
always be able to fulfil the requirements given in the later edition. These changes have
to be considered for products in conformity with the preceding edition. For these
changes additional information is provided in Clause B below.
NOTE These changes represent current technological knowledge. However, these changes should not
normally have an influence on equipment already placed on the market.
B) Information about the background of ‘Major technical changes’
C1: Introduction of type tests for separation elements according to “4.1.3.2 b)”
The text of this standard is based on the following documents:
FDIS Report on voting
31/1146/FDIS 31/1155/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60079 series, published under the general title Explosive
atmospheres, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
EXPLOSIVE ATMOSPHERES –
Part 26: Equipment with Equipment Protection Level
(EPL) Ga
1 Scope
This part of IEC 60079 specifies the particular alternative requirements for construction, test
and marking for electrical equipment that provides Equipment Protection Level (EPL) Ga
when single standardised Types of Protection (e.g. Ex “ia” , Ex “ma”, Ex “da”) cannot be
applied. This standard also applies to equipment mounted across a boundary where different
Equipment Protection Levels may be required.
EXAMPLE: Equipment installed in the wall of a storage vessel containing Zone 0 (requiring EPL Ga) inside an
area defined as Zone 1 (requiring EPL Gb).
This electrical equipment, within the operational parameters specified by the manufacturer,
ensures a very high Level of Protection that includes rare faults malfunctions related to the
equipment or two faults malfunctions occurring independently of each other.
NOTE A malfunction may result from a failure of the component parts of the electrical equipment or from
anticipated externally applied influences. Two independent malfunctions which may occur more frequently and
which, separately, would not create an ignition hazard but which, in combination, could create a potential ignition
hazard, should be are regarded as occurring together to form a rare fault malfunction.
NOTE 2 This electrical equipment is intended for use in zone 0 hazardous areas, in which explosive gas
atmospheres caused by mixtures of air and gases, vapours or mists under normal atmospheric conditions are
present continuously, for long periods or frequently.
This standard also applies to equipment mounted across a boundary where different
protection levels may be required.
EXAMPLE: In the wall of a storage vessel containing zone 0 with an ambient defined as zone 1.
This standard also applies to equipment installed in an area requiring a lower protection level,
but electrically connected to equipment with equipment protection level (EPL) Ga (associated
apparatus).
This standard supplements and modifies the general requirements of IEC 60079-0. Where a
requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of
this standard takes precedence. and the requirements of the standardized types of protection,
in accordance with the IEC 60079 series, to adapt the level of safety provided by those
standards in order to provide EPL Ga.
NOTE 3 In designing equipment for operation in explosive gas atmospheres under conditions other than the
atmospheric conditions given in IEC 60079-0, this standard may be used as a guide. However, additional testing is
recommended related specifically to the intended conditions of use. This is particularly important when the types of
protection ‘Flameproof enclosures’ (IEC 60079-1) and ‘Intrinsic safety’ (IEC 60079-11) are applied.
NOTE 4 The classification of hazardous areas in zones is defined in IEC 60079-10.
NOTE 5 There may be other non-electrical sources of ignition (for example ultrasonic, optical or ionizing radiation)
that are not addressed by this standard; these should also be taken into consideration (see, for example, EN 1127-1).
NOTE 6 This concept provides equipment protection level (EPL) Ga. For further information, see Annex A.
– 8 – IEC 60079-26:2014 RLV © IEC 2014
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60079-0:2004, Explosive atmospheres − Part 0: Equipment − General requirements
IEC 60079-1, Explosive atmospheres − Part 1: Equipment protection by flameproof enclosures
"d"
IEC 60079-10, Electrical apparatus for explosive gas atmospheres – Part 10: Classification of
hazardous areas
IEC 60079-11, Explosive atmospheres − Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-18, Electrical apparatus for explosive gas atmospheres – Part 18: Construction,
test and marking of type of protection encapsulation "m" electrical apparatus
IEC 60529, Degrees of protection provided by enclosures (IP Code)
IEC 60695-11-10, Fire hazard testing − Part 11-10: Test flames − 50 W horizontal and vertical
flame test methods
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60079-0 and the
following apply.
NOTE Additional definitions applicable to explosive atmospheres can be found in IEC 60050-426.
3.1
EPL
abbreviation of equipment protection level as defined in Annex A
3.1
separation element
mechanical element inside the equipment, which separates different parts of the equipment
with different EPLs
Note 1 to entry: A separation element consists of a mechanical partition wall, which may be combined with a
flameproof joint or a natural ventilation
4 Requirements for design and construction
4.1 General
The equipment shall comply with the requirements of 4.2 for the electrical circuits and with the
requirements of 4.3 to 4.6 for mechanical and electrostatic ignition hazards.
4.1 Protection measures against ignition hazards of the electrical circuits
4.1.1 General
The equipment shall comply with the requirements of either
a) 4.2.2 or 4.2.3 in the event of two faults occurring independently of each other in a single
equipment means of protection; or
b) 4.2.4 or 4.2.5 4.1.2 or 4.1.3 in the event of a failure of one equipment means of protection,
by the provision of a second independent means of protection.
NOTE 1 Types of Protection according to EPL Ga do not require a second independant means of protection, e.g.
Ex “ia” (IEC 60079-11), Ex “ma” (IEC 60079-18), Ex “da” (IEC 60079-1).
Electrical connections and permanently connected cables of the equipment sited within an
area requiring EPL Ga equipment shall comply with the same Level of Protection required by
this standard, for example an Ex “e” a cable suitable for EPL Gb containing non-Ex “ia”
circuits additionally protected by a flameproof conduit or an Ex “e” a cable suitable for EPL Gb
provided with earth leakage protection.
NOTE 2 Detailed cable and installation requirements for non Types of Protection accepted as achieving EPL Ga
beyond intrinsically safe circuits providing EPL Ga are under consideration in IEC 60079-14.
NOTE 3 Because of ignition hazards which can arise from faults and/or transient circulating currents in the
potential equalization system, galvanic isolation in the power and signal connections to the equipment according to
4.1.2 and 4.1.3 4.2.2, 4.2.3 and 4.2.4 is preferred. Consideration should also be given to minimize is commonly
applied along with minimizing the effect of transient fault currents in the potential equalization network by the use
of electrical protection equipment such as sensitive earth leakage monitors.
4.2.2 Intrinsic safety as a sole means of protection
Intrinsically safe electrical equipment providing EPL Ga and intrinsically safe electrical circuits
of associated apparatus entering an area requiring EPL Ga shall comply with the
requirements of IEC 60079-11, intrinsic safety “ia”.
NOTE Intrinsic safety “ib” in accordance with IEC 60079-11 may be considered as one of two independent means
of protection according to 4.2.4.
4.2.3 Encapsulation as a sole means of protection
Electrical equipment which is protected by encapsulation providing EPL Ga shall comply with
the requirements of IEC 60079-18, encapsulation “ma”.
NOTE Encapsulation “mb” in accordance with IEC 60079-18 may be considered as one of two independent means
of protection according to 4.2.4.
4.1.2 Application of two independent Types of Protection providing EPL Gb
Electrical equipment shall comply with the requirements of two independent Types of
Protection that provide EPL Gb. If one Type of Protection fails, the other Type of Protection
shall continue to function. The independent Types of Protection shall not have a common
mode of failure, except as specified in this clause. Combined types of protection providing
EPL Gb shall depend on different physical protection principles.
NOTE 1 An example of a common mode of failure is if an Ex “d” enclosure containing arcing contacts
components is used installed inside an Ex “e” enclosure. Should the Ex “d” enclosure be compromised, then
arcing inside the enclosure will it would also compromise the Ex “e” enclosure.
NOTE 2 Combined types of protection providing EPL Gb should depend on different physical protection principles.
For example The combination of Ex “d” and Ex “q” both depend on the avoidance of flame propagation (same
physical protection principle) and may not be useful in combination. In practice, some combinations may not be
useful, for example the combination of oil immersion “o” and powder filling “q”.
Where combined types of protection are used, it shall be possible for each Type of Protection
to be tested individually (see 5.1).
Both Types of Protection shall be assessed using the most arduous fault condition of the
other Type of Protection. When combining intrinsic safety, Type of Protection “ib”, with other
Types of Protection, the second Type of Protection shall be assessed, with the most arduous
– 10 – IEC 60079-26:2014 RLV © IEC 2014
fault condition applied to the intrinsically safe circuit. Thermal dissipation shall be considered
in case of a fault of one Type of protection.
When using two Types of Protection, which both rely on the same parameter (for example, the
creepage distance combining Ex “ib” with Ex “e”), the most stringent requirement of both
Types of Protection shall be applied.
If two Types of Protection are combined which both rely on the enclosure, one of the following
shall be met:
a) if two enclosures are used (one totally enclosed within the other), each enclosure shall
comply with the requirements of the respective Type of Protection; or
b) if only one enclosure is used, the enclosure and the cable glands shall meet the impact
test requirements of 26.4.2 of IEC 60079-0, using the Group I values.
Examples of relevant combinations of two independent Types of Protection are as follows:
– inductive transmitters (for example proximity switches, electrical position sensors) with
intrinsic safety “ib” enclosed by encapsulation “mb”. The connections to intrinsically safe
“ib” circuits can be protected by the increased safety “e”;
– a lamp with the bulb luminaire designed as increased safety “e”, the lamp circuit with the
switch as intrinsic safety “ib”. These components may be incorporated included in a
flameproof enclosure “d”;
– measuring transducers with intrinsic safety “ib” and a flameproof enclosure “d”;
– equipment with electrical circuits of intrinsic safety “ib”, additionally protected by powder
filling “q”;
– electromagnetic valves with encapsulation “mb”, enclosed by a flameproof enclosure “d”;
– increased safety “e”, with pressurized equipment “pxb”.
4.1.3 Application of a Type of Protection providing EPL Gb and a separation element
4.1.3.1 General
Equipment which is mounted through or forms part of the boundary wall to an area requiring
EPL Ga and contains electrical circuits which do not comply with protection level EPL Ga shall
comply with at least one of the Types of Protection providing EPL Gb. Additionally, it shall
contain a mechanical separation element as part of the equipment to seal off separate the
electrical circuits of the equipment from the area requiring EPL Ga.
If the Type of Protection fails, the separation element shall:
a) prevent flame propagation through the equipment into the area requiring EPL Ga,
b) maintain its safety characteristics,
c) not be heated above exceed the maximum surface temperature of the specified
temperature class of the equipment (see 5.3).
Separation elements consist of a partition wall, possibly combined with a flameproof joint or
an air gap with natural ventilation.
4.1.3.2 Partition walls
Partition walls shall be constructed of either:
a) corrosion-resistant metals, glass or ceramics, which are specified in the manufacturer’s
documentation; or
b) other materials which can be verified to provide the same level of safety. In this case, X-
marking or an advisory marking in accordance with 29.2 of IEC 60079-0 shall be applied
and the certificate shall clearly specify the material and its thermal and mechanical
properties to enable the user to confirm the suitability for the particular application the
certificate number shall include the "X" suffix in accordance with the marking requirements
of IEC 60079-0.
If the wall thickness is less than 1 mm, the equipment shall be marked with an “X” or an
advisory marking according to 29.2 of IEC 60079-0 with a special condition for safe use the
certificate number shall include the "X" suffix in accordance with the marking requirements of
IEC 60079-0 and the Specific Conditions of Use listed on the certificate shall indicate that the
material shall not be subject to environmental conditions which might adversely affect the
partition wall.
If the partition wall is under constant vibrational stress (for example vibrating membranes), the
minimum endurance limit at maximum amplitude shall be defined in the documentation (see
Clause 7). Due to specified process pressure, loads or temperature, the separation element
shall not impair the Type of Protection.
NOTE 1 A wall thickness less than 1 mm is only permitted in combination with intrinsic safety
“ib”, or a flameproof joint or natural ventilation (see 4.1.3.3).
NOTE 2 For glass or ceramics, a minimum thickness of 1/10 of the diameter/maximum
dimension but not less than 1 mm is recommended required.
In addition to the requirements of 4.1.3.1 to 4.1.3.3, metallic partition walls with a thickness
≥ 1 mm may be provided with suitable conductor bushings (see Figure 1).
To avoid a critical concentration of explosive gas atmosphere diffusing from the area requiring
EPL Ga into the enclosure containing the electrical circuits, the leakage rate through the
bushing shall be low compared to the leakage rate from the enclosure into the free
atmosphere.
NOTE 3 For example this could be done using a standard enclosure with an IP67 rating
according to IEC 60529, a bushing with a leakage rate equivalent to a helium-leakage rate
-2 –4 5
less than 10 Pa×l/s (10 mbar × l/s) at a pressure difference of 10 Pa (1 bar) is sufficient.
This can be achieved, for example, by using a glass or ceramic bushing as shown in Figure 1.
Metallic sleeve, corrosion
resistant (wall thickness ≥ 1 mm)
Bushing insulator (e.g. melted
≥ 10 mm glass, brazed ceramics)
Less hazardous
area
“ia” circuit
Area
Ex “ia” circuit
requiring
Non-“ia”
EPL Ga
Non-“ia” supply circuit
circuit
(e.g. Ex “e”)
Partition wall
Welded
(t ≥1 mm)
(joint ≥ 1 mm)
Electrical equipment
IEC
Figure 1 – Example of a partition wall with a conductor bushing
considered as gas diffusion tight
– 12 – IEC 60079-26:2014 RLV © IEC 2014
4.1.3.3 Requirements depending on the thickness of the partition wall
The combinations of separation elements and additional protective measures depend on the
wall thickness, t, of the partition wall as described below and shown in Table 1:
i) For homogeneous partition walls with a thickness ≥3 mm, no additional protection
measures are required.
ii) For homogeneous partition walls with a thickness of 3 mm > t ≥ 1 mm, one EPL Gb type of
protection is required (see example a) of Table 1). A homogeneous part of the enclosure
of an equipment with a EPL Gb type of protection may form the partition wall, even for
types of protection which rely on the enclosure, provided the equipment does not contain
an ignition capable source, for example exposed contacts (see example a) of Table 1). If
the equipment contains a source of ignition in normal operation, either a flameproof joint
(example b) of Table 1) or a ventilated air gap (example c) of Table 1) is also required.
iii) Behind partition walls of 1 mm > t ≥ 0,2 mm, one of the following protective measures is
required:
– Type of Protection intrinsic safety “ib” according to IEC 60079-11 (example a) of Table
1); or
– one EPL Gb Type of Protection in combination with a flameproof joint (example b) of
Table 1); or
– one EPL Gb Type of Protection in combination with a ventilated air-gap and a
flameproof joint (example c) of Table 1).
iv) For a partition wall with t < 0.2 mm (for example membranes), a flameproof joint and one
EPL Gb Type of Protection are required (example b) of Table 1). If the equipment contains
a source of ignition in normal operation (for example by exposed contacts), a ventilated air
gap is also required (example type c) of Table 1).
NOTE In the context of this clause, ‘homogeneous’ means a membrane constructed of a single piece of material
without any insertions such as feed-throughs, bushings.
Table 1 – Separation elements
Requirements depending on the thickness, t, of the partition wall
i) t ≥ 3 mm: no additional requirements
ii) iii) iv)
Type of construction
3 mm > t ≥ 1 mm 1 mm > t ≥ 0.2 mm t < 0.2 mm
(“X” marking required) (“X” marking
required)
a) Partition wall
Less hazardous
area Area
requiring a
EPL Gb Type of
Area
lower EPL than
Protection
requiring
Ga
EPL Ga and
Type of Protection
Not permissible
intrinsic safety’ “ib”
no ignition source
Electrical
under normal operation
Partition
equipment
(for example no exposed
wall
contacts)
b) Partition wall + joint
Less hazardous
area Area
Area
requiring a
EPL Gb Type of
requiring
lower EPL than
Protection
EPL Ga
Ga
and
EPL Gb Type of Protection
Partition
Electrical
no ignition source
a
wall
equipment
under normal operation
(for example no
exposed contacts)
a
Joint
c) Partition wall + ventilation
Less hazardous
area Area
requiring a
Area lower EPL than
requiring Ga
EPL Gb Type of Protection
a
EPL Ga
(Joint )
EPL Gb Type of
and
Protection
Electrical
Partition
flameproof joint (dashed)
a
equipment
wall
Natural
ventilation
a
Flameproof joint and partition wall are exchangeable in sequence of order.
4.1.3.4 Partition wall combined with a flameproof joint
Joints supplementing partition walls shall comply with either:
a) the requirements in IEC 60079-1;
NOTE 1 to determine the joint characteristics, the free volume of the enclosure containing
the electrical circuits should shall be considered; or
b) a construction, where the same level of safety as for a) can be demonstrated.
– 14 – IEC 60079-26:2014 RLV © IEC 2014
NOTE For example, a cylindrical PTFE-bushing pressed form-fit into a metallic enclosure at a length
≥ 40 mm. A permanently compressed joint with a length of at least 17 mm is also suitable (for example using a
conical PTFE-bushing compressed by a spring).
Non-metallic components in separation elements shall meet the requirements of IEC 60695-
11-10, flammability category V-0 and have a chemical resistivity equivalent, for example to
that of glass, ceramics, non-regenerated PTFE or epoxy resin for petrol petrochemical
applications. The materials of the separation element and its mechanical and thermal stress
limits shall be clearly defined in the documentation to enable the user to confirm their
suitability for the particular application.
4.1.3.5 Partition wall combined with an airgap with natural ventilation
The ventilation shall ensure that under the most onerous arduous process conditions specified
by the manufacturer and the anticipated leakages, an accumulation of flammable materials in
the equipment is prevented. Under atmospheric process conditions, the ventilation is valid
sufficient for all gases, vapours and mists, if the length of the air-gap is ≥10 mm and the
effective perforation in the circumference is at least 50 %. In addition to the requirements of
4.1.3.1 to 4.1.3.3, metallic partition walls with a thickness ≥1 mm and a suitable air-gap may
be provided, for example with a cylindrical flameproof shaft joint according to IEC 60079-1
(see Figure 2). In this case, the ventilation air gap shall have a minimum length of 10 mm or a
length equal to the diameter of the shaft, whichever is greater.
a
≥ 10 mm
Perforation > 50 %
Less hazardous
area
Natural
ventilation
Shaft
Area e.g. electric motor
requiring
Ex “d”
Non-“ia” supply circuit
EPL Ga
Partition wall
(≥1 mm)
Cylindrical shaft joint flameproof
according to IEC 60079-1
IEC
a
Required for sufficient ventilation.
NOTE The cylindrical shaft joint inside the partition wall as shown in Figure 2 is not a supplementing joint as
referred to in 4.1.3.4.
NOTE 2 The electrical equipment should be selected in accordance with the appropriate gas group.
Figure 2 – Example of a separation element
with a cylindrical shaft joint and natural ventilation
4.2 Equipment with moving parts
4.2.1 Frictional heating
If the equipment contains moving parts, temperature rise due to frictional heating may occur
under normal operation or fault condition. It shall be taken into consideration when
determining the maximum surface temperature.
4.2.2 Damage arising from failure of moving parts
In case of a failure of moving parts, the Types of Protection shall not be adversely affected.
4.2.3 Light metals
Operational friction or impact between equipment parts made of light metals or their alloys
(with concentrations above the limits given in IEC 60079-0) with equipment parts made of
iron/steel is not permitted. Operational friction or impact between two light metals is
permitted.
NOTE Light metals include for example aluminium, magnesium, titanium or zirconium.
4.4 Isolated conductive components
Isolated conductive components on the surface of the equipment shall be bonded to ground,
except where they cannot be charged to an ignition capable level as demonstrated by the
charging test procedure of IEC 60079-0.
4.5 Non-conductive enclosures and accessible non-conductive components
4.5.1 General
Precautions shall be taken to ensure that the risk of ignition from electrostatic discharge is
reduced to a negligible level, particularly since equipment providing EPL Ga may be applied
directly in the process and non-conductive surfaces may be charged by the flow of non-
conductive media (for example in stirring vessels or pipes).
Therefore, the accessible chargeable surfaces of the equipment shall comply with the
requirements of 7.3 of IEC 60079-0 or one of the following:
a) limitation of the size of chargeable non-conductive surfaces – see 4.5.2;
b) limitation of the thickness of chargeable non-conductive layers – see 4.5.3;
c) provision of a conductive coating – see 4.5.4.
If none of these requirements can be complied with, X-marking or an advisory marking in
accordance with 29.2 of IEC 60079-0 shall be applied and the certificate shall contain special
conditions for safe use to enable the user to decide on the suitability of the equipment for the
particular application.
4.5.2 Limitation of the size of chargeable non-conductive surfaces
The projection of the chargeable non-conductive surface shall be limited to the values given in
in Table 4 of IEC 60079-0 for zone 0 (EPL Ga). In the case of long parts with non-conductive
surfaces, such as tubes, bars, cables or ropes, independent of their length, the diameters or
widths shall not exceed
a) 3 mm for equipment of groups IIA and IIB;
b) 1 mm for equipment of group IIC.
4.5.3 Limitation of the thickness of chargeable non-conductive layers
Where a non-conductive layer covers a bonded conductive surface, the thickness of that layer
shall not exceed
a) 2 mm for equipment of group IIA, IIB;
b) 0,2 mm for equipment of group IIC.
The bonded conductive surface may be formed by a wire mesh with a mesh area as defined
in IEC 60079-0, Table 4 for zone 0 (EPL Ga).
NOTE 1 Cables with a protective covering over a screen may comply.
NOTE 2 It should, however, be noted that in the presence of a very efficient charge generating mechanism
propagating brush discharges could occur.
– 16 – IEC 60079-26:2014 RLV © IEC 2014
4.5.4 Provision of a conductive coating
Non-conductive surfaces may be covered with a bonded durable conductive coating. The
resistance between coating and the point of bond shall not exceed 1 GΩ.
The resistance shall be measured in accordance with 26.13 of IEC 60079-0 using a 1 cm
electrode at the worst case position of the surface and the point of bond.
X-marking or an advisory marking in accordance with 29.2 of IEC 60079-0 shall be applied
and the certificate shall advise on the use of the bonding connection (if separately accessible
to the user and not an integral part of the equipment) and provide information to enable the
user to decide on the durability of the coating material with respect to the environmental
conditions (see Clause 7).
NOTE The requirements of 4.5 will be deleted after incorporation in IEC 60079-0.
4.3 Process connection
If the equipment is mounted across the boundary wall between an area requiring EPL Ga and
a less hazardous area, the construction shall ensure that either under normal operation
conditions:
a) explosive gas atmospheres cannot be released from an area requiring EPL Ga creating an
explosive atmosphere in the surrounding area; and
b) that in case of an ignition of an explosive gas atmosphere in the surrounding area there is
no flame propagation into the area requiring EPL Ga.
The equipment shall be designed to allow installation in a manner that will result in a
sufficiently tight joint (IP 66 or IP 67) or a flameproof joint according to IEC 60079-1 (joints
specified for a volume ≤ 100 cm )
...
IEC 60079-26 ®
Edition 3.0 2014-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Explosive atmospheres –
Part 26: Equipment with Equipment Protection Level (EPL) Ga
Atmosphères explosives –
Partie 26: Matériel d'un niveau de protection du matériel (EPL) Ga
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
IEC Catalogue - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
The stand-alone application for consulting the entire The world's leading online dictionary of electronic and
bibliographical information on IEC International Standards, electrical terms containing more than 30 000 terms and
Technical Specifications, Technical Reports and other definitions in English and French, with equivalent terms in 14
documents. Available for PC, Mac OS, Android Tablets and additional languages. Also known as the International
iPad. Electrotechnical Vocabulary (IEV) online.
IEC publications search - www.iec.ch/searchpub IEC Glossary - std.iec.ch/glossary
The advanced search enables to find IEC publications by a More than 55 000 electrotechnical terminology entries in
variety of criteria (reference number, text, technical English and French extracted from the Terms and Definitions
committee,…). It also gives information on projects, replaced clause of IEC publications issued since 2002. Some entries
and withdrawn publications. have been collected from earlier publications of IEC TC 37,
77, 86 and CISPR.
IEC Just Published - webstore.iec.ch/justpublished
Stay up to date on all new IEC publications. Just Published IEC Customer Service Centre - webstore.iec.ch/csc
details all new publications released. Available online and If you wish to give us your feedback on this publication or
also once a month by email. need further assistance, please contact the Customer Service
Centre: csc@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Catalogue IEC - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
Application autonome pour consulter tous les renseignements
Le premier dictionnaire en ligne de termes électroniques et
bibliographiques sur les Normes internationales,
électriques. Il contient plus de 30 000 termes et définitions en
Spécifications techniques, Rapports techniques et autres
anglais et en français, ainsi que les termes équivalents dans
documents de l'IEC. Disponible pour PC, Mac OS, tablettes
14 langues additionnelles. Egalement appelé Vocabulaire
Android et iPad.
Electrotechnique International (IEV) en ligne.
Recherche de publications IEC - www.iec.ch/searchpub
Glossaire IEC - std.iec.ch/glossary
Plus de 55 000 entrées terminologiques électrotechniques, en
La recherche avancée permet de trouver des publications IEC
en utilisant différents critères (numéro de référence, texte, anglais et en français, extraites des articles Termes et
comité d’études,…). Elle donne aussi des informations sur les Définitions des publications IEC parues depuis 2002. Plus
projets et les publications remplacées ou retirées. certaines entrées antérieures extraites des publications des
CE 37, 77, 86 et CISPR de l'IEC.
IEC Just Published - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications IEC. Just
Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur cette
Disponible en ligne et aussi une fois par mois par email. publication ou si vous avez des questions contactez-nous:
csc@iec.ch.
IEC 60079-26 ®
Edition 3.0 2014-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Explosive atmospheres –
Part 26: Equipment with Equipment Protection Level (EPL) Ga
Atmosphères explosives –
Partie 26: Matériel d'un niveau de protection du matériel (EPL) Ga
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX Q
ICS 29.260.20 ISBN 978-2-8322-1903-4
– 2 – IEC 60079-26:2014 © IEC 2014
CONTENTS
FOREWORD . 3
1 Scope . 6
2 Normative references. 6
3 Terms and definitions . 7
4 Requirements for design and construction . 7
4.1 Protection measures against ignition hazards of the electrical circuits . 7
4.1.1 General . 7
4.1.2 Application of two independent Types of Protection providing EPL Gb . 7
4.1.3 Application of a Type of Protection providing EPL Gb and a separation
element . 8
4.2 Equipment with moving parts . 12
4.2.1 Frictional heating . 12
4.2.2 Damage arising from failure of moving parts . 12
4.2.3 Light metals . 12
4.3 Process connection . 13
5 Type tests . 13
5.1 Standardized types of protection . 13
5.2 Separation elements . 13
5.3 Temperature evaluation . 13
6 Marking . 14
6.1 General . 14
6.2 Examples of marking . 14
7 Instructions. 14
7.1 Separation elements: . 14
7.2 Process connection: . 15
7.3 EPL allocation . 15
Bibliography . 16
Figure 1 – Example of a partition wall with a conductor bushing considered as gas
diffusion tight . 9
Figure 2 – Example of a separation element with a cylindrical shaft joint and
naturalventilation . 12
Table 1 – Separation elements . 11
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EXPLOSIVE ATMOSPHERES –
Part 26: Equipment with Equipment Protection Level
(EPL) Ga
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60079-26 has been prepared by IEC technical committee 31:
Equipment for explosive atmospheres.
This third edition cancels and replaces the second edition published in 2006 and constitutes a
technical revision.
– 4 – IEC 60079-26:2014 © IEC 2014
This edition includes the following significant changes with respect to the previous edition:
Type
Changes Clause Minor and Extension Major
editorial technical
changes changes
Notes deleted 1 X
Reference to associated apparatus deleted 1 X
Additional normative references included 3 X
Requirements against mechanical and
electrostatic ignition hazards deleted (now 4.1 X
covered in IEC 60079-0)
Requirement for separation element detailed
4.1.3.2 X
regarding external influences
Intrinsic safety Ex ia as single type of protection
4.2.2
including associated apparatus deleted (now X
(ed.2)
covered by EPL)
Encapsulation Ex ma as single type of protection 4.2.3
X
deleted (now covered by EPL) (ed.2)
Conditions a) and b) linked with an “and” ,
therefore requirement of “flameproof joint” deleted
in following clause. Both requirements already 4.3 X
covered by separation elements and standardised
process connections.
Process connection requires a sufficiently tight
4.3 X
joint: IP66 added alternatively to IP67
Requirement for isolated conductive components 4.4
X
deleted (now covered in IEC 60079-0) (ed.2)
Requirements for non-conductive enclosures 4.5
X
deleted (now covered in IEC 60079-0) (ed.2)
Test of partition walls according to 4.1.3.2 b) is
5.2 C1
specified in more detail
Marking example for associated apparatus deleted 6.2 b) X
Note 3 with an additional example added 6.2 X
Specification of material of partition wall required
7 X
in instructions (also required in 4.1.3.2)
Alternative risk assessment method deleted (is AnnexA
X
now generally introduced) (ed.2)
NOTE The technical changes referred to include the significance of technical changes in the revised IEC
Standard, but they do not form an exhaustive list of all modifications from the previous version.
Explanation of the types of changes:
A) Definitions
1) Minor and editorial changes:
• Clarification
• Decrease of technical requirements
• Minor technical change
• Editorial corrections
These are changes which modify requirements in an editorial or a minor technical way.
They include changes of the wording to clarify technical requirements without any
technical change, or a reduction in level of existing requirement.
2) Extension: Addition of technical options
These are changes which add new or modify existing technical requirements, in a way
that new options are given, but without increasing requirements for equipment that was
fully compliant with the previous standard.Therefore, these will not have to be
considered for products in conformity with the preceding edition.
3) Major technical changes:
• addition of technical requirements
• increase of technical requirements
These are changes to technical requirements (addition, increase of the level or
removal) made in a way that a product in conformity with the preceding edition will not
always be able to fulfil the requirements given in the later edition. These changes have
to be considered for products in conformity with the preceding edition. For these
changes additional information is provided in Clause B below.
NOTE These changes represent current technological knowledge. However, these changes should not
normally have an influence on equipment already placed on the market.
B) Information about the background of ‘Major technical changes’
C1: Introduction of type tests for separation elements according to “4.1.3.2 b)”
The text of this standard is based on the following documents:
FDIS Report on voting
31/1146/FDIS 31/1155/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60079 series, published under the general title Explosive
atmospheres, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – IEC 60079-26:2014 © IEC 2014
EXPLOSIVE ATMOSPHERES –
Part 26: Equipment with Equipment Protection Level
(EPL) Ga
1 Scope
This part of IEC 60079 specifies alternative requirements for construction, test and marking
for electrical equipment that provides Equipment Protection Level (EPL) Ga when single
standardised Types of Protection (e.g. Ex “ia” , Ex “ma”, Ex “da”) cannot be applied. This
standard also applies to equipment mounted across a boundary where different Equipment
Protection Levels may be required.
EXAMPLE: Equipment installed in the wall of a storage vessel containing Zone 0 (requiring EPL Ga) inside an
area defined as Zone 1 (requiring EPL Gb).
This electrical equipment, within the operational parameters specified by the manufacturer,
ensures a very high Level of Protection that includes rare malfunctions related to the
equipment or two malfunctions occurring independently of each other.
NOTE A malfunction may result from a failure of the component parts of the electrical equipment or from
anticipated externally applied influences. Two independent malfunctions which may occur more frequently and
which, separately, would not create an ignition hazard but which, in combination, could create a potential ignition
hazard, are regarded as occurring together to form a rare malfunction.
This standard supplements and modifies the general requirements of IEC 60079-0. Where a
requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of
this standard takes precedence.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60079-0, Explosive atmospheres − Part 0: Equipment − General requirements
IEC 60079-1, Explosive atmospheres − Part 1: Equipment protection by flameproof enclosures
"d"
IEC 60079-11, Explosive atmospheres − Part 11: Equipment protection by intrinsic safety "i"
IEC 60695-11-10, Fire hazard testing − Part 11-10: Test flames − 50 W horizontal and vertical
flame test methods
IEC 60529, Degrees of protection provided by enclosures (IP Code)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60079-0 and the
following apply.
NOTE Additional definitions applicable to explosive atmospheres can be found in IEC 60050-426.
3.1
separation element
mechanical element inside the equipment, which separates different parts of the equipment
with different EPLs
Note 1 to entry: A separation element consists of a mechanical partition wall, which may be combined with a
flameproof joint or a natural ventilation
4 Requirements for design and construction
4.1 Protection measures against ignition hazards of the electrical circuits
4.1.1 General
The equipment shall comply with the requirements of 4.1.2 or 4.1.3 in the event of a failure of
one equipment means of protection, by the provision of a second independent means of
protection.
NOTE 1 Types of Protection according to EPL Ga do not require a second independant means of protection, e.g.
Ex “ia” (IEC 60079-11), Ex “ma” (IEC 60079-18), Ex “da” (IEC 60079-1).
Electrical connections and permanently connected cables of the equipment sited within an
area requiring EPL Ga equipment shall comply with the same Level of Protection required by
this standard, for example a cable suitable for EPL Gb containing non-Ex “ia” circuits
additionally protected by a flameproof conduit or a cable suitable for EPL Gb provided with
earth leakage protection.
NOTE 2 Detailed cable and installation requirements for Types of Protection accepted as achieving EPL Ga
beyond intrinsically safe circuits are under consideration in IEC 60079-14.
NOTE 3 Because of ignition hazards which can arise from faults and/or transient circulating currents in the
potential equalization system, galvanic isolation in the power and signal connections to the equipment according to
4.1.2 and 4.1.3 is commonly applied along with minimizing the effect of transient fault currents in the potential
equalization network by the use of electrical protection equipment such as sensitive earth leakage monitors.
4.1.2 Application of two independent Types of Protection providing EPL Gb
Electrical equipment shall comply with the requirements of two independent Types of
Protection that provide EPL Gb. If one Type of Protection fails, the other Type of Protection
shall continue to function. The independent Types of Protection shall not have a common
mode of failure, except as specified in this clause. Combined types of protection providing
EPL Gb shall depend on different physical protection principles.
NOTE 1 An example of a common mode of failure is if an Ex “d” enclosure containing arcing components is
installed inside an Ex “e” enclosure. Should the Ex “d” enclosure be compromised, it would also compromise the
Ex “e” enclosure.
NOTE 2 The combination of Ex “d” and Ex “q” both depend on the avoidance of flame propagation (same physical
protection principle) and may not be useful in combination. In practice, some combinations may not be useful, for
example the combination of oil immersion “o” and powder filling “q”.
Where combined types of protection are used, it shall be possible for each Type of Protection
to be tested individually (see 5.1).
Both Types of Protection shall be assessed using the most arduous fault condition of the
other Type of Protection. When combining intrinsic safety, Type of Protection “ib”, with other
– 8 – IEC 60079-26:2014 © IEC 2014
Types of Protection, the second Type of Protection shall be assessed, with the most arduous
fault condition applied to the intrinsically safe circuit. Thermal dissipation shall be considered
in case of a fault of one Type of protection.
When using two Types of Protection, which both rely on the same parameter (for example, the
creepage distance combining Ex “ib” with Ex “e”), the most stringent requirement of both
Types of Protection shall be applied.
If two Types of Protection are combined which both rely on the enclosure, one of the following
shall be met:
a) if two enclosures are used (one totally enclosed within the other), each enclosure shall
comply with the requirements of the respective Type of Protection; or
b) if only one enclosure is used, the enclosure and the cable glands shall meet the impact
test requirements of IEC 60079-0, using the Group I values.
Examples of relevant combinations of two independent Types of Protection are as follows:
– inductive transmitters (for example proximity switches, electrical position sensors) with
intrinsic safety “ib” enclosed by encapsulation “mb”. The connections to intrinsically safe
“ib” circuits can be protected by the increased safety “e”;
– a luminaire designed as increased safety “e”may be included in a flameproof enclosure
“d”:
– measuring transducers with intrinsic safety “ib” and a flameproof enclosure “d”;
– equipment with electrical circuits of intrinsic safety “ib”, additionally protected by powder
filling “q”;
– electromagnetic valves with encapsulation “mb”, enclosed by a flameproof enclosure “d”;
– increased safety “e”, with pressurized equipment “pxb”.
4.1.3 Application of a Type of Protection providing EPL Gb and a separation element
4.1.3.1 General
Equipment which is mounted through or forms part of the boundary wall to an area requiring
EPL Ga and contains electrical circuits which do not comply with EPL Ga shall comply with at
least one of the Types of Protection providing EPL Gb. Additionally, it shall contain a
mechanical separation element as part of the equipment to separate the electrical circuits of
the equipment from the area requiring EPL Ga.
If the Type of Protection fails, the separation element shall:
a) prevent flame propagation through the equipment into the area requiring EPL Ga,
b) maintain its safety characteristics,
c) not exceed the maximum surface temperature of the specified temperature class of the
equipment (see 5.3).
4.1.3.2 Partition walls
Partition walls shall be constructed of either:
a) corrosion-resistant metals, glass or ceramics,
b) other materials which can be verified to provide the same level of safety. In this case, the
certificate number shall include the "X" suffix in accordance with the marking requirements
of IEC 60079-0.
If the wall thickness is less than 1 mm, the certificate number shall include the "X" suffix in
accordance with the marking requirements of IEC 60079-0 and the Specific Conditions of Use
listed on the certificate shall indicate that the material shall not be subject to environmental
conditions which might adversely affect the partition wall.
If the partition wall is under constant vibrational stress (for example vibrating membranes), the
minimum endurance limit at maximum amplitude shall be defined in the documentation (see
Clause 7). Due to specified process pressure, loads or temperature, the separation element
shall not impair the Type of Protection.
A wall thickness less than 1 mm is only permitted in combination with intrinsic safety “ib”, or a
flameproof joint or natural ventilation (see 4.1.3.3). For glass or ceramics, a minimum
thickness of 1/10 of the diameter/maximum dimension but not less than 1 mm is required.
In addition to the requirements of 4.1.3.1 to 4.1.3.3, metallic partition walls with a thickness
≥ 1 mm may be provided with suitable conductor bushings (see Figure 1).
To avoid a critical concentration of explosive gas atmosphere diffusing from the area requiring
EPL Ga into the enclosure containing the electrical circuits, the leakage rate through the
bushing shall be low compared to the leakage rate from the enclosure into the free
atmosphere. For example this could be done using a standard enclosure with an IP67 rating
according to IEC 60529, a bushing with a leakage rate equivalent to a helium-leakage rate
-2 –4 5
less than 10 Pa×l/s (10 mbar × l/s) at a pressure difference of 10 Pa (1 bar). This can be
achieved, for example, by using a glass or ceramic bushing as shown in Figure 1.
Metallic sleeve, corrosion
resistant (wall thickness ≥ 1 mm)
Bushing insulator (e.g. melted
≥ 10 mm glass, brazed ceramics)
Less hazardous
area
“ia” circuit
Area
Ex “ia” circuit
requiring
Non-“ia”
EPL Ga
Non-“ia” supply circuit
circuit
(e.g. Ex “e”)
Partition wall
Welded
(t ≥1 mm)
(joint ≥ 1 mm)
Electrical equipment
IEC
Figure 1 – Example of a partition wall with a conductor bushing
considered as gas diffusion tight
4.1.3.3 Requirements depending on the thickness of the partition wall
The combinations of separation elements and additional protective measures depend on the
wall thickness, t, of the partition wall as described below and shown in Table 1:
i) For homogeneous partition walls with a thickness ≥3 mm, no additional protection
measures are required.
ii) For homogeneous partition walls with a thickness of 3 mm > t ≥ 1 mm, one EPL Gb type of
protection is required (see example a) of Table 1). A homogeneous part of the enclosure
of an equipment with a EPL Gb type of protection may form the partition wall, even for
types of protection which rely on the enclosure, provided the equipment does not contain
an ignition capable source, for example exposed contacts (see example a) of Table 1). If
– 10 – IEC 60079-26:2014 © IEC 2014
the equipment contains a source of ignition in normal operation, either a flameproof joint
(example b) of Table 1) or a ventilated air gap (example c) of Table 1) is also required.
iii) Behind partition walls of 1 mm > t ≥ 0,2 mm, one of the following protective measures is
required:
– Type of Protection intrinsic safety “ib” according to IEC 60079-11 (example a) of Table
1); or
– one EPL Gb Type of Protection in combination with a flameproof joint (example b) of
Table 1); or
– one EPL Gb Type of Protection in combination with a ventilated air-gap and a
flameproof joint (example c) of Table 1).
iv) For a partition wall with t < 0.2 mm (for example membranes), a flameproof joint and one
EPL Gb Type of Protection are required (example b) of Table 1). If the equipment contains
a source of ignition in normal operation (for example by exposed contacts), a ventilated air
gap is also required (type c) of Table 1).
NOTE In the context of this clause, ‘homogeneous’ means a membrane constructed of a single piece of material
without any insertions such as feed-throughs, bushings.
Table 1 – Separation elements
Requirements depending on the thickness, t, of the partition wall
i) t ≥ 3 mm: no additional requirements
ii) iii) iv)
Type of construction
3 mm > t ≥ 1 mm 1 mm > t ≥ 0.2 mm t < 0.2 mm
(“X” marking required) (“X” marking
required)
a) Partition wall
Area requiring
Area
EPL Gb Type of
a lower EPL
requiring
Protection
than Ga
EPL Ga
and
Type of Protection
Not permissible
Electrical
intrinsic safety’ “ib”
no ignition source
Partition
equipment
under normal operation
wall
(for example no exposed
contacts)
b) Partition wall + joint
Area requiring a
Area
EPL Gb Type of
lower EPL than
requiring
Protection
Ga
EPL Ga
and
EPL Gb Type of Protection
Partition
Electrical
no ignition source
a
wall
equipment
under normal operation
(for example no
exposed contacts)
a
Joint
c) Partition wall + ventilation
Area requiring a
lower EPL than
Area
Ga
requiring
a
EPL Ga EPL Gb Type of Protection
(Joint )
EPL Gb Type of
and
Protection
Electrical
Partition
a flameproof joint (dashed)
equipment
wall
Natural
ventilation
a
Flameproof joint and partition wall are exchangeable in sequence of order.
4.1.3.4 Partition wall combined with a flameproof joint
Joints supplementing partition walls shall comply with either:
a) the requirements in IEC 60079-1; to determine the joint characteristics, the free volume of
the enclosure containing the electrical circuits shall be considered; or
b) a construction, where the same level of safety as for a) can be demonstrated.
NOTE For example, a cylindrical PTFE-bushing pressed form-fit into a metallic enclosure at a length
≥ 40 mm. A permanently compressed joint with a length of at least 17 mm is also suitable (for example using a
conical PTFE-bushing compressed by a spring).
– 12 – IEC 60079-26:2014 © IEC 2014
Non-metallic components in separation elements shall meet the requirements of IEC 60695-
11-10, flammability category V-0 and have a chemical resistivity equivalent, for example to
that of glass, ceramics, non-regenerated PTFE or epoxy resin for petrochemical applications.
4.1.3.5 Partition wall combined with an airgap with natural ventilation
The ventilation shall ensure that under the most arduous process conditions specified by the
manufacturer and the anticipated leakages, an accumulation of flammable materials in the
equipment is prevented. Under atmospheric process conditions, the ventilation is sufficient for
all gases, vapours and mists, if the length of the air-gap is ≥10 mm and the effective
perforation in the circumference is at least 50 %. In addition to the requirements of 4.1.3.1 to
4.1.3.3, metallic partition walls with a thickness ≥1 mm and a suitable air-gap may be
provided, for example with a cylindrical flameproof shaft joint according to IEC 60079-1 (see
Figure 2). In this case, the ventilation air gap shall have a minimum length of 10 mm or a
length equal to the diameter of the shaft, whichever is greater.
a
≥ 10 mm
Perforation > 50 %
Less hazardous
area
Natural
ventilation
Shaft
Area
e.g. electric motor
requiring Ex “d”
Non-“ia” supply circuit
EPL Ga
Partition wall
(≥1 mm)
Cylindrical shaft joint flameproof
according to IEC 60079-1
IEC
a
Required for sufficient ventilation.
NOTE The cylindrical shaft joint inside the partition wall as shown in Figure 2 is not a supplementing joint as
referred to in 4.1.3.4.
Figure 2 – Example of a separation element
with a cylindrical shaft joint and natural ventilation
4.2 Equipment with moving parts
4.2.1 Frictional heating
If the equipment contains moving parts, temperature rise due to frictional heating may occur
under normal operation or fault condition. It shall be taken into consideration when
determining the maximum surface temperature.
4.2.2 Damage arising from failure of moving parts
In case of a failure of moving parts, the Types of Protection shall not be adversely affected.
4.2.3 Light metals
Operational friction or impact between equipment parts made of light metals or their alloys
(with concentrations above the limits given in IEC 60079-0) with equipment parts made of
iron/steel is not permitted. Operational friction or impact between two light metals is
permitted.
NOTE Light metals include for example aluminium, magnesium, titanium or zirconium.
4.3 Process connection
If the equipment is mounted across the boundary wall between an area requiring EPL Ga and
a less hazardous area, the construction shall ensure that under normal operation conditions:
a) explosive gas atmospheres cannot be released from an area requiring EPL Ga creating an
explosive atmosphere in the surrounding area; and
b) that in case of an ignition of an explosive gas atmosphere in the surrounding area there is
no flame propagation into the area requiring EPL Ga.
The equipment shall be designed to allow installation in a manner that will result in a
sufficiently tight joint (IP 66 or IP 67) or a flameproof joint according to IEC 60079-1 (joints
specified for a volume ≤ 100 cm ) between the less hazardous area and area requiring EPL
Ga.
NOTE 1 For example, equipment with an integrated separation element according to 4.1.3 or with an IP67 rating
according to IEC 60529 between the area requiring EPL Ga and the less hazardous area is suitable.
Process connections shall comply with an international or equivalent national standard.
NOTE 2 Examples of process connections which are considered as suitable include:
a) gas-tight standardized industry flange;
b) gas-tight standardized tube fitting;
c) gas-tight standardized thread connection.
If, for functional purposes, an opening is required in the boundary wall of the area requiring
EPL Ga (for example chemical sampling at the open nozzle, rope guide for probes),
instructions for the user are required to indicate the risk of flammable gas release and flame
entrance (see Clause 7).
5 Type tests
5.1 Standardized types of protection
Equipment in which EPL Gb Types of Protection are applied shall be submitted to type
verifications and tests as specified in the respective standards. If the combination of two EPL
Gb Types of Protection according to 4.1.2 are applied, both Types of Protection shall be
tested independently.
5.2 Separation elements
Separation elements in accordance with 4.1.3 shall be tested in such a way that the
operational parameters (for example pressure or temperature limits) stated by the
manufacturer are verified.
Partition walls according to “4.1.3.2b)”
– which are exposed to operational pressure shall be subject to the thermal endurance test
of IEC 60079-0 followed by the pressure test. The pressure test shall be performed at
maximum operational pressure for 1 min without leakage;
– which are exposed to constant vibrational stress the specified vibrational endurance limit
(cycles) shall be verified at the maximum amplitude and at the specified temperature
limits.
5.3 Temperature evaluation
For the temperature evaluation, two independent faults shall be taken into account.
– 14 – IEC 60079-26:2014 © IEC 2014
This applies also to separation elements of any thickness combined with or partly formed by
equipment with one EPL Gb type of protection.
6 Marking
6.1 General
The equipment shall be marked with the EPL and according to the Type of Protection as
defined in the applicable standard.
Equipment intended for installation in the boundary wall between an area requiring EPL Ga
and a less hazardous area shall have both EPLs marked on the label separated by a slash “/”.
If the equipment group or temperature class differ for the two Types of Protection, the
complete designation of each rating shall be used and separated by a space.
Where more than one Type of Protection is used in accordance with 4.1.2, the symbols for the
Types of Protection shall be joined with a “+”.
6.2 Examples of marking
a) Equipment protected by two Types of Protection which is intended to be completely
installed inside the area requiring EPL Ga for example:
Ex d+e IIB T4 Ga
b) Equipment which is installed in the boundary wall between an area requiring EPL Ga and
the less hazardous area, both EPLs are marked on the label separated by a slash “/”, for
example:
Ex d IIC T6 Ga/Gb
or
Ex ia/d IIC T6 Ga/Gb
NOTE 1 Intrinsic safety “ia” equipment providing EPL Ga with a flameproof “d” compartment providing EPL
Gb.
or
Ex d+e / d IIB T4 Ga/Gb
NOTE 2 Two independent Types of Protection flameproof “d” and increased safety “e” providing EPL Ga with
a flameproof “d” compartment providing EPL Gb.
or
Ex ia IIC T4 / Ex d IIB T6 Ga/Gb
NOTE 3 An intrinsically safe sensor providing EPL Ga suitable for Group IIC and having a temperature class
T4 and a flameproof compartment providing EPL Gb suitable for Group IIB, having a temperature class T6.
7 Instructions
7.1 Separation elements:
For equipment according to 4.1.3 the instructions according to IEC 60079-0 shall additionally
specify the following details, to enable the user to confirm its suitability for the particular
application:
– the material of the partition wall;
– if the wall thickness is less than 1 mm, the instructions shall indicate that the material shall
not be subject to environmental conditions which might adversely affect the partition wall;
– if the partition wall is under constant vibrational stress (for example vibrating membranes),
the minimum endurance limit at maximum amplitude;
– for partition walls according to 4.1.3.2 b): the material and its mechanical and thermal
properties;
– for separation elements according to 4.1.3.4: the material of non metallic components in
the separation element and its mechanical and thermal stress limits ;
– for separation elements according to 4.1.3.5 to avoid obstruction of the natural ventilation
e.g. by presence of dust.
7.2 Process connection:
If an opening is required in the boundary wall of the area requiring EPL Ga the risk of
flammable gas release and flame entrance shall be specified.
7.3 EPL allocation
If the marking indicates several EPLs for the equipment (e.g. Ga/Gb), it shall be specified
which parts of the equipment comply with the different EPLs.
– 16 – IEC 60079-26:2014 © IEC 2014
Bibliography
IEC 60050-426, International Electrotechnical Vocabulary − Part 426: Equipment for explosive
atmospheres
IEC 60079-7, Explosive atmospheres − Part 7: Equipment protection by increased safety "e"
IEC 60079-14, Explosive atmospheres − Part 14: Electrical installations design, selection and
erection
IEC 60079-18, Explosive atmospheres – Part 18: Equipment protection by encapsulation "m"
_____________
– 18 – IEC 60079-26:2014 © IEC 2014
SOMMAIRE
AVANT-PROPOS . 19
1 Domaine d'application . 23
2 Références normatives . 23
3 Termes et définitions . 24
4 Exigences relatives à la conception et la construction . 24
4.1 Moyens de protection contre les risques d’allumage dus aux circuits
électriques . 24
4.1.1 Généralités . 24
4.1.2 Application de deux modes de protection indépendants procurant l'EPL
Gb . 24
4.1.3 Application d’un mode de protection procurant l’EPL Gb et d'un
élément de séparation . 25
4.2 Matériels avec des pièces en mouvement . 29
4.2.1 Échauffement de frottement . 29
4.2.2 Dommages résultant de la défaillance de pièces en mouvement . 29
4.2.3 Métaux légers .
...
Frequently Asked Questions
IEC 60079-26:2014 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Explosive atmospheres - Part 26: Equipment with Equipment Protection Level (EPL) Ga". This standard covers: IEC 60079-26:2014 specifies alternative requirements for construction, test and marking for electrical equipment that provides Equipment Protection Level (EPL) Ga when single standardised Types of Protection (e.g. Ex "ia", Ex "ma", Ex "da") cannot be applied. This standard also applies to equipment mounted across a boundary where different Equipment Protection Levels may be required. This electrical equipment, within the operational parameters specified by the manufacturer, ensures a very high Level of Protection that includes rare malfunctions related to the equipment or two malfunctions occurring independently of each other. This standard supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. This third edition cancels and replaces the second edition published in 2006 and constitutes a technical revision. The numerous changes are identified in the Foreword of the document. Keywords: Equipment Protection Level (EPL) Ga
IEC 60079-26:2014 specifies alternative requirements for construction, test and marking for electrical equipment that provides Equipment Protection Level (EPL) Ga when single standardised Types of Protection (e.g. Ex "ia", Ex "ma", Ex "da") cannot be applied. This standard also applies to equipment mounted across a boundary where different Equipment Protection Levels may be required. This electrical equipment, within the operational parameters specified by the manufacturer, ensures a very high Level of Protection that includes rare malfunctions related to the equipment or two malfunctions occurring independently of each other. This standard supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. This third edition cancels and replaces the second edition published in 2006 and constitutes a technical revision. The numerous changes are identified in the Foreword of the document. Keywords: Equipment Protection Level (EPL) Ga
IEC 60079-26:2014 is classified under the following ICS (International Classification for Standards) categories: 29.260.20 - Electrical apparatus for explosive atmospheres. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 60079-26:2014 has the following relationships with other standards: It is inter standard links to IEC 60079-26:2006/COR1:2009, IEC 60079-26:2021, IEC 60079-26:2006. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase IEC 60079-26:2014 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...